Professional Documents
Culture Documents
SCOPE OF WORK
2.0
3.0
SITE CONDITIONS
3.1
3.2
3
3
Environment
Rating
4.0
SYSTEM OPERATION
5.0
GENERAL
6.0
7.0
BATTERY BANK
8.0
AUXILIARY EQUIPMENT
9.0
ENCLOSURE
10.0
WIRING
11.0
GROUNDING
12.0
LABELING
13.0
14.0
WARRANTY
15.0
SPARES
16.0
DOCUMENTS REQUIRED
10
17.0
10
18.0
11
File: F:\WPDATA\NEWVES\2002\VES-6405
Page 2 of 11
VES-6405
Rev. 4, 11/02
1.0
2.0
SCOPE
1.1
This specification describes the minimum technical requirements for the design,
manufacture, testing and delivery for single phase and three phase solid state rectifier
and battery banks.
1.2
The purpose of these units is to supply direct current to vital and essential plant
systems and associated instrument and control devices, required for the safe
operation and control of plant shutdown under normal and emergency conditions.
1.3
Where the rectifiers and battery banks are utilized in conjunction with inverter
systems refer to specification VES-6400, Uninterruptable Power Supply (UPS)
systems for additional requirements.
3.0
SITE CONDITIONS
3.1
3.2
Environment
3.1.1
The battery bank unit shall be installed indoors in a separate battery room,
the battery room shall be provided with adequate ventilation to exhaust any
hydrogen gas to the outside air.
3.1.2
Ambient Temperature
Maximum
Minimum
Mean Relative Humidity
:
:
:
105oF (40oC)
65oF (18oC)
80% - 100%
Rating
3.2.1
3.2.2
The altitude will not exceed 1000 meters above mean sea level.
File: F:\WPDATA\NEWVES\2002\VES-6405
Page 3 of 11
VES-6405
Rev. 4, 11/02
4.0
SYSTEM OPERATION
4.1
5.0
Under normal conditions, both rectifier, and battery bank will be connected
to the load (floating).
4.1.2
During prime power failure the batteries will automatically supply the load.
No switching shall be employed in this transfer.
4.1.3
GENERAL
5.1
The load requirements and rectifier input voltage are specified on the data sheet(s).
5.2
The rectifier and battery bank unit shall be capable of supplying the maximum load,
continuously with prime power available. The rectifier capacity shall meet the output
of the unit as indicated on the data sheets and the following battery charge
requirements.
5.2.1
5.3
The batteries shall be sized so that on prime power failure the batteries will supply the
maximum load current output for the full time specified on the data sheets, without
the voltage falling below the specified minimum volt/cell value.
5.4
Each unit shall consist of a rectifier, battery bank and auxiliary equipment. The
rectifier shall be housed in a free standing sheet metal cabinet suitable for the
specified area classification. The batteries shall be mounted on stepped type floor
mounted battery rack so that the electrolyte level of all cells is clearly visible.
5.5
5.6
All components shall be of a proven quality, of current manufacture and shall be rated
to withstand normal variations in prime power voltage, current and frequency.
5.7
The rectifier, battery bank unit shall be designed to maximize personnel safety during
all operating, inspection and maintenance situations.
File: F:\WPDATA\NEWVES\2002\VES-6405
Page 4 of 11
VES-6405
Rev. 4, 11/02
6.0
6.2
No inversion or switching shall be employed. Loss of rectifier input supply shall not
disrupt battery supply to the load.
6.3
The rectifier shall be supplied with float and equalize charging facilities as follows:
6.3.1
Float Charging
Under normal operating conditions the rectifier shall operate on floating
charge, supplying charging current to the batteries to compensate for the
self discharged of the batter bank. The float level voltage shall be factory
adjusted to offer the best compromise between keeping the battery bank
fully charged and minimum maintenance.
