You are on page 1of 50

OSM15/25_Al_2

SEL-651R COMPATIBLE SERIES


Outdoor Switching Module
15 kV, ...16 kA, ...630 A
27 kV, ...12.5 kA, ...630 A
Application Guide MAN5002230
Revision 5

This application guide contains information necessary for installation, commissioning


and operation. It is absolutely necessary for the proper and safe use of the OSM to
read this application guide carefully before starting and to adhere to the instructions
as well as relevant regulations.

Safety First
Installation, operation and maintenance shall only be carried out by trained and
experienced personnel who are familiar with the equipment and the electrical
safety requirements.
During installation, commissioning, operation and maintenance of the equipment
the relevant legal regulations (such as NFP70E, CEC, ANSI), accident prevention

regulations and the connecting conditions of the electric utilities shall be followed.
Take note that during operation of the OSM certain parts are subject to
dangerous voltage. Mechanical parts, also remote-controlled, can move quickly.
Failure to comply may result in death, severe personal injury or damage to
equipment.
Pay attention to the hazard statements located throughout this manual.
The operating conditions of the OSM shall comply with the technical data specified
in this manual.
Personnel installing, operating and maintaining the equipment shall be familiar
with this manual and its contents.
For special configurations please contact Tavrida Electric North America.

Table of Contents
1. Introduction




Applicability ..........................................................................................................................................7
Hazard Statements..................................................................................................................................8
Safety Instructions..................................................................................................................................8
Definitions..............................................................................................................................................9
General .................................................................................................................................................9

2. OSM Recloser
2

3
4
5

Overview .............................................................................................................................................. 11
Vacuum Circuit Breaker - VCB................................................................................................................ 12
Protective Tank..................................................................................................................................... 14
Main Circuit Bushings........................................................................................................................... 15
Bushing extensions............................................................................................................................... 15
Cable Clamps......................................................................................................................................... 16
Current Transformers............................................................................................................................. 17
Mechanical Trip..................................................................................................................................... 18
Mechanical Position Indicator............................................................................................................... 18
Protective lid........................................................................................................................................ 18

3. Installation: Primary Part

General, Preparation............................................................................................................................. 20
Bracket Mounting.................................................................................................................................. 20
Main Terminal Connection..................................................................................................................... 21

4. Installation: Secondary Part





Secondary Connections of the OSM........................................................................................................ 23


Auxiliary Circuit Terminations................................................................................................................ 23
Protective Earthing............................................................................................................................... 25
Fitting of the Manual Trip Hook............................................................................................................. 25

5. Commissioning, Maintenance




General................................................................................................................................................. 27
Commissioning Primary Part.................................................................................................................. 27
Commissioning Secondary Part.............................................................................................................. 27
Maintenance......................................................................................................................................... 27
Non-conformity..................................................................................................................................... 27

6. Receiving and Inspection


Packing ................................................................................................................................................ 30



Transport ............................................................................................................................................. 31
Unpacking, GoodsReceived Control....................................................................................................... 31
Rating Plate, Seal................................................................................................................................. 32
Storage................................................................................................................................................. 32

7. Product Line
Outdoor Switching Module(OSM).......................................................................................................... 34
Accessories........................................................................................................................................... 34

8. Dimensions and Weights





Dimensions and Weights of the OSM...................................................................................................... 36


Dimensionsof the OSM Earthing Provisions........................................................................................... 36
Dimensions of the Mounting Provisions................................................................................................. 36
Standard Mounting Hardware ................................................................................................................ 37

9. Circuit Diagrams
10. Technical Data
Outdoor Switching Module (OSM).......................................................................................................... 41
Ambient Conditions............................................................................................................................... 43

11. Legal Information









Warranty............................................................................................................................................... 45
Quality Regulations............................................................................................................................... 45
Complaints and .................................................................................................................................... 45
Transport Damage................................................................................................................................. 45
Environmental Friendliness.................................................................................................................... 46
Non-conformity Report.......................................................................................................................... 46
Liability................................................................................................................................................ 46
Copyright.............................................................................................................................................. 46

7
8
9
10
11
12
13
14

Introduction

Applicability
This application guide applies to a range of Outdoor Switching Modules (OSM) manufactured by Tavrida Electric that
work specifically with the Schweitzer Engineering SEL-651R Recloser Control:

Model Types - 15 kV
OSM15_Al_2(630_150)

Model Types - 27 kV

OSM25_Al_2(630_150)

The OSM_Al_2(xxx_150) series are compatible only with the Schweitzer Engineering SEL-651R. Chapters in this manual
refering to mounting, primary connection and operation of the OSM; for all information relating to the operation, mounting
and functionality of the SEL-651R control please consult the applicable manual provided by Schweitzer Engineering.
The model number is shown on the equipment rating plates. If your equipment does not correspond to the numbers in the
table above then this manual is not applicable. Please contact your nearest Tavrida Electric office or Distributor for the
correct documents.
Every care has been taken in preparation of this manual. However, please note that not all the details or variations
in the equipment or process being described can be covered. Neither is it expected to address all contingencies
associated with the installation and operation of this equipment. For any further information please contact your nearest
Tavrida Electric office or Distributor.

Hazard Statements
This manual contains three types of hazard statements, as follows:

DANGER:

Indicates an imminently hazardous situation that, if not avoided, will result in death or
serious injury.


WARNING:
Indicates a potentially hazardous situation that, if not avoided, could result in death
or serious injury.

