Wiring Diagrams
INDEX
UNIT 50BYN
006
008
012
014
016
024
V-PH-Hz
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
208/230-3-60
460-3-60
575-3-60
LABEL DIAGRAM
FIG. NUMBER
11720011-C
11720960-B
1172007-C
ACCESSORY WIRING
UNIT 50BYN
006-024
ACCESSORY DESCRIPTION
Winter Start
Evaporator Defrost Thermostat
TEMP Thermostat
Variable Volume and Temperature (VVTT) and Relay Pack
Airside Economizer
Airside Economizer with Indoor Air Quality (IAQ) Sensor
Fire and Smoke Control
Heater
FIG. NUMBER
4
5
6
7
8
9
10
11
006-024
THERMOSTAT
33CS071-01
33CS220-01
33CS250-01
33CS220-LA
33CS250-LA
33CSPTN-01
33CSTM--01 and 33CSUCE-06
33CSTMT-01 and 33CSUCE-06
33CSVM--32 and 920008
33CSVMT-32 and 920008
DESCRIPTION
Non-Programmable
Programmable; 7-Day and Non-Communicating
Programmable; 7-Day and Communicating Without Clock
Programmable; 7-Day and Communicating With Clock
VVT; Programmable Without Clock
VVT; Programmable With Clock
FIG. NUMBER
1, 2, 3
1, 2, 3
6
6
7
7
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
PC 111
Catalog No. 535-051
Printed in U.S.A.
Form 50BY-1W
Pg 1
3-99
Replaces: New
Tab 2b 7a
Compressor Contactor
Circuit Breaker
Compressor Lockout
Control Relay
Defrost Thermostat (Evaporator)
Equipment
Filter Status
Ground
High-Pressure Switch
Humidity Sensor
Indoor Air Quality
Indoor-Fan Contactor
IFM
IFP
LPS
NEC
OFC
OFM
OFP
R
T
TB
TDR
TRAN
Indoor-Fan Motor
Indoor-Fan Protector
Low-Pressure Switch
National Electrical Code
Outdoor-Fan Contactor
Outdoor-Fan Motor
Outdoor-Fan Protector
Resistor
Timer
Terminal Block
Time-Delay Relay
Transformer
Field Splice
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Factory Wiring
Field Wiring
OPERATING SEQUENCE
Economizer
DESCRIPTION
Wall Mount Sensor (No Display)
Wall Mount Sensor With Display
Duct Mount Sensor (No Display)
Sensor Calibration Service Kit
User Interface Program (UIP)
The CO2 sensors listed above are all factory set for a range
of 0 to 2000 ppm and a linear voltage output of 2 to 10 vdc.
The relay normally open dry contacts (TB-3 and TB-4) are
factory set to close at 1000 ppm. Refer to the installation
instructions with the CO2 sensor for electrical ratings of contacts and information on connecting to power supply. Switch
contacts can be used to set off an alarm or light to indicate
CO2 levels higher than the switch set point. Any changes to
the factory configuration require the purchase of the User
Interface Program (UIP) or Sensor Calibration Service Kit,
which also contains the UIP. For correct modulation of the
economizer actuator motor, a separately ordered adapter
(Honeywell part no. Q769C1007) is required.
NOTE: If a CO2 sensor is used, the economizer can modulate based on the carbon dioxide level in the space. There is
no low leaving-air temperature limit control. Controls to accomplish this must be field-supplied and installed.
