Professional Documents
Culture Documents
in
power system
M.G.Morshad / ACM
( Elect.)
Transformer Mtce. Division /
TS II
References
1. REPORT
Series
Shunt
REACTOR
REACTOR
PURPOSE
To reduce short
circuit current
PURPOSE
To reduce over
voltage
AREA OF
APPLICATION
Tie Lines
AREA OF
APPLICATION
Bus , Lines,
Tertiary winging of
ICT
Z
Z
Acts as inductance and
opposes the flow of short
circuit current.
Shunt Reactors
Dry Type
(system voltage
Below 72.5 KV)
Delta connected
Range below 30 MVAR
Connected at the tertiary
winding of transformer
Air Core
Core less
Gapped Core
Permanently connected
type with thyristor
controlled
Installed
Capacity
44220 MW
Availability
28450
MW
Peak Load
demand 34224
MW
Grid voltage lower
than rated (Max
0.95PU or 399 KV)
11Hrs
15Hrs
22
Hrs
03
Hrs
Formula
Data
System Voltage
Skv
420 KV
FkA
40 KA
V1 = 441 KV or
(441/420) PU
1.05 PU
Acceptable Bus
voltage
V2 = 416 KV or
(416/420)PU
0.99 PU
Sst
63 MVAR
Commercial
1. Being a capital item, investment on this equipment will
be adjusted in the fixed cost portion of tariff so that
entire amount ( capital + interest ) will return within the
operating period of the reactors.
Basic operating
principle
2.
3.
System
Voltage, (V)
Induced
Voltage, (e)
Op
e
ra
tin
cu
rre
nt
(I)
System
Voltage
Reactive current (I x Sin )
to reactive load (KVAR)
Ir
Iy
Ib
2. Induced voltage (e) depends upon the construction and magnetization characteristic of
the core
3. Shunt reactor is a device with the fixed impedance value. Therefore the individual phase
current is directly proportional to the applied phase voltage (i.e. I=U/Z).
4. For balance three phase current (Ir + Iy + Ib = 0), no current flows through the neutral.
5.Only during fault when phase current becomes un balance (Ir + Iy + Ib 0), current less
than 1 PU passes through the neutral. It is due to the fact that positive sequence
reactance(X1) is more or less equal to zero sequence reactance (x0) in five limbs core
configuration (Normally X1/Xo = 0.9).
6. During operation heat is produced as a result of copper loss ( due top I2R) and core
Loss ( due to Hysteresis and eddy current)
7. Typical total core & copper loss (KW)= rating of reactor (MVAR) x 0.2%
8. Typical core loss & copper loss = 75% & 25% of total loss respectively
2. Magnetization characteristic
VI
linearity
range
The flux produced by the core remains proportional to the current passes through the coil
till the core gets saturated.
After saturation of core it can not produce flux further with the increase of current.
Because of this magnetic saturation of the core, reactor coil can not develop inductive
voltage (e) further.
In such condition impedance of the coil becomes lower with respect to the applied
voltage and higher current drawn by the winding causing high I2R loss ( heat generation)
or earth fault.
Components of Reactor
WTI
OTI
1.
2.
3.
4.
5.
Buchholtz relay, Pressure relief valve and sudden pressure valve for protection
6.
Floor mounted marshalling box for providing WTI,OTI and required control circuit for
protection
7.
8.
Two numbers treated earth pit for earthing neutral through steel flat
9.
Two number earth grid terminals for earthing reactor tank and other metal structure.
Components of reactor
The core sections between consecutive air gaps are moulded in epoxy
resin to prevent movement between individual laminations. The spacers
forming the air gaps are blocks of ceramics with a high modules of elasticity
and the whole stacking of core modules is cemented together during the
assembly to form a solid column without possibility of rocking , or rubbing
between individual parts.
23
M0H
Hi-B grade
27
M0H
M4
M5
M6
Interleaved disc winding has been used for rated voltages 220 KV
and above. This type of winding configuration provides better impulse
voltage
distribution. For lower voltage classes a continuous disc winding or a multi
layer helical winding are used.
Vibration in reactor
1.
2.
3.
To reduce the vibration within the limit ( 200 micron) following measures are
taken during construction 1. Air gap are filled with ceramic materials 2.
Earthing of Reactor
To earthing grid
LA
LA
LA
To earthing grid
Cooling of reactor
Approximate heat generation
during operation of reactor
due to core and copper loss =
0.2% x MVAR rating
=
120 KW
Copper loss due to I2R loss is
about 25% of total loss i.e.
