Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

2x85kva Parallel Redundant UPS System

dubas

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

CONGRATULATION

Congratulation for choosing dubas product. You now


belong

to

dubas

family

customer

across

dedicated

company

With

absolute

the

of

over

world.

to

Power

knowledge

many

dubas

is

Electronics
of

satisfied
a

100%

Industry.

technologies

and

understanding the importance of UPS in a critical


automated environment, we have built our products
to

provide

commerce.
industry

reliability

dubas
over

is
a

been

decade

to

the

in
and

industry

power
has

and

electronics
done

various

pioneering works in power electronics. dubas is an


ISO

9001

certified

uncompromised

company.

quality

products

dubas
and

services

accomplish highest customer satisfaction.

delivers
to

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

Operational & Instructional Manual For


2x85kVA Parallel Redundant
UPS System

This

DESCRIPTION

: 2 x 85 KVA, 3 - 1 ON-LINE UPS

RATING

: 2 x 85 KVA, 3 - 1

INPUT

: 415 V AC, 10%,

OUTPUT

: 230 V AC, 1%, 50HZ

DC VOLT

: 268V

UNIT SL #

W.O.NO

: 1301001

manual

is

accompanying

the

above-referred

product,

which

has

been

manufactured in accordance with the customer purchase order, conforming to dubas quality systems
for manufacturing quality. The operating procedure, maintenance, installation, trouble shooting in the
event of fault occurrence has been given in this manual. Electrical hazards given in this manual must
be understood and strictly followed otherwise it could prove fatal. Please refer to warranty certificate
for warranty cover details.

PLEASE READ THE MANUAL THOROUGHLY,


BEFORE OPERATING THE SYSTEM.
3

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

Table Of Contents
Un-interrupted Power Supply (UPS)
1.0

System Description

----------

2.0

Technical Specification

----------

3.0

Drawings
Single line diagram

----------

09

General arrangement

----------

10

Room layout diagram

----------

11

Interconnection power wiring diagram

----------

12

Interconnection control wiring diagram

----------

12

System power wiring

----------

13

4.0

5.0

Installation & Commissioning


General

----------

15

Installation

----------

16

Commissioning

----------

18

Functional Checks

----------

19

Controls

----------

20

Indications and Alarms

----------

21

Indications, Controls

6.0

Display at UPS

----------

23

7.0

Routine Maintenance for UPS

----------

25

----------

25

----------

29

8.0
9.0

Trouble Shooting For UPS


Failure Report

10.0 Warranty Details

----------

30

11.0 Quality Policy

----------

31

12.0 Electrical Supply Better Way

----------

31

13.0 Product Varieties

----------

32

14.0 Bill of materials

----------

33

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

1.0 SYSTEM DESCRIPTION


Double conversion, Online Uninterruptible power supply here after known as UPS provides emergency
back-up power in the event of a black-out and also protects the electrical and electronic equipment
from critical power disturbances such as spikes, noise, sags and surges.
The main objective of GX-III Series UPS is to take polluted, fluctuating and erratic electrical power
that exists in the main power supply today and replace it with well regulated, computer grade power.
The back-up time is a function of the amount of battery reserve that is available along with the
system.
The whole unit consists of 2 nos. of GX-III Series UPS systems, a SW Cubicle and one number of servo
stabilizer. The whole system operates in Parallel mode.
Operating Modes
During Normal operation two units will be paralled and feed the load. (ie 50% each and 85 kva total )
On failure of AC input supply, the inverter will obtain the power from battery and continues to feed the
load without disturbance at the load. The battery will supply back up power to Inverters for a specified
period. On power resumption the converter output voltage gradually builds to the set value and
recharges the battery simultaneously feeding the inverters.
If any one of the ups goes fault, the second unit will take the load. After clearing the fault the
rectified inverter gets paralled and share the load equally.
On Failure of both inverters the load will be transferred to Static bypass source. The retransfer
of load from static bypass source to Inverter shall be done by automatically.
Note:
1) There is no common battery bank for the ups system.
For periodic UPS maintenance or for rectification of fault, Manual bypass switch is provided to bypass
the UPS and to feed the power to load from bypass source; this operation is achieved without load
break.

The UPS System consists of essentially 5 blocks.

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

CONVERTER
BATTERY CHARGER / BUCK CONVERTER
INVERTER
BOOSTER
STATIC BYPASS

A. CONVERTER
Input Voltage is connected to the rectifier module configured by IGBTs, which is controlled by DSP
with active Power Factor Correction. The IGBTs are switched ON / OFF by means of gate pulses
generated by the DSP control card. Output of the IGBT Bridge; is connected to parallel bank of DC
capacitors. Input active Power Factor Controller circuit maintains the input power factor near to unity
and the input current pattern exactly follows the input voltage .DC output, line voltage & line currents
are sensed by signal conditioning network in Control PCB & then given to the analog inputs of the DSP.
Bonded on the feedback, the gate pulse is varied within the DSP, which controls & regulates the DC
voltage along with power factor correction. This well-regulated DC output from 3ph-IGBT Bridge, is
connected to the capacitor bank. The Converter control logic is fully software based & is performed by
Worlds leading Digital Signal Processor. Converter Control card which is a combination of analog
and a digital card generates the sine weighed pulses, whose width is modulated as per the feed back
signals. The input current is sensed via Hall Sensor. The output of converter is supported to inverter
and battery charger / buck converter. All the input parameters of the converter are directly displayed
on to the LCD screen provided in the front panel.