On a call for cooling from the thermostat (Y1 energized),
the actuator logic module determines if the outdoor air enthalpy is acceptable according to the set point on the actuator. If the outdoor air enthalpy is acceptable, the economizer
begins to modulate open and is controlled to maintain a
56 F leaving air temperature. If outdoor air enthalpy is
unacceptable, the logic module bypasses the use of outdoor
Fig. 1 Wiring Schematic and Component Arrangement; 50BYN006-008; 208/230-3-60, 460-3-60, 575-3-60
Fig. 2 Wiring Schematic and Component Arrangement; 50BYN012-016; 208/230-3-60, 460-3-60, 575-3-60
Fig. 3 Wiring Schematic and Component Arrangement; 50BYN024; 208/230-3-60, 460-3-60, 575-3-60
BLK
ORN
RED
RED
50 BYN UNIT
LOW VOLTAGE WIRING
CB
TRAN
A
RED
BRN
3.2 AMPS
24V
BLU
CR
1
IFP
3
RED
BLK
C1 IFC C2
R
BRN
TB2
BLK
C1 OFC C2
BRN
BRN
T1
ORN
LOGIC
Y1
ORN
3
2
RED
TDR1
X
ORN
BLU
R1
LOGIC
CLO1
BRN
LPS1
OFP
HPS1
BLU
BLU
BLU
C1 C1 C2
BLU
BRN
C1 CR C2
TDR
WINTER
START
BRN
BLK
ORN
RED
RED
50 BYN UNIT
LOW VOLTAGE WIRING
CB
TRAN
A
RED
BRN
3.2 AMPS
24V
BLU
CR
1
IFP
3
RED
BLK
C1 IFC C2
R
BRN
TB2
BLK
G
REMOVE
ORN WIRE
T1
C1 OFC C2
BLU
R1
ORN
LOGIC
3
2
Y1
RED
TDR1
X
BRN
BRN
CLO1
X
ORN
LOGIC
BRN
LPS1
OFP
HPS1
BLU
BLU
BLU
C1 C1 C2
BLU
BRN
C1 CR C2
DT
BRN
COMMUNICATION
BUS
BLACK
RED
GREEN
RED (+)
TO HEATER
IF USED
REMOTE ROOM
BLACK (-)
SENSOR
SEE NOTE BELOW
FIGURE "A"
HUMIDITY SENSOR
W
R
HS
10
11
WHITE
RED
BLUE
YELLOW
GREEN
FILTER STATUS
SWITCH
10
FSS
11
IAQ SWITCH
FAN STATUS SWITCH
DX COIL
TEMPERATURE
SENSOR
SEE "A"
BLACK
BLACK
BLACK
RED
RED
RED
OUTSIDE AIR
TEMPERATURE
SENSOR
W
R
B
Y
G
6
7
8
9
10
11
12
13
14
15
16
17
COOL
R
V
F
A
N
HEAT
13
12
11
10
9
8
7
6
5
4
3
2
1
FIELD-INSTALLED
JUMPERS
FAN
HEAT 2
HEAT 1 NC
HEAT 1
HEAT/FAN COM
COOL 2
COOL 1
COOL COM
24 VAC (REQ)
24 VAC (COMMON)
GROUND
JUMPER
7 TO 4 TO 3
SUPPLY AIR
TEMPERATURE
SENSOR
50 BYN UNIT
LOW VOLTAGE WIRING
BLK
ORN
RED
CB
TRAN
A
RED
BRN
3.2 AMPS
24V
RED
CR
TB2
1
ORN
IFP
3
RED
BLK
C1 IFC C2
R
BRN
TB2
BLK
C1 OFC C2
BRN
BRN
BRN
T1
ORN
LOGIC
Y1
BLU
ORN
3
2
RED
LOGIC
TDR1
X
ORN
BRN
CLO1
X
BRN
LPS1
OFP
HPS1
BLU
BLU
BLU
C1 C1 C2
BLU
C1 CR C2
LOGIC
Y2
BLK
T2
BLK
3
2
BRN
RED
TDR2
LOGIC
CLO2
ORN
BRN
BRN
LPS1
ORN
HPS1
BLU
C1 C2 C2
BLACK
GREEN
WHITE
RED
COMMUNICATION
BUS
BLACK
RED
GREEN
RED (+)
DAMPER
ACTUATOR
BLACK (-)
RED
WHITE
BLUE
YELLOW
GREEN
HUMIDITY SENSOR
WHITE
RED
BLACK
GREEN
WHT
BLK
GRN
BLK
ORN
RED
BLK
RED
BLK
RED
VELOCITY SENSOR
BLACK
RED
DX COIL SENSOR
BLACK
RED
MONITOR STAT
W/TIME CLOCK
TRANSFORMER
24 VAC/25VA
DC CONNECTOR HARNESS TO
DAMPER ACTUATOR BOARD
REMOTE ROOM
