Report

Page 1 of 14

Tampa Fire Rescue


808 E Zack Street
Tampa, Fl 33602
813-274-7000
Fax 813-274-7144

Occupant Name:

Tampa Convention Center

Address:

333 South FRANKLIN


Street

Suite:

Inspection
2/16/2016
Date:
InspectionType: Stadium Exhibition Halls ArenaT2
Inspected By:
Richard Rodriguez
813-274-7138

Occupant
Number:

Pass Fail N/A


FL NFPA 01 13
Floor 1
Chapter 4 General
Requirements
4.5.8.6 Excerpt: Any device,
equipment, system,
condition, arrangement, level
of protection...

Any device, equipment, system, condition, arrangement, level


of protection, fire-resistive construction, or any other feature
requiring periodic testing, inspection, or operation to ensure its
maintenance shall be tested, inspected, or operated as
specified elsewhere in this Code or as directed by the AHJ.
[101:4.6.12.4]

Chapter 10 General Safety


Requirements
10.1.2 Florida Fire
Life Safety Code.
Prevention Code
Every new and existing building shall comply with this Code
and NFPA 101, Life Safety Code.
10.4.1 Required to maintain Whenever or wherever any device, equipment, system,
systems, ratings, equipment condition, arrangement, level of protection, fire-resistive
construction, or any other feature is required for compliance
etc. (see photo 1.1)
with the provisions of this Code, such device, equipment,
system, condition, arrangement, level of protection, fireresistive construction, or other feature shall thereafter be
continuously maintained. Maintenance shall be provided in
accordance with applicable NFPA requirements or
requirements developed as part of a performance-based
design, or as directed by the AHJ. [101:4.6.12.1]
Action Required: Where Fire doors have been Removed,
provide signed and sealed letter from a fire protection engineer
or Lic. Architect stating the doors are not Required.
Location: Fire doors in the Meeting Room egress
corridor ,Upper Parking Garage.

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 2 of 14

10.19.3.2 Sprinkler head


clearance from storage. (see

The clearance between the deflector and the top of storage


shall be 18 in. (457 mm) or greater. [13:8.6.6.1]

photo 2.1)

Action Required: Storage too high, Lower.


Location: Aramark Storage Area "E",
10.19.5.1 General- Storage Combustible material shall not be stored in boiler rooms,
in boiler rooms, mechanical mechanical rooms, or electrical equipment rooms.
rooms, or electrical
equipment rooms. (see photo 3.1, Action Required: Remove Storage.
3.2)

Location: Mechanical Level (see pic) Rain Water leader Room,


Chapter 11 Building
Services
11.1.7.6 Extension Cords,
Permanent wiring (see photo

Extension cords shall not be used as a substitute for permanent


wiring.

4.1)

Action Required: Remove Extension cords where used as


permanent wiring.
Location: First Aid Office, Concession # 7, Aramark Sandwich
Co, Aramark OPS office Area.
11.7.5.2 GENERATOR
INSPECTION

Stationary generators required by this Code, the building code,


or other NFPA codes and standards shall be maintained in
accordance with NFPA 110.
Action Required: Witnessed full transfer of power to Life Safety
Generator.

Chapter 12 Features of
Fire Protection

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 3 of 14

12.3.3.2 Fire-rated gypsum Where required, fire-rated gypsum wallboard walls or ceilings
wallboard walls or ceilings
that are damaged to the extent that through openings exist, the
(see photo
damaged gypsum wallboard shall be replaced or returned to
that are damaged
5.1, 5.2, 5.3, 5.4, 5.5, 5.6, 5.7, 5.8, 5.9,
the required level of fire resistance using a listed repair system
5.10, 5.11, 5.12, 5.13, 5.14, 5.15, 5.16,
or using materials and methods equivalent to the original
5.17, 5.18, 5.19, 5.20, 5.21, 5.22, 5.23,
construction.
5.24, 5.25, 5.26, 5.27, 5.28, 5.29, 5.30)

