Professional Documents
Culture Documents
Safety First
Installation, operation and maintenance shall only be carried out by trained and
experienced personnel who are familiar with the equipment and the electrical
safety requirements.
During installation, commissioning, operation and maintenance of the equipment
the relevant legal regulations (such as NFP70E, CEC, ANSI), accident prevention
regulations and the connecting conditions of the electric utilities shall be followed.
Take note that during operation of the OSM certain parts are subject to
dangerous voltage. Mechanical parts, also remote-controlled, can move quickly.
Failure to comply may result in death, severe personal injury or damage to
equipment.
Pay attention to the hazard statements located throughout this manual.
The operating conditions of the OSM shall comply with the technical data specified
in this manual.
Personnel installing, operating and maintaining the equipment shall be familiar
with this manual and its contents.
For special configurations please contact Tavrida Electric North America.
Table of Contents
1. Introduction
Applicability ..........................................................................................................................................7
Hazard Statements..................................................................................................................................8
Safety Instructions..................................................................................................................................8
Definitions..............................................................................................................................................9
General .................................................................................................................................................9
2. OSM Recloser
2
3
4
5
Overview .............................................................................................................................................. 11
Vacuum Circuit Breaker - VCB................................................................................................................ 12
Protective Tank..................................................................................................................................... 14
Main Circuit Bushings........................................................................................................................... 15
Bushing extensions............................................................................................................................... 15
Cable Clamps......................................................................................................................................... 16
Current Transformers............................................................................................................................. 17
Mechanical Trip..................................................................................................................................... 18
Mechanical Position Indicator............................................................................................................... 18
Protective lid........................................................................................................................................ 18
General, Preparation............................................................................................................................. 20
Bracket Mounting.................................................................................................................................. 20
Main Terminal Connection..................................................................................................................... 21
5. Commissioning, Maintenance
General................................................................................................................................................. 27
Commissioning Primary Part.................................................................................................................. 27
Commissioning Secondary Part.............................................................................................................. 27
Maintenance......................................................................................................................................... 27
Non-conformity..................................................................................................................................... 27
Transport ............................................................................................................................................. 31
Unpacking, GoodsReceived Control....................................................................................................... 31
Rating Plate, Seal................................................................................................................................. 32
Storage................................................................................................................................................. 32
7. Product Line
Outdoor Switching Module(OSM).......................................................................................................... 34
Accessories........................................................................................................................................... 34
9. Circuit Diagrams
10. Technical Data
Outdoor Switching Module (OSM).......................................................................................................... 41
Ambient Conditions............................................................................................................................... 43
Warranty............................................................................................................................................... 45
Quality Regulations............................................................................................................................... 45
Complaints and .................................................................................................................................... 45
Transport Damage................................................................................................................................. 45
Environmental Friendliness.................................................................................................................... 46
Non-conformity Report.......................................................................................................................... 46
Liability................................................................................................................................................ 46
Copyright.............................................................................................................................................. 46
7
8
9
10
11
12
13
14
Introduction
Applicability
This application guide applies to a range of Outdoor Switching Modules (OSM) manufactured by Tavrida Electric that
work specifically with the Schweitzer Engineering SEL-651R Recloser Control:
Model Types - 15 kV
OSM15_Al_2(630_150)
Model Types - 27 kV
OSM25_Al_2(630_150)
The OSM_Al_2(xxx_150) series are compatible only with the Schweitzer Engineering SEL-651R. Chapters in this manual
refering to mounting, primary connection and operation of the OSM; for all information relating to the operation, mounting
and functionality of the SEL-651R control please consult the applicable manual provided by Schweitzer Engineering.
The model number is shown on the equipment rating plates. If your equipment does not correspond to the numbers in the
table above then this manual is not applicable. Please contact your nearest Tavrida Electric office or Distributor for the
correct documents.
Every care has been taken in preparation of this manual. However, please note that not all the details or variations
in the equipment or process being described can be covered. Neither is it expected to address all contingencies
associated with the installation and operation of this equipment. For any further information please contact your nearest
Tavrida Electric office or Distributor.