0.25X120 = 30 KW
Significance of parameters
1. Capacity (S) As reactor is used as inductive load which only absorb
reactive power, it capacity is given in MVAR .
Rated Voltage
1 PU ( 420
KV)
1.05 PU
(441KV)
Rated Capacity
63 MVAR
69.45 MVAR
Current ( MVARx100)/
(1.732xKV)
86.6 Amps
90.92 Amps
VA
0K
0
0
630
110KW
630000KVAR
Operation
TS II Expansion
Gen (2 X 250MW)
400KV
Extension
Bus
Reactor I
Power Grid
Feeder
Tie Line
Stage II Gen
(4 X 210MW)
Power Grid
Feeder
400KV
Bus
Power Grid
Feeder
ICT
Stage I Gen
(3 X 210MW)
230KV
Bus
Mines Feeder
Under excitation
Increasing tap
Decreasing tap
Switchyard Bus
395 415KV
Delivers reactive
power to boost up
voltage
C
A
P
R
E
C
Absorb reactive
power to reduce
bus voltage
Capacitive loading
105% Grid Voltage (445KV)
nt
e
r
r
Cu
Leading
MVAR
Cur
ren
t
Lagging
MVAR
Inductive loading
WHENEVER THE BUS VOLTAGE RAISES TO 4%TO 5% MORE THAN THE RATED
VOLTAGE, SHUNT REACTOR IS TO BE KEPT IN SERVICE AND 2% TO 3% LESS THAN
THE RATED VOLTAGE THIS MAY BE KEPT OUT OF SERVICE.
DC Off set
current
Switching off
During switching off operation of reactor high transient over
voltage is developed due to breaking of inductive current.
This switching transients are inversely proportional to the shunt
reactor rated power
Internal fault
Phase to ground
fault at line side
Phase to ground
fault at neutral side
Phase to phase
short circuit fault
External fault
Phase to ground
fault
Un balance in
phase current
Zero seq
current
(<1 PU)
Shunt reactor is a device with the fixed impedance value. Therefore the
individual phase current is directly proportional to the applied phase voltage
(i.e. I=U/Z). During external fault voltage of the faulty phase becomes lower
than other phases and a result of that unbalance is created in the phase
current. Because of unbalance phase current , zero seq. current less than 1
PU passes through the neutral.
Unbalance in phase
current due to external
earth fault
Un balance in
phase current
N
Zero seq
current
Rated current
passes through the
line side phase
Summary protection
CAUSES
Switching
ON
EFFECTS
RESULTS IN
PROTECTION
ACTUATES
Switching
OFF
External
phase to
ground
fault
Lower than
rated current
through the
faulty phase
Unbalance in three
Line side residual
phase line current
current protection
Low zero sequence
Differential protection
current
( 1PU)
passes through the
neutral
Internal
High current at Unbalance in three
phase to
line side in the phase line current
ground
faulty phase
Low zero sequence
fault at line
current
( 1PU)
side
passes through the
neutral
Internal
High current at Rated current at line Neutral side over
phase to
line neutral
side phases
current protection
ground
side
High current at
Differential protection
fault at
neutral side
neutral side
Internal
As the chance of this fault is very remote due constructional
Phase to
feature of the reactor , protection for this fault is not
phase short recommended.
circuit
Inter turn
fault
Low magnitude
voltage
unbalance
Electrical Protection&
relay scheme
Reactor protection
PURPOSE OF SHUNT REACTOR PROTECTION
The purpose of the protection relaying is to disconnect the reactor and limit damage in
case of internal short circuits, earth faults, inter turn faults and over voltage or over load.
The reactor forms certain impedance for rated frequency, and as it is shunt connected, as
over load may be caused by over voltage or harmonics in voltage and current.
PROTECTION DEVICES INBUILT OR MOUNTED ON REACTOR
a) Oil immersed reactor usually have a gas detector and oil surge detector (Buchholz
alarm & trip devices), which are excellent for detecting internal faults.
b) Temperature monitors for oil & winding provide good over load protection.
c) Pressure relief device is provided to safe guard the reactor from high pressures.
Bus II
Transfer bus
R
E
A
C
T
O
R
I
51N
21
87U
87BB2
87BB1
R
E
A
C
T
O
R
II
51N
21
87U
87BB2
87BB1
1. Differential protection
Purpose :Internal / external phase to ground fault.