B. BUCK CONVERTER
The output of the converter is connected to the buck converter. The function of this module is step
Down the dc voltage to required battery voltage. Output of this module is connected to the battery to
Charging purpose. Battery charging current is sensed through hall sensor and is connected at the
Output of this module. Battery float & boost mode of working is decided by this current sensor.
Normally battery is charging under float mode by constant voltage and current limit. The voltage and
6

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

Current feedbacks are sensed through Digital signal processor. The control logic of this Operation is
Fully software based. The battery float charging and boost charging voltage is setted as per battery
Float and boost Charging voltage recommended by manufacturer. In this unit we setted float voltage
As 248V (Number of cell X float volt per cell. i.e.110X2.25=248V) and boost Voltage as 303V (number
Of cell X boost volt per cell. i.e.110X2.75=303V). The float charging current setted as 10% of the
Battery AH i.e. 65A and is adjustable 5-65A. Boost charging current normally setted as 5% of the
Battery AH i.e. 32A and is adjustable 5-65A. Battery boost charging ENABLE/DISABLE option is
Given in the setting. The charging current is limited to the specified value by using the current
Feedback through a current sensor provided in the battery path. The excessive demand of battery
Current is reduced by bringing down the dc o/p voltage using the DC Fold back action as per the
Signals from the current sensors at the battery charging path. All the DC (battery) parameters are
Directly displayed on to the LCD screen provided in the front panel.

C. INVERTER
DC output of the converter is the input to the 1 bridge configured Inverter.

The output of the

inverter bridge is isolated by output transformer. Harmonic voltages are filtered by output filter
capacitor.
IGBTs are switched ON and OFF as per the pulses from driver cards, received at their gate terminals.
IGBTs Q1 to Q4 are switched ON and OFF as per the driver pulses received at their basis from driver
card.
The inverter control logic is software based & is performed by worlds leading Digital Signal Processor.
Inverter Control card which is a combination a analog and a digital card generates the sine weighed
pulses, whose width is modulated as per the feedback signal. The output current is sensed via current
transformers.
Indications and alarms are generated for announcing the status of the system. All the output
parameters and the fault status of the UPS are directly displayed on to the LCD screen for user
information.

D. BOOSTER
7

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

During failure of AC mains supply, this module supports the inverter using the battery voltage without
disturbed the load. Input for this module is from battery. The function of this module is boosting the
battery voltage to required input voltage for the inverter. Discharging current is sensed through hall
sensor, which is located at this module.

E. STATIC BYPASS
If load is on inverter and bypass source is in healthy condition, then load will transfer to bypass
source, if inverter is tripped. If load is connected to bypass source and Ups is healthy, then output
load will retransfer to inverter automatically.
For maintenance work of UPS, UPS is bypassed to bypass source through Manual Bypass Switch, so
that maintenance work can be done on ups panel.

2.0 TECHNICAL SPECIFICATION


Sl.
UPS PARTICULARS/SPECIFICATION
No
GENERAL
1.0
Make & Country
2.0
Type
3.0

4.0

Input

Voltage

No. of Phase

Frequency

P.F
UPS Capacity
At 0.8 PF

5.0
6.0

Output Voltage and regulation


Frequency and regulation

7.0

Metering

DUBAS INDIA
Double Conversion Online
415V, 10%
3, 5wire (3P+N+Earth)
50Hz. 5%
> 0.9 at rated load
68KW
1, 230V AC, 2%
50 Hz 0.5%

Type
Accuracy

8.0
Type of cooling
CONVERTER
1.0
Type

LCD (32 Bit display) with operating key pads


2%
Forced Air
Constant voltage current limit type

2.0

Type of Control

3.0
4.0
5.0

Input voltage
output Voltage
Voltage Regulation for AC Input Variations of +
10% & Load Variations
Ripple

6.0

DATA

DSP Based PWM Technology


415V+ 10%
400 VDC
+ 1%
< 2%

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system
7.0

Power Walk-in circuit provided

dubas

Yes

BATTERY CHARGER/BUCK CONVERTER


1.0

Type

Constant voltage current limit type

2.0
3.0

Type of Control
Input voltage

DSP Based PWM Technology


400 VDC

4.0

Nominal Output Voltage



Float Voltage

Float Current

Boost voltage

Boost current

248 VDC
248V
65A Factory set
303V
90A starting current
45A finishing current

5.0

+2%

6.0

Voltage Regulation for Input Variations & Load


Variations
Ripple

7.0

Power Walk-in circuit provided

Yes

< 2%

INVERTER SYSTEM
1.0

Type

Solid state, static control, using IGBTs

2.0

Type of Control

DSP Based PWM Technology

3.0

Input

400V DC

4.0

Output AC voltage

1, 230V AC

5.0

Accuracy (Steady State)

Better than 98%

6.0

Output Frequency

50 Hz @ free running condition

7.0

Frequency regulation

+ 0.5%

8.0
9.0

Harmonic Distortion
Transient Voltage For
 50% step load change
 Sudden input voltage change of 10%
 Loss and return of input AC power

< 3% on 100% linear load

TRANSIENT RECOVERY TIME


 Recovery to 95%
BOOSTER
1.0
Type
2.0
Type of Control

5%
5%
5%
<15 m sec.
Constant voltage current limit type
DSP Based PWM Technology

3.0

Input voltage

193-248 VDC

4.0

Output Voltage

400 VDC

STATIC TRANSFER SWITCHES


1.0
Type
2.0
Voltage
3.0
Frequency
4.0
Transfer time
INVERTER / RECTIFIER TRANSFORMER
1.0
Type
2.0
Type of cooling
3.0

Insulation class

Solid state static control (SCR based)


230 V
50Hz, + 5%
< 4 msec (sync transfer)
Dry type, Forced Air cooled, Double wound
Forced air
Class H with temperature raise limit to
Class F

MANUAL BYPASS SWITCH


1.0

Capacity

Full rated
9

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

ENCLOSURE
1.0
2.0
3.0
4.0
5.0
6.0

Type
Sheet Thickness Frame
Degree of protection
Paint Shade
Cable Entry
Overall Dimensions
Converter
Inverter
Switching cubicle
SCVS (BYPASS)

Free standing, Floor vertical mounted


2 mm
IP 42
RAL 7035
TOP
WXDXH
800x800x2200mm
800x800x2200mm
600x800x2200mm
800x800x2200mm

