You are on page 1of 6

Table of contents

RED indicates NEW information

Low Voltage, Branch Circuit Rated Fuses . . . . . 7

Low Voltage Supplementary Fuses . . . . . . . . . . 39


Electronic - PC Board and
Small Dimension
Fuses
. .Small
. . . . . . . . . . . . . . . 53
Electronic
- PC Board
and

Medium Voltage Fuses and Fuse Links . . . . . . . 67

High Speed Fuses . . . . . . . . . . . . . . . . . . . . . 87

IEC &
British
Fuses

IEC & British Standard Fuses . . . . . . . . . . . . . 213

Fuse
Holders
& Blocks

Fuse Holders and Blocks . . . . . . . . . . . . . . . . 231

Power
Distribution
Blocks

Telpower TPC & TPCDS compact fused disconnect switches . . . . . . . . 332


Telpower TPM & TPMDS miniature fused disconnect switches . . . . . . . 333
Fused disconnect switches for TPA fuses . . . . . . . . . . . . . . . . . . . 334-335
Fused disconnect switches for TPS fuses . . . . . . . . . . . . . . . . . . . . . . 336
Fused disconnect switches . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 337-338
Telpower high-current switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 339
Telpower 70-600A: 170Vdc fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . 340
Telpower 1-600A: 170Vdc fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 341
Indicating fuses & holders . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 342-343
Telpower specialty fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 344-345
F38, FE2475 & F7036 Series filtered terminal blocks . . . . . . . . . . . 346-348
Series C7021 & C7024 power feed thru terminal blocks . . . . . . . . 349-350

Page

High Speed
Fuses

Telecom Protection Devices . . . . . . . . . . . . . . . . . . 331

Catalog Sections

Medium
Voltage
Fuses

Safety Module fused disconnect switch . . . . . . . . . . . . . . . . . . . . . . . 304


Coordination Module fused panelboard . . . . . . . . . . . . . . . . . . . . . . . 305
Power Module elevator disconnects . . . . . . . . . . . . . . . . . . . . . . . . . 306
Overview for fusible disconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 307
30A Base & rail mount fusible disconnects . . . . . . . . . . . . . . . . . . 308-309
60-100A Base & rail mount fusible disconnects . . . . . . . . . . . . . . 310-311
200-800A Base & rail mount fusible disconnects . . . . . . . . . . . . . 312-313
30-800A 2-, 3-, 4- & 6-Pole enclosed fusible disconnects . . . . . . . 314-317
Overview for non-fusible disconnects . . . . . . . . . . . . . . . . . . . . . . 318-319
16-100A Base & rail mount non-fusible disconnects . . . . . . . . . . . 320-321
16-100A door mounted non-fusible disconnects . . . . . . . . . . . . . . . . . . 322
400-800A Non-fusible disconnects & accessories . . . . . . . . . . . . . 323-324
16-80A 3-Pole enclosed non-fusible disconnects . . . . . . . . . . . . . . . . . 325
16-3150A 3-Pole enclosed non-fusible disconnects . . . . . . . . . . . . . . . 326
16-400A 2-, 4- & 6-Pole enclosed non-fusible disconnects . . . . . . 327-328
A/C disconnects - fused and non-fused . . . . . . . . . . . . . . . . . . . . . . . . 329
Fused, dead front disconnect switches . . . . . . . . . . . . . . . . . . . . . . . . . 330

Low Voltage Low Voltage


Electronic
Branch
Supplementary
Fuses
Circuit
Fuses

Disconnects . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 303

Power Distribution Blocks . . . . . . . . . . . . . . . 275

TVS transient voltage surge suppressors . . . . . . . . . . . . . . . . . . . . . . . 352


TVSS transient surge suppression limiters . . . . . . . . . . . . . . . . . . . . . 353

Wire
Connection
Products

Surge Suppression Devices . . . . . . . . . . . . . . . . . . . . 351

Wire Connection Products . . . . . . . . . . . . . . . 281

Disconnects . . . . . . . . . . . . . . . . . . . . . . . . 303

Application Guide . . . . . . . . . . . . . . . . . . . . . . . . . . 361

Telecom Protection Devices . . . . . . . . . . . . . 331

Surge
Application
Suppression Accessories
Guide
Devices

Cooper Bussmann Electrical Safety Services . . . . . . . . . . . . . . . . . . . . . 262


Fuse technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 363-369
Motor circuit branch circuit protection . . . . . . . . . . . . . . . . . . . . . . . . . 370
Conductor & termination considerations . . . . . . . . . . . . . . . . . . . . 371-373
Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 374-376
Out-of-stock substitution/upgrades . . . . . . . . . . . . . . . . . . . . . . . . . . . . 376
Cooper Bussmann electrical trademarks . . . . . . . . . . . . . . . . . . . . . . . . 376
Industrial & commercial fuse applications . . . . . . . . . . . . . . . . . . .377-378