CAUTION:

Indicates a potentially hazardous situation that, if not avoided, could result in personal
injury or equipment damage.

Safety Instructions
General hazard statements applying to this equipment are described in this section. Statements relating to specific
tasks or procedures are located throughout this manual.

DANGER:

Contact with hazardous voltage will cause death or severe personal injury. Contact with
Recloser or Control Cubicle terminals should only be undertaken when equipment is
isolated from applicable sources of voltage.


WARNING:

This equipment is not intended to protect human life. Follow all locally approved safety
procedures when installing or operating this equipment. Failure to comply may result in
death or severe personal injury.


WARNING:

Before working with equipment described in this manual carefully read and understand the
contents of this manual. Improper handling, installation, operation or maintenance can
result in death, severe personal injury or damage to equipment.


WARNING:

Power distribution equipment must be properly selected for the intended operation. It
must be installed, used and understand all relevant safety procedures. Failure to comply
can result in death, personal injury or equipment damage.

Definitions
The following abbreviations are used in this operating manual:
AR
CM
CO
SM
LED
MCB

Automatic reclosing
Control module
Close open cycle
Switching module
Light emitting diode
Miniature circuit breaker

NC
Normally closed contact
NO
Normally open contact
OSM Outdoor switching module
PCD Pole center distance
SCADA Supervisory control and data aquisition
VCB Vacuum circuit breaker
VI
Vacuum interrupter

Make time
The make time is the time period from the energising of the closing circuit to the time when the current begins to
flow in the first pole.
Closing time
The closing time is the time period from the energising of the closing circuit to the time when all three poles have
contact.
Pre-arcing time
Interval of time between the initiation of current flow in the first pole during a closing operation and the instant
when the contacts touch in all poles for three-phase conditions and the instant when the contacts touch in the
arcing pole for single-phase conditions.
Opening time
The opening time is the time period from energising of the closing circuit up to the time when all the switching
poles are separated.
Break time
The break time is the time period from the energising of the closing circuit up to the time when the arcs of all the
poles are extinguished.
Open-close time (during AR)
Interval of time between the instant when the arcing contacts have separated in all poles and the instant when the
contacts touch in the first pole during a reclosing cycle.
Dead time (during AR)
Interval of time between final arc extinction in all poles in the opening operation and the first reestablishment of
current in any pole in the subsequent closing operation.

General
The outdoor switching module (OSM) is designed for use as an automatic
circuit recloser or a sectionalizer on overhead distribution lines and as
an outdoor switching module in distribution substation applications for
voltages up to 27 kV.

Figure 1

OSM Recloser

10

Overview
Tavrida Electrics outdoor switching module provides the following advantages:
Environmentally friendly
The OSM is an air insulated outdoor switching module.
The patented combined insulation makes it the environmentally friendly option.
The reliability of the design is proven by the worlds most severe climate and pollution conditions test at the Koeberg
Insulator Pollution Test Station (KIPTS) in South Africa.

Smallest Dimensions and lowest Weight


Tavrida Electrics light weight vacuum circuit breaker and the robust aluminium tank contribute to the light weight
of the OSM - not more than 76kg - making these the most light weight outdoor switching modules on the market,
greatly simplifying shipping, handling and installation.
Highest Availability
30,000 C-O operations at rated current and up to 200 operations with full short circuit breaking current without any
maintenance, makes them the most reliable product on the market.
Optimized Measurement
Built-in voltage sensors on all six pole and three current transformers guarantee high accuracy over a wide
measurement range.

1. Terminal
2. Six HV bushings
3
4
5
6

3. Current transformers built into the bushings


4. Vacuum circuit breaker
5. Protective tank
6. Mechanical position indicator
7. Manual trip operation mechanism
8. Protective lid with Harting connector

9. Support rail

8
9

Figure 2
General arrangement of the OSM

11

Vacuum Circuit Breaker - VCB


Each OSM is equipped with Tavrida Electrics innovative vacuum circuit breaker (VCB). Tavrida Electric has simplified
the mechanical structure of the vacuum circuit breaker to the greatest possible degree. It uses three single-coil
magnetic actuators, one per pole. All switching elements are assembled along a single axis. All mechanical
movements are therefore direct and linear. The three actuators are mounted in a steel frame and mechanically
linked by a synchronizing shaft. Optimal selection of all components makes these the most compact vacuum
circuit breakers in the world.
Failure of critical components, such as
mechanical latching
gears, chains, bearings and levers
tripping and closing coils
motors to charge springs
are completely avoided.

Maximizing the benefits of the drive mechanism requires vacuum interrupters that combine small dimensions with an
extraordinarily long mechanical and electrical lifespan. The use of a predefined axial magnetic field shape provides
even distribution of current density and consequently substantial improvement of vacuum interrupting performance.
Carefully selected contact material and expert contact design as well as optimized movement and switching speed
result in bounce-free closing.
Substantial increase in mechanical lifespan as well as size reduction of Tavrida Electric vacuum interrupters was achieved
by utilizing metal bellows consisting of welded single discs as opposed to the conventional use of folded steel.
The result is 30,000 C-O cycles at rated current or up to 200 operations at full short-circuit breaking current without
the need to replace or adjust any parts of the vacuum circuit breaker.
Tavrida Electrics vacuum circuit breaker are entirely maintenance free over a total life expectancy of at least 30 years.

