Professional Documents
Culture Documents
water pressure, and corrosion of sprinkler pipes, water tanks, sprinkler heads and others (Hall,
2009). For instance, on 15th October, 2004, a fire broke out in South Americas tallest
high-rise building, a 56-story government office building in Caracas, Venezuela. The fire
sprinkler system installed in the building was not functioning as required due to improper
maintenance. Furthermore, the system was disconnected to the alarm panel for monitoring.
This caused the fire alarm fail to detect the fire occurrence in the building (Moncada, 2005).
This scenario indicated that maintenance of automatic sprinkler system is important factor to
ensure that the fire sprinkler system is well functioning. Hence, this paper will review
objectives of this research on the factors that are affecting implementation of maintenance for
automatic fire sprinkler system and to illustrate how these factors could affect maintenance
performance of automatic fire sprinkler system.
According to Soh, (2000), the sprinkler system comprises of fire pumps, water storage tanks,
control valve sets, sprinkler heads, flow switches, pressure switches, pipe work, valves, water
supply, alarm gong and piping arrays (Puchovsky, 1997). All automatic fire sprinklers should
be in good working condition and if not so, should be replaced. They must free from dust,
grease, or paint, particularly on the heat-responsive element (Huggins, 2002). For instance,
sprinklers head that have coatings of paint, whitewash, excessive deposits, bronzing, or other
coating should be replaced by new sprinklers. Piping should be checked to ensure that it is in
good condition, free from mechanical damage and not being used to support fixtures, ladders,
or any other loads to prevent delayed of sprinkler response, an inoperable sprinkler head, or
system failure. Sprinkler pipe should also not suffer for corrosion and it must be properly
protected against corrosion (NFPA, 1981). Water-flow alarm devices should be tested
regularly along with the scheduled inspections of fire protection equipment. Main drain test
should be conducted annually according to the procedure established in NFPA 25. This test
provides a comparison with the original main drain test pressure values. It can be used to
detect deterioration in the system water supply (Huggins, 2002).
system in the high-rise building (Sherwin and Lees, 1980). For instance, nowadays, there are
not many people who can align the bearings and seals with the shaft in a pump (Sherwin,
2000). Due to that, maintenance manager need to carefully identify the person who can repair
the system. Different degree of knowledge could influence the performance of an automatic
fire sprinklers system which in turn affect the maintenance cost and frequency of failure.
Therefore, effort to increase skill and knowledge of maintenance personnel may improve the
performance of an automatic fire sprinkler system, reduce operation and maintenance cost for
corrective maintenance and increase the system availability (Dirickx and Kristner, 1979).
cannot be performed individually. Without good relationship of working team, the number of
equipment breakdown will subsequently increase. For instance, without teamwork, a
maintenance personnel will work individually thus, causing other individual personnel to
repeat the work. This situation leads to the increase the overhead and administrative cost for
maintenance works.
Stage 1: The problem area was identified as the failure of automatic fire sprinkler system.
Preliminarily data is an important step in the research process and can be gathered or
collected through literature survey. Literature survey is the documentation of a
comprehensive review for the published and unpublished work from secondary sources of
data and it is one way of summarizing secondary data (Sekaran, 2005).
Stage 2: During the preliminary study, problem statement and area of study were clearly
identified. In this research, literature finding was carried out after the general area of interest
and problem is identified in initial stage to set the parameters of this research. The relevant
data was collected from literature survey while the aims, objectives and scope of study were
formulated at these stages. Data gathering includes the questionnaire survey which was
Stage 3: The data of this research was collected from primary data and secondary data. The
primary data used are from the questionnaire survey. Secondary data includes books, websites,
journal, articles and others. The questionnaire survey was designed according to objectives of
this study. Researcher used self-constructed closed-ended questions survey for the study. The
closed-ended questions have a limited set of response categories and therefore it was easier
for the respondents to answer the questions. The closed-ended primary data were collected by
distributing questionnaire survey form to the target respondents in high-rise office building at
Petaling Jaya and Kuala Lumpur in order to achieve the research objectives. Three parameters
have been set up as limitation in this study which includes the height of the building (more
than 10 storeys), installed with an automatic fire sprinkler system and the built up area for the
building must be more than 50,000sf. 35 closed-ended questionnaires responses were
obtained during field data collection at Petaling Jaya and Kuala Lumpur.
