Design Of Column In Limit State

Method
The Design of R.C.C. Columns is very important, as in the Framed Structured Building that is in the
modern day construction the Frames are formed by networks of Columns and Beams. A Column is a
Structural Member which is vertical and axially loaded and subjected to Compressive forces, and
having its Effective Length (Height) Three times greater than the least cross-sectional dimension of
itself. To Satisfactorily Complete the Design of Columns The Following Steps must followed.

STEP 1 :- Calculation of the Influence Area of the Columns :


The first step is to find out the Influence Area of the Column to be Designed. The Influence Area of a
column is the area of which load is being transferred to the column to be designed for. For this purpose
in a framed structure small and medium building the design of column is done for the column whose
Influence Area is the largest hence the load coming on the column will be so the greater of the any
other column in that building hence all the other column having lesser Influence Area hence lesser
Loads if provided with the same Designed parameters that required for the column having largest
Influence Area, then the whole Structure will automatically become safe against the Loads.

DETERMINATION OF INFLUENCE AREAS FOR LOAD DISTRIBUTION ON COLUMNS

STEP 2:- Calculation of the Loads Coming on Columns from


the Influence Area :
In this step the Load Calculation is being done. This is done by calculating all the loads acting within the
influence area.

I.
II.
III.
IV.
V.

The Loads acting are broadly classified as Dead Load (DL) and Live Load (LL). Dead Loads are the load of
objects which cannot be moved from on place to another like the loads of Brick Work, Beams, Slabs etc.
and the Live Loads are the loads coming from movable objects such as Humans, Chair, Table etc.
Thus We Need to Calculate the Dead Loads as well as Live Loads within the Influence Area, these are as
follows in the general case of a Building :A)Dead Loads :
Due to weight of Slab
[25000 N/m3 ]
Due to weight of Floor Finish
[500 N/m2]
Due to weight of Brick Masonry
[19200 N/m3]
Due to weight of Beam
[25000 N/m3]
Due to weight of Self Weight of Column
[25000 N/m3]
B) Live Load :
It depends upon the Nature of the Structure, and it values for different structural nature are given in
the concerned Code of Practice, like in India these are given in I.S.: 875-Part II.
For Residential Buildings it is generally considered @ 2KN/m 2 = 2000 N/m2

COLUMN FORM WORK OF BUILDING

Now after correct calculation of above loads the Total Load is Calculated by,
Total Load on each floor = Dead Load + Live Load
Now this the actual load which will be acting on column for each floor, now if the building say 5 storied,
then just multiply the value with the nos. of floors, like for five storied building multiply the Total Load
on each story with 5.
Now thus the Total load acting on column at Column Base is Obtained and it is denoted with P.
Hence P= Total Load on each Floor X Nos. of Stories = (Dead Load + Live Load) X Nos. of Stories.
Now we shall move to the actual Designing to determine suitable Column sections and its
Reinforcements so that the above load is safely resisted by the column Designed.
It can be done by Three main Methods of Design : a) Working Stress Method b) Ultimate Load Method
and c) Limit State Method.
The Modern Practice is to use Limit State Method for all types of Designing, Hence Ill discuss here the
Limit State Method Of Design Of Column.

STEP 3 :- Finding The Gross Cross-Sectional Area Required


For The Columns :
This is the one of the most important and main step of the Design of Columns.
First in the Limit State Method of Design we must increase the load acting on the column with a Load
Factor so that if there will be any accidental increase of loads the column will be still safe to resist the
load without a failure. The Factor of Safety for Dead Load + Live Load Combination is 1.5, hence we
must multiply the load action on column (P) with the 1.5 to obtain the Ultimate Load that is the
Factored Load of the Column that is Pu.
Hence Factored Load, Pu = 1.5 X P
For Design we will work with this value of load.
Now before going on Im here to say that I will design according to the Code Of Practice of I.S.: 4562000
The Ultimate Load of a Column is given by,
Pu = 0.4.fck.Ac + 0.67.fy.Asc [Equation I]
Where, Pu = Ultimate Load of the Column in N/mm2
fck= Yield Strength of Concrete in N/mm2
Ac = Area of Concrete (Cross-Sectional Area) of Column in mm 2
fy = Yield Strength Of Steel in N/mm2
Asc = Area of Steel (Cross-Sectional Area) in Column in mm2
Now the column consists of Concrete and as well as Steel in the form of Reinforcements hence the
Total Cross-Sectional Area of Column is made of Area of Concrete and Area of Steel.
The Total Cross-Sectional area of Column can be also termed as Gross Cross-Sectional Area of Column
and its denoted by Ag.
Hence, Gross Cross-Sectional Area of Column = C/S Area of Concrete + C/S Area of Steel
Therefore, Ag = Ac + Asc
And hence, Ac = Ag - Asc
Now putting the above obtained value in the original equation (Equation I) we get,
Pu = 0.4.fck.(Ag-Asc) + 0.67.fy.Asc [Equation II]
Now Assume the Percentage of Steel you want to use ranging anywhere from 0.8% to 6% with Respect
to Gross Cross-Sectional Area of the Column (Ag). Say Assuming Steel as 1% of Ag it means Area of
Steel Asc = 1% of Ag = 0.01Ag
The higher will be the percentage of steel used the lower will be A g and thus lesser will be the crosssectional dimension of the column. But the as the Price of Steel is very high as compared to the
Concrete hence it is desirable to use as less as steel possible to make the structure economical, again if
the percentage of steel is lowered then the Ag will increase at higher rate, about 30% with decrease of
just 1% of steel and so each lateral dimension of the column will increase and will cause a gigantic
section to be provided to resist the load. Therefore both the factors are to be considered depending
upon the amount of loadings.
My suggestion is to use the following Percentage of steel for the Design, Which Ive found to be
effective and to produce economical and safe section of Column.

