PROJECT:UttamSucrotech

CABNO.
FROM

CABLESCHEDULE

PANEL
TO

CABLESIZE

SCOPE

LENGTH
FROM

inSqmm

TDC/CS/USL

TBDETAIL
TO

REMARKS

TGMCC
(ACDB)

TCP

3CX2.5SqmmCu

CLIENT

40

TB:P1:1
TB:P1:2

240VACsupply

TGMCC
(ACDB)

TGP

3CX2.5SqmmCu

CLIENT

40

TB:P2:1
TB:P2:2

240VACsupply

TGMCC
(ACDB)

MCSP

3CX2.5SqmmCu

CLIENT

40

X1:1
X1:2

240VACsupply

TGMCC
(ACDB)

AVRPANEL

3CX2.5SqmmCu

CLIENT

40

X90:1
X90:2

240VACsupply

TGMCC
(ACDB)

GRP

3CX2.5SqmmCu

CLIENT

40

TB3:1
TB3:2

240VACsupply

TGMCC
(ACDB)

WATERLEAKAGE
DETECTOR

3CX2.5SqmmCu

CLIENT

40

L1
L2

240VACsupply

TGMCC
(ACDB)

LASCPTP

3CX2.5SqmmCu

CLIENT

20

ACTB:1
ACTB:2

240VACsupply

TGMCC
(ACDB)

NGRP

3CX2.5SqmmCu

CLIENT

20

X5:1
X5:2

240VACsupply

TGMCC
(ACDB)

ALTERNATOR
AUXTB

3CX2.5SqmmCu

CLIENT

40

HR1
HR2

240VACsupply

10

TGMCC
(ACDB)

ALTERNATOR
AUXTB

3CX2.5SqmmCu

CLIENT

40

HS1
HS2

240VACsupply

11

TGMCC
(ACDB)

DCMSP

3CX2.5SqmmCu

CLIENT

40

X6:1
X6:6

240VACsupply

12

CHARGER
CUMDCDB

DCMSP

3CX16SqmmCu

CLIENT

20

X3+
X3

X1:1
X1:2

110VDCsupply

13

CHARGER
CUMDCDB

TCP

3CX2.5SqmmCu

CLIENT

20

X4+
X4

TB:P2:1
TB:P2:2

110VDCsupply

14

CHARGER
CUMDCDB

MCSP

3CX2.5SqmmCu

CLIENT

20

X5+
X5

X2:1
X2:2

110VDCsupply

15

CHARGER
CUMDCDB

GRP

3CX2.5SqmmCu

CLIENT

20

X6+
X6

TB3:4
TB3:5

110VDCsupply

16

CHARGER
CUMDCDB

AVRPANEL

3CX2.5SqmmCu

CLIENT

20

X7+
X7

X80:1
X80:2

110VDCsupply

17

CHARGER
CUMDCDB

NGRP

3CX2.5SqmmCu

CLIENT

40

X8+
X8

X6:1
X6:2

110VDCsupply

010716

SHEET:1OF21

PROJECT:UttamSucrotech

18

DCMSP

CABLESCHEDULE

TCP

12Cx1.5SqmmCu.

CLIENT

30

TDC/CS/USL

X4:4
X4:5
X4:8
X4:9
X4:12
X4:13
X4:10
X4:11
X4:1
X4:2

TB:X7:7
TB:X7:8
TB:X7:1
TB:X7:2
TB:X7:3
TB:X7:4
TB:X7:5
TB:X7:6
TB:X7:9
TB:X7:10

EOPmotorstart/stopcommand
EOPmotorONfeedback
EOPmotorOverloaded
EOPmotorFFRoperated
Shuntinputtoammeter

19

DCMSP

EOPARMATURE

3CX10SqmmCu

CLIENT

30

X2:1
X2:2

(+)
()

110VDCsupply

20

DCMSP

EOPFIELD

3CX2.5SqmmCu

CLIENT

30

X3:1
X3:2

(+)
()