Hazard Statements
This manual contains three types of hazard statements, as follows:
DANGER:
Indicates an imminently hazardous situation that, if not avoided, will result in death or
serious injury.
WARNING:
Indicates a potentially hazardous situation that, if not avoided, could result in death
or serious injury.
CAUTION:
Indicates a potentially hazardous situation that, if not avoided, could result in personal
injury or equipment damage.
Safety Instructions
General hazard statements applying to this equipment are described in this section. Statements relating to specific
tasks or procedures are located throughout this manual.
DANGER:
Contact with hazardous voltage will cause death or severe personal injury. Contact with
Recloser or Control Cubicle terminals should only be undertaken when equipment is
isolated from applicable sources of voltage.
WARNING:
This equipment is not intended to protect human life. Follow all locally approved safety
procedures when installing or operating this equipment. Failure to comply may result in
death or severe personal injury.
WARNING:
Before working with equipment described in this manual carefully read and understand the
contents of this manual. Improper handling, installation, operation or maintenance can
result in death, severe personal injury or damage to equipment.
WARNING:
Power distribution equipment must be properly selected for the intended operation. It
must be installed, used and understand all relevant safety procedures. Failure to comply
can result in death, personal injury or equipment damage.
Definitions
The following abbreviations are used in this operating manual:
AR
CM
CO
SM
LED
MCB
Automatic reclosing
Control module
Close open cycle
Switching module
Light emitting diode
Miniature circuit breaker
NC
Normally closed contact
NO
Normally open contact
OSM Outdoor switching module
PCD Pole center distance
SCADA Supervisory control and data aquisition
VCB Vacuum circuit breaker
VI
Vacuum interrupter
Make time
The make time is the time period from the energising of the closing circuit to the time when the current begins to
flow in the first pole.
Closing time
The closing time is the time period from the energising of the closing circuit to the time when all three poles have
contact.
Pre-arcing time
Interval of time between the initiation of current flow in the first pole during a closing operation and the instant
when the contacts touch in all poles for three-phase conditions and the instant when the contacts touch in the
arcing pole for single-phase conditions.
Opening time
The opening time is the time period from energising of the closing circuit up to the time when all the switching
poles are separated.
Break time
The break time is the time period from the energising of the closing circuit up to the time when the arcs of all the
poles are extinguished.
Open-close time (during AR)
Interval of time between the instant when the arcing contacts have separated in all poles and the instant when the
contacts touch in the first pole during a reclosing cycle.
Dead time (during AR)
Interval of time between final arc extinction in all poles in the opening operation and the first reestablishment of
current in any pole in the subsequent closing operation.
General
The outdoor switching module (OSM) is designed for use as an automatic
circuit recloser or a sectionalizer on overhead distribution lines and as
an outdoor switching module in distribution substation applications for
voltages up to 27 kV.
Figure 1
OSM Recloser
10
Overview
Tavrida Electrics outdoor switching module provides the following advantages:
Environmentally friendly
The OSM is an air insulated outdoor switching module.
The patented combined insulation makes it the environmentally friendly option.
The reliability of the design is proven by the worlds most severe climate and pollution conditions test at the Koeberg
Insulator Pollution Test Station (KIPTS) in South Africa.
1. Terminal
2. Six HV bushings
3
4
5
6
9. Support rail
8
9
Figure 2
General arrangement of the OSM
11
Maximizing the benefits of the drive mechanism requires vacuum interrupters that combine small dimensions with an
extraordinarily long mechanical and electrical lifespan. The use of a predefined axial magnetic field shape provides
even distribution of current density and consequently substantial improvement of vacuum interrupting performance.
Carefully selected contact material and expert contact design as well as optimized movement and switching speed
result in bounce-free closing.
Substantial increase in mechanical lifespan as well as size reduction of Tavrida Electric vacuum interrupters was achieved
by utilizing metal bellows consisting of welded single discs as opposed to the conventional use of folded steel.
The result is 30,000 C-O cycles at rated current or up to 200 operations at full short-circuit breaking current without
the need to replace or adjust any parts of the vacuum circuit breaker.
