You are on page 1of 3

TECHNICAL SELECTION

Page 1 / 3

AXO/AXU/MOD 15
Software version:
Report version:
DB version:
User:
Print data:

3.3.5.0 - 3.3.5.0
1.0.1.0
3.7.0.0
Ristea Diana
04/04/2016 17:18

INDOOR UNIT
GENERAL DATA
Model
Version
Frame
Primary circuit type
No. Circuits
Refrigerant
UNIT DESCRIPTION [General descriptions and images of
the range, not specific to the choice of model]

AXO/AXU/MOD 15
MOD
F02
DIRECT EXPANSION AIR COOLED
1
R410A
Close control unit, air cooled, direct expansion

MAIN CIRCUIT
DESIGN CONDITIONS
Dry bulb temperature
Relative humidity
Altitude
Air flow
ESP External Static Pressure
Outdoor air temperature

C
%
m
m/h
Pa
C

21.0
50
0
4900
20
35.0

kW
kW
kW
kW

kW
C
%

15.2
15.2
14.3
14.3
1.00
3.28
4.64
11.9
89

N
kW

SCROLL
1
3.79

N
m/h
kW

EC BASIC
2
4900
0.86

PERFORMANCE AT DESIGNED CONDITIONS


Total cooling capacity gross
Sensible cooling capacity gross
Net cooling capacity
Net sensible cooling capacity
SHR
EER (Indoor unit)
Total power input (Comp.+fans)
Outlet air temperature
Relative humidity outlet

COMPRESSORS
Compressor type
Compressors nr.
Compressors power absorption

FANS
Fans type
Quantity
Air flow
Fans power input

ACCESSORIES
FILTERS
Accessory filter type

G2 filter

ELECTRICAL HEATER
Heater description
Quantity
Steps
Elettrical power abs.
Max absorbed current (FLA)
Power supply

N
N
kW
A
V/ph/Hz

The performance shown are obtained from theoretical calculations and tolerances will apply.

Basic heater 8,1 kW400/3/50


1
3
8.10
11.7
400/3/50

TECHNICAL SELECTION

Page 2 / 3

AXO/AXU/MOD 15
Software version:
Report version:
DB version:
User:
Print data:

3.3.5.0 - 3.3.5.0
1.0.1.0
3.7.0.0
Ristea Diana
04/04/2016 17:18

HUMIDIFIER
Humidifier type
Quantity
Capacity
Elettrical power abs.
Max absorbed current (FLA)
Power supply

Humidifier 5 kg/h
1
5.0
3.75
5.50
400/3/50

N
kg/h
kW
A
V/ph/Hz

NOISE DATA
Spectrum
Noise Power
Noise Pressure
Distance

Hz
dB(A)
dB(A)
m

63
64
44

125
67
47

250
72
52

500
70
50

1000
67
47
2.0

2000
64
44

WEIGHT & DIMENSIONS


A
B
H
Weight
Packaged dimension A
Packaged dimension B
Packaged dimension H
Packaged weight

mm
mm
mm
kg
mm
mm
mm
kg

1000
500
1980
224
1060
560
2120
229

V/ph/Hz
kW
A
A
kW

400/3+N/50
15.0
27.5
73.5
4.65

ELECTRICAL DATA (refer to indoor unit)


Power supply
Max Electrical power absorbed (FLI)
Max absorbed current (FLA)
Max inrush current (SA)
Power input (OI)

REMOTE CONDENSER
MAIN CIRCUIT
REMOTE CONDENSER
Code
Quantity
Version
Circuits
Outdoor air temperature
Air flow
Rejection capacity
Dimension A
Dimension B
Dimension H
Weight
Packaged dimension A
Packaged dimension B
Packaged dimension H
Packaged weight
Power supply
Elettrical power abs.
Max absorbed current

N
N
C
m/h
kW
mm
mm
mm
kg
mm
mm
mm
kg
V/ph/Hz
kW
A

The performance shown are obtained from theoretical calculations and tolerances will apply.

BRE 022m BASIC


1
BASIC
1
35.0
8200
18.8
1360
703
1114
89
1472
830
1252
35
230/1/50
0.60
2.62

4000
60
40

8000
58
38

Tot
73
53

TECHNICAL SELECTION

Page 3 / 3

AXO/AXU/MOD 15
Software version:
Report version:
DB version:
User:
Print data:

3.3.5.0 - 3.3.5.0
1.0.1.0
3.7.0.0
Ristea Diana
04/04/2016 17:18

NOISE DATA
Noise Power
Noise Pressure
Heating capacity

dB(A)
dB(A)
m

The performance shown are obtained from theoretical calculations and tolerances will apply.

76
57
2.0

You might also like