110VDCsupply

21

LASCPTP

MCSP

5Cx2.5SqmmCu

CLIENT

40

X2:1
X2:2
X2:3
X2:4

X21:1
X21:2
X21:3
X21:4

MeteringPTsupply

22

LASCPTP

GRP

5Cx2.5SqmmCu

CLIENT

40

X1:3
X1:6
X1:9
X1:10

TB1:1
TB1:2
TB1:3
TB1:4

DiffCTsupply

23

LASCPTP

GRP

5Cx2.5SqmmCu

CLIENT

40

X3:1
X3:2
X3:3
X3:4

TB2:9
TB2:10
TB2:11
TB2:12

ProtectionPTsupply

24

LASCPTP

GRP

3CX2.5SqmmCu

CLIENT

40

X4:4
X4:5
X4:6

TB2:13
TB2:14
TB2:15

Mainexcitationsupplyforfusemonitoring

25

LASCPTP

GRP

3CX2.5SqmmCu

CLIENT

40

X2:9
X2:10
X2:11
X2:12

TB2:1
TB2:2
TB2:3
TB2:4

MeteringPTsupplyforfusemonitoring

26

LASCPTP

AVRPANEL

3CX2.5SqmmCu

CLIENT

40

X2:5
X2:6
X2:7
X2:8

X10:1
X10:2
X10:3

SensingPTsupply

27

LASCPTP

AVRPANEL

3CX2.5SqmmCu

CLIENT

40

X4:1
X4:2
X4:3

X01:4
X01:5
X01:6

Standbyexcitationsupply

28

NGRP

AVRPANEL

3CX2.5SqmmCu

CLIENT

40

X1:1
X1:3

X11:1
X21:2

DroopCT

010716

SHEET:2OF21

PROJECT:UttamSucrotech

CABLESCHEDULE

TDC/CS/USL

29

NGRP

MCSP

3Cx1.5SqmmCu

CLIENT

40

X7:1
X7:2

X4:23
X4:24

TGNISNOcontact

30

NGRP

MCSP

5CX1.5SqmmCu

CLIENT

40

X5:3
X5:4
X5:7
X5:8

X3:5
X3:6
X3:3
X3:4

NISOpencommand
NISClosecommand

31

NGRP

MCSP

5Cx2.5SqmmCu

CLIENT

40

X2:3
X2:6
X2:9
X2:10

X20:1
X20:2
X20:3
X20:4

MeteringCTsupply

32

NGRP

GRP

5Cx2.5SqmmCu

CLIENT

40

X3:3
X3:6
X3:9
X3:10

TB1:8
TB1:7
TB1:6
TB1:5

DiffCTsupply

33

NGRP

GRP

3CX2.5SqmmCu

CLIENT

40

X4:1
X4:3

TB1:9
TB1:10

E/FCTsupply

34

TGMCC

TCP

12Cx1.5SqmmCu.

CLIENT

40

TB:X1:5
TB:X1:6
TB:X1:1
TB:X1:2
TB:X1:3
TB:X1:4
TB:X1:7
TB:X1:8

BarringgearmotorStart/stopcommand
BarringgearONfeedback
Barringgearmotortripindication.
CTinput.

35

TGMCC

TGP

3Cx1.5SqmmCu

CLIENT

40

TB:FX7:11
TB:FX7:12

PS204:BarringgearmotorI/L

36

TGMCC

TCP

12Cx1.5SqmmCu.

CLIENT

40

TB:X2:5
TB:X2:6
TB:X2:1
TB:X2:2
TB:X2:3
TB:X2:4
TB:X2:7
TB:X2:8

GVCmotorstart/stopcommand

TB:X9A:5
TB:X9A:6
TB:X9A:1
TB:X9A:2
TB:X9A:3
TB:X9A:4
TB:X9A:7
TB:X9A:8

ACOP1motorstart/stopcommand.

37

010716

TGMCC

TCP

12Cx1.5SqmmCu.

CLIENT

40

GVCmotorONfeedback
GVCtripindication.
CTinput.

ACOP1motorONfeedback
ACOP1motortripindication.
CTinput.

SHEET:3OF21

PROJECT:UttamSucrotech

38

39

40

TGMCC

TGMCC

TGMCC

CABLESCHEDULE

TCP

TCP

TCP

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

CLIENT

CLIENT

CLIENT

40

40

40

TDC/CS/USL

TB:X9B:5
TB:X9B:6
TB:X9B:1
TB:X9B:2
TB:X9B:3
TB:X9B:4
TB:X9B:7
TB:X9B:8

ACOP2motorstart/stopcommand.

TB:X4:5
TB:X4:6
TB:X4:1
TB:X4:2
TB:X4:3
TB:X4:4
TB:X4:7
TB:X4:8

Vapourextractorstart/stopcommand

TB:X3:5
TB:X3:6
TB:X3:1
TB:X3:2
TB:X3:3
TB:X3:4
TB:X3:7
TB:X3:8

AOPmotorstart/stopcommand

ACOP2motorONfeedback
ACOP2motortripindication.
CTinput.

VapourextractorONfeedback
Vapourextractortripindication.
CTinput.

AOPmotorONfeedback
AOPmotortripindication.
CTinput.

41

TGMCC

TCP

3Cx1.5SqmmCu

CLIENT

40

TB:HX1:9
TB:HX1:10

LubeoilheaterOncommand

42

TGMCC

BARRING
GEARMOTOR

3CX6SqmmCu

CLIENT

40

U1
V1
W1

415V3Phsupply

43

TGMCC

AOPMOTOR

3CX6SqmmCu

CLIENT

40

U1
V1
W1

415V3Phsupply

44

TGMCC

ACOP1

3CX2.5SqmmCu

CLIENT

40

U1
V1
W1

415V3Phsupply

45

TGMCC

ACOP2

3CX2.5SqmmCu

CLIENT

40

U1
V1
W1

415V3Phsupply

46

TGMCC

GVCMOTOR

3CX2.5SqmmCu

CLIENT

30

U1
V1
W1

415V3Phsupply

47

TGMCC

VEMOTOR

3CX2.5SqmmCu

CLIENT

30

U1
V1
W1

415V3Phsupply

010716

SHEET:4OF21

PROJECT:UttamSucrotech

48

49

50

51

52

53

54

TCP

TCP

TCP

TCP

TCP

TCP

TCP

CABLESCHEDULE

BGMLPBS

GVCLPBS

AOPLPBS

VELPBS

EOPLPBS

ACOP1LPBS

ACOP2LPBS

5CX1.5SqmmCu

5CX1.5SqmmCu

5CX1.5SqmmCu

5CX1.5SqmmCu

5CX1.5SqmmCu

5CX1.5SqmmCu

5CX1.5SqmmCu

CLIENT

CLIENT

CLIENT

CLIENT

CLIENT

CLIENT

CLIENT

30

30

30

30

30

30

30

TDC/CS/USL

TB:X1:17
TB:X1:18
TB:X1:15
TB:X1:16

START

Startcommand

STOP

Stopcommand

TB:X2:13
TB:X2:14
TB:X2:15
TB:X2:16

START

Startcommand

STOP

Stopcommand

TB:X3:15
TB:X3:16
TB:X3:13
TB:X3:14

START

Startcommand

STOP

Stopcommand

TB:X4:13
TB:X4:14
TB:X4:15
TB:X4:16

START

Startcommand

STOP

Stopcommand

TB:X7:19
TB:X7:20
TB:X7:17
TB:X7:18

START

Startcommand

STOP

Stopcommand

TB:X9A:17
TB:X9A:18
TB:X9A:15
TB:X9A:16

START

Startcommand

STOP

Stopcommand

TB:X9B:17
TB:X9B:18
TB:X9B:15
TB:X9B:16

START

Startcommand

STOP

Stopcommand

55

TCP

AVRPANEL

3Cx1.5SqmmCu

CLIENT

20

TB:FX6:1
TB:FX6:2

X800:9
X800:10

Underspeedcontact

56

TCP

VIBJB600

8TX0.5SqmmCu

CLIENT

40

TB:VX1:1
TB:VX1:2
TB:VX1:3
TB:VX1:4
TB:VX1:5
TB:VX1:6
TB:VX1:7
TB:VX1:8
TB:VX3:1
TB:VX3:2
TB:VX3:3
TB:VX3:4
TB:VX3:5
TB:VX3:6
TB:VX3:7
TB:VX3:8