Telcom
Protection
Devices

Fuse service kits & assortments . . . . . . . . . . . . . . . . . . . . . . . . . . 255-257


Clip clamps & rail adapters (DIN & American) . . . . . . . . . . . . . . . . . . 258
Spare fuse holders, pullers, testers & cabinets . . . . . . . . . . . . . . . . . . 259
Fuse reducers & dummy "neutrals" . . . . . . . . . . . . . . . . . . . . . . . . . . . 260

Disconnects

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255

Surge Suppression Devices . . . . . . . . . . . . . . 351

Accessories . . . . . . . . . . . . . . . . . . . . . . . . 255

Catalog Number Index . . . . . . . . . . . . . . . . . . . . 379-383


Sales support & manufacturing facilities . . . . . . . . . . . 384

Application Guide . . . . . . . . . . . . . . . . . . . . . 361

Cross reference and Low-Peak Fuse Stock Consolidation


Index

Inside back cover

Index by Part Number . . . . . . . . . . . . . . . . . . 379

For product Data Sheets, visit www.cooperbussmann.com/products/datasheet.asp

Low Voltage, Branch Circuit Rated Fuses

Selecting circuit protection


The following fuse selection guides are based on the 2005
NEC and provided fuse recommendations for the various
applications listed.
These are only suggestions. Final fuse selection should be
performed only by a qualified personnel able to fully asses
an applications circuit protection requirements. If you need
assistance in selecting a fuse for a particular application, call
the Cooper Bussmann Application Engineering team. This

team is staffed by degreed electrical engineers and available


by phone for technical and application support Monday
Friday, 8:00 a.m. 5:00 p.m. Central Time.
Application Engineering can be reached via phone, fax or
e-mail:
Phone: 636-527-1270
Fax: 636-527-1607
E-mail: fusetech@cooperbussmann.com

Ballasts
Indoor

Fluorescent

Consult fixture manufacturer for size and type.

All Other (Mercury,


Sodium, etc.)

Consult fixture manufacturer for size and type.

Fuse & Holder Recommendations


Fuse
GLR
GMF
GRF

Holder(s)
HLR

Fuse
GLQ
GMQ

Holder(s)
HLQ

Fuse & Holder Recommendations


Fuse
BAF
BAN
KTK
FNM
FNQ
FNW

Holder(s)
HPF
HPS

Fuse
KTK-R
FNQ-R
LP-CC

Holder(s)
HPS-RR
HPF-RR

KTQ
BBS

HPS-L
HPF-L

Fuse
SC 0-15

Holder(s)
HPF-EE
HPS-EE
SC 20
HPF-JJ
HPS-JJ
SC 25-30 HPF-FF
HPS-FF

Fuse & Holder Recommendations


Outdoor

Mercury, Sodium, etc.

Consult fixture manufacturer for size and type.

Fuse
BAF
BAN
KTK
FNM
FNQ
FNW

Holder(s)
HEB
HEX
HPC-D

Fuse
KTK-R
FNQ-R
LP-CC

Holder(s)
HEY

Capacitors (NEC 460)


Protected by
Time-Delay Fuses.

150% to 175% of Full Load Current

Protected by
Non-Time-Delay Fuses.

250% to 300% of Full Load Current.

Volts
0-250
0-600
0-600

On Load Side of Motor Running


Overcurrent Device.

Fuse Recommendations

Protection recommended as shown, but not required.

Fuse(s)
LPN-RK_SP, FRN-R
LPS-RK_SP, FRS-R
LPJ_SP, LP-CC,
FNQ-R, TCF

Fuse Recommendations
Volts
0-250
0-300
0-600
0-600
0-600

For product Data Sheets, visit www.cooperbussmann.com/products/datasheet.asp

Fuse(s)
KTN-R, NON
JJN
KTS-R, NOS
JKS, KTK-R
JJS

Low Voltage, Branch Circuit Rated Fuses

Selecting circuit protection


Electric Heat (NEC 424)
Size at 125% or next size larger but in no case larger than
60 amps for each subdivided load.

Electric Space Heating

Fuse Recommendation
Volts
0-250
0-300
0-480
0-600
0-600
0-600

Electric Boilers with


Resistance Type Immersion
Heating Elements in an ASME
Rated and Stamped Vessel

Size at 125% or next size larger but in no case larger than


150 amps for each subdivided load.

Fuse(s)
LPN-RK_SP
FRN-R, NON
JJN
SC 25 to SC 60
LPS-RK_SP
FRS-R, NOS
JJS
LPJ_SP, LP-CC
FNQ-R, JKS, KTK-R,
TCF, SC 12 to SC 20

Mains, Feeders, Branches


Feeder Circuits
(600A & Less)

No Motor Load

100% of non-continuous load plus 125% of continuous load.