SENSOR (RRS)
(OPTIONAL)
TO HEATING COIL
(IF USED)
WHITE H1
BROWN H2
YELLOW C1
BLUE C2
GREEN FSN
RED 24 VAC
BLACK (RVH)
ORANGE (RVC)
BLK
ORN
RED
50 BYN UNIT
LOW VOLTAGE WIRING
CB
TRAN
A
RED
BRN
3.2 AMPS
24V
RED
CR
TB2
1
ORN
IFP
3
RED
BLK
C1 IFC C2
R
BRN
TB2
BLK
C1 OFC C2
BRN
BRN
BRN
T1
ORN
LOGIC
Y1
BLU
ORN
3
2
RED
LOGIC
TDR1
X
ORN
BRN
CLO1
X
BRN
LPS1
OFP
HPS1
BLU
BLU
BLU
C1 C1 C2
BLU
C1 CR C2
LOGIC
Y2
BLK
T2
BLK
3
2
BRN
RED
TDR2
LOGIC
CLO2
ORN
BRN
BRN
LPS1
ORN
HPS1
BLU
10
C1 C2 C2
ORN
BLK
RED
50 BYN UNIT
LOW VOLTAGE WIRING
CB
A
RED
ER
TRAN
BRN
3.2 AMPS
24V
RED
FIELD THERMOSTAT
NEC CLASS II
CR
TB2
IFP
ORN
C1 IFC C2
RED
BLK
CONT
BRN
BLK
AUTO
C1 OFC C2
BRN
BRN
BRN
COOL
T1
ORN
Y1
ORN
TC1
LOGIC
3
2
OFF
RED
LOGIC
TDR1
BRN
CLO1
LPS1
ORN
BLU
OFP
HPS1
BLU
BLU
BLU
C1 C1 C2
BLU
BRN
C1 CR C2
LOGIC
TC2
Y2
BLK
T2
BLK
3
2
BRN
RED
LOGIC
TDR2
ORN
CLO2
BRN
BRN
LPS2
HPS2
BLU
ORN
C1 C2 C2
TR
24 VAC
ER
WHT
WHT
TR
TR1
SO
SR
TR1
GRN
ENTHALPY
+
ECONOMIZER
ACTUATOR
ORN
S
SENSOR
RESISTOR
SEE NOTE 2
YEL
1K
RED
BRN
1S
2K
SAT
SENSOR
GRA
C
CB
CLO
CR
ER
HPS
IFC
IFP
LPS
NEC
OFC
OFP
SAT
TB
TDR
TR
TRAN
LEGEND
Compressor Contactor
Circuit Breaker
Compressor Lockout
Control Relay
Economizer Relay
High-Pressure Switch
Indoor-Fan Contactor
Indoor-Fan Protector
Low-Pressure Switch
National Electrical Code
Outdoor-Fan Contactor
Outdoor-Fan Protector
Supply-Air Temperature
Terminal Block
Time-Delay Relay
Terminal
Transformer
SEE NOTE 1
MIXED AIR
SENSOR
1S1
GRA
T
T1
P1
T1
MINIMUM POSITION
ADJUSTMENT
P1
P
MINIMUM
POSITION
BLU
NOTES:
1. If system has single-stage cooling, disregard and terminate blue wire in
harness. If thermostat is single stage cooling, disregard and terminate
brown wire.
2. Factory installed 620 ohm, 1 watt, 5% resistor should be removed only
if a C7400 enthalpy sensor is added to SR and + for differential enthalpy.
3. Economizer relay closes outside air damper when fan is not powered.
Terminals
Wire Nut or Equivalent Connection
Field Wiring
Factory Wiring
11
HONEYWELL DAMPER
ACTUATOR M7415 AND
W7459 LOGIC MODULE
P1
WHITE BLACK
LEGEND
P
Pressurization Relay
PPM Parts per Million
TB
Terminal Block
NOTES:
1. CO2 Ventilation controller can be mounted in return-air duct or wall
mounted. Locate for best room air sampling. If duct mounted,
install in aspiration box.
2. Damper actuator and logic module ordered separately.
3. The CO2 ventilation controller has a range of 350 to 2250 PPM
and has a hysteresis of 50 PPM.
4. Optional temperature switches can be added to lockout occupied
modes setting for extreme high or low temperatures.