ZT600

ZT600:AxialdisplacementXaxis

ZT601

ZT601:AxialdisplacementYaxis

XT600

XT600:TurbineforebearingredialvibrationXaxis

XT601

XT601:TurbineforebearingredialvibrationYaxis

010716

SHEET:5OF21

PROJECT:UttamSucrotech

57

58

010716

TCP

TCP

CABLESCHEDULE

VIBJB601

JB200

8TX0.5SqmmCu

8TX0.5SqmmCu

CLIENT

CLIENT

40

40

TB:VX4:1
TB:VX4:2
TB:VX4:3
TB:VX4:4
TB:VX4:5
TB:VX4:6
TB:VX4:7
TB:VX4:8
TB:VX5:1
TB:VX5:2
TB:VX5:3
TB:VX5:4
TB:VX5:5
TB:VX5:6
TB:VX5:7
TB:VX5:8
TB:VX6:1
TB:VX6:2
TB:VX6:3
TB:VX6:4
TB:VX6:5
TB:VX6:6
TB:VX6:7
TB:VX6:8
TB:TS:1
TB:TS:2
TB:TS:3
TB:TS:4
TB:TS:25
TB:TS:26
TB:TS:27
TB:TS:28
TB:TS:29
TB:TS:30
TB:TS:31
TB:TS:32
TB:TS:33
TB:TS:34
TB:TS:35
TB:TS:36
TB:TS:37
TB:TS:38
TB:TS:39
TB:TS:40

TDC/CS/USL

XT602

XT602:TurbineafterbearingredialvibrationXaxis

XT603

XT603:TurbineafterbearingredialvibrationYaxis

XT604

XT604:GearboxforebearingredialvibrationXaxis

XT605

XT605:GearboxforebearingredialvibrationYaxis

XT606

XT606:GearboxafterbearingredialvibrationXaxis

XT607

XT607:GearboxafterbearingredialvibrationYaxis

TB:1
TB:2
TB:3

RTD200I/P(Icore):TurbineHPbearingtemp

TB:8
TB:9
TB:10

RTD220I/P(Icore):Turbinethrustactivetopbearingtemp

TB:15
TB:16
TB:17

RTD221I/P(Icore):Turbinethrustnonactivetopbearing
temp

RTD218I/P(Icore):Lubeoiltempbeforecooler
TB:22
TB:23
TB:24
RTD219I/P(Icore):Lubeoiltempaftercooler
TB:26
TB:27
TB:28

SHEET:6OF21

PROJECT:UttamSucrotech

59

60

TCP

TCP

CABLESCHEDULE

JB201

JB200

8TX0.5SqmmCu

12Cx1.5SqmmCu.

CLIENT

CLIENT

40

30

TDC/CS/USL

RTD202I/P(Icore):Pinionforebearingtemp

TB:TS:9
TB:TS:10
TB:TS:11
TB:TS:12
TB:TS:13
TB:TS:14
TB:TS:15
TB:TS:16
TB:TS:17
TB:TS:18
TB:TS:19
TB:TS:20
TB:TS:21
TB:TS:22
TB:TS:23
TB:TS:24
TB:TS:5
TB:TS:6
TB:TS:7
TB:TS:8