Vacuum Circuit Breaker (VCB)

1. Upper terminal
2. VI
1

3. Lower terminal
4. Movable contact with bellows
5. Flexible junction shunt

2
3
4

15

6. Drive insulator
7. Opening and contact pressure springs
8. Magnetic actuator (complete module)
9. Armature
10. Synchronizing shaft
11. Actuator coil
12. Interlocking pins

6
7

14

13

12

11

10

13. Auxiliary contacts


14. Frame
15. Support insulator

Figure 3
View into the VCB

12

Closing
Closing operation is possible only if manual trip hook is in upper position. In the open position the contacts
are kept open by the force of the opening springs. To close the contacts the coils of the magnetic actuators
are excited by a current impulse of the close capacitors of the CM. As a result the contacts close. At the
same time the opening springs are compressed. In the close position the contacts are kept closed by means
of the magnetic force only. The VCB maintains the closed position without mechanical latching also in case
of a failure of the auxiliary power supply (Figure 4).

Opening

To open the contacts a current impulse in the reverse polarity derived from the opening capacitors of the

CM is injected in the coils of the magnetic actuators releasing the magnetic holding force. The compressed

opening springs and contact pressure springs open the contacts (Figure 4).

Position main
contacts

Open position kept by


opening springs

SM main contacts open

Trip impuls to SM-coils

Trip command CM
(dry contact)

Start anchor movement

Switch off actuator


current for close operation

Manual Trip
When the manual trip hook is pulled down the synchronizing shaft is rotated. A force exceeding the
magnetic attraction forces of the ring magnet is applied to the armature, which subsequently starts to move.
As the air gap increases, the opening springs and the contact pressure springs overcome the magnetic
holding force, and the vacuum interrupter opens.

SM main contacts closed


Stop anchor movement

Close impuls to SM-coils

Manual Closing
The VCB can only be closed electrically via the CM. In the case of a failure of auxiliary power supply the
contacts can be closed using an alternative auxiliary power supply such as a battery. Mechanical closing
is not possible and leads to the destruction of the VCB.

Close command CM (dry contact)




Warning

Open
Closed

Actuator coil
current

0
Closed

Anchor travel

Open 0

Anchor velocity

20

40

60

80

100

120

140

160
Time (ms)

Figure 4
Typical oscillogram of VCB operation

13

Protective Tank
The OSM are constructed from an aluminium tank incorporating the vacuum circuit breaker with single coil magnetic
actuators. The protective tank consists of two main parts: The housing and the bottom protective cover riveted to the
housing. The OSM housing and the cover are made of a corrosion resistant aluminium alloy. Water-tight aluminium
rivets are used to secure the cover. The tank is powder coated in light grey (RAL 7038). The tank including the
control cable cover provides IP65 degree of protection.
Four threaded holes (M12x30) on each side of the tank allow mounting equipment for pole or substation
installation to be fitted. Two of these threaded holes are used to install the set of lifting lugs on the tank.
The earthing provision (M12x30 threaded hole) is labelled for easy identification.

Provisions for Lifting lugs

Mounting Provisions

Figure 5
Earthing Provision

The tank supports provide a firm, stable support. The


supports are protection against chipping of the powder
coating during transportation. These supports shall be
removed after installation on the pole.
The protective tank is equipped with a ceramic breather
on the bottom.
The breather ensures that no dust or pollution ingress
occurs.
Figure 6

Drainage filter
Tank supports

Each OSM has the following rating plates:


Serial number plate
Rating plate

Figure 7

Rating plate

Serial number plate

14

Main Circuit Bushings


The main circuit bushings are manufactured from UV stable
polymer. They are covered by light grey silicon rubber bushing
boots which provide a creepage distance of 500mm for the
15.5 kV version and 860 mm for the 27 kV version.
The bushings are indelibly marked by stickers with the
terminal designation X1, X2, X3 for the normal incoming
side and X4, X5 and X6 for the normal outgoing side.

Allowable wire pull at the connection point is 300 N.

Figure 8
Phase Marking

Bushing extensions
Bushing extensions of the OSM end with cylindrical rods with a milled surface profile for connection of cables. This
surface is necessary for placing of cable conductors. All parts are tin plated, which allows the connection of both
aluminum and copper conductors. A special clamp is used for connection of the cables.
NOTE: Bushing extensions shown for illustrative purposes only. Bushings on the OSM are not removable.
Bushing extension of 15.5 kV OSMs

Bushing extension of 27 kV OSMs

Figure 10

Figure 9

Each type of bushing extension has special inserts in the bull-end.


Inserts are initially fitted with plastic plugs that must be removed before connection of lugs.

Plastic plugs
Insert
Figure 11

Figure 12

15

Cable Clamps
The clamps allow reliable connection of cable
conductors from 35 to 240 mm2.

Clamp

Cleat
Nut

Plain washer
Spring lock washer
Figure 13

One clamp is enough for connection of cables


up to 90 mm2. Two clamps shall be used for
connection of cables 120 mm2 and more.

Figure 14

Nuts should be torqued to 201 Nm.

Figure 15

Figure 16
For protection of connections against
environmental conditions protective covers are
used.
If the diameter of connected cable is more than
10 mm the end of covers shall be cut off by a
corresponding length to provide tight stretching
of cover to cable.