U1
Line side CT 1
V1
W1
1s1
1s1
1s1
1s2
1s2
1s2
DP
87
Neutral side CT 1
U2
1s1
1s1
1s1
1s2
1s2
1s2
V2
W2
CT Specification
1. Ratio: 200/1A
2. Class: PS
3. Knee point voltage: 200V
4. Magnetizing current: 40 mA
5. Secondary resistance: 1 Ohms
2.
U1
V1
W1
1s1
1s1
1s1
1s2
1s2
1s2
Instantaneous
Residual over
Current Relay (50N)
Or
AC Time residual
Over Current relay
(51N)
CT Specification
1. Ratio: 200/1A
2. Class: PS
3. Knee point voltage: 200V
4. Magnetizing current: 40 mA
5. Secondary resistance: 1
Ohms
U2
V2
W2
U1
V1
W1
1s1
1s1
1s1
1s2
1s2
1s2
CT Specification
1. Ratio: 200/1A
2. Class: PS
3. Knee point voltage: 200V
4. Magnetizing current: 40 mA
5. Secondary resistance: 1
Ohms
U2
V2
W2
Set low set to 130% with time delay in between 0.6s and 1s.
Set high set to 250% with time delay of 0.1s.
U1
V1
1s1
1s1
1s1
500/1A
500/1A
500/1A
1s2
1s2
1s2
1000/1A
U2
Line Side
W1
1000/1A
1000/1A
1s3
1s3
2000/1A
2000/1A
2000/1A
1s4
1s4
1s4
V2
1s3
W2
Instantaneous
Over Current
Relay (50)
Or
AC time over
current relay
(51)
Over current
protection
Neutral Side
Measurement of WR
2.
Measurement of IR & PI
3.
4.
5.
Isolation test
Temperature rise test along with DGA before and after test
2.
Full wave lighting impulse voltage withstanding test at 550 KVp on neutral terminal
3.
4.
5.
6.
2.
Induced over voltage withstand test with PD indication at 364 KV AC (1.5/3 PU ) for
30 minutes during which the PD level shall not exceed 500pc
3.
Full wave lighting impulse voltage withstand test at 1300 KVp on line terminal
4.
FRA test
2.
3.
4.
5.
6.
Measurement of WR
Purpose - To measure DC resistance per phase of coil for calculating I2R
loss in the coil, which in turns decides the temperature rise. The
measurement also shows whether the winding joints are in order and the
windings are correctly connected.
Voltage lead
Current lead
Resistance
measuring Kit
Measuring methods 1.
Only at the stable value of current (I), corresponding voltage (V) value
is taken for measuring the value of resistance ( R = V/I).
2.
Applied current must not be higher than 15% of the rated current
3.
4.
Measurement of IR
Purpose - To ascertain minimum insulation strength (IR Value) and dryness
level (PI Value) of the winding required to charge the reactor.
5 KV IR measuring
Kit (Megger)
Procedure Measure IR and PI value between (R-E),(Y-E),(B-E) and
(R+Y+B) (Tank + E) with 5 KV Megger and confirm the minimum IR and
PI value as per the table given below.
Minimum Below 6.6 KV 6.6 - 11KV
IR value
22 33 KV
Above 66 KV
K = 1.00 30 Deg
C
200 M
400 M
500 M
600 M
K = 1.65 40 Deg C
121 M
242 M
303 M
363 M
K = 2.60 50 Deg C
77 M
153 M
192 M
230M
K = 4.20 60 Deg C
47 M
95M
119 M
142 M
K = 6.6 70 Deg C
30 M
60 M
75 M
90 M
K = 10.5 80 Deg C
19 M
38 M
47 M
57M
Isolation test
Purpose - To ascertain that the reactor core is insulated from the tank and
core frame.
CC
CL
Core clamp
Core Bolt
Core
Tank
Procedure :
1.Disconnect the closing link that connects the two terminals CL-G.