Fuse Recommendations
Volts
0-250
0-300
0-600
0-600
0-600

Combination Motor
Loads and Other Loads

Motor Loads

150%* of the FLA of largest motor (if there are two or more
motors of same size, one is considered to be the largest) plus
the sum of ail the FLA for all other motors plus 100% of noncontinuous, non-motor load plus 125% of continuous, nonmotor load.

150%* of the FLA of largest motor (if there are two or more
motors of same size, one is considered to be the largest) plus
the sum of ail the FLA for ail other motors.

Fuse(s)
LPN-RK_SP, FRN-R
JJN
LPS-RK_SP, FRS-R
JJS
LPJ_SP, LP-CC
JKS, KTK-R, LPT

Fuse Recommendations
Volts
0-25O
0-600
0-600

Fuse(s)
LPN-RK_SP, FRN-R
LPS-RK_SP, FRS-R
LPJ- SP, LP-CC

*A max. of 175% (or the next standard size if 175% does not
correspond to a standard size) is allowed for all but wound
rotor and all dc motors.

Main, Branch &


Feeder Circuits
(601-6000A)

150% to 225% of full load current of largest motor plus 100%


of full load current of all other motors plus 125% of continuous
non-motor load plus 100% of non-continuous non-motor load.

For product Data Sheets, visit www.bussmann.com/products/datasheet.asp

Fuse Recommendation
Volts
0-600

Fuse(s)
KRP-C_SP

Low Voltage, Branch Circuit Rated Fuses

Selecting circuit protection


Motor Loads (NEC 430)
Fuse Sized For:
600V & Less

Protected by TimeDelay Fuses

Backup Overload w/
Motor Starter & ShortCircuit Protection

Fuse Recommendations
125% of motor FLA or next size larger.

Volts
0-250
0-600

Fuse(s)
FRN-R
FRS-R

Fuse Recommendations
130% of motor FLA or next size larger.

Short-Circuit Only

Protected by NonTime Delay Fuses &


all Class CC Fuses

Short-Circuit Only

175%* of motor FLA or next size larger. (If 175% does not correspond to a standard size). If this will not allow motor to start,
due to higher than normal inrush currents or longer than normal acceleration times (5 sec. or greater), fuse may be sized up
to 225% or next size smaller.

Max. of 300%* of motor FLA or next size larger (if 300% does
not ocrrespond to a standard size). If this will not allow motor
to start due to higher than normal inrush currents or longer
than normal acceleration times (5 sec. or greater), fuses
through 600 amps may be sized up to 400% or next size
smaller.

Volts
0-250
0-600

Fuse Recommendations
Volts
0-250
0-600
0-600

Compare the min. melting time-current characteristics of the fuses with the time-current characteristics of the overload relay
curve. The size fuse which is selected should be such that short.circuit protection is provided by the fuse and overload protection is provided by the controller overload relays.

Fuse(s)
LPN-RK_SP, FRN-R
LPS-RK_SP, FRS-R
LPJ_SP, TCF

Fuse Recommendations
Volts
0-250
0-300
0-600
0-600
0-600

*150% for wound rotor and all DC motors.

Above 600V

Fuse(s)
LPN-RK_SP
LPS-RK_SP

Fuse(s)
KTN-R, NON
JJN
KTS-R, NOS
JJS
LP-CC, JKS, KTK-R,
LPT

Fuse Recommendations
Volts
2400
4800
7200

Fuse(s)
JCK, JCK-A, JCH
JCL, JCL-A, JCG
JCR, 7.2 WKMSJ

Solenoids (Coils)
Branch Circuit
Fuses

Fuse Recommendation
Size at 125% or next size smaller.

Volts
0-250
0-600
0-600

Supplementary
Fuses

Size at 125% or next size larger.

Fuse Recommendation
Volts
0-32
0-125
0-250

0-500

For product Data Sheets, visit www.cooperbussmann.com/products/datasheet.asp

Fuse(s)
Best: LPN-RK_SP
FRN-R
LPS-RK_SP
FRS-R
LPJ_SP, LP-CC
FNQ-R, TCF

Fuse(s)
MDL 9-30A,
FNM 20-30A
MDA 25-30A,
FNM 12-15A
MDL 116-8A,
MDA 210-20A,
FNM 110-10A,
FNW 12-30A,
MDQ 1100-7A
FNQ 110-30A

