Generating set technical data: Model Electra Molins EMD-350 SOUNDPROOF / AUTOMATIC SOUNDPROOF

Model: EMD-350
Form of Construction: Soundproof / Automatic Soundproof
Brand of the Genset
Control panel type

ELECTRA MOLINS
AUT-MP12

Output in standby service on mains failure


(LTP "Limited Time Power" according to norm ISO 8528-1)

350 kVA 280 kW

Output in prime service


(PRP "Prime Power" according to norm ISO 8528-1)

315 kVA 252 kW

Tolerance of the maximum active power (kW)

5%

Current intensity in standby service on mains failure

505 A

Current intensity in prime service

455 A

Voltage

400 V

N of phases

3+N

Precision of the voltage in steady state

0,5%

Range of voltage adjustment


Power factor
Speed
Frequency
Frequency variation in steady state
Coolant heater output (only for automatic construction)

5%
0,8 - 1
1.500 r.p.m.
50 Hz
0,5%
1.000 W

Admissible first step load

145 kW

Mean sound level at 10 m

67 dBA

Mean sound level at 1 m

77 dBA

Acoustic power Lwa

95 dBA

Date: 05/07/2016. Electra Molins reserves the right to modify these specifications according to its own technical criteria.

Page 2 of 2
Generating set technical data: Model Electra Molins EMD-350 SOUNDPROOF / AUTOMATIC SOUNDPROOF

Dimensions and Consumptions


Length x Width x Height
Weight empty of fuel

4.114 x 1.453 x 2.350 mm


3.890 kg

Fuel tank capacity


Specific fuel consumption
Fuel consumption with 75% of load (210 kW)

540 l
0,26 l/kW-h
54,6 l/h

Diesel Engine
Make of the engine and model
Cycle

DOOSAN P-126TI-II
Diesel 4 stroke

Cooling
N and configuration of the cylinders
Total swept volume
Air aspiration
Speed governor

Water-cooled radiator
6 in line
11,1 l
Turbocharger with air-air cooler
Electronic

Total oil capacity


Oil consumption at full load

23 l
0,35 l/h

Capacity of the cooling circuit (40% antifreeze cooling liquid)

51 l

Alternator
Make of the alternator and model

LEROY SOMER LSA 472 VS2

Connection

Star

Insulation class
Voltage electronic regulator
Sustained short-circuit current
Protection

H
AREP R450
3 In during 10 seconds
IP-23

Batteries
Quantity
Connection

2
En paralelo

Direct current voltage


Capacity of each battery
Type

24 V
125 Ah
Lead-acid

The stated outputs correspond to the maximum continuous power with variable load according to ISO-8528-1, in atmospheric
conditions of 25C and 1000 m of altitude. The generating set can operate at higher temperatures and altitudes with the
application of power correcting factors.
The prime power output admits a 10% overload in limited time peaks, maximum one hour every 12 hours. However, in order to
extend the engines life, it is advised that the average active power charges (kW), either continuous or discontinuous, connected
to the generating set during any 24 hours working period, should not exceed:
70% PRP power, in main service.
80% LTP power, in standby service on mains failure.

Date: 05/07/2016. Electra Molins reserves the right to modify these specifications according to its own technical criteria.