Once all of the data were obtained, it was analyzed by using statistical method. Data analysis
is the phase that is important in interpreting findings. In order to achieve the objectives, the
data were analysed by using the Statistical Package for the social science (SPSS) software,
version 16.0. Cronbachs Alpha coefficient test is the most common method of checking on
the instrument used; it only allows a reading of more than 0.70 (Pallant, 1996). In this study
the reading of the test is 0.75 which indicates that the scale and data obtained is reliable.
Stage 4: This was the final stage of the research. This included the process of documentation
together with conclusion and future recommendation of the research. At this stage, all of the
relevant data were written up in the report.
2.
4.60
0.553
.065
-.340*
-.377*
.151
4.57
0.698
.172
-.297
-.315
.238
4.40
0.812
.220
-.332
-.415*
.298
4.40
0.881
.299
-.389
-.475
.196
3.71
1.100
.151
-.351
-.364
.226
Implementation of
planned maintenance
scheduled
3.
Frequency of building
maintenance
4.
Teamwork of
maintenance personnel
5.
Outsourcing of
maintenance work
Legend:
* Correlation is significance at 5 percent
** Correlation is significance at 1 percent
1: Ratio of actual maintenance cost to target maintenance cost
5.1 The effect of skill and knowledge of maintenance personnel in automatic fire
sprinkler performance: Skill and knowledge of maintenance personnel have significant
correlation with average numbers of breakdown maintenance works and average numbers of
complaints received. As mention by Chan, et al (2001), skill and knowledge plays important
roles in planning and revising the maintenance program. Maintenance personnel must have
their knowledge and skill to retain the fire sprinkler system in the building. For instance,
maintenance personnel must have clear understanding on the systems requirement, operation
and details of the system. Such knowledge is crucial for the maintenance personnel to reduce
an error to occur when they are conducting maintenance activities especially in high-rise
building. Sherwin (2000), in her Journal of Quality in maintenance engineering stated that
there are few people who can align the bearings and seals with the shaft in a pump nowadays.
This could affect the performance of an automatic fire sprinkler system in case it fails or
breakdown. Therefore, by increasing skills and knowledge of maintenance personnel may
improve the performance of an automatic fire sprinkler system through minimization of
failure (Dirikx and Kristner, 1979). Fewer complaints will be filed by the employees or the
occupants of the building if there were fewer breakdown or failure of the buildings services.
For instance, the employees or occupants may feel comfortable and satisfied if the building is
free from any breakdown and failure of its facilities such as leakage of fire sprinkler.
5.2 The effect of building maintenance frequency to the performance of automatic fire
sprinkler: Table 2 shows that frequencies of building maintenance have significant
correlation with the average complaints received. Tam et al. (2007) found that the
performance of equipment is affected by frequencies of planned maintenance. Frequency of
maintenance can be done daily, weekly, quarterly, annually and others. An appropriate
frequency for fire sprinkler maintenance is important as it can disclose its true status and early
action can be taken to prevent it from breakdown or failure. This statement is supported by Ito
Nakagawa (2000). Decrement of breakdown or failures can reduce the average numbers of
complaints lodged by employees or occupant in the building. For instance, the employees or
occupants may complaints if there is defect such as rusty of sprinkler head. Employees or
occupants may feel comfortable or satisfied if the building is free of breakdown or failure.
6.0 Conclusion
The result of this inferential analysis showed that the higher skill and knowledge of
maintenance personnel and frequencies of maintenance works may result in lowering the
number of breakdown of fire sprinklers system and this will reduce the number of complaints
received indirectly. It could be concluded that proper management of building maintenance is
vital to ensure the well functioning of fire sprinkler system.