Single line diagram for 2x85 kva UPS system

PART DESCRIPTION:

10

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

Fig-1

General arrangement diagram for 2x85 kva UPS system

11

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

Fig-2

ROOM LAYOUT ARRANGEMENT DIAGRAM FOR 2X85 KVA UPS SYSTEM


12

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

Fig-3

INTERLOOPING POWER WIRING DIAGRAM


13

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

Fig 4

INTERLOOPING CONTROL WIRING DIAGRAM


CONVERTER TO INVERTER

CONVERTER TO SWITCHING CUBICLE

INVERTER TO CONVERTER & SWC

INVERTER1 TO INVERTER2

14

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

SWITCHING CUBICLE TO CONVERTER

Fig-5

System Power wiring diagram


1. Converter block

Fig-6

2. Inverter block
15

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

Fig-7

3. Static switch block

Fig-8

4.0 INSTALLATIONS AND COMMISSIONING


16

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

General Awareness
1. Confirm the product by noting down the name plate details and model No. Provided in the
system.
2. Inspect the product for external damage caused during transit. If any damage found, report to
the transport and dubas immediately.
3. Handle the equipment carefully and install the equipment according to the installation details
given.
4. Install the equipment in safe area, protected from moisture sunlight, harmful gases.
5. Do not store or use corrosive materials in the vicinity of the UPS.

NOTE: UNAUTHORIZED PERSON SHOULD NOT TOUCH, ELECTRICAL HAZARD AREA, SINCE
THE SYSTEM IS WORKING WITH HIGH VOLTAGE.

CAUTION: ONE SET CONSISTS OF 2 UPS SYSTEMS, ONE SWITCHING CUBICLE, ONE SERVO
STABILIZER AND 1 SET OF BATTERY BANK. IN CASE ANY ONE SYSTEM IS MISSING, THEN
IT IS NOT POSSIBLE TO INSTALL AT THE SITE.

System Packing
The system is fully tested and quality control inspection done prior to delivery.
1. The whole system consists of UPS-2No, 1 Sw Cubicle, 1 Servo Stabilizer and 1 battery bank,
2. Each unit is covered with a bubble sheet and thermacoal. Finally each wrapped unit is placed
inside a wooden box.
3. Bottom Sockets with all its accessories and interloping cables are packed in separate boxes
cotton box.

INSTALLATION
Initial Checks - General
1.

On receipt of material unload the material carefully, to rest on its bottom. Store the equipment

in safe area protected from harmful gases, water, theft etc. Please store the material in packed
condition if the installation is expected to take a while.
2.

After unpacking, before installation & Power ON, please check the equipment for transportation

damages. Incase of damage to equipment, please notify the manufacturer & transport company.
3.

Check for loose connections; especially all the fasteners for tightness, & cable terminations &

interconnections; tighten them if required.


4.

Check all the wiring connections & flat-band connectors for loose contacts. Ensure proper

contact of wire terminations & plug / sockets.

Place of Installation
17

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system
1.

dubas

Ensure that the equipment is installed as per FIG-3 at a place conforming to the ambient

operating conditions as specified in technical Specification and please ensure that it is housed
indoor, in a closed safe room; having adequate ventilation and light.
2.

Avoid installing equipment near heat generating units or extreme dirt, high moisture & harmful

gases. These can damage the equipment seriously.


3.

Maintain minimum clearance of 1000mm from front side and 800mm from rear side for

maintenance purpose.

Battery Bank Installation


1. Battery bank has to be protected from sunlight and rain.
2. Place the battery on the Battery Rack/Enclosure as per the Battery GA drawing.
3. Connect the entire intercell / battery interlinks as per the drawing.
4. Battery contains acid, which are harmful to human body in contact and to be disposed carefully
or to be returned back to us.

NOTE: A Battery terminal gives electrical shock. The battery will flashover and explode if
battery terminals are shorted accidentally.

The entire system has to be operated only by skilled operators, with necessary authorization.
Only qualified service technicians shall have the access to open the door. Inside of UPS have
Very dangerous electrical components, which can potentially electrocute the careless operator.

Pre Connection Checks


Before making the power supply connection, please observe that, all the switches are in OFF position.
Ensure that the utility power connection has voltage and frequency as per the rating given on
nameplate, or specification sheet.

Connection
1. Provide suitable breakers as per chart shown below for individual UPS system at customer
Distribution Board.
2. Ensure input source is not live & then connect Input cable (as per the given chart) through gland
plate to the Input terminals of SWC at the front bottom of the system.
3. Use suitable glands and ensure cable weight does not fall on the terminals.
4. Connect Load cable (as per the given chart) through gland plate to the output terminals.

18

dubas

Operational & Instruction Manual for 2x85kVA Parallel redundant UPS system

5. Connect all the Power and control interconnection cables between CONVERTER1 to INVERTER1,
INVERTER1 to SWC, CONVERTER1 to SWC, CONVERTER2 to INVERTER2, INVERTER2 to SWC,
CONVERTER2 to SWC and INVERTER1 to INVERTER2 as per FIG-4 & 5
6. Check the Battery voltage; verify if it corresponds to the UPS DC bus range & design.
7. Wire the battery + ve & - ve lead from battery bank to the battery Terminal Block.
8. Connect the cable + ve & - ve leads to their corresponding terminals on battery terminals.
9. At any instance UPS output should not be shorted or paralleled to EB output. Hence care has to be
taken in power distribution network.
10. Connect utility ground to the earth bus for all the equipments provided at the both side of each
system.