Figure 17

Figure 18

16

In case of connection of cables with lugs the lugs shall


have 10.5 mm holes.
The range of connected cables with lugs is from 16 to
240 mm2. Bolts M1025 at torque 302 Nm are used. In
this case protective covers are not placed.

Figure 19

NEMA two-hole and four-hole pads are available for


installation onto the OSM.
For both variants, align the pads with the bolt
connections as shown in Figure 20. Tighten the bolts to
252Nm.

Figure 20
NEMA pads installed

Current Transformers
The OSM15/25_Al_2 are equipped with protection
transformers in the bushings X1, X2, X3. The parameters
of the current transformers are specified in the Chapter
Technical Data on page 42.

Figure 21
Current Transformer

17

Mechanical Trip
The mechanical trip hook is made of zinc anodised
steel and coated with powder polymer paint RAL1023
(Figure 22). When pulled down, the OSM is mechanically
locked in the OPEN position and electrically interlocked
against closing.
Until the hook stick lever is pushed back in the closed
position, the OSM remains locked and cannot be
electrically operated.

Figure 22
Manual Trip Hook

Mechanical Position Indicator


The position indicator is located under a protective
cover underneath the tank and is clearly visible from
the ground. The indicator colour is red when the
OSM is closed and green when it is opened.
Figure 23
Open / Close Marking

Protective lid
The OSM are delivered with a Protective lid. It provides protection for the wiring terminals.
The lid provides IP 65 degree of protection and is mounted on the tank by
using eight captive screws (M5x20). The cover has provisions to fix
additional equipment:
4 studs M3x14 (see Figure 24)
2 standoffs with threaded M3 holes (see Figure 24)
Figure 24
Protective Lid

18

Installation:
Primary Part

19

General, Preparation
All local and national electrical codes, standards and practices must be adhered to during installation and
comissioning of this device. Only licensed and qualified personnel shall perform installation, commissioning and
operation.

Bracket Mounting
There are different mounting bracket sets available on request. They can be complimented with surge arrestor
brackets and PT brackets. After mounting of OSM its support rails should be removed. Please contact your nearest
Tavrida Electric partner for further information:
Application sample for round wooden pole
(Hardware type with two 1kVA transformers for loop schemes shown).

Figure 25
Mounting kit TNA1001140

20

Application sample for trapezoidal concrete pole

Figure 26
Mounting kit 2TES.029.002-01

Main Terminal Connection


Tools and lubricant required:
A torque wrench
Inhex socket head 8mm
CG60 contact lubricant (Electrolube, http://www.electrolube.co.uk).
Procedure:
If an existing cable shall be reconnected the old lubricant shall be removed from the contact surfaces.
If an insulated cable is used the insulation of the connecting trip should be stripped to 70 mm (Figure 27).

Figure 27
End of connected tail

Contact surfaces shall be preliminarily smoothed out


with a card file or metallic brush and the abrasive
dust shall be removed with rags. Then a thin layer of
the lubricant, with a thickness not more than 1 mm,
shall be applied onto the connection tip.
Connect tail to the OSM terminal according to Figures
14 and 15.
Fix the tail tighten the nuts hard to 20 1 Nm or bolt
- to 30 2 Nm.
For protection of connections against environments use
protective covers according to Figures 16, 17 and 18.

21

Installation:
Secondary Part

22

Secondary Connections of the OSM


The secondary connection of the OSM is realized with help of Harting terminal Han-K 8/24 type which is placed on
the protective lid. Protective lid is installed on the bottom of OSM protective tank.

Figure 28
Protective lid is intended for water and dust protection in place of auxiliary circuit connection. It is made from
aluminum and has a finish similar to the protective tank. They are supplied with a rectangular rubber seal to provide
IP65 degree of protection of the module.

Auxiliary Circuit Terminations


Pin arrangement of Harting terminal Han-K 8/24 is as follows:

Figure 29

23

Termination of Harting terminals for:


OSM15_Al_2(xxx_150)
OSM25_Al_2(xxx_150)

24

Terminal No.

Designation

Note

Connected internal
WAGO terminals of OSM2

SC.1

Actuator coil (1)

XT3.1 - SC.1

Gnd

Ground

XT3.11 - Gnd

SC.2

Actuator coil (2)

XT3.2 - SC.2

Gnd

Ground

XT3.11 - Gnd

1NC.1

NC auxiliary switch 1(1)

XT3.3 - 1NC.1

Gnd

Ground

XT3.12 - Gnd

1NC.2

NC auxiliary switch 1(2)

XT3.4 - 1NC.2

Gnd

Ground

XT3.12 - Gnd

2NC.1

NC auxiliary switch 2(1)

XT3.5 - 2NC.1

10

TX1.1

Input of protection CT into X1 bushing

XT5.1 - TX1.1

11

TX2.1

Input of protection CT into X2 bushing

XT5.2 - TX2.1

12

TX3.1

Input of protection CT into X3 bushing

XT5.3 - TX3.1

13

2NC.2

NC auxiliary switch 2(2)

XT3.6 - 2NC.2

14

TC

Common point of coil ends of protection CTs

15

16

17

3NC.1

NC auxiliary switch 3(1)

XT3.7 - 3NC.1

18

CX1

Outlet of high arm capacitor into X1 bushing

XT5.5 - CX1

19

CX2

Outlet of high arm capacitor into X2 bushing

XT5.6 - CX2

20

CX3

Outlet of high arm capacitor into X3 bushing

XT5.7 - CX3

21

3NC.2

NC auxiliary switch 3(2)