Tavrida Electrics vacuum circuit breaker are entirely maintenance free over a total life expectancy of at least 30 years.
1. Upper terminal
2. VI
1
3. Lower terminal
4. Movable contact with bellows
5. Flexible junction shunt
2
3
4
15
6. Drive insulator
7. Opening and contact pressure springs
8. Magnetic actuator (complete module)
9. Armature
10. Synchronizing shaft
11. Actuator coil
12. Interlocking pins
6
7
14
13
12
11
10
Figure 3
View into the VCB
12
Closing
Closing operation is possible only if manual trip hook is in upper position. In the open position the contacts
are kept open by the force of the opening springs. To close the contacts the coils of the magnetic actuators
are excited by a current impulse of the close capacitors of the CM. As a result the contacts close. At the
same time the opening springs are compressed. In the close position the contacts are kept closed by means
of the magnetic force only. The VCB maintains the closed position without mechanical latching also in case
of a failure of the auxiliary power supply (Figure 4).
Opening
To open the contacts a current impulse in the reverse polarity derived from the opening capacitors of the
CM is injected in the coils of the magnetic actuators releasing the magnetic holding force. The compressed
opening springs and contact pressure springs open the contacts (Figure 4).
Position main
contacts
Trip command CM
(dry contact)
Manual Trip
When the manual trip hook is pulled down the synchronizing shaft is rotated. A force exceeding the
magnetic attraction forces of the ring magnet is applied to the armature, which subsequently starts to move.
As the air gap increases, the opening springs and the contact pressure springs overcome the magnetic
holding force, and the vacuum interrupter opens.
Manual Closing
The VCB can only be closed electrically via the CM. In the case of a failure of auxiliary power supply the
contacts can be closed using an alternative auxiliary power supply such as a battery. Mechanical closing
is not possible and leads to the destruction of the VCB.
Warning
Open
Closed
Actuator coil
current
0
Closed
Anchor travel
Open 0
Anchor velocity
20
40
60
80
100
120
140
160
Time (ms)
Figure 4
Typical oscillogram of VCB operation
13
Protective Tank
The OSM are constructed from an aluminium tank incorporating the vacuum circuit breaker with single coil magnetic
actuators. The protective tank consists of two main parts: The housing and the bottom protective cover riveted to the
housing. The OSM housing and the cover are made of a corrosion resistant aluminium alloy. Water-tight aluminium
rivets are used to secure the cover. The tank is powder coated in light grey (RAL 7038). The tank including the
control cable cover provides IP65 degree of protection.
Four threaded holes (M12x30) on each side of the tank allow mounting equipment for pole or substation
installation to be fitted. Two of these threaded holes are used to install the set of lifting lugs on the tank.
The earthing provision (M12x30 threaded hole) is labelled for easy identification.
Mounting Provisions
Figure 5
Earthing Provision
Drainage filter
Tank supports
Figure 7
Rating plate
14
Figure 8
Phase Marking
Bushing extensions
Bushing extensions of the OSM end with cylindrical rods with a milled surface profile for connection of cables. This
surface is necessary for placing of cable conductors. All parts are tin plated, which allows the connection of both
aluminum and copper conductors. A special clamp is used for connection of the cables.
NOTE: Bushing extensions shown for illustrative purposes only. Bushings on the OSM are not removable.
Bushing extension of 15.5 kV OSMs
Figure 10
Figure 9
Plastic plugs
Insert
Figure 11
Figure 12
15
Cable Clamps
The clamps allow reliable connection of cable
conductors from 35 to 240 mm2.
Clamp
Cleat
Nut
Plain washer
Spring lock washer
Figure 13
Figure 14
Figure 15
Figure 16
For protection of connections against
environmental conditions protective covers are
used.
If the diameter of connected cable is more than
10 mm the end of covers shall be cut off by a
corresponding length to provide tight stretching
of cover to cable.
Figure 17
Figure 18
16
Figure 19
Figure 20
NEMA pads installed
Current Transformers
The OSM15/25_Al_2 are equipped with protection
transformers in the bushings X1, X2, X3. The parameters
of the current transformers are specified in the Chapter
Technical Data on page 42.