Action Required: Repair All Walls, Ceilings, Doors, Floors


where Fire and Smoke barriers have been Compromised.
Location: CATWALK LEVEL; West Lighting Control Room, East
Lighting Control Room, Wall over - meeting rooms
37/37,***** LEVEL 4; Air Handler Equipment Room # 29 (SEE
PIC), IDF # 8 (SEE PIC) , Air Handler # 26 (SEE PIC),
BallRoom Corridor Stairs to roof NEXT TO Mech Room (1012)
level 3 Riser penetrations, Penetrations into Mechanical Room,
level 3 Block separation (see pic)
****** Operations Level - Electrical Room, ***** Center Exhibit
Hall - Room 3119 Trash room, Moveable Wall Storage,
***** EAST HALL - Paint Storage Room, East - Franklin
Emergency Exit Stairwell, ***** West Hall Elevator Lobby Rm
3016
Janitors Closet, Platt Street Pump Rm, ****** Ballroom Corridor
Mech Rm 1012, ****** Mechanical Level - Penetrations
Pervasive, A/H # 15 near exit door, Ball Room A/B power
Access, Ball Room Power Access C/D, Rooms 16/17 , 14/15
at door to cat walk over meeting Rm 1 Corridor, Cat wallk over
Meeting Room 9 / 10 (keep doors closed), ***** Ball Room
Level service corridors behind meeting rooms 18/25, Mechnical
Room 1264, Stage Rail Storage Rm next to 1264, Rm
1222 Tele PBX , Room 1026 Janitors Room, EXECUTIVE
OFFICES GLASS DOOR, MARKETING GLASS DOOR.
Chapter 13 Fire Protection
Systems
13.1.7 FIRE PROTECTION All fire protection systems and devices shall be maintained in a
SYSTEMS
reliable operating condition and shall be replaced or repaired
where defective or recalled.
Location: Re-Attach Smoke detector room 1237 Housekeeping.

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 4 of 14

13.3.3.3 Ceiling Tiles in


sprinkled buildings (see photo
6.1, 6.2, 6.3, 6.4, 6.5, 6.6, 6.7, 6.8, 6.9,
6.10, 6.11)

Ceiling Tiles and Ceiling Assemblies.


Where automatic sprinklers are installed, ceilings necessary for
the proper actuation of the fire protection device in accordance
with NFPA 13 shall be maintained.
Action Required: Replace or Repair ceiling Tiles where
required.
Location: Concession # 5, Storage Room between 34-25,
Office Rm next to Room 31, East Hall Show office
, Concession # 7, UPS Store, Aramark Sandwich Co.; 2nd
Level Room # 24 # 25, # 18 Storage, # 19 Storage, # 20
storage, # 21 Storage, # 22 Storage, # 23 storage, Bistro
(1000), West Employee Entrance Corridor; Ballroom Level
Room 1252 Pantry, Room 1237 Housekeeping Room # 1238
Pantry, Room # 1312 Pantry, Kitchen replace ACT around
Cooler, Kitchen Baskets and Display area, Kitchen Ballroom
level, Room # 1304 Control Rm, Security Command Ctr
Phone Rm, RETAIL STORAGE/PARKING GARAGE- South
Side Retail, Room # 3117.

13.3.3.5.1.8 Sprinklers Sprinklers shall not be altered in any respect or have any type
Altered finish (paint, rust,
of ornamentation, paint, or coatings applied after shipment from
coatings...) (see photo 7.1, 7.2, 7.3, the place of manufacture. [25:5.4.1.8]
7.4, 7.5, 7.6)

***** ACTION REQUIRED: Where Sprinkler Heads Have


Covers, I.E. plastic bags, tape, or Coatings Remove or Replace
Sprinkler Head.
LOCATION: PERVASIVE throughout EAST, CENTER AND
WEST EXHIBIT HALL.; ****** Mechanical Level Pervasive
Throughout; ****** Parking Garage, Retail South Side Remove
Bags, Machine Shop Remove bags, Wood Shop remove
bags, North Retail Remove Bags. ***** West Lighting Control
Rm, East lighting Control Rm.

Chapter 14 Means of
Egress

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 5 of 14

14.4.1 Means of EgressObstructions (see photo 8.1, 8.2,


8.3, 8.4, 8.5, 8.6, 8.7, 8.8, 8.9, 8.10, 8.11,
8.12)

General.
Means of egress shall be continuously maintained free of all
obstructions or impediments to full instant use in the case of fire
or other emergency. [101:7.1.10.1]
Action Required: Provide a Continuous Unobstructed Path of
Egress. Ball Room Level Egress Corridor ( Back Area) shall be
marked as intended in the Approved set of Plans. Provide Sign
"Emergency Exit - Do Not Block" where Required.
Location: Re-Stripe loading Dock area, Meeting Room 18/25
back Hallway Exit provide Sign, " Emergency exit - Do
Not Block," Kitchen Exit to Produce loading Dock Sign "
Emergency Exit Do Not Block," Meeting Room Service Corridor
No Storage Allowed, BALLROOM BACK AREA EGRESS
CORRIDOR, DESIGNATE AREAS AS PER PLAN, (SEE
PICTURES)

14.6.3 Under Stair


Storage (see photo 9.1)

Usable Space.
Enclosed, usable spaces, within exit enclosures shall be
prohibited, including under stairs, unless otherwise permitted by
14.6.3.2. [101:7.2.2.5.3]
Action Required: Remove Storage
Location: Stairwell behind meeting room # 16

14.14.1.3 Exit Stair Door


Tactile Signage.