RTD203I/P(Icore):Pinionafterbearingtemp

RTD204I/P(Icore):Gearboxforebearingtemp

RTD205I/P(Icore):Gearboxafterbearingtemp

RTD201I/P(Icore):TurbineLPbearingtemp

TB:FX4:3
TB:FX4:4
TB:FX2:11
TB:FX2:12
TB:FX2:15
TB:FX2:16

TB:34
TB:35
TB:37
TB:38
TB:40
TB:41

DPIS201:DiffPracrossthecontroloilfilterhigh
ESVclosefeedback
ESVopenfeedback

61

TCP

JB201

3Cx1.5SqmmCu

CLIENT

40

TB:FX7:19
TB:FX7:20

tobechecked ManualhandwheelI/L
atsite

62

TCP

JB202

3Cx1.5SqmmCu

CLIENT

30

TB:FX4:1
TB:FX4:2

TB:1
TB:2

DPIS201:DiffPracrossthelubeoilfilterhigh

63

TCP

LAL203

3Cx1.5SqmmCu

CLIENT

30

TB:FX4:17
TB:FX4:18

LAL203

LAL203:OverheadLubeoiltanklevellow

64

TCP

LAH202

3Cx1.5SqmmCu

CLIENT

30

TB:FX4:19
TB:FX4:20

LAH202

LAH202:OverheadLubeoiltanklevelhigh

65

TCP

SV200

3CX2.5SqmmCu

CLIENT

40

TB:X10:1
TB:X10:2

SV200

110VDCsupply

66

TCP

SV201

3CX2.5SqmmCu

CLIENT

30

TB:X14:1
TB:X14:2

SV201

110VDCsupply

67

TCP

S203

3CX2.5SqmmCu

CLIENT

40

TB:X13:1
TB:X13:2

S203

110VDCsupply

68

TCP

HPACTUATOR

1Px0.5SqmmCu

CLIENT

30

TB:AX2:1
TB:AX2:2
TB:AX2:3

HPACTUATOR GovernorO/Ptoactuator

010716

SHEET:7OF21

PROJECT:UttamSucrotech

CABLESCHEDULE

TDC/CS/USL

69

TCP

TGP

3CX2.5SqmmCu

CLIENT

30

TB:P3:1
TB:P3:2

TB:P1:1
TB:P1:2

24VDCsupply

70

TCP

TGP

1Px0.5SqmmCu

CLIENT

30

TB:FX1:1
TB:FX1:2

TB:S1:1
TB:S1:2

SI200:Speedsignal

71

TCP

TGP

1Px0.5SqmmCu

CLIENT

30

TB:FX1:10
TB:FX1:11

TB:AI:10
TB:AI:11
TB:AI:12

PT101:Exhaustpr

72

TCP

TGP

12Cx1.5SqmmCu.

CLIENT

30

TB:FX8:3
TB:FX8:4
TB:FX8:1
TB:FX8:2
TB:FX8:7
TB:FX8:8
TB:FX8:5
TB:FX8:6
TB:FX8:7
TB:FX8:8

TB:T2:1
TB:T2:2
TB:T2:3
TB:T2:4
TB:T2:5
TB:T2:6
TB:T2:7
TB:T2:9
TB:T2:10
TB:T2:11

TAL101:Inletsteamtemplow(TI101/R1)

TB:FX2:3
TB:FX2:4
TB:FX2:5
TB:FX2:6
TB:FX2:3
TB:FX2:14
TB:FX2:7
TB:FX2:8
TB:FX2:9
TB:FX2:10

TB:FX2:1
TB:FX2:2
TB:FX2:7
TB:FX2:8
TB:FX2:13
TB:FX2:14
TB:FX2:20
TB:FX2:21
TB:FX2:26
TB:FX2:27
TB:FX2:31
TB:FX2:32

PS203:Lubeoilprverylow

TB:FX4:1
TB:FX4:2
TB:FX4:7
TB:FX4:8
TB:FX4:14
TB:FX4:15
TB:FX4:20
TB:FX4:21
TB:FX4:26
TB:FX4:27

PS200:Lubeoilprlow

73

74

010716

TCP

TCP

TGP

TGP

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

CLIENT

CLIENT

30

30

TB:FX4:5
TB:FX4:6
TB:FX4:7
TB:FX4:8
TB:FX4:9
TB:FX4:10
TB:FX4:11
TB:FX4:12

TALL101:Inletsteamtempverylow(TI101/R2)
TAH101:Inletsteamtemphigh(TI101/R3)
TAHH101:Inletsteamtempveryhigh(TI101/R4)
TAH102:Exhauststeamtemphigh(TI102/R1)

PS206:Controloilprverylow
PS209:Tripoilprverylow
PS103:Exhaustprveryhigh
PS101:Inletprveryhigh
PS101A:Ineltprverylow

PS205:Controloilprlow
PS102:Exhaustprhigh
PS100:Ineltprhigh
PS100A:Ineltprlow

SHEET:8OF21

PROJECT:UttamSucrotech

75

76

TCP

TCP

CABLESCHEDULE

TGP

TGP

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

CLIENT

CLIENT

30

30

TDC/CS/USL

PS200:AOPautostart

TB:FX7:1
TB:FX7:2
TB:FX7:3
TB:FX7:4
TB:FX7:11
TB:FX7:12
TB:FX7:13
TB:FX7:14
TB:FX7:5
TB:FX7:6

TB:FX7:2
TB:FX7:3
TB:FX7:5
TB:FX7:6
TB:FX7:14
TB:FX7:15
TB:FX7:17
TB:FX7:18
TB:FX7:8
TB:FX7:9

TB:FX7:7
TB:FX7:8
TB:FX7:9
TB:FX7:10
TB:FX7:15
TB:FX7:16
TB:FX7:17
TB:FX7:18

TB:FX7:20
TB:FX7:21
TB:FX7:23
TB:FX7:24
TB:FX7:26
TB:FX7:27
TB:FX7:29
TB:FX7:30

202
203

TI100:Inletsteamtempindicator

202
203

TI102:Exhauststeamtempindicator

PS200:AOPautostop
PS201:EOPautostart
PS201:EOPautostop
PS204:BarringgearmotorI/L
PS207:ACOP1autostart
PS207:ACOP1autostop
PS208:ACOP2autostart
PS208:ACOP2autostop

77

TE101

TGP

2Cx16swg
Ktype

CLIENT

30

78

JB201

TGP

2Cx16swg
Ktype

CLIENT

30

79

TE100

TGP

2Cx16swg
Ktype

CLIENT

30

3
2

TT100:Inletsteamtemptransmitter

80

TE102

TGP

2Cx16swg
Ktype

CLIENT

30

3
2

TT102:Exhauststeamtemptransmitter

81

MCSP

TCP

5CX1.5SqmmCu

CLIENT

20

X8:5
X8:6
X8:7
X8:8

TB:DX1:5A
TB:DX1:6A
TB:DX1:7A
TB:DX1:8A

Speedraise/lowercommand

82

GRP

TCP

3Cx1.5SqmmCu

CLIENT

20

TB4:9
TB4:10

TB:X10:11
TB:X10:12

SV200contact

83

GRP

TCP

3Cx1.5SqmmCu

CLIENT

20

TB4:62
TB4:63

TB:FX2:1
TB:FX2:2

86TNCcontact

84

MCSP

TCP

3Cx1.5SqmmCu

CLIENT

20

X24:3
X24:4

TB:DX1:9
TB:DX1:10

TGCB(521)NOcontact

85

MCSP

TCP

3Cx1.5SqmmCu

CLIENT

20

X24:133
X24:134

TB:DX1:11
TB:DX1:12

TGsynchwithGrid/DG

86

MCSP

TCP

3Cx1.5SqmmCu

CLIENT

20

X24:135
X24:136

TB:DX1:33
TB:DX1:34

TGsynchwithGrid

010716

SHEET:9OF21

PROJECT:UttamSucrotech

CABLESCHEDULE

TDC/CS/USL

87

MCSP

TCP

1Px0.5SqmmCu

CLIENT

20

TDTB1:1
TDTB1:2

TB:FX1:7
TB:FX1:8

kWtransducerinput

88

MCSP

TGCB(521)