Figure 21
Current Transformer
17
Mechanical Trip
The mechanical trip hook is made of zinc anodised
steel and coated with powder polymer paint RAL1023
(Figure 22). When pulled down, the OSM is mechanically
locked in the OPEN position and electrically interlocked
against closing.
Until the hook stick lever is pushed back in the closed
position, the OSM remains locked and cannot be
electrically operated.
Figure 22
Manual Trip Hook
Protective lid
The OSM are delivered with a Protective lid. It provides protection for the wiring terminals.
The lid provides IP 65 degree of protection and is mounted on the tank by
using eight captive screws (M5x20). The cover has provisions to fix
additional equipment:
4 studs M3x14 (see Figure 24)
2 standoffs with threaded M3 holes (see Figure 24)
Figure 24
Protective Lid
18
Installation:
Primary Part
19
General, Preparation
All local and national electrical codes, standards and practices must be adhered to during installation and
comissioning of this device. Only licensed and qualified personnel shall perform installation, commissioning and
operation.
Bracket Mounting
There are different mounting bracket sets available on request. They can be complimented with surge arrestor
brackets and PT brackets. After mounting of OSM its support rails should be removed. Please contact your nearest
Tavrida Electric partner for further information:
Application sample for round wooden pole
(Hardware type with two 1kVA transformers for loop schemes shown).
Figure 25
Mounting kit TNA1001140
20
Figure 26
Mounting kit 2TES.029.002-01
Figure 27
End of connected tail
21
Installation:
Secondary Part
22
Figure 28
Protective lid is intended for water and dust protection in place of auxiliary circuit connection. It is made from
aluminum and has a finish similar to the protective tank. They are supplied with a rectangular rubber seal to provide
IP65 degree of protection of the module.
Figure 29
23
24
Terminal No.
Designation
Note
Connected internal
WAGO terminals of OSM2
SC.1
XT3.1 - SC.1
Gnd
Ground
XT3.11 - Gnd
SC.2
XT3.2 - SC.2
Gnd
Ground
XT3.11 - Gnd
1NC.1
XT3.3 - 1NC.1
Gnd
Ground
XT3.12 - Gnd
1NC.2
XT3.4 - 1NC.2
Gnd
Ground
XT3.12 - Gnd
2NC.1
XT3.5 - 2NC.1
10
TX1.1
XT5.1 - TX1.1
11
TX2.1
XT5.2 - TX2.1
12
TX3.1
XT5.3 - TX3.1
13
2NC.2
XT3.6 - 2NC.2
14
TC
15
16
17
3NC.1
XT3.7 - 3NC.1
18
CX1
XT5.5 - CX1
19
CX2
XT5.6 - CX2
20
CX3
XT5.7 - CX3
21
3NC.2
XT3.8 - 3NC.2
22
Gnd
Ground
XT5.11 - Gnd
23
Gnd
Ground
XT5.11 - Gnd
24
Gnd
Ground
XT5.11 - Gnd
25
1NO.1
XT3.9 - 1NO.1
26
CX4
XT5.8 - CX4
27
CX5
XT5.9 - CX5
28
CX6
XT5.10 - CX6
29
1NO.2
30
Gnd
Ground
XT5.12 - Gnd
31
Gnd
Ground
XT5.12 - Gnd
32
Gnd
Ground
XT5.12 - Gnd
XT5.4 - TC
XT3.10 - 1NO.2
Protective Earthing
For personnel protection the metal housing of the OSM must
be connected according to the applicable regulations, such as
DIN VDE 0141, via the marked earth screw of the OSM to the
earth arrangement of the pole earth bus or substation. The earth
connections can be carried out with cables or flat bar (zinccoated
steel or copper). The cross section must be dimensioned such
that a worst-case fault current (short circuit) does not cause a
weakening of the earth connection (Figure 31).
Tighten the earthing bolt to 30 2 Nm torque.
Reference values for cross sections of earth connection (copper):
Duration of fault
current (1 s)
Max. temperature of
earth connection
Cross section
earth connection
<10 kA/10 kA
300 C
16 kA
300 C
OSM
Voltage
transformer
Umbilical
cable
4
Earth bus
SEL-651R
Figure 31
Figure 30
Installation of the manual trip hook
25
Commissioning,
Maintenance
26
General
Commissioning, operation and maintenance is only permitted for qualified and trained personnel.