6.3.2
Equalize Charging
The rectifier shall be equipped with equalize charge facilities to quickly
recharge the discharged battery bank. The equalize charge mode shall be
initiated automatically (once primary power returns) with a manual provision
that allows setting a switch or timer. The equalize charge circuit shall be
supplied with an automatic facility to revert the rectifier back to float charging
mode, when the batter bank becomes fully charged.
6.4
6.5
6.6
6.6.2
File: F:\WPDATA\NEWVES\2002\VES-6405
Page 5 of 11
VES-6405
Rev. 4, 11/02
7.0
8.0
BATTERY BANK
7.1
The battery size shall be in accordance with the data given on the data sheet(s).
Unless otherwise stated on the data sheet(s) the batteries shall be Nickel-Cadmium
type.
7.2
Nickel-Cadmium batteries shall have a life expectancy of not less than 15 years. The
battery plates shall be contained in high volume plastic electrolyte containers with
visual electrolyte level. The plastic containers shall be of non-flame-propagating,
shock resistant material.
7.3
The batteries shall be supplied complete with mounting racks, proper connectors,
filling funnels, hydrometer, glass measuring jug, instruction book, chart of cell voltage
discharge characteristics and 0.5 pound of oxide resistant grease.
7.4
The batteries shall be supplied discharged and without electrolyte. Electrolyte for the
batteries shall be supplied in separate, adequately protected containers.
7.5
Batteries shall be complete with all necessary links and cable lugs.
7.6
7.7
Battery racks shall be of suitably sized 90o angle iron construction, stepped type with
insulated runners supplied in knocked down assembly. The battery rack shall be
blasted to near white SA 22 and painted with two coats of alkali resistant finish.
AUXILIARY EQUIPMENT
8.1
All components for controlling, measuring and protection of the rectifier shall be built
into the cabinet in accordance with manufacturer's standard, but logically grouped for
the rectifier operation.
The following accessories shall be provided as a minimum:
8.1.1
Switches
a.
b.
c.
8.1.2
Measuring Instruments
a.
b.
File: F:\WPDATA\NEWVES\2002\VES-6405
Page 6 of 11
VES-6405
Rev. 4, 11/02
8.1.3
Indicating Lights
a.
b.
8.1.4
Alarms
a.
b.
c.
d.
e.
Mains failure
Charge failure
Ground fault
Overvoltage
Undervoltage
Fuses
Fuses shall be of the high-interrupt capacity cartridge type which fit in to the
fuse holder by knife blade contacts.
9.0
ENCLOSURE
9.1
The rectifier unit enclosure shall be fabricated from steel sheet to form a free
standing cabinet sufficiently rigid to prevent distortion during lifting, jacking and
transportation.
9.2
The cabinet shall be suitably partitioned between the individual items to allow for
maintenance or repairs to be carried out in a safe way.
9.3
Enclosure design shall be in compliance with the area classification specified on the
data sheet.
9.4
9.5
9.6
Painting and finish shall be to the manufacturer's standard for the service conditions
specified. Details thereof shall be provided in the Tender for Company approval.
File: F:\WPDATA\NEWVES\2002\VES-6405
Page 7 of 11
VES-6405
Rev. 4, 11/02
10.0
11.0
12.0
WIRING
10.1
Wire shall be run in harnessed bundles or in ventilated plastic tray with covers
(panduit type). Refer to VES-6000, Installation of Plant Electrical Systems.
10.2
Power wiring shall be generously sized and derated for maximum ambient
temperatures within the cabinets.
10.3
Conductors shall be stranded copper. Insulation shall be rated for 600 V minimum.
Color coding shall be provided in compliance with VES-6050, Engineering and Design
of Plant Electrical Systems.
10.4
Terminals shall be Klippon or approved equal and shall be numbered. No more than
one wire shall be terminated on one terminal.
10.5
All wires shall have plastic ferrules at both ends, numbered in accordance with the
relevant wiring diagrams.
GROUNDING
11.1
The cabinet shall be provided with a copper ground lug for connection to the plant
grounding system.