3Cx1.5SqmmCu

CLIENT

40

X4:1
X4:2

TGCB(521)NOcontact

89

MCSP

TGCB(521)

3Cx1.5SqmmCu

CLIENT

40

X3:1
X3:2

Autotripindication

90

MCSP

TGCB(521)

3Cx1.5SqmmCu

CLIENT

40

X3:3
X3:4

Springchargedindication

91

MCSP

TGCB(521)

5CX1.5SqmmCu

CLIENT

40

X9:9
X9:10
X9:1
X9:2

Closecommand
Tripcommand

92

MCSP

GRIDCB(522)

3Cx1.5SqmmCu

CLIENT

40

X4:3
X4:4

GRIDCB(522)NOcontact

93

MCSP

GRIDCB(522)

5CX1.5SqmmCu

CLIENT

40

X10:9
X10:10
X10:1
X10:2

Closecommand
Tripcommand

94

MCSP

AUXTRAFOCB1(52 3Cx1.5SqmmCu
3)

CLIENT

40

X4:5
X4:6

AUXTRAFOCB1(523)NOcontact

95

MSCP

AUXTRAFOCB1(52 5CX1.5SqmmCu
3)

CLIENT

40

X11:9
X11:10
X11:1
X11:2

Closecommand
Tripcommand

96

MCSP

LTCB1(524)

3Cx1.5SqmmCu

CLIENT

40

X4:7
X4:8

LTCB1(524)NOcontact

97

MCSP

LTCB1(524)

5CX1.5SqmmCu

CLIENT

40

X12:9
X12:10
X12:1
X12:2

Closecommand
Tripcommand

98

MCSP

AUXTRAFOCB2(52 3Cx1.5SqmmCu
5)

CLIENT

40

X4:9
X4:10

AUXTRAFOCB2(525)NOcontact

99

MCSP

AUXTRAFOCB2(52 5CX1.5SqmmCu
5)

CLIENT

40

X13:9
X13:10
X13:1
X13:2

Closecommand

X4:11
X4:12

100

010716

MCSP

LTCB2(526)

3Cx1.5SqmmCu

CLIENT

40

Tripcommand

LTCB2(526)NOcontact

SHEET:10OF21

PROJECT:UttamSucrotech

101

MCSP

CABLESCHEDULE

LTCB2(526)

5CX1.5SqmmCu

CLIENT

40

TDC/CS/USL

X14:9
X14:10
X14:1
X14:2

Closecommand
Tripcommand

102

MCSP

AUXTRAFOCB3(52 3Cx1.5SqmmCu
7)

CLIENT

40

X4:9
X4:10

AUXTRAFOCB2(527)NOcontact

103

MCSP

AUXTRAFOCB3(52 5CX1.5SqmmCu
7)

CLIENT

40

X15:9
X15:10
X15:1
X15:2

Closecommand
Tripcommand

104

MCSP

LTCB3(528)

3Cx1.5SqmmCu

CLIENT

40

X4:11
X4:12

LTCB3(528)NOcontact

105

MCSP

LTCB3(528)

5CX1.5SqmmCu

CLIENT

40

X16:9
X16:10
X16:1
X16:2

Closecommand
Tripcommand

106

MCSP

DGCB1(529)

3Cx1.5SqmmCu

CLIENT

40

X4:17
X4:18

DGCB1(529)NOcontact

107

MCSP

DGCB1(529)

5CX1.5SqmmCu

CLIENT

40

X17:9
X17:10
X17:1
X17:2

Closecommand
Tripcommand

108

MCSP

DGCB2(5210)

3Cx1.5SqmmCu

CLIENT

40

X4:19
X4:20

DGCB2(5210)NOcontact

109

MCSP

DGCB2(5210)

5CX1.5SqmmCu

CLIENT

40

X18:9
X18:10
X18:1
X18:2

Closecommand
Tripcommand

110

MCSP

LTB/CCB1(5211)

3Cx1.5SqmmCu

CLIENT

40

X4:17
X4:18

LTB/CCB1(5211)NOcontact

111

MCSP

LTB/CCB1(5211)

5CX1.5SqmmCu

CLIENT

40

X19:9
X19:10
X19:1
X19:2

Closecommand
Tripcommand

112

MCSP

BUSPT(PT2)

3CX2.5SqmmCu

CLIENT

40

X7:1
X7:2
X7:3

BUSPT(PT2)supply

113

MCSP

GRIDPT(PT3)

3CX2.5SqmmCu

CLIENT

40

X7:4
X7:5
X7:6

GRIDPT(PT3)supply

010716

SHEET:11OF21

PROJECT:UttamSucrotech

CABLESCHEDULE

TDC/CS/USL

114

MCSP

DGCB(524)

3CX2.5SqmmCu

CLIENT

40

X7:7
X7:8
X7:9

PT5supply

115

MCSP

LTPT1(PT5)

3CX2.5SqmmCu

CLIENT

40

X7:10
X7:11
X7:12

LTPT1(PT5)supply

116

MCSP

LTPT2(PT6)

3CX2.5SqmmCu

CLIENT

40

X7:13
X7:14
X7:15

LTPT2(PT6)supply

117

MCSP

LTPT3(PT7)