Tactile signage shall be provided to meet the following criteria,


unless otherwise provided in 14.14.1.4:
(1) Tactile signage shall be located at each exit door requiring
an exit sign.
(2) Tactile signage shall read as follows: EXIT
(3) Tactile signage shall comply with ICC/ANSI A117.1,
American National Standard for Accessible and Usable
Buildings and Facilities. [101:7.10.1.3]
Action Required: Provide approved signs where required.
Location: Level 4 Exit Stairs,

14.14.1.5.1 Excerpt: Access Access to exits shall be marked by approved, readily visible
to exits shall be marked by signs in all cases where the exit or way to reach the exit is not
approved, readily...
readily apparent to the occupants. [101:7.10.1.5.1]
Action Required: Replace Exit sign , Repair Exit Sign , Add or
Delete Chevron, or Relocate.
location: Catwalk, Add Exit Signs, Room 36, Room 39, Room
31, Storage Area J, Service Corridor Behind 13/16 Exit sign
direction, Outside stairwell loading dock egress Exit signs,
Meeting Rm # 16, Rotunda center Exit, Rotunda Left Exit add
chevron,
Chapter 50 Commercial
Cooking Equipment

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 6 of 14

50.5.2.1 Hood Serviced and Maintenance of the fire-extinguishing systems and listed
Maintained
exhaust hoods containing a constant or fire-activated water
system that is listed to extinguish a fire in the grease removal
devices, hood exhaust plenums, and exhaust ducts shall be
made by properly trained, qualified, and certified person(s)
acceptable to the AHJ at least every 6 months. [96:11.2.1]
Action Required: Provide current inspections for all ansul
systems where required. Provide Deficient free Ansul Report.
Location: CONCESSION # 5 PROVIDE REPORT, Concession
# 7, Kitchen Ansul out of date since 2014!, Bistro Rm 1000,
Pass Fail N/A
FL NFPA 101 13
Floor 1
Chapter 8 Features of Fire
Protection
8.3.3.3 Fire doors shall be Unless otherwise specified, fire doors shall be self-closing or
self-closing (see photo 10.1, 10.2, automatic-closing in accordance with 7.2.1.8.
10.3)

Action Required: Replace, Repair or Adjust Door, Door closure


where door closes and Latches without assistance.
Location: West Exhibit Hall double doors leading to the outside2nd door from the right, West Exhibit Hall Exit Doors,
West Hall Center Doors Non functional doors with Cones in
front ( see Picture) East Hall Exit to Channelside and ashley
3rd door from Rt NON-Functional, East Exhibit Franklin Street
Emergency Exit door Non functional at street level and
Exhibit Level, Doors leading to PBX room, Ballroom Corridor
doors leading to main corridor near AV room, Fire Exit to
Platt Street Door non-functional 2nd door from Rt, Kitchen
Doors-Doors shall close and latch-Provide Magnetic Door
holders if necessary to keep open continuously. Parking
Garage South stair door non-functional Upper to
Lower.*********** MEETING ROOMS # 19, # 21, # 22, # 23,
West Exit Meeting room #10 , Meeting Rooms 12/13, # 16, #
24, # 25, Ball Room # D # C, # B, # A, Parking Garage Door
next to Diesel Storage.

Chapter 13 Existing
Assembly Occupancies

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 7 of 14

13.7.9.3.1 Excerpt: Every


Every room constituting an assembly occupancy and not having
room constituting an
fixed seats shall have the occupant load of the room posted in a
assembly occupancy and not conspicuous place near the main exit from the room.
having...
Action Required: Provide Signs in every assembly room
meeting the above criteria.
Location. All Meeting Rooms, All Ball Rooms, All Exhibit Halls,
All Conference Rooms......
Pass Fail N/A
CUSTOM
Floor 1
Square Footage - Check
101 Verify square footage.
Pass Fail N/A
NFPA 13 10
Floor 1
Chapter 6 System
Components and
Hardware