Loading (Pu) in N
Satisfactory Design

Percentage Of Steel for

Below 250000 --------------------------------------------0.8%


250,000 to 500,000 --------------------------------------1.0%
500,000 to 750,000 --------------------------------------1.5%
750,000 to 1000,000 -------------------------------------2.0%
1000,000 to 1500,000 -----------------------------------2.5%
1500,000 to 2000,000 -----------------------------------3.0%
And so on, with increase of each 250,000 N increasing the Percentage of Steel as 0.5%.
Now input the value of the Asc in the form of Ag in the Equation I. For example suppose 1% Steel is used
then the equation will be like the one below :Pu = 0.4.fck.(Ag-0.01Ag) + 0.67.fy.0.01Ag
Therefore, if we know the Grade of Concrete and Grade of Steel to be used and Factored Load coming
on the Column and Assuming the Percentage of steel required appropriately then we can Very Easily
Calculate the Gross-Sectional Area (Ag) of the Column required from the above form of the equation.
Now as the Ag is obtained thus the Lateral Dimensions of the Column that are the sides of the column
can be easily determined.
The Ag or Gross-Sectional Area of the Column means that it is the product of the two lateral sides of a
column [i.e. Breadth (b) X Depth (D)], hence reversely knowing the A g we can determine the Lateral
Dimensions.
For making a Square Section just Determine the Root Value of the Ag. Like if the Value of Ag is 62500
mm2 Then considering square section of a column we can get each side

Also Rectangular Column Sections Can be made by using different proportion say b : D = 1 : 2 , Hence
D=2b , Therefore, Ag = b X D = b X 2b = 2b2 or b=

Hence D can be also determined as D=2b after Calculating the b.


Most of the times after calculating the sides of a column it will give results such as 196.51mm or 323.62
etc. values, which practically cannot be provided at field, hence we must increase those values to the
nearest greater multiple of 25mm (i.e. 1 inch). For examples a value of 196.51mm may be increased to
200mm or 225mm or 250 mm even, and a value of 323.62mm may be increased to 350mm. more it will
be increased the more it will be safer, but it is uneconomical to increase by a very high amount, it should
not be increased more than by 75mm to consider the economical factor.

STEP 4Check For Long/Short Columns:

Depending upon the ratio of Effective Length to the Least Lateral Dimension of a column, a column may
be classified as Long Column and Short Column. If the value of this ratio is less than 12 then its called
as a short column and if the value is more than 12 then its called as a Long Column. A short column
mainly fails by direct compression and has a lesser chance of failure by buckling. And in the case of a
long column the failure mainly occurs due to the buckling alone. Long column being slender, that is
being thin like stick as compared with its length it grows a tendency to get bended by deviating from its
verticality under the action of loads. Due to this tendency of long column to get buckled (bended) a
long column of all same properties and dimensions that of a short column will be able to carry much
lesser load safely than that of the short column. Suppose a 400mmx400mm short column can take a
load of 1000KN , then a long column of 400mmx400mm having same grade of concrete, same amount
of reinforcement and same workmanship will be able to carry a lesser load like say about 800KN only,
hence we get a loss of 200KN which is 20% loss of load carrying capacity. So the above formula used in
Step 3 holds good only for the Short Column. For using it in long column a little modification is needed,
which I will update it later when I will get hands on this article again. For now let us concentrate on
Short Column. First of all we need to find out the effective length of a column, which can be obtained by
multiplying a factor with the actual unsupported length of the column. The factor depends upon the
end condition of the column. In most general cases we use a Both End Fixed Column for which The
Factor is 0.65.
Therefore, Effective Length = Effective Length Factor (0.65) x Unsupported Length (l). suppose a
column has a unsupported length of 2.7m = 2700mm, hence the effective length will be lef = 0.65x2700
= 1755mm. Least lateral dimension means the shorter of the two dimensions of column that is length
and breadth. But in case of a circular column as there is only diameter, hence we will use the diameter.
Suppose a column is of 400mmx200mm section and has an unsupported length of 2700mm, then the
Ration of Effective length t the Least Lateral Dimension will be as follows :(Effective Length/Least Lateral Dimension) = (lef/b) = (1755/200) = 8.775 which is less than 12 and
hence is a Short Column.