3CX2.5SqmmCu

CLIENT

40

X7:16
X7:17
X7:18

LTPT3(PT7)supply

118

MCSP

LTBUSPT1(PT8)

3CX2.5SqmmCu

CLIENT

40

X7:19
X7:20
X7:21

LTBUSPT1(PT8)supply

119

MCSP

LTBUSPT2(PT9)

3CX2.5SqmmCu

CLIENT

40

X7:22
X7:23
X7:24

LTBUSPT2(PT9)supply

120

MCSP

LTBUSPT3(PT10)

3CX2.5SqmmCu

CLIENT

40

X7:25
X7:26
X7:27

LTBUSPT3(PT10)supply

121

MCSP

GRP

5Cx2.5SqmmCu

CLIENT

20

X20:5
X20:7
X20:9
X20:11

TB1:14
TB1:13
TB1:12
TB1:11

MeteringCTsupply

122

MCSP

AVRPANEL

3Cx1.5SqmmCu

CLIENT

20

X24:5
X24:6

X200:21
X200:22

TGCB(521)NOcontact

123

MCSP

AVRPANEL

3Cx1.5SqmmCu

CLIENT

20

X24:15
X24:16

X100:13
X100:14

TGsynchwithGrid

124

GRP

AVRPANEL

3Cx1.5SqmmCu

CLIENT

20

125

MCSP

AVRPANEL

5CX1.5SqmmCu

CLIENT

20

X8:1
X8:2
X8:3
X8:4

X100:7
X100:8
X100:11
X100:12

Voltageraise/lowercommand

126

GRP

AVRPANEL

3Cx1.5SqmmCu

CLIENT

20

TB4:11
TB4:12

AVRTripfeedback

127

GRP

AVRPANEL

3Cx1.5SqmmCu

CLIENT

20

TB4:58
TB4:59

X800:1
X800:2

Tripcommand(86Gcontact)

010716

PTfusefailurefeedback

SHEET:12OF21

PROJECT:UttamSucrotech

CABLESCHEDULE

TDC/CS/USL

128

GRP

MCSP

3Cx1.5SqmmCu

CLIENT

20

TB4:1
TB4:2

X24:7
X24:8

TGCB(521)NOcontact

129

GRP

MCSP

3Cx1.5SqmmCu

CLIENT

20

TB4:1
TB4:2

X24:13
X24:14

GRIDCB(522)NOcontact

130

GRP

ALTERNATOR
AUXTB

3CX2.5SqmmCu

CLIENT

40

TB2:23
TB2:24
TB2:25

SLIPRING

SlipringinputforrotorE/F

131

ALTAUXTB

AVRPANEL

3CX2.5SqmmCu

CLIENT

40

X01:1
X01:2
X01:3

PMGsupply

132

GRP

ALTERNATOR
AUXTB

8TX0.5SqmmCu

CLIENT

30

TB5:1
TB5:2
TB5:3
TB5:4
TB5:5
TB5:6
TB5:7
TB5:8
TB5:9
TB5:10
TB5:11
TB5:12
TB5:13
TB5:14
TB5:15
TB5:16
TB5:17
TB5:18

R11
R12
R13
R71
R72
R73
R21
R22
R23
R81
R82
R83
R31
R32
R33
R91
R92
R93

WindingRTD(Rph1)

TB5:19
TB5:20
TB5:21
TB5:22
TB5:23
TB5:24
TB5:25
TB5:26
TB5:27
TB5:28
TB5:29
TB5:30
TB5:31
TB5:32
TB5:33
TB5:34
TB5:35
TB5:36

B11
B12
B13
B21
B22
B23
A11
A12
A13
A21
A22
A23
A31
A32
A33
A41
A42
A43

AlternatorDEbearingRTD

133

010716

GRP

ALTERNATOR
AUXTB

8TX0.5SqmmCu

CLIENT

30

WindingRTD(Rph2)

WindingRTD(Yph1)

WindingRTD(Yph2)

WindingRTD(Bph1)

WindingRTD(Bph2)

AlternatorNDEbearingRTD

HotairRTD1

HotairRTD2

ColdairRTD1

ColdairRTD2

SHEET:13OF21

PROJECT:UttamSucrotech

134

GRP

CABLESCHEDULE

ALTERNATORAUXTB 5CX1.5SqmmCu

CLIENT

30

TDC/CS/USL

TB3:27
TB3:28
TB3:29
TB3:30

COM
NO
COM
NO

WLD1Acted
WLD2Acted

135

ALTERNATOR AVRPANEL
AUXTB

3CX6SqmmCu

CLIENT

30

F1
F2

X05:1
X05:2

Fieldsupply

136

FT100

TCP

1Px0.5SqmmCu

CLIENT

40

FT100

TB:FIQR:1
TB:FIQR:2
TB:FIQR:3

FT100:Inletflow

137

MPU200

TCP

1Px0.5SqmmCu

CLIENT

30

MPU200

TB:AX1:1
TB:AX1:2
TB:AX1:3

Speedsignal1

138

MPU201

TCP

1Px0.5SqmmCu

CLIENT

30

MPU201

TB:AX1:4
TB:AX1:5
TB:AX1:6

Speedsignal2

139

JB200

RTD218(Icore)

1Tx0.5Sqmmcu

CLIENT

20

TB:22
TB:23
TB:24

RTD218
(Icore)

Lubeoiltempbeforecooler

140

JB200

RTD219(Icore)

1Tx0.5Sqmmcu

CLIENT

20

TB:26
TB:27
TB:28

RTD219
(Icore)

Lubeoiltempaftercooler

141

JB202

DPIS200

3Cx1.5SqmmCu

CLIENT

10

TB:1
TB:2

DPIS200

DPIS200:DiffPracrossthelubeoilfilterhigh.

142

DCMSP

DCS

12Cx1.5SqmmCu.