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 8 of 14

6.2.7.3 Excerpt: Cover


Cover plates used with concealed sprinklers shall be part of the
plates used with concealed listed sprinkler assembly.
sprinklers shall be part... (see
photo 11.1, 11.2, 11.3, 11.4, 11.5, 11.6,
6.2.7.1 : Plates, escutcheons, or other devices used to cover
11.7, 11.8, 11.9, 11.10, 11.11)
the...
Plates, escutcheons, or other devices used to cover the annular
space around a sprinkler shall be metallic or shall be listed for
use around a sprinkler.
6.2.6.3.1 : Ornamental finishes shall only be applied to
sprinklers and...
Ornamental finishes shall only be applied to sprinklers and, if
applicable, their concealed cover plates, by the sprinkler
manufacturer.`
Action Required: Where Painted, Missing or NON-UL Listed
Concealed covers are present, Replace with New Concealed
Covers.
Location: Concession # 5; LEVEL 4 EXEC OFFICES AND
MEETING ROOMS In front of meeting rooms 38/39,
Corridor In front of Room36, Mens Room, Corridor in Front of
Mens/ Womens Room, ******LEVEL 4 PAINTED,
MISSING OR NON-UL LISTED CONCEALED COVERS
PERVASIVE THROUGHOUT FLOOR***** 3RD LEVEL WEST
EXHIBIT
HALL, Mens / Womens rooms, CENTER EXHIBIT MEN'S
ROOM, EAST EXHIBIT WOMEN'S ROOM, East Hall Show
Office, EAST EXHIBIT Family restroom, MEN'S ROOM,
WOMEN'S ROOM, *****3RD LEVEL PERVASIVE
THROUGHOUT***** East Hall Women's Room, East Hall Men's
Room, East Hall Family Restroom, West Hall Family
Restroom, UPS Store, Cucina Rosa, Taste of YBOR, Room #
3066 Janitors Closet, Men's Room, Women.'s Room,
***** 2nd Level Riverwalk stairwell***** 1st LEVEL- A-D hall,
Rotunda, Marketing Office- Elec closet, 1st room on right;
Meeting Rooms- # 18, 19, 20, 21, 22, 23. West Exit Meeting
Rm 10, Mens Room, Womens Room, MEETING ROOMS
# 1,2,3,4,6,7,8,9,10, 11,13,16,17, Ballroom Corridor, ****** 1st
level PERVASIVE THROUGHOUT ****** Men's Room,
Women' Room, 1st Aid Room, Women's Restroom, Room # 24,
25, Family Restroom, Ball Room # D, # C, # B, # A, Ball
Room Meeting Room Corridor. Womens Room # 5 Janitor's
Closet,

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 9 of 14

Chapter 8 Installation
Requirements

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 10 of 14

8.1.1 Excerpt: The


requirements for spacing,
location, and position of
sprinklers... (see photo 12.1, 12.2,
12.3, 12.4, 12.5, 12.6, 12.7, 12.8, 12.9,
12.10, 12.11, 12.12, 12.13, 12.14, 12.15,
12.16)

The requirements for spacing, location, and position of


sprinklers shall be based on the following principles: (1)
Sprinklers shall be installed throughout the premises. (2)
Sprinklers shall be located so as not to exceed the maximum
protection area per sprinkler. (3) Sprinklers shall be positioned
and located so as to provide satisfactory performance with
respect to activation time and distribution. (4) Sprinklers shall
be permitted to be omitted from areas specifically allowed by
this standard. (5) When sprinklers are specifically tested and
test results demonstrate that deviations from clearance
requirements to structural members do not impair the ability of
the sprinkler to control or suppress a fire, their positioning and
locating in accordance with the test results shall be permitted.
(6) Clearance between sprinklers and ceilings exceeding the
maximums specified in this standard shall be permitted,
provided that tests or calculations demonstrate comparable
sensitivity and performance of the sprinklers to those installed
in conformance with these sections. (7) Furniture, such as
portable wardrobe units, cabinets, trophy cases, and similar
features not intended for occupancy, does not require sprinklers
to be installed in them. This type of feature shall be permitted to
be attached to the finished structure.
Action Required: Add, Adjust, Relocate or Remove Sprinkler
Coverage where required.
Location: OPERATIONS LEVEL - ******SPRINKLER
COVERAGE IS DEFICIENT SECONDARY TO WORK
COMPLETED WITHOUT REQUIRED PERMITS******* CREW
SUPERVISOR'S OFFICE, LINEN STORAGE, MENS
ROOMS- NO COVERAGE, WOMENS ROOM- NO
COVERAGE, ELECTRICAL CLOSET, IN RACK STORAGE,
OP 5
DECK OBSTRUCTION S/S HEAD ABOVE DUCT WORK,
BRIAN'S OFFICE, ENCLOSED STAIR STORAGE OPS/
DECK SECOND STAIRWELL,******* OPS LEVEL SHALL BE
ACCESSED BY LIC SPRINKLER CONTRACTOR TO
DETERMINE PROPER SPRINKLER COVERAGE********
Room 3098 East Hall Storage A/V Storage- Remove ACT or
Lower S/S Heads, Admin Office heads Too close,
Mechanical Level Heads too close, Mechanical Level Area H
Reposition Head, Aramark Liquor Storage No Coverage,
Room 1242 No Coverage, Smart City Office No Coverage,
KITCHEN Drink Cooler provide S/S coverage, Aramark
Operations Office closet no coverage, Chiller Plant Office No
Coverage, Ballroom Corridor Mech Rm 1012 no coverage,
Mens Restroom # 4 Janitors Closet No Coverage, Platt Street
Pump Room Storage Rm No Coverage, Meeting Rooms #
16, # 2, Room 1304 Sound Room Relocate obstructed by