Insofar as installation, commissioning or retrofit is carried out on energized equipment, the relevant safety
regulations, including all national and local standards must be adhered to.
Danger
The OSM must always be tested and operated together with the appropriate recloser control. Individual
testing is not possible and may lead to the destruction of the OSM.
Caution
Maintenance
Under normal operating conditions (see chapter Ambient conditions, page 43) the OSM is maintenance free for a
period of at least 30 years or until it has reached the permissible number of operating cycles.
Non-conformity
If during installation, commissioning, operation or maintenance any non-conformity occurs, action shall be taken
in accordance with the non-conformity report on pages 47, 48.
27
28
Receiving and
Inspection
29
Packing
The OSM/TEL is delivered in a corrugated box with dimensions 810 (L) x 810 (b) x 890 (h) and a weight of not more
than 76 kg*. The following information are provided on the OSM packing cartons (Figure 34):
Handling symbols for transport and storage of the delivery unit (Figure 32)
Label 1 for manufacturers product information (Figure 33)
Label 2 for logistics data (Figure 35)
6
1
1. This side up
2. Fragile
3. Protect from rain
100
4. Max. weight on
the delivery unit
OSM15_Al_2(630_150)
5. Serial number
5
Figure 32
Figure 33
Handling symbols
Mark:
TEG-C-000111
Place of delivery:
Consignee:
Consignee:
Address
Address
Address
Address
Address
Phone:
Contact person
P/O Number:
Customer reference
Article:
Article description
Serial Number:
150218
Figure 35
Figure 34
Packing carton
* In some cases the OSM will be delivered in a wooden crate, or packaged as a single lift device with mounting
hardware, OSM and accessories pre-assembled. In these cases please check with the Tavrida shipping department
for weights and dimensions of the packaging.
30
Transport
The OSM shall be transported in the original packing only. The packed goods shall be handled in accordance with the
handling symbols. Loading procedures for OSM packing units shall be carried out only with fork lifts or cranes.
Lifting gear must not be attached to the bushings, use only lifting lugs attached to the side mounts with suitable
clearance of straps or chains. During transportation the OSM must not be exposed to impacts or dropped.
d
Dd
K^D
sZs
^E
/
W
K
t
D
s^
Ds
^^D>z,<^
Z^h>d
W^^
W^^
K
W^^
d^d
W^^Z/dZ/
Z^h>d
K
K
K
Z
K
Z
K
Z
K
d^d
WtK
d^ds>h
s
Z^h>d
W^^
Wt
s
W^^
t
s
W^^
W
s
Dd
D
W^^
DKd
W^^
:LWKGHUDWLQJSHU$16,VWDQGDUGDERYHPHWHUV
OSM/TEL
Screwdriver
Operating manual
Protective cover
31
Figure 37
Seal of the OSM
OSM
1. Rating plate
2. Serial number
3. Seal
Figure 36
Labelling of the OSM
2
DdK^D
E^//
KKKK
Z
s
Z
,
Z
K
Z
Z
Z
Z
s
dyyy
z
K^D
dEDZ
Please check that the rating plates of the delivered devices correspond to the data of the order and technical data
given on page 40.
Tavrida Electric accepts no warranty for a device if the seal is broken or has been removed.
Storage
Should immediate installation not be possible, the OSM shall be stored in the original packing under the following
conditions:
The OSM is switched off.
Dessicants must be placed in the packing.
Storage must be closed dry, well ventilated and the room temperature should be between - 40C and + 40C
(IEC62271-1/ DIN VDE 0670 Part 1000).
If several OSM are stacked a maximum of two layers is permitted.