CLIENT

30

X5:3
X5:4
X5:5
X5:6
X5:7
X5:8

EOPmotorOnfeedback

010716

EOPmotoroverloadfeedback
EOPmotorfieldfailfeedback

SHEET:14OF21

PROJECT:UttamSucrotech

143

144

010716

TGP

CABLESCHEDULE

DCS

ALTERNATOR DCS
AUXTB

8Px0.5SqmmCu

8TX0.5SqmmCu

CLIENT

CLIENT

40

40

TB:AI:1
TB:AI:2
TB:AI:3
TB:AI:4
TB:AI:5
TB:AI:6
TB:AI:7
TB:AI:8
TB:AI:9
TB:AI:10
TB:AI:11
TB:AI:12
TB:AI:28
TB:AI:29
TB:AI:30
TB:AI:31
TB:AI:32
TB:AI:33
R14
R15
R16
R74
R75
R76
R24
R25
R26
R84
R85
R86
R33
R34
R35
R94
R95
R96

TDC/CS/USL

PT100Inletpressure

TT100Inlettemp

PT101Exhaustpressure

TT102Exhausttemp

PT200LubeoilPr.

PT201ControloilPr.

Windingtemp,Rphase1

Windingtemp,Rphase2

Windingtemp,Yphase1

Windingtemp,Yphase2

Windingtemp,Bphase1

Windingtemp,Bphase2

SHEET:15OF21

PROJECT:UttamSucrotech

145

146

CABLESCHEDULE

ALTERNATOR DCS
AUXTB

JB200

DCS

8TX0.5SqmmCu

8TX0.5SqmmCu

CLIENT

CLIENT

40

40

TB:4
TB:5
TB:6

TB:11
TB:12
TB:13
TB:18
TB:19
TB:20
147

JB201

DCS

8TX0.5SqmmCu

CLIENT

40

TDC/CS/USL

B14
B15
B16
B24
B25
B26
A14
A15
A16
A24
A25
A26
A34
A35
A36
A44
A45
A46

DEbearingtemp

NDEbearingtemp

DEhotairtemp

NDEhotairtemp

DEcoldairtemp

NDEcoldairtemp

RTD200I/P(Icore):TurbineHPbearingtemp

RTD220I/P(Icore):Turbinethrustactivetopbearingtemp

RTD221I/P(Icore):Turbinethrustnonactivetopbearing
temp

RTD202I/P(Icore):Pinionforebearingtemp

RTD203I/P(Icore):Pinionafterbearingtemp

RTD204I/P(Icore):Gearboxforebearingtemp

RTD205I/P(Icore):Gearboxafterbearingtemp

RTD201 I/P (Icore): Turbine LP bearing temp

010716

SHEET:16OF21

PROJECT:UttamSucrotech

148

149

150

010716

TCP

TCP

TCP

CABLESCHEDULE

DCS

DCS

DCS

8Px0.5SqmmCu

8Px0.5SqmmCu

8PX0.5SqmmCu

CLIENT

CLIENT

CLIENT

40

30

30

TDC/CS/USL

TB:AI:1
TB:AI:2
TB:AI:3
TB:AI:4
TB:AI:5
TB:AI:6
TB:AI:7
TB:AI:8
TB:AI:9
TB:AI:10
TB:AI:11
TB:AI:12
TB:AI:13
TB:AI:14
TB:AI:15
TB:AI:22
TB:AI:23
TB:AI:24

TB:AI:34
TB:AI:35
TB:AI:36
TB:AI:37
TB:AI:38
TB:AI:39
TB:AI:46
TB:AI:47
TB:AI:48
TB:AI:49
TB:AI:50
TB:AI:51
TB:AI:52
TB:AI:53
TB:AI:54
TB:AI:55
TB:AI:56
TB:AI:57

TB:AI:58
TB:AI:59
TB:AI:60
TB:AI:61
TB:AI:62
TB:AI:63
TB:AI:64
TB:AI:65
TB:AI:66
TB:AI:67
TB:AI:68
TB:AI:69

TurbineSpeedsignal.

Referencespeedsignal.

KWTransducersignal.

PT101:Exhaustpr

HPActuatorsignal.

FT100:Inletflow.