XT3.8 - 3NC.2

22

Gnd

Ground

XT5.11 - Gnd

23

Gnd

Ground

XT5.11 - Gnd

24

Gnd

Ground

XT5.11 - Gnd

25

1NO.1

NO auxiliary switch 1(1)

XT3.9 - 1NO.1

26

CX4

Outlet of high arm capacitor into X4 bushing

XT5.8 - CX4

27

CX5

Outlet of high arm capacitor into X5 bushing

XT5.9 - CX5

28

CX6

Outlet of high arm capacitor into X6 bushing

XT5.10 - CX6

29

1NO.2

NO auxiliary switch 1(2)

30

Gnd

Ground

XT5.12 - Gnd

31

Gnd

Ground

XT5.12 - Gnd

32

Gnd

Ground

XT5.12 - Gnd

Internal WAGO terminals are placed under the Protective lid.

XT5.4 - TC

XT3.10 - 1NO.2

Protective Earthing
For personnel protection the metal housing of the OSM must
be connected according to the applicable regulations, such as
DIN VDE 0141, via the marked earth screw of the OSM to the
earth arrangement of the pole earth bus or substation. The earth
connections can be carried out with cables or flat bar (zinccoated
steel or copper). The cross section must be dimensioned such
that a worst-case fault current (short circuit) does not cause a
weakening of the earth connection (Figure 31).
Tighten the earthing bolt to 30 2 Nm torque.
Reference values for cross sections of earth connection (copper):
Duration of fault
current (1 s)

Max. temperature of
earth connection

Cross section
earth connection

<10 kA/10 kA

300 C

35-70 mm (1...3/0 AWG)

16 kA

300 C

70-95 mm (3/0...4/0 AWG)

The area around the earth screws shall be cleaned before


providing the earth connections. After the occurrence of a short
circuit, the proper condition of the protective earthing must be
checked.

OSM

Voltage
transformer

Power supply cable


OSM earthing

Umbilical
cable

4
Earth bus

SEL-651R

Control cubicle earthing

Figure 31

Installation of the Manual Trip Hook


Installation procedure:
Install the hook after final OSM-installation
The M8 nut should be screwed on the threaded end of the hook
The hook with the nut to be drawn up at the mounting seat checking comfortable orientation of the hook
Holding the hook in this position tighten the M8 nut with 10 Nm as shown in Figure 30.

Figure 30
Installation of the manual trip hook

25

Commissioning,
Maintenance

26

General
Commissioning, operation and maintenance is only permitted for qualified and trained personnel.

Insofar as installation, commissioning or retrofit is carried out on energized equipment, the relevant safety
regulations, including all national and local standards must be adhered to.

Danger

The OSM must always be tested and operated together with the appropriate recloser control. Individual
testing is not possible and may lead to the destruction of the OSM.
Caution

Commissioning Primary Part


Tests at the end of the installation shall include at least:
Operating conditions of OSM comply with requirements of the rating plate.
Check for damage, remove dirt.
Check bolted connections for fixing points and main terminals (also torques) according to page 16.
Protective earthing according to page 25.
Check the manual trip mechanism as follows:
Pull down the manual trip hook when the module is in the closed position. Manual trip hook shall remain in the lowered
position and the module shall open. Initiate Close instruction. It shall be ignored, as in this position of the manual
trip hook the actuator coils are isolated. Push the hook upward. It shall remain in the upper position. Initiate Close
instruction again. This time it shall be executed.

Commissioning Secondary Part


Please consult the SEL-651R manual for commissioning procedures with the control.

Maintenance
Under normal operating conditions (see chapter Ambient conditions, page 43) the OSM is maintenance free for a
period of at least 30 years or until it has reached the permissible number of operating cycles.

Non-conformity
If during installation, commissioning, operation or maintenance any non-conformity occurs, action shall be taken
in accordance with the non-conformity report on pages 47, 48.

27

28

Receiving and
Inspection

29

Packing
The OSM/TEL is delivered in a corrugated box with dimensions 810 (L) x 810 (b) x 890 (h) and a weight of not more
than 76 kg*. The following information are provided on the OSM packing cartons (Figure 34):
Handling symbols for transport and storage of the delivery unit (Figure 32)
Label 1 for manufacturers product information (Figure 33)
Label 2 for logistics data (Figure 35)

6
1

1. This side up
2. Fragile
3. Protect from rain

100

4. Max. weight on
the delivery unit

OSM15_Al_2(630_150)

5. Serial number
5

Figure 32

Figure 33

Handling symbols

Label 1 for manufacturers


and product information

Mark:

TEG-C-000111
Place of delivery:

Consignee:
Consignee:

Address
Address
Address
Address
Address
Phone:
Contact person

P/O Number:

Customer reference

Article:

Article description

Serial Number:

150218

TAVRIDA ELECTRIC AG, Wetterkreuz 3, 91058 Erlangen, Germany, Phone: 0049-9131-972079-0

Figure 35

Figure 34

Label 2 Logistics data

Packing carton

* In some cases the OSM will be delivered in a wooden crate, or packaged as a single lift device with mounting
hardware, OSM and accessories pre-assembled. In these cases please check with the Tavrida shipping department
for weights and dimensions of the packaging.