STEP 5Check For Eccentricity :


Eccentricity means deviating from the true axis. Thus an Eccentric Load refers to a load which is not
acting through the line of the axis of the column in case of column design. The eccentric load cause the
column to bend towards the eccentricity of the loading and hence generates a bending moment in the
column. In case of eccentric loading we have to design the column for both the Direct Compression and
also for the bending moment also. Practically all columns are eccentric to some extent which may vary
from few millimetres to few centimetres. In practical field it is almost impossible to make a perfectly
axially loaded column, as a reason we have to consider a certain value of eccentricity for safety even
though if we are designing for a axially loaded column. The conditions of considering eccentricity and
its value may differ from code to code according to the country. Here I will tell you what I.S. : 46-2000
says. According to it the eccentricity which we have to consider for design must be taken as the greater
of the followings :i) 20mm.
ii) (lef/500) + (b/30)
Where,
lef = Effective Length of the Column
b = Lateral Dimension of the Column (We have to calculate two separate values for two sides in case of
rectangular column)

Permissible Eccentricity :- 0.05b where b is the dimension of a side of a column, we have to check for
two sides separately in case of rectangular column.
The Permissible eccentricity must be greater than or equal to the actual eccentricity
of the column. Or else we have to design it for bending also.

STEP 6 :- Calculating The Area Of Steel Required :


Now the Area of Steel Required Asc is to be calculated from the Ag as the predetermined percentage of
Ag. For example if the Gross-Sectional Area of the Column is 78600 mm 2 and at the starting of
calculation of Ag it was assumed that 1% Steel is used then we get,
Asc = 1% of Ag = 0.01Ag = 0.01 X 78600 = 786 mm2
Now we shall provide such amount of Reinforcements that the Cross-Sectional Area of the
Reinforcement provided is Equal to or Greater than the Cross-Sectional Area of Steel required above.
Hence in the above case we shall Provide 4 Nos. of 16mm Diameter Bars
Hence, The Actual Area of Steel Provided,

Hence the Area of Steel Provided is Greater than Area Of Steel Required, Hence the Structure will be
Safe.
NOTE : The minimum of 4 Nos. of Bars to be provided at the four corners of a
rectangular or Square Columns and minimum diameter of Bars that to be used
is 12mm Diameter. Hence 4 Nos. of 12mm Diameter Bars are must in any
Columns irrespective of their necessities.

STEP 7 :- Determining The Diameter and Spacing Of The


Lateral Ties:
In this step we will Determine the Diameter and the Spacing of the Lateral Ties or Transverse Links or
Binders.
The Diameter of the Ties shall not be lesser than the Greatest of the following two values
1. 5mm
2. 1/4th of the Diameter of the Largest Diameter Bar
For an example if a Column has 16mm and 20mm both types of bar as Longitudinal Bars or main
Reinforcement then 1/4th of 20mm = 5mm Hence we shall provide 5mm diameter Ties.
The Spacing of Ties shall not exceed the least of the followings three values
1. Least Lateral Dimension
2. 16 Times of the Diameter of the Smallest Diameter Longitudinal Bar

3. 48 Times of the Diameter of Ties


For an example A Column of 250mm X 350mm Dimension having 20mm and 16mm Diameter
Longitudinal Bars and 5mm Diameter Ties we get,

Least Lateral Dimension = 250mm

16 Times of the Diameter of the Smallest Diameter Longitudinal Bar = 16 X 16 =


256mm

48 Times of the Diameter of Ties = 48 X 5 = 220mm

Hence Provide 5mm Diameter Ties @ 200mm C/C


[In this case our objective is to minimize the value to reduce the spacing and to make the structure
more stable, hence we shall take least value and suitably in a multiple of 25mm]