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 11 of 14

HVAC.

8.16.5 Protection of Risers


Subject to Mechanical
Damage. (see photo 13.1)

Sprinkler risers subject to mechanical damage shall be


protected by steel posts, concrete barriers, or other approved
means.
Action Required: Provide protection for Supply Riser for Fire
Sprinkler System.
Location: Parking Garage/Retail Building.

Pass Fail N/A


NFPA 10 07
Floor 1
Chapter 6 Installation of
Portable Fire
Extinguishers
6.1.3.3.2 Excerpt: In large
rooms, and in certain
locations where visual...

In large rooms, and in certain locations where visual


obstructions cannot be completely avoided, means shall be
provided to indicate the extinguisher location.
Action Required: Provide Signs indicating location of fire
extinguisher where required.
Location East, Center and West Exhibit Halls.

6.2.1.2 Extinguisher
placement

Fire extinguishers shall be located so that the maximum travel


distances shall not exceed those specified in Table 6.2.1.1,
except as modified by 6.2.1.4. (See Annex E.)
7.1.2.1 Excerpt: A trained and certified person who has
undergone the...
A trained and certified person who has undergone the
instructions necessary to reliably perform maintenance and has
the manufacturer's service manual shall service the fire
extinguishers not more than 1 year apart, as outlined in Section
7.3.
Action Required: Replace Missing F/E or Provide Current
Inspection.

Location: Concession # 5 K and 2A10 BC, Air Handler # 28, 27


AND 25, Storage area "J", Cat Walk where required,
First Aid Office Hang and Out of Date, Concession # 7
"K" (Hang on Wall ) and 2A10 BC out of Date, UPS Store,
Aramark Sandwich Co, Cucina Rosa, Kitchen, So Side Retail,
Mechanical Rm (1012) Missing 2A10BC, Marketing
Office, Bistro Rm 1000,

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

Page 12 of 14

Inspector Comments: ***** Catwalk, Identify All Fire Department Connections, Use white reflective Tape *****
*****PROVIDE EXIT SIGNS ON CATWALK LEVEL; IDENTIFY DEAD-END CORRIDORS*****
***** PROVIDE DEFICIENT FREE FIRE ALARM, FIRE SPRINKLER, FIRE PUMP, STANDPIPE, LIFE
SAFETY GENERATOR AND KITCHEN ANSUL REPORTS*****
***** WITNESSED TRANSFER OF LIFE SAFETY GENERATOR TRANSFER TIME AND EMERGENCY
LIGHTING CIRCUITS*****
***** 2nd Level Exterior Patio Provide weather proof Fire Alarm Notification device. *****
***** All Roll-up Doors within Egress corridors shall be kept in the closed position*****
***** DOOR LEADING TO DIESEL STORAGE, MARK "DIESEL STORAGE" OR UNIVERSAL HAZMAT
SYMBOL*******

Inspector will return on or after 9/6/2016


All commercial establishments are subject to periodic fire code compliance inspections per City Code chapter 11-27. A fee is charged for
the fire code compliance inspection per City Code chapter 11-47. The amount due for the inspection is listed on the bottom of your
invoice.

