Professional Documents
Culture Documents
TCE.M6-EL-GL-8166307
SECTION: TITLE
DESIGN GUIDE
FOR
SYSTEM NEUTRAL EARTHING
FLOPPY NO
FILE NAME
: TCE.M6-EL-FP-DOC-005
: M6-6307.DOC
REV.NO
R0
R1
R2
ISSUE
INITIALS
SIGN
INITIALS
SIGN
INITIALS
SIGN
PPD.BY
MNB
-Sd-
RRD
-Sd-
RRD
-Sd-
CKD.BY
DVM
-Sd-
BSK
-Sd-
BSK
-Sd-
APP.BY
VNM
-Sd-
UAK
-Sd-
UAK
-Sd-
DATE
76-04-02
98-09-08
INITIALS
SIGN
R2
99-05-14
FORM NO. 020R2
SECTION:
REV. STATUS
REV. NO.
DATE
DESCRIPTION
R1
1998-09-08
a)
b)
c)
Generally revised
R2
1999-05-14
ISSUE
R2
FORM NO. 020R2
SECTION: CONTENTS
CONTENTS
SL.NO.
TITLE
SH. NO.
1.0
SCOPE
2.0
3.0
RECOMMENDED PRACTICE
4.0
DISCUSSION
5.0
EQUIPMENT RATING
6.0
REFERENCES
TABLE 1
RECOMMENDED TYPES OF
SYSTEM EARTHING
10
TABLE 2
RECOMMENDED GENERATOR EARTHING
APPLICATIONS
12
ANNEXURE-1
SAMPLE CALCULATION OF GROUNDING TRF.
13
ANNEXURE-2
ARTIFICIAL GROUNDING METHODS
15
ANNEXURE-3
16
ISSUE
R2
FORM NO. 020R2
1.
SECTION: WRITE UP
SHEET 1
OF 16
SCOPE
This design guide covers methods of neutral earthing to be adopted
for various systems and incorporates calculations for earthing
equipment ratings.
2.
2.1
Effectively Earthed
A system earthed through an earthing connection of sufficiently low
impedance (inherent or intentionally added or both) such that ground
faults that may occur cannot build up voltages in excess of limits
established for apparatus circuits, or systems so earthed. The criteria
for meeting these requirements are
i)
ii)
2.2
R 0 < X1
X0 < 3X1 The coefficient of earthing (cl.2.8) of such systems
< 0.8
Where, R0= Zero sequence resistance of the system
X0= Zero sequence impedance of the system
X1= Positive sequence impedance of the system
Solidly Earthed
A system earthed through an adequate earth connection, in which no
impedance has been inserted intentionally, (i.e. a solid metallic
connection from system neutral to earth).
2.3
Unearthed
A system, circuit or apparatus without an intentional connection to
earth except through potential indicating or measuring devices or
other very high impedance devices.
2.4
ISSUE
R2
FORM NO. 020R2
2.5
SECTION: WRITE UP
SHEET 2
OF 16
2.6
Reactance Earthed
A system where a reactor is intentionally added into the system
earthing connection such that XO < 10X1.
2.7
2.8
Co-efficient of Earthing
Coefficient of earthing is the ratio ELG/ELL expressed as percentage of
the highest r.m.s. line to earth power frequency voltage ELG on a
sound phase at a selected location, during a fault to earth affecting
one or more phases, to the line to line power frequency voltage ELL
which would be obtained at the selected location, with the fault
removed.
3.0
RECOMMENDED PRACTICE
3.1
3.2
3.3
4.0
DISCUSSION
4.1
ISSUE
R2
FORM NO. 020R2
SECTION: WRITE UP
SHEET 3
OF 16
Generator Earthing
The maximum stress, which a generator is normally designed to
withstand, is that associated with the currents of a three phase fault at
the machine terminals. Because of relatively low zero sequence
impedance inherent in most synchronous machines, a solid line to
earth fault at machine terminals results in a machine winding current
higher than three phase fault current. Therefore, some impedance in
the generator neutral earthing is necessary.This impedance will be
used to limit the generator ground fault currents within the safe limits
as specified /recommended by the generator manufacturer.