32
Product Line
33
Model Types - 27 kV
OSM25_Al_2(630_150)
Accessories
Item number
Description
Quantity
TNA1001140
2TES.029.002
2TES.029.002-01
TNA1000709
TENA.685624.009
TENA.685624.009-02
TENA.685624.009-01
TENA.685624.009-03
AXCA754529.001
34
Protective Cover
Note
35
Dimensions, mm
Rated voltage, kV
B
Creepage
distance
Minimum taut
string distance
15.5
216
260
652
637
500
203
65
27
296
294
731
703
860
203
72
36
Weights, kg
Figure 38
Pole mounting hardware with provision for up to x6
surge arrestors and x2 1kVA transformers for loop
scheme control power
Figure 39
Substation frame mounting hardware with provision
for up to x3 external CTs
37
Circuit Diagrams
38
39
10
Technical Data
40
OSM15_Al_2
(630_150)
OSM25_Al_2
(630_150)
15.5 kV
27 kV
Rated data
Rated voltage (Ur)
10
50 kV
60 kV (70 kV) 1)
45 kV
50 (60 kV) 1)
110 kV
150 kV
10 pC @ 13.2 kV
10 pC @ 16.4 kV
16 kA
12.5 kA
41.6 kA
32.5 kA
16 kA
12.5 kA
50/60Hz
25 A
31.5 A
3.33 A
5A
Switching performance
Mechanical life (CO-cycles)
30 000
30 000
200
2)
35 ms
2)
15 ms
2)
23 ms
Standards
International Standard
American Standard
Russian Standard
Chinese Standard
Other data
Current sensing
3 current transformers
Voltage sensing
6 voltage sensors
85 Ohm
Solar radiation
Degree of protection
Weight
95 Ohm
1.1 kW/m
IP65
65 kg
72 kg
1)
800 A continuous current and 70 kV dielectric products available by special order. Please contact Tavrida Electric
North America for further information.
2)
OSM closing, opening and break times based on Tavrida CM_15 series controls without processing acceptance time.
Please see SEL-651R manual for more information on additional time to calculate a complete fault interruption cycle.
41
OSM15_Al_2
(630_150)
OSM25_Al_2
(630_150)
10
100 mA
Minimum current for 12 V AC / DC, inductive load (t=20 ms, cosj =0.3)
100 mA
5A
3A
1A
1A
0.75 A
0.75 A
0.5 A
0.03 A
0.25 A
0.03 A
5A
5A
5A
5A
OSM15/OSM25_Al_2(630_150)
Current transformers
Rated primary current A
600
600
1
2.5
2.5
25
25
C25
C25
630
630
Voltage Sensors
Capacitance of high arm
42
20...25pF
-770 ppm/oC
Ambient Conditions
The OSM and CM were designed for the following ambient and operating conditions for outdoor installations (OSM) and
indoor installations (CM).
Maximum ambient temperature
+ 55 C
- 50 C
Humidity
100% condensing
Altidude
to 3000 m
10
Figure 40
43
11
Legal Information
44
Warranty
Unless otherwise stated in the contract, the warranty period is 3 years from date of invoice. If agreed to otherwise,
the contract conditions apply. No warranty is given in the case of
a) the warranty period having run out during the period of storage with the customer.
b) the operating conditions, ambient conditions, transport and storage conditions have not been adhered to
according to the application description or the application guide.
c) an unauthorized manipulation of the device has been carried out, such as opening the housing or damaging the seal.
d) the device has not been properly installed, such as incorrect connection voltages.
11
Quality Regulations
All manufacturing facilities of the company have been
certified by KEMA in the Netherlands and comply with (DIN
EN) ISO 9001:2000.
All technical data of the vacuum circuit breaker are stored
in an electronic database for each step of the manufacturing
process. Testing of the circuit breakers is carried out in
accordance with the relevant standards and beyond that
the following test are carried out:
1000 C-O cycles
Insulation strength of the primary and auxiliary circuits
at operating frequency
Measurement of the resistance of the main circuit
All test results are automatically stored
Complaints and
Transport Damage
All products are shipped exclusively with original packing
to ensure safe transport and avoid transport damage (see
Packing, Goods Received).
Tavrida Electric will not accept any claims for damages
caused by improper transport, storage as well as
unpacking. Transport damage must be reported in writing
to the supplier as soon as it is discovered. A period
of maximum 3 weeks after receipt is allowed for this.