30

Transport
The OSM shall be transported in the original packing only. The packed goods shall be handled in accordance with the
handling symbols. Loading procedures for OSM packing units shall be carried out only with fork lifts or cranes.
Lifting gear must not be attached to the bushings, use only lifting lugs attached to the side mounts with suitable
clearance of straps or chains. During transportation the OSM must not be exposed to impacts or dropped.

Unpacking, GoodsReceived Control


Before unpacking, please check the carton for damage and dampness. Removal of the products from the original
packing must be carried out with due care. Every OSM and shall be subject to a completeness control.
Unpacking procedure:
Remove corrugated box
Install lifting lugs
Fit lifting slings (polyester) to the lifting lugs and lift the OSM
Do not attach the lifting slings to the HV-bushings

Scope of delivery for the OSM:

d
Dd

K^D

sZs

^E

/

W

K

t

D

s^

Ds

^^D>z,<^

Z^h>d
W^^



W^^

K

W^^
d^d

W^^Z/dZ/

Z^h>d













K

K

K

Z

K

Z

K

Z

K

d^d
WtK

d^ds>h
s

Z^h>d
W^^

Wt

s

W^^

t

s

W^^

W

s

Dd

D

W^^

DKd

W^^

Life cycle of OSM


Number of closing-opening cycles

7KLVSURGXFWLVFHUWLHGWRKDYHSDVVHGDOOUHOHYDQWIDFWRU\DFFHSWDQFH URXWLQH WHVWV


UHTXLUHGXQGHU$16,&

:LWKGHUDWLQJSHU$16,VWDQGDUGDERYHPHWHUV

OSM/TEL

Screwdriver

Operating manual

The following parts are included into corresponding installation kit:


Hook
1
Bolt DIN933 M12x25
8
Nut DIN934 M8
1
Washer DIN 125A 13
8
Washer DIN 7980 12
8
Protective cover AXCA.754529.001 6

Routine test certificate

Protective cover

31

Rating Plate, Seal


3

Figure 37
Seal of the OSM

OSM
1. Rating plate
2. Serial number
3. Seal

Figure 36
Labelling of the OSM

2
DdK^D
E^//

KKKK

Z

s

Z

,

Z


K

Z




Z




Z




Z


s

dyyy

z

K^D
dEDZ

Please check that the rating plates of the delivered devices correspond to the data of the order and technical data
given on page 40.
Tavrida Electric accepts no warranty for a device if the seal is broken or has been removed.

Storage
Should immediate installation not be possible, the OSM shall be stored in the original packing under the following
conditions:
The OSM is switched off.
Dessicants must be placed in the packing.
Storage must be closed dry, well ventilated and the room temperature should be between - 40C and + 40C
(IEC62271-1/ DIN VDE 0670 Part 1000).
If several OSM are stacked a maximum of two layers is permitted.

32

Product Line

33

Outdoor Switching Module(OSM)


Model Types - 15 kV
OSM15_Al_2(630_150)

Model Types - 27 kV
OSM25_Al_2(630_150)

Accessories
Item number

Description

Quantity

TNA1001140

ANSI Mounting Kit, single lift


type, for wooden pole

For installation of OSM on a wooden


pole, with option for surge arrestors and
transformer(s)

2TES.029.002

IEC Mounting Kit for wooden pole

For installation of OSM on a wooden pole,


with option for surge arrestors

2TES.029.002-01

IEC Mounting Kit for concrete pole

For installation of OSM on a concrete pole,


with option for surge arrestors

TNA1000709

ANSI Mounting Kit for wooden pole

For installation of OSM on a wooden pole,


with option for surge arrestors

TENA.685624.009

Umbilical Cable, 8 meter length

For connection of OSM to SEL-651R

TENA.685624.009-02

Umbilical Cable, 11 meter length

For connection of OSM to SEL-651R

TENA.685624.009-01

Umbilical Cable, 14 meter length

For connection of OSM to SEL-651R

TENA.685624.009-03

Umbilical Cable, 4 meter length

For connection of OSM to SEL-651R

Rubber cover for protection of connection


places from environmental effects.
A set of these covers (6 pcs) is included in
the OSM package, however can be ordered
separately if required.

AXCA754529.001

34

Protective Cover

Note

Dimensions and Weights

35

Dimensions and Weights of the OSM

Dimensions, mm
Rated voltage, kV
B

Creepage
distance

Minimum taut
string distance

15.5

216

260

652

637

500

203

65

27

296

294

731

703

860

203

72

Dimensionsof the OSM Earthing Provisions

Dimensions of the Mounting Provisions

36

Weights, kg

Standard Mounting Hardware

Figure 38
Pole mounting hardware with provision for up to x6
surge arrestors and x2 1kVA transformers for loop
scheme control power

Figure 39
Substation frame mounting hardware with provision
for up to x3 external CTs

37

Circuit Diagrams

38

39

10

Technical Data

40

Outdoor Switching Module (OSM)


Basic Operating Parameters

OSM15_Al_2
(630_150)

OSM25_Al_2
(630_150)

15.5 kV

27 kV

Rated data
Rated voltage (Ur)

10

up to 630 A (800 A) 1) depending on CT rated


primary current

Rated current (Ir)


Rated power frequency withstand voltage (Ud), 1 min dry

50 kV

60 kV (70 kV) 1)

Rated power frequency withstand voltage (Ud), 10s wet

45 kV

50 (60 kV) 1)

Rated lightning impulse withstand voltage (peak) (Up)