4.3
4.3.1
When there are two or more major bus sections, each bus section
should have at least one earthed neutral point.
4.3.2
4.4
Artificial Grounding
Where one machine only is tied to a bus with feeders requiring a
permanent system earthing, generator neutral earthing of any type is
usually inadequate,as removal of the generator from service for any
reason also removes the only earth point. This also may be the case
with several machines on the bus where, for most economic
scheduling of generation or other reasons, all the generators on that
bus may at some time be shut down. In such cases, when generator
ISSUE
R2
FORM NO. 020R2
SECTION: WRITE UP
SHEET 4
OF 16
4.4.2
SECTION: WRITE UP
SHEET 5
OF 16
4.6
4.6.1
The typical levels of available earth fault current that can be expected
from various types of system earthing are as follows :
(a) Solidly earthed, Effectively : Same order of fault current as is
earthed, Earthed for serving available for the three phase short
line to neutral loads
circuit current (more than 60% of
three phase fault current)
(b) Reactance earthed
4.6.2
ISSUE
R2
FORM NO. 020R2
SECTION: WRITE UP
SHEET 6
4.7
4.7.1
4.7.2
4.7.3
OF 16
Arrester Application
4.8.1
4.8.2
4.8.3
4.8.4
4.8.5
ISSUE
R2
FORM NO. 020R2
4.9
SECTION: WRITE UP
SHEET 7
OF 16
5.0
EQUIPMENT RATING
5.1
Earthing Transformer
i)
Voltage - Line to Line voltage of the system
ii)
Reactance XET, Such that
(X0/X1) (System Line to Line voltage in kV)
3E
Ie = ---------------------------X1 + X2 + X0 + 3 Xep
Note : Where resistor/reactor is inserted between the neutral and the earth
connection the transformer should be rated to carry the required
current for rated time.
iv)
5.2
Earthing Resistance
5.2.1
High Resistance
The resistor is designed to dissipate kW equal to 1.5 times charging
kVA of distributed capacitance continuously. In calculating the
capacitance to earth, the important items are the machine winding
capacitance, the surge protective capacitors and the load carrying
power cable and surge suppressor capacitance for HT Motor feeders,
if used. The capacitance to earth of bus duct, lightning arrester and
ISSUE
R2
FORM NO. 020R2
SECTION: WRITE UP
SHEET 8
OF 16
P = 0.472V C for 50 Hz
Where V = Line to line voltage
C = Distributed capacitance to earth in
f N = Turns ratio of distribution
transformer
iii)
iii)
iv)
v)
5.2.2
Resistor
EL
R = --------3.I
EL.I
ohms, P = -------- Watts
3
ISSUE
R2
FORM NO. 020R2
SECTION: WRITE UP
SHEET 9
OF 16
5.3
Reactor
5.3.1
5.3.2
IE =
Note:
3E
-----------------------------------X1 + X2 + X0 + 3 (Xn + Xep)
For X1 of generators and synchronous motors use
subtransient reactance. For X2 of generators, synchronous
and induction motors, use transient reactance (X1, X2, X0 etc.
refer to source to point of fault reactances).
5.3.3
5.4
5.4.1
5.4.2
Current I = 3E/XCO
5.4.3
6.0
REFERENCES
6.1
for
Grounding
of
Industrial
6.2
6.3
IEEE Standard-2.
&
ISSUE
R2
FORM NO. 020R2
SECTION: TABLE
SHEET 10 OF 16
TABLE-I
Sl. System
No.
1.
Ref.
Fig.
Remarks
Industrial Plants
a) Upto 415V
2.
Recommended
Method of
Earthing
Solidly earthed
c) Above 11 kV
Solidly earthed
d) For
diesel High resistance
generator sets earthed
of
voltage
rating
above
415V
and
emergency DG
sets
of
all
voltages
e) For
diesel Solidly earthed
generator sets
of
voltage
rating of 415V
Power Plants
a) 415V Auxiliary
systems (New)
Solidly earthed
b) 415V Auxiliary
systems
(Extension)
c) Above 415V &
upto11 kV
SECTION: TABLE
SHEET 11 OF 16
3.