Low Voltage, Branch Circuit Rated Fuses

Selecting circuit protection


Transformers 600V Nominal or Less (NEC 450.3)
Primary
Protection
Only

Primary And
Secondary
Protection

Note: Components on the secondary still


need overcurrent protection

Without Thermal
Overload
Protection

With Thermal
Overload
Protection

NEC Maximums

Optimum Protection
Rated primary current less
than 2 amps

125% or next size larger

Max. 300% or next size smaller (See


NEC 430.72(C) for control circuit
transformer maximum of 500%

Rated primary current


greater than or equal to 2
amps but less than 9 amps

125% or next size larger

Max. 167% or next size smaller

Rated primary current


greater than or equal to 9
amps

125% or next size larger

Max. of 125% or next larger*

Rated secondary current


less than 9 amps

A
Maximum Fuse Size

Transformer
Impedance of 6%
or Less

Transformer
Impedance of
More Than 6%
But Less Than
10%

Rated secondary current 9


amps or greater

Rated secondary current


less than 9 amps

Rated secondary current 9


amps or greater

Rated secondary current


less than 9 amps

Rated secondary current 9


amps or greater

C
Primary and secondary
fuses at 125% of primary and secondary FLA or
next size larger

% of Primary FLA
(or next FLA size smaller)
A = 250%
B = 250%
C = 600%
D = 600%
E = 400%
F = 400%
% of Secondary FLA
A = 167% or next size smaller
B = 125% or next size larger*
C = 167% or next size smaller
D = 125% or next size larger*
E = 167% or next size smaller
F = 125% or next size larger*

*When 125% of FLA corresponds to


a standard rating, the next larger size
is not permitted.

Fuse Recommendations
Volts
250V
600V

Fuse(s)
LPN-RK_SP, FRN-R
KRP-C_SP, LPJ_SP, LPS-RK_SP, FNQ-R, FRS-R, TCF

For product Data Sheets, visit www.bussmann.com/products/datasheet.asp

Low Voltage, Branch Circuit Rated Fuses

Selecting circuit protection


Transformers Over 600V Nominal (NEC 450.3)
Supervised
Installations

Primary
Protection
Only

Primary at code max. of 250% or


next standard size if 250% does not
correspond to a standard rating

Primary
and
Secondary
Protection

Transformer
Impedance Less
Than or Equal to 6%

Transformer
Impedance Greater
Than 6% But Less
Than 10%

Unsupervised
Installations

Transformer
Impedance Less
Than or Equal to 6%

Transformer
Impedance Greater
Than 6% But Less
Than 10%

Primary
at code
max. of
300%

Primary
at code
max. of
300%

Primary at code max. of


300% or next standard size
if 300% does not correspond to a standard rating

Primary at code max. of


300% or next standard size
if 300% does not correspond to a standard rating

Note: Components on the secondary still need


overcurrent protection

Secondary
Over 600V

Secondary at
code max. of
250%

Secondary
600V or
Below

Secondary at
code max. of
250%

Secondary
Over 600V

Secondary at
code max. of
225%

Secondary
600V or
Below

Secondary at
code max. of
250%

Secondary
Over 600V

Secondary at code max. of


250% or next standard size
if 250% does not correspond to a standard rating

Secondary
600V or
Below

Secondary at code max. of


125% or next standard size
if 125% does not correspond to a standard rating

Secondary
Over 600V

Secondary at code max. of


225% or next standard size
if 225% does not correspond to a standard rating

Secondary
600V or
Below

Secondary at code max. of


125% or next standard size
if 125% does not correspond to a standard rating

Fuse Recommendations
Volts
250V
600V

Fuse(s)
LPN-RK_SP, FRN-R
LPS-RK_SP, LPJ-_SP,
KRP-C_SP, FRS-R, FNQ-R,
TCF
2475V
JCD
2750V
JCX
2750/5500V JCW
5500V
JCE, JCQ, JCY, JCU,
5.5 ABWNA, 5.5 AMWNA,
5.5 FFN
7200V
7.2 ABWNA, 7.2 SDLSJ,
7.2 SFLSJ
8300V
JCZ, JDZ, 8.25 FFN
15500V
JCN, JDN, JDM, 15.5 CAVH
17500V
17.5 CAV, 17.5 SDM
24000V
24 SDM, 24 SFM, 24 FFM
36000V
36 CAV, 36 SDQ, 36 SFQ
38000V
38 CAV

Solid State Devices (Diodes, SCRs, Triacs, Transistors)


Short-Circuit
Protection
Only

Fuse Recommendations
F, S, K, & 170M Series fuses sized up to several sizes
larger than full load RMS or dc rating of device.

Volts
0-130
0-250
0-500
0-600
0-700
0-1000

For product Data Sheets, visit www.cooperbussmann.com/products/datasheet.asp

Fuse(s)
FWA
FWX
FWH
FWC, KAC, KBC
FWP, 170M Series,
SPP
FWJ, 170M Series,
SPJ