P1
BLACK
REAR TOP IS "P1"
WHITE
REAR BOTTOM IS "P"
TB10
TB9
CO 2 VENTILATION
CONTROLLER
Fig. 9 Wiring Diagram; Airside Economizer With Indoor Air Quality (IAQ) Sensor
12
BLK
ORN
RED
RED
ER
TRAN
BRN
3.2 AMPS
FIRE OR SMOKE
DETECTOR
CONTACTS
(SHUTS DOWN
TB2
FIELD THERMOSTAT UNIT)
NEC CLASS II
50BYN UNIT
LOW VOLTAGE WIRING
CB
24V
RED
CR
1
ORN
IFP
3
C1 IFC C2
RED
BLK
CONT
P1
BRN
BLK
AUTO
C1 OFC C2
BRN
BRN
BRN
COOL
T1
ORN
Y1
ORN
TC1
LOGIC
P2
OFF
3
2
RED
LOGIC
TDR1
X
BLU
BRN
CLO1
ORN
LPS1
OFP
HPS1
BLU
BLU
BLU
C1 C1 C2
BLU
BRN
C1 CR C2
LOGIC
F1
Y2
TC2
BLK
BRN
RED
TDR2
T2
ORN
BLK
LOGIC
CLO2
BRN
BRN
LPS2
HPS2
BLU
ORN
ER
C1 C2 C2
EXH
FAN
TR
24 VAC
ER
WHT
WHT
TR
TR1
SO
SR
TR1
GRN
ENTHALPY
+
ECONOMIZER
ACTUATOR
ORN
5
SENSOR
RESISTOR
SEE NOTE 2
1
S
YEL
1K
RED
BRN
1S
2K
SAT
SENSOR
MIXED AIR
SENSOR
1S1
GRA
GRA
T1
P1
ER
T1
LEGEND
C
CB
CLO
CR
ER
HPS
IFC
IFP
LPS
NEC
OFC
OFP
P1
R
SAT
TB
TDR
TRAN
Compressor Contactor
Circuit Breaker
Compressor Lockout
Control Relay
T
Economizer Relay
High-Pressure Switch
Indoor-Fan Contactor
Indoor-Fan Protector
Low-Pressure Switch
National Electrical Code
Outdoor-Fan Contactor
Outdoor-Fan Protector
Pressurization Relay
Resistor
Supply-Air Temperature
Terminal Block
Time-Delay Relay
Transformer
SEE NOTE 1
MINIMUM POSITION
ADJUSTMENT
P1
P
MINIMUM
POSITION
BLU
NOTES:
1. If system has single-stage cooling, disregard and terminate blue wire in harness. If thermostat is single stage cooling, disregard and terminate brown wire.
2. Factory installed 620 ohm, 1 watt, 5% resistor should be removed only if a C7400
enthalpy sensor is added to SR and + for differential enthalpy.
3. Economizer relay closes outside air damper when fan is not powered.
Terminals
Wire Nut or Equivalent Connection
Field Wiring
Factory Wiring
13
H1
H2
ORN
BLK
RED
C
CB
A
RED
TRAN
H2
BRN
3.2 AMPS
24V
RED
CR
TB2
IFP
ORN
RC
BRN
RH
OFF
HEAT
AUTO
FAN
SW
COOL
TH1
BLK
ON
BRN
BRN
T1
AHA
LOGIC
Y1
AHA
BLU
ORN
ORN
3
2
RED
LOGIC
TDR1
TH2
C1 OFC C2
BRN
G
AUTO
W1
ORN
BRN
BRN
CLO1
LPS1
OFP
HPS1
BLU
BLU
X
OFF
HEAT
AUTO
BLU
C1 C1 C2
BLU
W2
C1 CR C2
LOGIC
C
COOL
C1 IFC C2
RED
BLK
Y2
BLK
T2
BLK
TC1
3
2
BRN
RED
TDR2
Y1
CC CC
ORN
LOGIC
CLO2
BRN
BRN
LPS2
HPS2
ORN
BLU
TC2
Y2
FIELD THERMOSTAT
LEGEND
AHA
C
CB
CLO
CR
H1, H2
HPS
IFC
IFP
LPS
OFC
OFP
R
TB
TDR
TRAN
Resistor
Terminal Block
Time-Delay Relay
Transformer
Terminal Block Connection
Marked Terminal
Unmarked Terminal
Factory Wiring
Field Wiring
14
C1 C2 C2