110 kV

150 kV

10 pC @ 13.2 kV

10 pC @ 16.4 kV

Rated short-circuit breaking current (Isc)

16 kA

12.5 kA

Rated short-circuit making current, peak

41.6 kA

32.5 kA

16 kA

12.5 kA

Partial discharge decay level, not less than

Rated short-time withstand current, 4s (Ik)


Rated frequency (fr)

50/60Hz

Cable charging current

25 A

31.5 A

Line charging current

3.33 A

5A

Switching performance
Mechanical life (CO-cycles)

30 000

Operating cycles, rated current (CO-cycles)

30 000

Maximum number of CO-cycles per hour

Refer to SEL-651R manual

Operating cycles, ratedshort circuit breaking current

200

2)

Closing time, not more than

Opening time, not more than

35 ms

2)

15 ms

2)

Break time, not more than

23 ms

Rated operating sequence

Refer to SEL-651R manual

Standards
International Standard
American Standard
Russian Standard
Chinese Standard

IEC 62271-100, IEC 62271-111


IEEE C37.60
GOST R 52565-2006
GB 1984-2003

Other data
Current sensing

3 current transformers

Voltage sensing

6 voltage sensors

Main contact resistance, not more than

85 Ohm

Solar radiation

Degree of protection
Weight

95 Ohm
1.1 kW/m
IP65

65 kg

72 kg

1)

800 A continuous current and 70 kV dielectric products available by special order. Please contact Tavrida Electric
North America for further information.
2)
OSM closing, opening and break times based on Tavrida CM_15 series controls without processing acceptance time.
Please see SEL-651R manual for more information on additional time to calculate a complete fault interruption cycle.
41

Basic Operating Parameters

OSM15_Al_2
(630_150)

OSM25_Al_2
(630_150)

Design, switching capacity of auxiliary contacts OSM


3 NC + 1 NO

Number of available auxiliary contacts for OSM

10

Minimum current for (12-30) V AC / DC, ohmic load

100 mA

Minimum current for 12 V AC / DC, inductive load (t=20 ms, cosj =0.3)

100 mA

Maximum current for 30 V DC, ohmic load

5A

Maximum current for 30 V DC, inductive load (t=20 ms)

3A

Maximum current for 50 V DC, ohmic load

1A

Maximum current for 50 V DC, inductive load (t=20 ms)

1A

Maximum current for 75 V DC, ohmic load

0.75 A

Maximum current for 75 V DC, inductive load (t=20 ms)

0.75 A

Maximum current for 125 V DC, ohmic load

0.5 A

Maximum current for 125 V DC, inductive load (t=20 ms)

0.03 A

Maximum current for 250 V DC, ohmic load

0.25 A

Maximum current for 250 V DC, inductive load (t=20 ms)

0.03 A

Maximum current for 125 V AC, ohmic load

5A

Maximum current for 125 V AC, inductive load (cosj =0.3)

5A

Maximum current for 250 V AC, ohmic load

5A

Maximum current for 250 V AC, inductive load (cosj =0.3)

5A

Parameter of Current Transformers


and Voltage Sensors

OSM15/OSM25_Al_2(630_150)

Current transformers
Rated primary current A

600

Rated secondary current A

600
1

Rated output, VA at PF=0.8...1

2.5

2.5

Accuracy limit factor for protective current transformers

25

25

Accuracy class of protective transformers acc. to IEC


60044 at the rated output, PF=0.8...1

C25

C25

Rated continuous thermal current, A

630

630

Voltage Sensors
Capacitance of high arm

42

20...25pF

Temperature coefficient of capacitance

-770 ppm/oC

Continuous reverse voltage of shunted


varistor of low arm

22 - 40V real dispersion

Ambient Conditions
The OSM and CM were designed for the following ambient and operating conditions for outdoor installations (OSM) and
indoor installations (CM).
Maximum ambient temperature

+ 55 C

Minimum ambient temperature

- 50 C

Humidity

100% condensing

Altidude

to 3000 m

10

Above 1000 m derating according to ANSI C37.60

Number of closing-opening cycles

Life cycle of OSM

Figure 40

43

11

Legal Information

44

Warranty
Unless otherwise stated in the contract, the warranty period is 3 years from date of invoice. If agreed to otherwise,
the contract conditions apply. No warranty is given in the case of
a) the warranty period having run out during the period of storage with the customer.
b) the operating conditions, ambient conditions, transport and storage conditions have not been adhered to

according to the application description or the application guide.
c) an unauthorized manipulation of the device has been carried out, such as opening the housing or damaging the seal.
d) the device has not been properly installed, such as incorrect connection voltages.

11

Quality Regulations
All manufacturing facilities of the company have been
certified by KEMA in the Netherlands and comply with (DIN
EN) ISO 9001:2000.
All technical data of the vacuum circuit breaker are stored
in an electronic database for each step of the manufacturing
process. Testing of the circuit breakers is carried out in
accordance with the relevant standards and beyond that
the following test are carried out:
1000 C-O cycles
Insulation strength of the primary and auxiliary circuits
at operating frequency
Measurement of the resistance of the main circuit
All test results are automatically stored

Complaints and
Transport Damage
All products are shipped exclusively with original packing
to ensure safe transport and avoid transport damage (see
Packing, Goods Received).
Tavrida Electric will not accept any claims for damages
caused by improper transport, storage as well as
unpacking. Transport damage must be reported in writing
to the supplier as soon as it is discovered. A period
of maximum 3 weeks after receipt is allowed for this.
For legitimate claims Tavrida Electric will supply replacement
equipment free of charge according to our warranty
regulations. Tavrida Electric reserves the right to verify
any claim.

