PD 1185

FIRE CODE OF THE PHILIPPINES


FIRE RESISTIVE RATING:
3 stories

1hr
4 stories or more

. 2hr

DISTANCE TO EXIT
From any point

. 15m in the room to exit door

WIDTH OF EXITS
..

0.71m min

DEAD END

. 6.00m max

HEADROOM (MEANS OF EGRESS)


Minimum headroom

2.30m
Floor ceiling projections

. 2.00m

WIDTH AND FLOOR LEVEL


Door in a doorway (min)

. 0.71m
Maximum width of doorway

1.22m

STAIRS
CLASS A Stairs
Width
Tread
Riser
Clear
Landing

1.12 m
0.25 m
0.19 m
2.00 m
2.75 m

CLASS B Stairs
Width
Tread
Riser
Clear
Landing

1.12 m
0.23 m
0.20 m
2.00 m
3.70 m

TREAD AND RISERS


Min number of risers

... 3 steps in one flight

GUARDS AND HANDRAIL


Height from nosing

. 0.76m 0.865m
Clearance from wall

.. 0.38m

SPACING OF RAILS

. 0.255m max

SPACING OF BALLUSTERS

.. 0.1525 apart

RAMPS
CLASS A
Width
Slope

1.12
8-10%

CLASS B
Width
Slope

0.76-1.12
10-17%

(Riser) when opening outside


0.25
1 steps is allowed
Height of panic hardware

... 0.76 1.12m


7 kilos to open
TURNSTILES
Height

0.91m
Width

. 0.56m
Revolving door

50% counted
as means of egress

CURB HEIGHTS
Stairs

. 0.76m
Floors

0.1525

SMOKE PROOF TOWER


Stairs in smoke proof tower
... 2hr fire resistance
open to a court

6.00m width
92 sqm (area)
Guards for balconies

.. 1.06 height
& vestibules

Access doorways

1.00m wide
from bldg to vestibule

CLASSIFICATION OF FIRE
CLASS A

ordinary combustible materials

For existing

.. 0.91m wide
CLASS B

flammable liquid and gas


CURVED STAIRS

. 7.5 max radius

CLASS C

energized electrical equipment


CLASS D

combustible metals

BRIDGES AND BALCONY

.. 1.12m width
3.0 sqm per person

DEFINITON OF TERMS
ESCALATOR AND MOVING WALKS
if 0.81 1 unit (width)
if 1.20 2 units (width)

FIRE ESCAPE ILLUMINATION

0.001 lumens

EMERGENCY LIGHTING

10 sec. Delay
for hour lighting

TRAVEL DISTANCE TO FIRE ESCAPE:

If not protected with fire protected

.. 46m
with automatic fire suppression

If protected with fire protected

. 61m
with automatic fire suppression

CLASSIFICATION OF HAZARD OF CONTENTS:


LOW Hazard Contents
low combustibility that no self propagating fire

Ordinary hazard contents


liable to burn with moderate rapidity

High Hazard Contents


liable to burn with extreme rapidity

AUTOMATIC FIRE SUPPRESSION SYSTEM


An integrated System of Underground or overhead piping or
both connected to a source of extinguishing agent or
medium and designed in accordance with fire protection
engineering standards which when actuated by its automatic
detecting device suppresses fire within the area protected.
COMBINATION STANDPIPE
Pipe line system filled with water and connected to a
constant water supply for the use of the service and the
occupants of the building solely for the use of the service
and the occupants of the building solely for fire suppression
purposes.
DRY STANDPIPE
A type of standpipe system in which the pipes are normally
not filled with water. Water is introduced into the system thru
Fire Service connections when needed.
FIRE ALERTING SYSTEM
A fire alarm system activated by the presence of a fire,
where the signal is transmitted to designated locations
instead of sounding a general alarm, in order to prevent
panic.
FIRE RESISTANCE RATING
The time duration that a material or construction can
withstand the effect of standard fire Test.

FIRE WALL
A wall designed to prevent the spread of fire, having a fire
resistance rating of not less that four (4) hours with sufficient
structural stability to remain standing even if construction on
either side collapse under fire conditions.
FLAME SPREAD RATING
The time in which flame will spread over the surface of a
burning material.
FLAME (FIRE) RETARDANT
Any compound, or mixture which when applied properly
improves the fire resistant quality of fabrics and other
materials like wood.
FUMIGANT
A gas, fume, or vapor used for the destruction or control of
insects, fungi, vermin, germs, rodents or other pests.
MEANS OF EGRESS
A continuous and unobstructed route or exit from any point
in a building, structure, or facility to a public way.
OCCUPANT LOAD
The maximum number of persons that may be allowed to
occupy a particular building, structure or facility or portions
thereof.
PANIC HARDWARE
A mechanical device consisting of linkages and a horizontal
bar across a door, which cause the door to open and
facilitates exit from a building, structure or facility.
PLENUM
An air compartment or chamber to which one or more ducts
are connected and which form part of an air distribution
system.