Cable Selection Chart


Cable Description

Recommended Cable size

Switchgear

Remarks

Output Cable from SWC


to ACDB for 400A Main
DB incomer

95 sq mm, 4 Core,1R,copper
cable/70 sq mm, 4 core, 2R,
Alluminium
95 sq mm, 2 Core,2R,copper
cable/150 sq mm, 2 core, 2R,
Alluminium

Output Cable from SWC


to ACDB for 63A Boiler
DB incomer

16 sq mm, 2 Core,1R,copper
cable/25 sq mm, 2 core, 1R,
Alluminium

63A,DP, 415V AC
MCB

cables are
Customer scope

Output Cable from SWC


to ACDB for 63A
Turbine DB incomer

16 sq mm, 2 Core,1R,copper
cable/25 sq mm, 2 core, 1R,
Alluminium

63A,DP, 415V AC
MCB

cables are
Customer scope

Battery Cable

95 sq mm, 2 Core,2R,copper
cable/150 sq mm, 2 core, 2R,
Alluminium

400A,TP,DC,
MCCB

cables are
Customer scope

Interconnection input
power Cable , AC

21.sq mm, 4 core, 1R, uninyvin

N.A

cables are
dubas scope

Interconnection output
power Cable , AC

21.sq mm, 2 core, 4R, uninyvin

N.A

cables are
dubas scope

Interconnection DC
power Cable

21.sq mm, 2 core, 4R, uninyvin

N.A

cables are
dubas scope

Input CableUPS &


Bypass

200A,50kA, TP,
415V AC , MCCB

cables are
Customer scope

400A,TP, 415V
AC , MCCB

cables are
Customer scope

NOTE: a) Use flexible pipe with cable gland for communication and power interloping cable.
b) If output earth is improper, spurious electrical noise will enter the ups output, which
may lead to malfunctioning of the ups.

Commissioning procedure:
19

Operational & Instruction Manual for 2x85kVA Parallel redundant UPS system

dubas

a) Make all the interloping power and control wiring as per wiring diagram.
b) Ensure proper earthing is connected for all the panels.
c) Ensure all the connectors and wires connected to PCAs are in without loose connection.
d) Ensure all the breakers and control switches are in OFF position.
e) Switch on the input breaker of separate source to UPS1, UPS2 and BYPASS at customer distribution
board.
f)

Check the voltage at SWC input terminal using voltmeter.

g) Switch on Input breaker of UPS1 first and check the Mains ON Indication is ON in front display of
converter panel.
h) After few seconds the front door control panel gets energized. Press ACK keypad at LCD display unit
to silence the alarm.
i)

Check the input voltage at LCD Display on front meter plate & confirm as per technical specification.

j)

Press the soft start push button until main contactor gets energized.

k) Press RESET switch to release the trip indications on Converter. Check the DC voltage at LCD
display.
l)

Switch on the input breaker for SCVS(BYPASS) panel.

m) Check the output voltage of SCVS(bypass) panel at before static input breaker for both UPS1 &
UPS2.
n)

Switch on Static input breaker of ups1.

o) Check Load on Bypass indication is ON.


p) Switch ON the CONVERTER CTR switch provided. DC voltage builds up gradually to set value after
few seconds. Check for Converter ON indication is ON
q) Switch on BATTERY breaker of UPS1.
r)

Check Battery charging current at display unit is reading and battery on charge indication is ON.

s) Press RESET switch to release the trip indications on Inverter.


t)

Keep output breaker in off condition before switch on the inverter control switch.

u) Switch ON INV. CTR switch the output voltage gradually builds to the set value. Check Inverter ON
indication is ON and voltage at LCD display unit is reading.
v) Same procedure is follows for switch on the UPS2.
w) After switch on the both the UPS individually, switch off static input breaker for both the UPS and
switch off the inverter control switch.
x) Switch on the output breaker of both the UPS.
y) Switch on the static bypass input breaker for both the UPS one by one.
z) Switch on the inverter control switch for UPS1 first. After voltage builds, master unit indication is
glow on front indication card at UPS1.
aa) Switch on the second UPS inverter control switch, after output voltage builds, both the unit will be
paralleled.

bb) Put the load at output and observe the sharing of the load percentage at both UPS LCD display.
20

dubas

Operational & Instruction Manual for 2x85kVA Parallel redundant UPS system

cc) If the load is connected initially before switch on the inverter control switch, load will be in bypass.
After switch on the inverter control switch, load will be transferred to UPS automatically.
dd) Check all the parameter and indications on front user display panel.

FUNCTIONAL CHECKS
Transfers/Re-Transfers
Check/transfer the load from inverter output to Static Bypass Source
a) Switch OFF INV CTR switch of UPS-1 and UPS2
RE-Transfer the Load from Static Bypass to Inverter
a) Press RESET switch of both the UPS and clear the faults if any exists.
b) Switch ON INV CTR switches of both UPS-1 and UPS-2 sequentially.
c) After inverter voltage build, load will transferred to UPS and paralled.

5.0 INDICATION, CONTROLS

5
2

FIG-9: USER INTERFACE FRONT CONTROL PANEL FOR UPS

1: LCD DISPLAY UNIT


2: CONVERTER ON/OFF SWITCH

3: RESET SWITCH
4: INV. ON/OFF SWITCH
21

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

5: UPS SYSTEM STATUS INDICATION

CONTROLS:
RESET: Operate this switch for clearing the faults at both Conv. & Inv. (HOLD FOR FEW SECONDS)

INV. CONTROL: This switch is provided on the front door. This switch facilitates inverter output to be
switched OFF/ON. This is to be operated whenever load is not active, but battery charging will be carried
on irrespective of the status of this switch.