If your inspection has deficiencies, a re-inspection is required. If you need more time or guidance to correct
the deficiencies, contact your inspector before the date of re-inspection so that the inspector can work
with you to bring your establishment into code compliance. If you have not corrected all of the deficiencies at
the time of your re-inspection, you will be charged a fee for the reinspection. The fee will be double the original
inspection fee. City code allows these additional charges. If up to a fourth re-inspection is required and the
deficiencies are not corrected, the fee will be double the re-inspection fee and you will be referred to code
enforcement.
If you have any questions, please contact the fire inspector listed at the top of this report.

Company
Representative:

Bill Sharpe Signature on file


2/16/2016

Inspector:
Richard Rodriguez
2/16/2016

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

1.1 - 10.4.1.
3.1 - 10.19.5.1.
4.1 - 11.1.7.6.
5.2 - 12.3.3.2.
5.4 - 12.3.3.2.
5.6 - 12.3.3.2.
5.8 - 12.3.3.2.
5.10 - 12.3.3.2.
5.12 - 12.3.3.2.
5.14 - 12.3.3.2.
5.16 - 12.3.3.2.
5.18 - 12.3.3.2.
5.20 - 12.3.3.2.
5.22 - 12.3.3.2.
5.24 - 12.3.3.2.
5.26 - 12.3.3.2.
5.28 - 12.3.3.2.
5.30 - 12.3.3.2.
6.2 - 13.3.3.3.
6.4 - 13.3.3.3.
6.6 - 13.3.3.3.
6.8 - 13.3.3.3.
6.10 - 13.3.3.3.
7.1 - 13.3.3.5.1.8.
7.3 - 13.3.3.5.1.8.
7.5 - 13.3.3.5.1.8.
8.1 - 14.4.1.
8.3 - 14.4.1.
8.5 - 14.4.1.
8.7 - 14.4.1.
8.9 - 14.4.1.
8.11 - 14.4.1.
9.1 - 14.6.3.
10.2 - 8.3.3.3.
11.1 - 6.2.7.3.
11.3 - 6.2.7.3.
11.5 - 6.2.7.3.
11.7 - 6.2.7.3.
11.9 - 6.2.7.3.
11.11 - 6.2.7.3.
12.2 - 8.1.1.
12.4 - 8.1.1.
12.6 - 8.1.1.
12.8 - 8.1.1.
12.10 - 8.1.1.
12.12 - 8.1.1.
12.14 - 8.1.1.

Page 13 of 14

Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file

2.1 - 10.19.3.2.
3.2 - 10.19.5.1.
5.1 - 12.3.3.2.
5.3 - 12.3.3.2.
5.5 - 12.3.3.2.
5.7 - 12.3.3.2.
5.9 - 12.3.3.2.
5.11 - 12.3.3.2.
5.13 - 12.3.3.2.
5.15 - 12.3.3.2.
5.17 - 12.3.3.2.
5.19 - 12.3.3.2.
5.21 - 12.3.3.2.
5.23 - 12.3.3.2.
5.25 - 12.3.3.2.
5.27 - 12.3.3.2.
5.29 - 12.3.3.2.
6.1 - 13.3.3.3.
6.3 - 13.3.3.3.
6.5 - 13.3.3.3.
6.7 - 13.3.3.3.
6.9 - 13.3.3.3.
6.11 - 13.3.3.3.
7.2 - 13.3.3.5.1.8.
7.4 - 13.3.3.5.1.8.
7.6 - 13.3.3.5.1.8.
8.2 - 14.4.1.
8.4 - 14.4.1.
8.6 - 14.4.1.
8.8 - 14.4.1.
8.10 - 14.4.1.
8.12 - 14.4.1.
10.1 - 8.3.3.3.
10.3 - 8.3.3.3.
11.2 - 6.2.7.3.
11.4 - 6.2.7.3.
11.6 - 6.2.7.3.
11.8 - 6.2.7.3.
11.10 - 6.2.7.3.
12.1 - 8.1.1.
12.3 - 8.1.1.
12.5 - 8.1.1.
12.7 - 8.1.1.
12.9 - 8.1.1.
12.11 - 8.1.1.
12.13 - 8.1.1.
12.15 - 8.1.1.

Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file
Picture on file

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016

Report

12.16 - 8.1.1.

Page 14 of 14

Picture on file

13.1 - 8.16.5.

Picture on file

http://mobile-eyes.com/MobileEyes3/TrackFire_Report_TabletReports.asp?Submit=Full+I... 5/26/2016