45

Environmental Friendliness
The modules are manufactured from environmentally
friendly material. Therefore, special disposal is not
required.

TAVRIDA ELECTRIC NA

Non-conformity Report

11

In order to be able to exchange or repair the device, we


kindly ask you to fill the accompanied Non-conformity
report and send it to our regional representative or
directly to us.
Please note:
Your request can only be handled if the accompanying
report is properly filled including the name and address
as well as a copy of the invoice.
For queries please contact your Tavrida Electric partner.

Service Department
1105 Cliveden Avenue
Delta, BC, Canada
V3M 6G9
Phone: 604-540-6600
Fax: 604-540-6604
E-Mail: info@tavrida-na.com
Web: www.tavrida-na.com

Liability
Damages and demands for reimbursement of expenses incurred by the customer (in the following: compensation)
for what-ever legal reasons, especially due to non-compliance of obligations of the contractual obligations and for
unauthorized actions, are excluded. This does not apply, insofar as there is a compulsory liability such as according
to the product liability law in cases of malice, gross negligence, because of damage to life, the body or health,
because of damage to important contractual obligations.
Compensation for damage to important contractual obligations, however, is limited to the damage which can be
predicted as typical of the contract insofar as there is no malice or gross negligence, because of damage to life, the
body or health. A change of the obligation to provide proof to the disadvantage of the customer is not connected
with these regulations.

Copyright
Without our written permission, this documentation may not be used, also not in extract form, for own general
publications, printouts, handbooks, training, lectures, etc. nor copied and further processed. This includes also
the duplicating or re-copying in any form of data carriers and microfilms. A one-time written permission is not
automatically to be taken as a part or complete surrender of the copyright provisions. We reserve the right to
changes. The issue of a new version of these operating instructions renders all other older versions obsolete.
Tavrida Electric and its associated companies make every effort to adapt the contents of their documentation to
the latest and most current state of development of the products.
The present documentation was produced with the greatest care. However, we are not liable for possible errors in
this information text, user-side incorrect interpretation and/or for consequences arising therefrom.

Copyright 2011; Tavrida Electric reserves the right to make changes to the design and data of their products. Tavrida Electric accepts no

responsibility or liability for losses or damage caused by improper actions based on this publication. Schweitzer Engineering, SEL-651R are
registered trademarks of Schweitzer Engineering Inc.

46

NON-CONFORMITY REPORT
From:

To:

TAVRIDA ELECTRIC NA
Service Department

Address:

Address:

1105 Cliveden Avenue

11

Delta, BC, Canada


Name:
Phone:

Phone:

604-540-6600

Fax:

Fax:

604-540-6604

E-Mail:

E-Mail:

info@tavrida-na.com

Type designation OSM

Serial No.:

Type designation CM

Serial No.:

Date when non-conformity was noticed:

Date of commissioning:

When did the non-conformity occur:


Incoming inspection
Installation/Commissioning
Service

Place of installation of SEL-651R:


Pole / substation frame mounted
Mounted in control room

Does your installation comply with the requirements of the application guide, OSM?
Primary Part (OSM):
Operating conditions of OSM comply with technical data
specified in application guide (pages 41-43)
Fixing points (page 14)
Protective earthing (page 25)
Description of non-conformity:

Non-conformity report issued by:


Date:

Name:

Signature:

Your warranty claim can only be handled if this non-conformity report is filled in completely including your name and address.
47

NON-CONFORMITY REPORT

11

From:

To:

TAVRIDA ELECTRIC NA
Service Department

Address:

Address:

1105 Cliveden Ave


Delta, BC, Canada

Name:
Phone:

Phone:

604-540-6600

Fax:

Fax:

604-540-6604

E-Mail:

E-Mail:

info@tavrida-na.com

Type designation OSM

Serial No.:

Type designation CM

Serial No.:

Date when non-conformity was noticed:

Date of commissioning:

When did the non-conformity occur:


Incoming inspection
Installation/Commissioning
Service

Place of installation of SEL-651R:


Pole / substation frame mounted
Mounted in control room

Does your installation comply with the requirements of the application guide, OSM?
Primary Part (OSM):
Operating conditions of OSM comply with technical data
specified in application guide (pages 41-43)
Fixing points (page 14)
Protective earthing (page 25)
Description of non-conformity:

Non-conformity report issued by:


Date:

Name:

Signature:

Your warranty claim can only be handled if this non-conformity report is filled in completely including your name and address.
48

Date:

11

49

Tavrida Electric North America


Tavrida Electric North America Ltd.
1105 Cliveden Avenue,
Delta, BC, Canada
V3M6G9
Phone: (604)-540-6600
Fax: (604)-540-6604
E-Mail: info@tavrida-na.com
Web: www.tavrida-na.com

This document is copyright and is intended for users and distributors of Tavrida Electric product. It contains information that is
the intellectual property of Tavrida Electric and the document, or any part thereof, should not be copied or reproduced in any form
without written permission from Tavrida Electric.
Tavrida Electric applies a policy of ongoing development and reserves the right to change product without notice.
Tavrida Electric does not accept any responsibility for loss or damage incurred as a result of acting or refraining from action based on
information in this application guide.