CONV. CONTROL: This switch shall be made ON only during initial START UP of the UPS and shall be
always kept in ON condition once the UPS is feeding the Load. (Note: by turning OFF this switch the
converter turns OFF and battery gets discharged through Inverter)

INDICATIONS AND ALARMS


Indication

Status

What it Says? (WIS)

What to Do? (WTD)

INDICATION
ON
(Green)
Mains ON
OFF

ON
(Green)
Converter ON

Batt. ON
Charge

a)Input breaker OFF


b)Input Phase Fail
c)Input voltage out of specified
range
d)Input fail
Converter is ON and the Converter
output voltage is = 248V DC

OFF

a)Conv. Control switch OFF


b)Conv. Fault

ON
(Green)

Converter is ON and battery


charging is under process

OFF
ON
(Green)

a)Switch on Input breaker


b) Check and restore all the 3 phases.
c) Wait till the voltage reaches within
specified range.
d) Wait till Input Supply is restored.
Healthy Condition

Healthy Condition

a)Conv. OFF/Fault
b)Battery Breaker OFF

a) Check WTD of Conv.OFF & Conv.Fault


b) Switch ON the breaker

Inverter is on and the output


voltage is greater 204V Ac

OFF
ON
(Green)

Self Inverter is ON and feeding the


load

OFF

Healthy Condition

a)Ensure switch is kept always ON


c)Check WTD of Conv. Fault

a)Inv. Control switch OFF


b)Output voltage is less than 204V
AC
c)Inverter Fault

Inverter ON

Load on UPS

Input breaker is ON, Input voltage


is healthy and within specified
range.

a)Self Inverter is OFF/fault


b)Load on Static Bypass

Healthy Condition
a)Switch On the Inv. Control switch
b)Check Inv. Output voltage set (240V)
c)Check WTD of Inv.Fault
Healthy Condition
a)Check WTD of Inv.OFF & Inv.Fault
b)Check WTD of Load on Static Bypass

22

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

ON
(Green)
Bypass
Healthy
OFF

Load on
battery

ON
(Yellow)

OFF

Batt. Low
Pre-Alarm

ON
(Yellow)

Load On
Bypass

ON
(Yellow)

Converter
trip

ON
(Red)

Input
Under/Over
volt

ON
(Red)

DC Low

ON
(Red)

static input breaker in on condition


and bypass input voltage is with in
the range
a) Static input breaker off
b) SCVS output voltage out of
specified range
Battery is supported to inverter for
the following condition.
a)converter fault
b)mains fail

dubas

Healthy Condition
a) Switch on the breaker
b) Wait till the voltage reaches within
specified range.

a)Check WTD of CON.Fault


b)Check the mains voltage

Converter in healthy condition


Gives alarm when battery has
discharged to its cut-off level
before Inv. Trips on Batt. Low Trip
under following condition.
a)Conv.OFF/Fault
b) Mains ON indication OFF
Load is fed through static switch
under following conditions
A) Self & Alnt. UPS tripped on Inv.
Fault.
B) Self & Alnt. UPS Inv. ON
indication OFF.
TRIP INDICATION WITH
Converter has tripped under
following conditions
a)Mains ON indication OFF
b)Converter output voltage high
c)Input Current high
Input Voltage is out of specified
limits
Battery has got discharged to its
cutoff level their by tripping
inverter.
Inverter has tripped under
following conditions
a) dc low.
b) output voltage out of specified
range.
c) inverter overload

a)Check WTD of Conv.OFF&Conv.Fault


b) Ensure Input supply (If Mains ON is
Off) is made ON within 5 minutes after
hearing of 1st Batt.low pre-alarm or turn
OFF the entire load.

a) Check WTD of Inv. Fault


b) Check WTD of Inv. ON

ALARM
a)Check WTD of Mains ON
b) Check Conv. Set voltage is as per
requirement & press RESET switch.
c) Check Input over current set & press
RESET switch.
Check Input supply for phase fail or
ensure the Input supply is within specified
limits
Ensure converter is ON and battery is on
charge.
a) Check WTD of dc low
b) Check output voltage setting & press
Reset switch
c) Check the load percentage & put the
load with in the unit rating.

Inverter trip

ON
(Red)

Inverter
Under/Over
volt

ON
(Red)

Inverter has tripped as output


voltage is low or High

Check output under & over voltage


setting and press Reset switch.

Inverter
Overload

ON
(Red)

Inverter has tripped on any one of


overloaded band as per Chart-1

Reduce the load and pres Reset switch.

System
Over Temp.

ON
(Red)

Inverter has tripped as any module


component temperature is beyond
max. limit
23

Check individual module fans are working


and ambient temperature is within
specified range. Wait for few minutes and

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

press Reset switch.

Master unit
Parallel mode
Load on
alternate ups
Sync ok

ON
(Green)

Based on which system is switched


on first.

Healthy Condition

ON
(Green)
ON
(Green)

If both the ups are working in


parallel conditions.

Healthy Condition

If load is feeding by the other ups

Check WTD of Inv.OFF & Inv.Fault in self


inverter.

If bypass voltage is synchronization


with UPS output voltage

Healthy Condition

ON
(Green)

NOTE: TRIP INDICATIONS ARE ACKNOWLEDGED BY PRESSING RESET SWITCH AND SYSTEM
WILL RESET FOR ITS OPERATION.

6. USER INTERFACE DISPLAY

Fig.10 Display Unit

KEY ITS FUNCTION

MODE KEY

24

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

Scroll the mode one by one.

ESCAPE KEY

To return to main mode.

ENTER KEY

To acknowledge the buzzer.

INCREMENT KEY

Enter into the sub modes of that selected mode.

DECREMENT KEY

Enter into the sub modes of that selected mode.

How to operate front panel Display unit at UPS?

To Measure Input Parameters (Line Voltage, Line Current & Frequency, power, P.F)
Press Mode key and scroll till INPUT PARAMETER is displayed. Then press increment key, phase-phase
voltage in Volts shall be displayed. By pressing increment key again and again input parameters of
current, frequency, power, and p.f shall be displayed.

To Measure DC Bus Parameters (DC Voltage, Charging Current & Discharging Current)
Press Mode key and scroll till DC BUS PARAMETER is displayed then press increment key DC voltage in
Volts shall be displayed. On the same mode press increment key again to measure battery
CHARGING/DISCHARGING current. Any one of the current shall be displayed depending upon BATT. ON
CHARGE or BATT. ON DISCHARGE
To Measure Output Parameters (Voltage, Current, Frequency & Power)
25

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

Press Mode key and scroll till OUTPUT PARAMETER is displayed. Then press increment key output voltage
in Volts shall be displayed. Press same increment key again and again to measure output current in
Amps along with %Full load current, frequency in Hz & output power in Kilo Watts respectively.