Synchronous
Generators
i) High
resistance
Earthed
Transmission
system
a)Effectively
earthed
b) Earth
fault
neutralize
r
5.
Artificial grounding
a) Solidly
earthed
b) Resistance
earthed
c) High
resistance
earthed
d) Reactance
earthed
is
ISSUE
R2
FORM NO. 020R2
TCE.M6-EL-GL-8166307
SECTION:ANNEXURE
SHEET 13 OF 16
ANNEXURE-1
CALCULATION OF SIZING OF GROUNDING TRANSFORMER FOR
PSEUDO GROUNDING FOR DELTA CONNECTED SYSTEM (3 NOS. OF
1
TRANSFORMERS)
System phase to phase voltage
= V Volts
=C
Micro farads/phase
IG = 1.5 * IC
-6
= 816.54 * 10 VC
Ampere
N = V/VS
Vod = 3VS
Volts
IS
Ampere
Ampere
RS = 3VS/ IS
= IO * N
-6
= 272.18 * 10 VCN
Ohms
2
Ohms
-3
kW
RS = 6364/(C * N )
Power rating of the resistor
PS = 3VSIS * 10
-6
PS = 0.471 * 10 CV
Rating of the transformer
= VSIS * 10
-3
-6
P = 0.272 * 10 CV
kW
kVA
kVA
TCE.M6-EL-GL-8166307
SECTION:ANNEXURE
SHEET 14 OF 16
ANNEXURE-1 CONTINUED
ISSUE
R2
FORM NO. 020R2
SECTION
ANNEXURE
SHEET
15 OF 16
TCE.MS-EL-GL-816-
6307
ANNEXURE-2
ARTI FICIAL GROUNDING
METHODS
N/ B
A
-
A
-
N/
cA
c-
B C
-s
N /
\-
cA
fl_.,
C
A
8 C
B
N
B C
6.
c
A
A
A
N/
-----
DISTRIBUTION
TRANSFORME R
B
N
fl
RESISTOR
A
B C
-s
N/ ,
\c-
c
-
HIGH RESISTANCE
RESISTOR
ISSUE
R2
TCE FORM 120 R1
TCE.MS-EL-GL-8166307
SECTION
TABLE
SHEET
12 OF 16
TABLE - II
SUMMARY OF GENERATOR GROUNDING APPLICATIONS
REACTOR
RESISTOR
GENERATOR
GROUNDING
METHOD
INHERANTLY HIGH
FAULT CURRENT
PERMITS USE OF
GROUNDED NEUTRAL
ARRESTORS IF
GENERATOR
SYSTEM
GENERAL
COMMENTS
Xo/X1 :!> 3.
LOW VOLTAGE
BUS OVER HEAD LOW
VOLTAGE FEEDERS
tLOW
VOLTAGE
BUS
CABLE FEEDERS
t-
PREFERRED.
GENERALLY NOT
APPLICABLE BUT MAY
USED IF SELECTIVE
RELAYING OF
MACHINES IS NOT
REQUIRED OR IF
SPECIAL RELAYING IS
USED TO OBTAIN
SEl..ECTM1Y.
DIRECT EXPOSURE
TO LIGHTNING.
GROUND CURRENT
FOR SELECTIVE
RELAYING REQUIRED.
SUFFICIANT
MACHINES TO
PROVIDE
PERMANENT
GROUND.
PREFERRED WHERE
LIGHTNING
EXPOSURE IS
SLIGHT
MAY BE PREFERRED.
FOR VERY LARGE
MACHINES BECAUSE
OF DESIRE TO
RESTRICT FAULT
CURRENT.
NOT SUITABLE
BECAUSE OF LACK
OF RELAYING
SELECTMTY.
PREFERRED
WHERE PRIMARY
OBJECTIVE IS TO
KEEP FAULT
CURRENT TO
MINIMUM.
NOT SUITABLE
BECAUSE OF LACK
OF RELAYING
SELECTMTY.
DOES NOT
PROVIDE
PERMANENT
GROUND
DOES NOT
PROVIDE
PERMANENT
GROUND.
DOES NOT
PROVIDE
PERMANENT
GROUND.