2.Connect the tank with earth
3. Use a Megger and measure IR value between CL and CC + G by applying
3.5 KV for 1 minute
4. The measured IR value shall be minimum 1000 kohms ( 1 M Ohms)
5. There is no general requirement on the insulation level CC-G .
Reactor
windings
U1 CT Ratio
M3 Mutual Inductance
100/5A
1.0032mH
CN standard
Capacitor
C4 Bridge
capacitance
R4 Bridge Resistance
Lx Inductance (H) of (M3/U1)X(C4/CN
)
the winding
Z Impedance
( Ohms) of the
winding
2 fLx
8.92 H
2800 Ohms
Reactors
windings
U1
CT Ratio
100/5A
M3
Mutual Inductance
1.0032mH
CN
standard Capacitor
C4
Bridge capacitance
R4
Bridge Resistance
Inductance (Lx)
(M3/U1)X(C4/CN)
8.92 H
Impedance (Z)
2 fLX
2800 Ohms
Tan delta ( D)
1 / ( C4 R4)
(U2/Z) x D x 10-3
kW
kW
Switching
Impulse
(KV Peak )
Lighting
impulse
(KV Peak )
0.415
1.1
3.3
3.6
10
20/40
6.6
7.2
20
40/60
11
12
28
60/75
15
17.5
38
75/95
24
50
95/125
36
70
145/170
52
95
250
72.6
140
325
123
185/230
450/550
145
230/275
550/650
170
230/275/325
550/650/750
245
325/370/395
750/850/950
300
395/460
750/850
950/1050
362
460/510
850/950
1050/1175
420
570/360
950/1050
1300/1425
33
66
230
400
KV
50 Hz, AC
Generator
Method
Maximum
test voltage
Duration of
test
60 sec
KV
50 Hz, AC
Generator
Method
Maximum test
voltage
Duration of test
Measurement of
test voltage
Confirmation
364KV
420KV
364KV
Impulse
Generator
+
5
0
0
Recorder
Method
Test voltage
Duration of
test
Confirmation
Impulse
Generator
+
5
0
0
Recorder
Method
Front time Tp> 100s , Time above 90% Td> 200s and Time
to the first zero passage T0> 500s ( preferably 1000 s )
Confirmation The test is successful if the test voltage does not collapse
during the test.
Type Test
1. Temperature rise test along with DGA before and
after test
2. Full wave lighting impulse voltage withstanding test at
550 KVp on neutral terminal
3. Measurement of zero sequence reactance
4. Measurement of acoustic noise level
5. Magnetizing curve test / knee voltage measurement
6. Measurement of capacitance and tan delta between
winding and tank
R1
R2
Ta
Tw = {R2(235+T)R1}
235
T1
T2
Td = (T1 - T2)
Tc = (Tw + Td)
(Tc Ta)
Impulse
Generator
+
5
0
0
Recorder
Method
Confirmation The test is successful if the test voltage does not collapse
during the test.
A
N
B
50 Hz, AC
Generator
Method
Zero seq
impedance
1 Meter
Microphone for
picking up noise
2 Meter
A sound spectrum analyses is used for measuring sound level. The sound
spectrum indicates the magnitude of sound components as a function of
frequency. The sound pressure level is the measured at various points
around at a distance (D) of 30 cm for ONAN or 2 m for ONAF cooling
system spaced at an interval (X) of 1 meter.
Limit
Sound level
Within 81db
Vibration level
Test procedure
Each phase of the reactor is charged one by one with direct current.
When the maximum test current reached, supply is switched off and the reactor
winding is short-circuited simultaneously by DC current breaker.
The saturation curve Flux () / Flux () nom. versus I/Inom is then determined
using the formula.
Imax
Imin
Measured value
I(t)
I
N
Ic
+ Ir
10 KV
Tan
Delta
Kit
Ir
Angle
Capacitance (pF)
[(I/2 f V ) x Cos ]
Condition of the
insulation
0.0 Deg
(I / 3140) x 1.000
Pure capacitor
0.5 Deg
(I / 3140) x 0.999
0.002
Very good
0.5 Deg
(I / 3140) x 0.999
0.004
Good
0.5 Deg
(I / 3140) x 0.999
0.006
Fairly good
0.5 Deg
(I / 3140) x 0.999
0.007
Acceptable
0.5 Deg
(I / 3140) x 0.999
0.008
Not acceptable
90.0 Deg
1.0
Pure resistance
Special Test
1. FRA test
2. DGA test before and after electrical test
3. Vacuum test on reactor tank
4. Oil leak test
5. Snap back test on HV bushing
FRA test
Purpose- Frequency Response Analysis (FRA) is carried out to
detect displacement (or movement) of the windings. Usually the
first measurement in the factory is used as a fingerprint. Results of
later measurements are compared with the first one in the factory.
DGA test
Chemical analysis of gas : The gas analyser loaded with these solution is
connected to the top pet cock. Small quantities of gas collected in the gas
relay (Bucholtz relay) is allowed to pass through the two solutions.
FFT
Natural
From FFT reading
frequency
X direction
Y
direction
3.25
3.25
Final Observations
Thank you