To Measure Bypass Parameters (Voltage & Frequency)


Press Mode key and scroll till BYPASS PARAMETER is displayed then press increment key bypass voltage
in Volts shall be displayed.

To Monitor UPS Status


Press Mode key and scroll till UPS STATUS is displayed then press Increment Key or Decrement Key to
toggle between various UPS status which are listed at Indications and Alarms.

To test all the indication along with alarm (LED Test)


Press Mode key and scroll till INDICATION TEST is displayed then press increment. All the LEDs lit one
by one along with buzzer beep for which ever indication is applicable. All indications are tested twice, to
stop in between press Mode Key.

POP-UP Display messages


Display Unit shall POP-UP the following messages
PRE ALARM FOR
BATT LOW
ALARM FOR

: When battery is discharged to its cut-off level after delivering the rated load for
a specified back-up time.
: When inverter output is overloaded as per the Chart:

INV OVERLOAD

7.0 ROUTINE MAINTENANCE FOR UPS


1. Record output voltage read from the output voltmeter periodically.
2. Check battery health condition periodically.
a. Measure the individual voltage of the battery with AC input power off condition.
b. Immediately measure and log the values in a periodicity of 45 days, take another reading at
battery per alarm.
c.

Compare the voltage values of corresponding batteries recording time instance.

d. Fall of corresponding battery voltage indicates need for maintenance service requirement. If the
battery voltages are comparable the battery is healthy.

8.0 TROUBLE SHOOTING FOR UPS


26

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

FAULT DIAGNOSTICS OF UPS


Sl.
No.

FAULT REPORT

Mains is present but


1

CHECK POINT

Input MCCB

Main-ON indication
is OFF

Input Voltage

OBSERVATION &
ACTION TO BE TAKEN
If input MCCB is OFF, then switch-ON the MCCB
& wait for 5 minutes.
If the input voltage is not within the specified
range then wait till the voltage comes back.
Check the type of trip.
If the display reads
CONVERTER TRIP
AC OV = Input Over Voltage trip
AC UV = Input Under Voltage trip.
AC OC = Input Over Current trip.
DC OV = DC Over Voltage trip.

Mains is present but


2

Converter Trip
indication is ON

Front user display


and indication

DC UV = DC Under Voltage trip.


If AC OV or ACUV or DCUV trip occurs,
then check the input voltage & wait till the
voltage returns.
If ACOC or DCOV or OT trip occurs, then
press Converter Reset switch provided in the
front panel. The trip will be cleared only if the
system is free from fault.
If the fault persists for longer time, then call for
the service.

Inverter is loaded on

Front user display

Battery always

and indication

If the Converter is tripped due to any one of


the above reasons, then press reset & reenergize the Converter.
Check the Battery Current & DC voltage

Battery is not

Front user display

charging

and indication

display. If the DC voltage is less than the float


voltage & Battery current is zero, then there
may be some loose connections. Consult the
service engineer for further help.
Loose connections.

Low Battery Back-up

Battery

Battery not in Healthy condition.


Battery electrolyte is drained.

27

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

Check whether all Fans are ON. If any fan is OFF,

Abnormal Heat

Fans

Electrical Noise

Ground connections

Checks whether the system is earthed properly


otherwise check the earth connections.
Disconnect the load & try to switch-ON the System

Abnormal noise & trip at

Load

switch-ON

Time in Min.

then it should be replaced.

again. If it continues, then contact the service


personnel.

70
Overload Chart
60

Load Current
Duaration Trip display
100%
Continous
---> 100% to 110% 60 minutes
OL1
> 110% to 125% 10 minutes
OL2
> 125% to 150% 60 seconds OL3
> 150%
< 1sec.
OL4

50
40
30
20
10
0
1.04

1.10

1.16

1.22

1.28

1.34

1.40
1.46
Load Current x In

Fig-11: Overload Chart for UPS


LIST OF ALL POSSIBLE ERROR / TRIP MESSAGES GIVEN THROUGH INTERNAL DISPLAY
Error Displayed

Error Description

Action to be taken

Inverter Output Under Voltage trip.

Press RESET switch, If problem

The UPS output has dropped below the set

persists

voltage level.

Authorized service personnel.

Inverter Output Over Voltage trip.

Press RESET switch, If problem

The UPS output has risen above the set

persists

voltage level.

Authorized service personnel.

INVERTER
INVERTER TRIP
UV

INVERTER TRIP
OV

inform

inform

to

to

the

the

Switch OFF inverter, allow the


INVERTER TRIP
BI

DC bus LOW trip

battery to get charged, press

This indicates that the battery has fully

reset switch and switch ON

given up its backup power.

inverter.

If

call dubas.

28

problem

persists

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

INVERTER TRIP
BH
INVERTER TRIP
OL1
OL2
OL3
OL4
A L A R M FO R
OL
A L A R M FO R

DC bus HIGH trip

Press RESET switch, If problem

This indicates that the DC bus voltage is

persists

beyond the specified limit.

Authorized service personnel.

Inverter Over Load or Over current trip.


This indicates that the Inverter Output
current/ power has exceeded its rated
value. (refer Fig-11)

inform

to

the

Load has to be reduced. Press


reset If problem persists call
dubas.

Load has to be reduced. Then


Inverter is overload for OL1/2/3

alarm

&

countdown

stops

automatically.
Battery is discharged to its end cell cut-Off

Ensure load is switched OFF or

voltage

input source is restored.

Error Description

Action to be taken

Input Over Voltage trip.

Wait till the Input source is

CONVERTER TRIP

This trip occurs when the Mains supply is

healthy. Press RESET switch, If

AC OV

above the specified window (Above 10%

problem persists inform to the

of the nominal input voltage)

Authorized service personnel.