11.2
All non-current carrying metal parts shall be bonded to provide a continuous ground to
the ground lug. Door hinges are not acceptable ground paths.
11.3
The battery and charger output shall not be grounded unless otherwise specified on
the data sheet(s).
LABELING
12.1
Every item of equipment shall be identified with an equipment tag bearing the tag
number appearing on the relevant drawings and the item service description.
12.2
Name plates on the front of cabinets shall be plastic laminate, white background,
black letters. They shall be attached to the cabinets with stainless steel screws.
Adhesive is not acceptable.
File: F:\WPDATA\NEWVES\2002\VES-6405
Page 8 of 11
VES-6405
Rev. 4, 11/02
13.0
Purchaser reserves the right to witness all tests and shall be notified at least four
weeks in advance.
13.2
14.0
15.0
WARRANTY
14.1
The warranty of the entire assembly shall be the responsibility of Vendor. The
warranty period shall be a minimum of 24 month, after shipment or 12 month after
commissioning.
14.2
Vendor shall replace or repair any portion of the equipment which is defective at his
own cost during the warranty period at a time suitable to Purchaser.
SPARES
Vendor shall include priced recommended spare parts for start-up and for one (1) year of
operation with proposal. Recommended spares should take into account related factors of
equipment reliability, remote location and availability of equipment service facilities. Vendor's
complete spare parts list shall be issued to Purchaser within four (4) weeks after receipt of
order.
File: F:\WPDATA\NEWVES\2002\VES-6405
Page 9 of 11
VES-6405
Rev. 4, 11/02
16.0
DOCUMENTS REQUIRED
Vendor shall furnish the following documentation prior to final invoicing. Ten (10) sets of
engineering documents shall specifically include.
a)
b)
c)
d)
e)
f)
g)
17.0
Operating Manuals
Maintenance Manuals
Manufacturer's Spare Parts List
Control Schematics and wiring diagrams
Printed Circuit Board Layouts
Dimensioned Outline Drawings
Rectifier Unit Test Report
17.2
17.3
Plug in components and component parts which may not be securely supported by
their sockets during shipment shall be removed, packaged separately and securely
stored within the cabinet. Adequate identification and instructions for remounting
shall be contained in each package.
17.4
All equipment shall be packed and crated so that it is fully protected from damage and
the effects of weather during transport and outdoor storage on site. Desiccant bags
shall be included with the rectifier which shall be sealed in plastic.
17.5
The outside of the crate shall be clearly marked with job (AFE) number, order
number, contents, destination, and total weight. Destination data shall be as detailed
on the Purchase Order.
File: F:\WPDATA\NEWVES\2002\VES-6405
Page 10 of 11
VES-6405
Rev. 4, 11/02
18.0
DATA SHEET
CONDITIONS
1
RECTIFIER
BATTERY
INPUT VOLTAGE
BATTERY CAPACITY
50 HZ ........................ WIRE
RATED OUTPUT
10
BATTERY TYPE
11
Ni-Cd/Pb ..............................................
12
A.C. CABLING
13
14
CABLE TYPE:
CABLE TYPE:
15
CABLE SIZE:
16
D.C. CABLING
CABLE SIZE:
INFORMATION TO BE SUBMITTED WITH TENDER
17
RATED OUTPUT:
VOLTS
KW
A AT
18
MAXIMUM INPUT:
KW
A AT
19
RECTIFIER EFFICIENCY:
20
21
22
BATTERY:
23
NUMBER OF CELLS:
24
TOTAL MASS:
OVERALL DIMENSIONS
26
RECTIFIER/BATTERY UNIT
27
RECTIFIER
28
BATTERY BANKS
HALF
FULL LOAD
A
MAKE
25
VOLTS
FULL LOAD
TYPE Ni-Cd/Pb
KG
LENGTH
29
WIDTH
DEPTH
SPECIAL REQUIREMENTS
30
VES-6405
Rev. 3, 4/93
File:\WP-023\VES6405
Page 11 of 11