ZT600:AxialdisplacementXaxis

ZT601:AxialdisplacementYaxis

XT600:TurbineforebearingredialvibrationXaxis

XT601:TurbineforebearingredialvibrationYaxis

XT602:TurbineafterbearingredialvibrationXaxis

XT603:TurbineafterbearingredialvibrationYaxis

XT604:GearboxforebearingredialvibrationXaxis

XT605:GearboxforebearingredialvibrationYaxis

XT606:GearboxafterbearingredialvibrationXaxis

XT607:GearboxafterbearingredialvibrationYaxis

SHEET:17OF21

PROJECT:UttamSucrotech

151

152

153

154

010716

TCP

TCP

TCP

TCP

CABLESCHEDULE

DCS

DCS

DCS

DCS

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

CLIENT

CLIENT

CLIENT

CLIENT

40

40

40

40

TDC/CS/USL

TB:DI:1
TB:DI:2
TB:DI:3
TB:DI:4
TB:DI:5
TB:DI:6
TB:DI:7
TB:DI:8
TB:DI:9
TB:DI:10
TB:DI:11
TB:DI:12

TB:DI:13
TB:DI:14
TB:DI:15
TB:DI:16
TB:DI:17
TB:DI:18
TB:DI:23
TB:DI:24
TB:DI:25
TB:DI:26

TB:DI:27
TB:DI:28
TB:DI:29
TB:DI:30
TB:DI:31
TB:DI:32
TB:DI:33
TB:DI:34
TB:DI:35
TB:DI:36
TB:DI:37
TB:DI:38

TB:DI:45
TB:DI:46
TB:DI:47
TB:DI:48
TB:DI:49
TB:DI:50
TB:DI:53
TB:DI:54
TB:DI:55
TB:DI:56

TCP:DCsupplyhealthy.
BarringgearspeedI/L
TurbinespeedVeryHigh
Turbine/GearboxbearingtempVeryHigh.
Lubeoiltempveryhigh
86Toperated.
PALL203:Lubeoilprverylow.
PALL206:Controloilprverylow.
PAHH102:Exhauststeamprveryhigh.
TurbineaxialmovementVeryHigh.
Turbine/gearboxpinionbearingVibration
veryHigh.
TurbineaxialmovementHigh.
Turbine/gearboxpinionbearingVibrationHigh.
DPIS200signal.
PAL202:Lubeoilprlow.
PAL205:Controloilprlow.
PAH102:Exhaustprhigh.
ZSO200:ESVopenfeedback
Turbine/GearboxbearingtempHigh.
Lubeoiltemphigh.
PS200:LowsetAOPautostart
PS200:HighsetAOPautostop

SHEET:18OF21

PROJECT:UttamSucrotech

155

156

157

158

010716

TCP

TCP

TCP

TCP

CABLESCHEDULE

DCS

DCS

DCS

DCS

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

CLIENT

CLIENT

CLIENT

CLIENT

40

40

40

40

TDC/CS/USL

TB:DI:57
TB:DI:58
TB:DI:59
TB:DI:60
TB:DI:61
TB:DI:62
TB:DI:63
TB:DI:64
TB:DI:65
TB:DI:66
TB:DI:67
TB:DI:68

TB:DI:69
TB:DI:70
TB:DI:71
TB:DI:72
TB:DI:79
TB:DI:80
TB:DI:83
TB:DI:84
TB:DI:85
TB:DI:86
TB:DI:87
TB:DI:88

TB:DI:101
TB:DI:102
TB:DI:103
TB:DI:104
TB:DI:105
TB:DI:106
TB:DI:107
TB:DI:108
TB:DI:109
TB:DI:110
TB:DI:111
TB:DI:112

TB:DI:113
TB:DI:114
TB:DI:115
TB:DI:116
TB:DI:117
TB:DI:118
TB:DI:119
TB:DI:120
TB:DI:121
TB:DI:122
TB:DI:123
TB:DI:124

PS204:BarringgearI/L
PS207:LowsetACOP1autostart
PS207:HighsetACOP1autostop
SolenoidValvecontact.
BarringgearmotorDCSselected.
GVCmotorDCSselected.
AOPmotorDCSselected.
VapourextractormotorDCSselected.
ACOP1motorDCSselected.
PS201:LowsetEOPautostart
PS201:HighsetEOPautostop
EMPBoperatedsignal.
TurbinethrustbearingtempveryHigh.
PAHH101:Inletprveryhigh
TALL100:Inlettempverylow
TAHH100:Inlettempveryhigh
ZSC201:SEVclosedfeedback
PAL202:Tripoilprlow
DPIS201:Diffpra/ccontroloilfilterhigh
PAH100:Inletsteamprhigh
TurbinethrustbearingtempHigh.
TAL101:Inlettemplow
TAH101:Inlettemphigh
TAH102:Exhausttemphigh

SHEET:19OF21

PROJECT:UttamSucrotech

159

160

161

162

010716

TCP

DCS

DCS

DCS

CABLESCHEDULE

DCS

TCP

TCP

TCP

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

12Cx1.5SqmmCu.

CLIENT

CLIENT

CLIENT

CLIENT

40

40

40

40

TDC/CS/USL

TB:DI:125
TB:DI:126
TB:DI:127
TB:DI:128
TB:DI:129
TB:DI:130
TB:DI:131
TB:DI:132
TB:DI:135
TB:DI:136
TB:DI:149
TB:DI:150

TB:DO:1
TB:DO:2
TB:DO:3
TB:DO:4
TB:DO:5
TB:DO:6
TB:DO:7
TB:DO:8
TB:DO:9
TB:DO:10
TB:DO:11
TB:DO:12

Speedraisecommond

TB:DO:13
TB:DO:14
TB:DO:15
TB:DO:16
TB:DO:17
TB:DO:18
TB:DO:19
TB:DO:20
TB:DO:33
TB:DO:34
TB:DO:35
TB:DO:36

AOPmotorstartcommond.

TB:DO:37
TB:DO:38
TB:DO:39
TB:DO:40
TB:DO:41
TB:DO:42
TB:DO:45
TB:DO:46
TB:DO:47
TB:DO:48
TB:DO:49
TB:DO:50

Turbinetripcommond.

LAL203:OverheadLubeoiltanklevellow
LAL202:OverheadLubeoiltanklevelhigh
PS207A:LowsetACOP2autostart
PS207A:HighsetACOP2autostop
ACOP2motorDCSselected.
HeaterOnfeedback

SpeedLowercommond
Barringgearmotorstartcommand
Barringgearmotorstopcommand
GVCmotorstartcommand
GVCmotorstopcommand

AOPmotorstopcommond.
Vepourextractormotorstartcommond.
Vepourextractormotorstopcommond.
ACOP1motorstartcommond.
ACOP1motorstopcommond.

AuxsetpointRaise.
AuxsetpointLower.
ACOP2motorstartcommond.
ACOP2motorstopcommond.
LPtripreset

SHEET:20OF21

PROJECT:UttamSucrotech

163

DCS

CABLESCHEDULE

TCP

5CX1.5SqmmCu

CLIENT

40

TDC/CS/USL

TB:DO:51
TB:DO:52
TB:DO:43
TB:DO:44

ESVtripreset
Governorstartpermissive

NOTE:
1.CABLELENGTHMENTIONEDINTHECABLESCHEDULEISINDICATIVE,EXACTLENGTHTOBEMEASUREDINSITE.

010716

SHEET:21OF21