NO DIRECT
EXPOSURE TO
LIGHTNING.
NO SELECTIVE
RELAYING
REQUIRED.
SATISFACTORY
BUT HIGH
GROUND FAULT
CURRENT.
SATISFACTORY
BUT HIGH
GROUND FAULT
CURRENT.
PREFERRED.
NO DIRECT
EXPOSURE TO
LIGHTNING.
NO SELEC1l\IE
RELAYING IS
REQUIRED.
GENERATOR NEUTRAL
NEED NOT BE
GROUNDED IF AUTO
TRANSF. l""5
TERTIARY AND
REQUIRED WHERE
AUTO-TRANS. HAS
NO TERTIARY
GENERATOR AND
AUTO-TRANS
SHOULD BE
CONNECTED TO
COMMON GROUND
POINT.
IMPEDANCE
UNDESIRABLY
HIGH, IF USED
WITH AUTO-TRANS .
HAVING NO
TERTIARY.
IMPEDANCE
UNDESIRABLY
HIGH, IF USED
WITH AUTO-TRANS.
HAVING NO
TERTIARY .
PREFERRED WHERE
LIGHTNING
EXPOSURE SEVERE.
REQUIRED FOR 4
WIRE SYSTEMS.
PREFERRED WHERE
NO DIRECT
PRIMARY OBJECTIVE
EXPOSURE TO
IS TO KEEP
LIGHTNING.
GROUND CURRENT
DYNAMIC OVER
FOR SELECll\IE
VOLTAGE ON CABLE
RELAYING REQUIRED. NETWORK TO
SUFFICIENT MACHINES MINIMUM.
TO PROYIDE
PERMANENT GROUND.
DESIRABLE TO KEEP
DYNAMIC VOLTAGES
AS WELL AS FAULT
CURRENTS LOW.
t-
o-1t-o-
GROUND FAULT
CURRENT VERYLOW.
NO CURRENT FOR
SELEC1l\IE RELAYING
UNGROUNDEDNEUTRAi.. ARRESTERS
REQUIRED.
SATISFACTORY
EXPOSURE TO
BUT FAULT
LIGHTNING.
CURRENT HIGH.
GROUND CURRENT
FOR SELECTIVE
RELAYING REQUIRED.
CANNOT DEPEND ON
SINGLE MACHINE
MACHINE NElJTRAL
LOW VOLTAGE FEEDERS FOR PERMANENT
GROUND.
GENERATOR NEUTRAL
GROUNDING DESIRABLE
TO
DETECT MACHINE
FAULTS BEFORE
SYNCHRONISING
UNIT SSYTEM
GROUND FAULT
CURRENT RESTRICTED
TO THAT REQUIRED
FOR RELAYING
UNGROUNDEDNEUTRAL ARRESTERS
REQUIRED.
610 d
DISTR TRANS. WITH
SEC. RESISTOR
GROUNDING TRANSF.
PROVIDES PERMANENT
GROUND SOURCE
GROUND FAULT CURREN!
RESTRICTED TO THAT
REQUIRED FOR RELAYING
UNGROUNDED-NEUTRAL
ARRESTERS USUALLY
REQUIRED
PREFERRED IN
ADDmON TO
REACTOR OR
DISTRIBUTION
TRANSF. GROUNDING
OF GENERATOR
NEUTRAL
b. ""'
STEP UP THROUGH
AUTO TRANSFORMER
o--1
=
Xo/)(1S.10.
ISSUE
R2
TCE.M6-EL-GL-816- i----6307
s_E_C_T_lO_N_A_N 1
SYSTEM NEUTRAL EARTHING
SHEET
16 OF 16
ANNEXURE-3
NOTE:
1. EITHER 89N 1, OR 89N2 SHALL BE
OPEN TO AVOI D CIRCULATION OF
ZERO SEQUENCE CURRENTS
LOAD BREAK
SWITCH
89N1
89N2
RN
FIG.-1
RN - NEUTRAL RESISTOR
Rs - SECONDARY
LOADING RESISTOR
GENERATOR
TRANSFORMER
Rs
UAT
FIG.-2
ISSUE
R2