BL

Error Displayed
CONVERTER

CONVERTER TRIP
AC UV

CONVERTER TRIP
OC

CONVERTER TRIP
DC OV

Wait till the Input source is

Input Under Voltage trip.


This trip is due to the low input voltage
(Below 10% of the nominal input voltage)

healthy. Press RESET switch, If


problem persists inform to the
Authorized service personnel.
If it happens frequently, then

Input Over Current trip.


This indicates that the line current is more
than the rated current of the system.

check the Inverter load & check


input

voltage.

If

problem

persists contact dubas

DC Over Voltage trip.

Press RESET switch, If problem

This indicates that the DC voltage has

persists

raised above the specified level.

Authorized service personnel.

DC Under Voltage trip.


CONVERTER TRIP

This indicates that the DC voltage has

DC UV

fallen below the specified value of the


Converter.

29

inform

to

the

Check the DC bus voltage OR


this can happen even during
short circuit.

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

Glossary
UPS

: Un-interrupted Power Supply

IT

: Isolation Transformer

Inv.

: Inverter

Conv. : Converter

9.0 FAILURE REPORT


All failures to be reported to Service Department, DUBAS ENGINEERING PVT. LTD

Before reporting a complaint call, check the following.


1. Input breaker ON.
2. Battery MCCB ON.
3. Output Distribution is OK.
4. No excessive or faults loads are connected.

While reporting a faulty; please inform,


1. Nature of fault
2. Indication on the, front panel.
3. Serial number of the unit / rating of the unit / date of installation / location / premises /
name of the contact person.

Please register your call at the following address

DUBAS ENGINEERING PVT. LTD.,


# 43(P) 2nd Phase, Electronics City, Hosur Main Road
Bangalore - 560 100
Phone: (080) 4033 6000
Fax: (080) 4033 6222

30

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

10.0 WARRANTY DETAILS


dubas engineering pvt. Ltd. warrants its products against all manufacturing defects, faulty
workmanship for a period of 12 months from the date of Invoice, subjected to the terms and
condition mentioned below.

TERMS AND CONDITIONS


1. The customer will notify the company promptly of any defects noticed and give the company
adequate opportunity to inspect Test, and remedy them, for which the customer will deposit
the goods if necessary with companys office/service center along with original invoice.
2. Inspections and Test Report of the Company/Service Center will be final and binding under
the warranty for determining defects, repairs/ alterations required or carried out or certifying
working of goods thereafter. The company is entitled to retain any defective parts replaced
under the warranty.
3. The companys liabilities under the warranty will be limited only to defects, which occur
under.
4. Conditions of normal operations and proper use. It excludes defects occurring because of
abuse, faulty care, or maintenance repairs/ alteration to goods or parts by unauthorized
persons, use under conditions beyond specified or damage caused by lightening.
5. In case Batteries are used along with our system the responsibility to do regular
maintenance of the batteries lie with the customer. Customers are required to maintain the
batteries under optimum working conditions as specified by the battery manufacturers
certification that the batteries are well maintained.
6. Our warranty or any other services is limited to manufacturing defects in the equipment
only.

31

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

11.0 QUALITY POLICY


We shall strive continually to be a dedicated team delivering UN compromised quality
products and services, befitting and be-timed value to accomplish highest customer
satisfaction.

12.0 ELECTRICITY SUPPLY BETTER WAY


At any moment an AC mains supply can be subjected to the electrical disturbances such as spikes
(usually lightning induced), electrical noise (flashes on monitors and TV screens), sags (lights go dim),
surges (lights go bright) and blackouts or complete loss of power.
1. Blackout Blackouts can be caused by excessive demand on the power grid, lightning storms,
equipment failure or any accident, which brings down a power line.
2. Sag or Brownout Sags or brownouts can be caused by heavy equipment coming on-line, short
circuits, undersized electrical circuitry, or when the utility company deliberately decreases voltage
levels in order to cope with peak load times (rolling brown outs). Brownouts usually occur during
the summer heat waves.
3. Spikes Spikes are generally caused by a nearby lightning strike, or if utility power lines are
downed in a storm or as a result of an accident.
4. Surge A surge is usually caused when high-powered appliances in the area are turned off. Short
circuits or undersized electrical circuits can also cause them.
5. Noise Lightning, load switching, generators, transmitters, transformers, and industrial
equipment can cause EMI and RFI noise.

These electrical disturbances will damage sensitive electrical / electronic equipments, unscheduled Power
shutdown, corruption of data, system hangs ups etc. These disturbances can be prevented and it comes
in the form of Uninterruptible Power Supply (UPS).

32

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

dubas

13.0 PRODUCT VARIETIES

1.

UPS SYSTEMS:

DU-Series are available from 1 KVA to 120KVA range


GX-Series are available from 6KVA to 480KVA in single modules. Seamless paralleling up to 6 modules
are possible in the GX-Series.
DUBAS UPS Systems are employed in thousands of mission critical applications in Data Centres,
Hospitals, Avionics, Critical Railway applications etc.

2.

INDUSTRIAL STABILIZERS:

Industrial Voltage Stabilizers are available from 1KVA to 1200KVA.


Air cooled versions are available up to 250KVA and Oil cooled versions are available up to 1200KVA
Dubas Stabilizers are deployed in various countries in critical applications safeguarding various critical
loads from voltage uncertainties.

3.

FREQUENCY CONVERTERS:

Frequency converters are available up to 200KVA rating with various voltage configurations. dubas is a
premier supplier of 60HZ or 400HZ Frequency converters for critical test laboratories and avionics
industry.

4.

DC POWER PLANTS:

Dubas manufactures entire range of thyristor based rectifiers / chargers up to 900 Amps in various
voltage configurations. Major users include Power Substations, Process Plants, and Telecom Networks
etc.

5.

ULTRA ISOLATION TRANSFORMERS:

Ultra Isolation Transformers are available from 1KVA to 200KVA range in air-cooled version; the
equipments can be configured for any specified voltage configurations. These transformers provide
ultimate isolation parameters for critical loads against switching spikes, surges and any electrical ground
noise.