References
Ali, A.S. (2008). Integrative mechanisms in the design process of building refurbishment
projects. Unpublished PhD thesis. UiTM Shah Alam, Malaysia
Al-Sultan, K.S. and Duffuaa, S.O., 1995. Maintenance control via mathematical programming.
Journal of Quality in Maintenance Engineering, 1(3): 36-46.
Alsyouf, I., 2006. Measuring maintenance performance using a balanced scorecard approach.
Journal of Quality in Maintenance Engineering. 12 (2): 133-149.
Berman, B. and Klefsjo, B., 2003. Quality: From Customer Needs to Customer Satisfaction,
2nd ed., Student literature: Lund.
Dirickx, Y.M.I. and Kistner, K.P., 1979. Reliability of a repairable system with redundant
units and preventive maintenance. IEEE Transactions on Reliability. 28(2): 170-1.
B.S. Dhillon, Y. Liu, 2006.Human error in maintenance: a review. Journal of Quality in
Maintenance Engineering. 12(1): 21-36
Hall, John R., January, 2009. U.S. Experience with Sprinklers and Other Fire Extinguishing
Equipment. Quincy, MA: National Fire protection Association.
Hinks, J. and McNay, P., 1999. The creation of a management-by-variance tool for facilities
management performance assessment. Facilities. 17(1/2): 31-53.
Ito, K. and Nakagawa, T., 2000. Optimum inspection policies for a storage system with
degradation at periodic tests. Math. Comput. Modeling. 31: 19-15
Lai, J.H.K., Yik, F.W.H. and Jones, P., 2004. Practices and performance of outsourced
operation and maintenance in commercial buildings, Proceedings of the CIBW70 2004 Hong
Kong International Symposium: Facilities Management and Maintenance, 7-8 December.
Hong Kong SAR, 357-67
Lewis, B., 1999. Facility Managers Operation and Maintenance Handbook. New York, NY:
McGraw-Hill. ONeill, J.G., 1982. Technology developments in automatic sprinkler system.
Plumbing Engineer. 10(6): 32-6.
Lee, R.H.K., Chan, K.T. and Burnett, J., 2001. Maintenance performance: a case study of
hospitality engineering systems. Facilities. 19(13/14): 494-503.
Mathew, S., 2004. Optimal inspection frequency. International Journal of Quality and
Reliability Management. 21(7): 763-771.
Moncada, J.A., March/April 2005, Fire spreads in South Americas tallest high-rise building
in Caracas, Venezuela, because its sprinkler system had not been properly tested or
maintained, Fire unchecked, Journal of NFPA. Pp. 46-52
National Fire Protection Association, September 1981. Fire Protection Handbook. Quincy,
Massachusetts: National Fire protection Association.
National Fire Protection Association, 2002. Automatic Sprinkler and other Water-Based Fire
Protection Systems. 8th ed. University of Maryland: Roland Huggins.
Nick Artim, September 1994. An introduction to Automatic Fire Sprinklers Part 1. WAAC.
16(3): 20.
Oakland, J., 1995. Total
Butterworth-Heinemann.
Quality
Management:
Text
With
Cases.
Oxford:
Oke, S.A. and Owaba, O.E.C., 2006. An approach for evaluating preventive maintenance
scheduling cost. International Journal of Quality & Realiblity Management. 23(7): 847-879.
Parida, A., 2007.Study and analysis of maintenance performance indicators (MPIs) for LKAB:
A case study. Journal of Quality Maintenance Engineering. 13(4):325-337
Puchovsky, M.T., 1997. Automatic sprinkler systems Handbook. 7thed. MA: National
Protection Association.
Fire
Ramachandran, G., 1999. Fire safety management and risk assessment. Facilities. 17: 363-7.
Reason, J., 2000. Cognitive Engineering in Aviation Domain. Mahwah, NJ: Lawrence
Erlbaum Associates.
Shabha, G., 2003. A low-cost maintenance approach to high-rise flats. Facilities. 21(13/14):
315-322.
Sherwin, D.J. and Lees, F.P., 1980. An investigation of the application of failure data analysis