For legitimate claims Tavrida Electric will supply replacement
equipment free of charge according to our warranty
regulations. Tavrida Electric reserves the right to verify
any claim.
45
Environmental Friendliness
The modules are manufactured from environmentally
friendly material. Therefore, special disposal is not
required.
TAVRIDA ELECTRIC NA
Non-conformity Report
11
Service Department
1105 Cliveden Avenue
Delta, BC, Canada
V3M 6G9
Phone: 604-540-6600
Fax: 604-540-6604
E-Mail: info@tavrida-na.com
Web: www.tavrida-na.com
Liability
Damages and demands for reimbursement of expenses incurred by the customer (in the following: compensation)
for what-ever legal reasons, especially due to non-compliance of obligations of the contractual obligations and for
unauthorized actions, are excluded. This does not apply, insofar as there is a compulsory liability such as according
to the product liability law in cases of malice, gross negligence, because of damage to life, the body or health,
because of damage to important contractual obligations.
Compensation for damage to important contractual obligations, however, is limited to the damage which can be
predicted as typical of the contract insofar as there is no malice or gross negligence, because of damage to life, the
body or health. A change of the obligation to provide proof to the disadvantage of the customer is not connected
with these regulations.
Copyright
Without our written permission, this documentation may not be used, also not in extract form, for own general
publications, printouts, handbooks, training, lectures, etc. nor copied and further processed. This includes also
the duplicating or re-copying in any form of data carriers and microfilms. A one-time written permission is not
automatically to be taken as a part or complete surrender of the copyright provisions. We reserve the right to
changes. The issue of a new version of these operating instructions renders all other older versions obsolete.
Tavrida Electric and its associated companies make every effort to adapt the contents of their documentation to
the latest and most current state of development of the products.
The present documentation was produced with the greatest care. However, we are not liable for possible errors in
this information text, user-side incorrect interpretation and/or for consequences arising therefrom.
Copyright 2011; Tavrida Electric reserves the right to make changes to the design and data of their products. Tavrida Electric accepts no
responsibility or liability for losses or damage caused by improper actions based on this publication. Schweitzer Engineering, SEL-651R are
registered trademarks of Schweitzer Engineering Inc.
46
NON-CONFORMITY REPORT
From:
To:
TAVRIDA ELECTRIC NA
Service Department
Address:
Address:
11
Phone:
604-540-6600
Fax:
Fax:
604-540-6604
E-Mail:
E-Mail:
info@tavrida-na.com
Serial No.:
Type designation CM
Serial No.:
Date of commissioning:
Does your installation comply with the requirements of the application guide, OSM?
Primary Part (OSM):
Operating conditions of OSM comply with technical data
specified in application guide (pages 41-43)
Fixing points (page 14)
Protective earthing (page 25)
Description of non-conformity:
Name:
Signature:
Your warranty claim can only be handled if this non-conformity report is filled in completely including your name and address.
47
NON-CONFORMITY REPORT
11
From:
To:
TAVRIDA ELECTRIC NA
Service Department
Address:
Address:
Name:
Phone:
Phone:
604-540-6600
Fax:
Fax:
604-540-6604
E-Mail:
E-Mail:
info@tavrida-na.com
Serial No.:
Type designation CM
Serial No.:
Date of commissioning:
Does your installation comply with the requirements of the application guide, OSM?
Primary Part (OSM):
Operating conditions of OSM comply with technical data
specified in application guide (pages 41-43)
Fixing points (page 14)
Protective earthing (page 25)
Description of non-conformity:
Name:
Signature:
Your warranty claim can only be handled if this non-conformity report is filled in completely including your name and address.
48
Date:
11
49
This document is copyright and is intended for users and distributors of Tavrida Electric product. It contains information that is
the intellectual property of Tavrida Electric and the document, or any part thereof, should not be copied or reproduced in any form
without written permission from Tavrida Electric.
Tavrida Electric applies a policy of ongoing development and reserves the right to change product without notice.
Tavrida Electric does not accept any responsibility for loss or damage incurred as a result of acting or refraining from action based on
information in this application guide.