33

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

14.0 MAJOR BILL OF MATERIALS


Sl.
No

Item Description

Specs / Cat No.

1.

INPUT TXM MODULE

2.

Legend

Qty

ONU-31/85/268/GX3-ITTP

----

INPUT CHOKE MODULE

ONU-31/85/268/GX3-CHL

---

3.

SOFTSTART MODULE

ONU-31/85/268/GX3-SSM

----

4.

CON BRIDGE MODULE

CONV/3FC/85I/268/GX3-CBM

----

5.

CAPACITOR MODULE

ONU-31/85/268/GX3-CM

----

CONVERTER

6.

BUCK CON MODULE

ONU-31/85/268/GX3-BCM

----

7.

MAIN CONTROL CARD MODULE

ONU-31/85/268/GX3-MCCM

----

8.

POWER SUPPLY MODULE

ONU-31/85/268/GX3-PSM

----

9.

FAN POWER SUPPLY MODULE

ONU-31/85/268/GX3-FPSM

----

10.

LCD DISPLAY

DU3013R1

--

11.

INDICATION CARD

DU2036

PCB 20

12.

SPACE HEATER

80W 230V AC

SPH

13.

SOCKET

6A 3PIN 240V AC

SKT

14.

CFL LAMP WITH HOLDER

11/12W, 230V AC

LAMP

15.

DOOR SWITCH

6A, 230V AC

DS

16.

COOLING FANS

3 24V DC

F1,F2,F3,F5

27NOS

17.

COOLING FAN

4 240V AC

F4

1NO

18.

EXHAUST FAN

6 240V AC

--

5NO

INVERTER

19.

TXM & FILTER MODULE

ONU-31/85/268/GX3-ITSP

----

20.

STATIC MODULE

ONU-31/85/268/GX3-SM

----

21.

INV BRIDGE MODULE

ONU-31/85/268/GX3-IBM

----

22.

BOOSTER MODULE

ONU-31/85/268/GX3-BM

----

23.

CAPACITOR MODULE

ONU-31/85/268/GX3-CM

----

24.

MAIN CONTROL CARD MODULE

ONU-31/85/268/GX3-MCCM

----

25.

POWER SUPPLY MODULE

ONU-31/85/268/GX3-PSM

----

26.

FAN POWER SUPPLY & PARALLEL


BLOCK MODULE

ONU-31/85/268/GX3-FPSPBM

----

27.

SPACE HEATER

80W 230V AC

SPH

28.

SOCKET

6A 3PIN 240V AC

SKT

29.

CFL LAMP WITH HOLDER

11/12W, 230V AC

LAMP

30.

DOOR SWITCH

6A, 230V AC

DS

31.

COOLING FANS

3 24V DC

F7-F9

29NOS

32.

COOLING FAN

4 240V AC

F6,F10

2NO

33.

EXHAUST FAN

6 240V AC

--

5NO

M1-M2

M3

M4-M6

SWITCHING CUBICLE

34.

INPUT MCCB FOR UPS

35.

INPUT MCCB FOR SCVS

36.

BATTERY MCCB

200 A, TP, 415VAC


T3S 250 FF TMD R200
ISDA051268R1 (50 KA )
250A, TP, 415VAC 50KA,
T3S250FF TMD
R200,1SDA051269R1)
400A, 3P, 500V DC,
T5N 400FF TMA R400
34

dubas

Operational & Instruction Manual for 2x85kVA Parallel Redundant UPS system

37.

UPS OUTPUT MCCB

38.

STATIC / BYPASS INPUT MCCB

39.

MANUAL BYPASS MCCB

40.

SPACE HEATER

41.

SOCKET

42.

400 A, 3P, 415VAC


T5N 400FF TMA R400
400 A, 3P, 415 VAC
T5N 400FF TMA R400
400 A, 3P, 415 VAC
T5N 400FF TMA R400

M9-M10

M7-M8

M11

80W 230V AC

SPH

6A 3PIN 240V AC

SKT

CFL LAMP WITH HOLDER

11/12W, 230V AC

LAMP

43.

DOOR SWITCH

6A, 230V AC

DS

44.

BUCK BOOST TRANSFORMER

SCVS/11/85/00-ITSP

BB1&BB2

45.

SENSING TRANSFORMER

DU-SVS-SENS-01

ST1

46.

ISOLATION TRANSFORMER

IT-31/85/00/TX-F

47.

VARIAC

60A 2COIL A/C TYPE

48.

MOTOR

49.

SCVS (BYPASS PANEL)

TXM3

VR1&VR2

220 V, 1, 50Hz, 60 RPM, 10 Kg


cm

---

COOLING FAN

6, 230V AC

---

50.

EXHAUST FAN

6 240V AC

--

5NO

51.

INPUT METER

3 DIGITAL (VAF 3)

M1

52.

OUTPUT METER

3 DIGITAL (VAF 1)

M2

53.

CONTACTOR

115A TP AC

CR3

54.

CONTROL CARD

DP-01
DP-001 M0 0

---

55.

SPACE HEATER

80W 230V AC

56.

CFL LAMP WITH HOLDER

11/12W, 230V AC

57.

SOCKET

58.

DOOR SWITCH

Sl.No ITEM DESCRIPTION

SPH

LAMP

6A 230V AC

SKT

6A, 230V AC

DS

MAKE

MAGNETICS

DUBAS

SWITCHGEAR / MCCB

SCHNEIDER / ABB / L & T / SEIMENS

PCA

DUBAS

CAPACITOR

SARDA / ALCON / RESCON / KENDEIL

COOLING FAN

HICOOL / NISIKI / SUNON

IGBT

SEMIKRON/FUJI/INFINEON/ MITSUBISHI

ENCLOSURE

DUBAS

BATTERY

EXIDE

VARIAC

RADIOTONE

10

SERVO MOTOR

PRECISSION / ALL-STEP

11

METER

EIC

35