You are on page 1of 19

TATA CONSULTING ENGINEERS

TCE.M6-EL-GL-8166307

SECTION: TITLE

SHEET (i) OF (iii)

SYSTEM NEUTRAL EARTHING

DESIGN GUIDE
FOR
SYSTEM NEUTRAL EARTHING

TATA CONSULTING ENGINEERS


73/1, ST. MARKS ROAD
BANGALORE 560 001

FLOPPY NO
FILE NAME

: TCE.M6-EL-FP-DOC-005
: M6-6307.DOC

REV.NO

R0

R1

R2

ISSUE

INITIALS

SIGN

INITIALS

SIGN

INITIALS

SIGN

PPD.BY

MNB

-Sd-

RRD

-Sd-

RRD

-Sd-

CKD.BY

DVM

-Sd-

BSK

-Sd-

BSK

-Sd-

APP.BY

VNM

-Sd-

UAK

-Sd-

UAK

-Sd-

DATE

76-04-02

98-09-08

INITIALS

SIGN

R2

99-05-14
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SYSTEM NEUTRAL EARTHING

SECTION:
REV. STATUS

SHEET (ii) OF (iii)

REVISION STATUS SHEET

REV. NO.

DATE

DESCRIPTION

R1

1998-09-08

a)

Annexure-1 & 3 included

b)

rtificial grounding methods


designated as Annexure-2

c)

Generally revised

R2

1999-05-14

Table-I Sl.No. 1.d and 1.e revised


and a note is added in annexure-1

ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SECTION: CONTENTS

SHEET (iii) OF (iii)

SYSTEM NEUTRAL EARTHING

CONTENTS
SL.NO.

TITLE

SH. NO.

1.0

SCOPE

2.0

DEFINITION OF SYSTEM EARTHING

3.0

RECOMMENDED PRACTICE

4.0

DISCUSSION

5.0

EQUIPMENT RATING

6.0

REFERENCES

TABLE 1
RECOMMENDED TYPES OF
SYSTEM EARTHING

10

TABLE 2
RECOMMENDED GENERATOR EARTHING
APPLICATIONS

12

ANNEXURE-1
SAMPLE CALCULATION OF GROUNDING TRF.

13

ANNEXURE-2
ARTIFICIAL GROUNDING METHODS

15

ANNEXURE-3

16

ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

1.

SYSTEM NEUTRAL EARTHING

SECTION: WRITE UP

SHEET 1

OF 16

SCOPE
This design guide covers methods of neutral earthing to be adopted
for various systems and incorporates calculations for earthing
equipment ratings.

2.

DEFINITIONS OF SYSTEM EARTHING

2.1

Effectively Earthed
A system earthed through an earthing connection of sufficiently low
impedance (inherent or intentionally added or both) such that ground
faults that may occur cannot build up voltages in excess of limits
established for apparatus circuits, or systems so earthed. The criteria
for meeting these requirements are
i)

ii)

2.2

R 0 < X1
X0 < 3X1 The coefficient of earthing (cl.2.8) of such systems
< 0.8
Where, R0= Zero sequence resistance of the system
X0= Zero sequence impedance of the system
X1= Positive sequence impedance of the system

Solidly Earthed
A system earthed through an adequate earth connection, in which no
impedance has been inserted intentionally, (i.e. a solid metallic
connection from system neutral to earth).

2.3

Unearthed
A system, circuit or apparatus without an intentional connection to
earth except through potential indicating or measuring devices or
other very high impedance devices.

2.4

Medium Resistance Earthed


A system where a resistance is intentionally added into the system
earthing connection such that R0 2X0.

ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

2.5

SYSTEM NEUTRAL EARTHING

SECTION: WRITE UP

SHEET 2

OF 16

High Resistance Earthed


A system where nearly the highest permissible resistance is inserted
in the earthing connection such that R0 < XCO / 3,Where XCO is the
Zero sequence capacitive reactance of the system.

2.6

Reactance Earthed
A system where a reactor is intentionally added into the system
earthing connection such that XO < 10X1.

2.7

Earthed for Serving Line to Neutral loads


System so earthed that Z0 < Z1.

2.8

Co-efficient of Earthing
Coefficient of earthing is the ratio ELG/ELL expressed as percentage of
the highest r.m.s. line to earth power frequency voltage ELG on a
sound phase at a selected location, during a fault to earth affecting
one or more phases, to the line to line power frequency voltage ELL
which would be obtained at the selected location, with the fault
removed.

3.0

RECOMMENDED PRACTICE

3.1

It is necessary to provide system neutral earthing at each voltage


level except where a certain voltage level is intentionally kept
unearthed.

3.2

Recommended type of earthing for various systems is given in TableI.

3.3

Recommended generator earthing applications are given in Table-II.

4.0

DISCUSSION

4.1

Location of Earthing Connection


Earthing should normally be provided at the source end. This is
necessary because loads may consist of transformers with delta
primaries or delta connected motors and neutral point may not be
readily available. Also earthing at load end may result in wide

ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SYSTEM NEUTRAL EARTHING

SECTION: WRITE UP

SHEET 3

OF 16

variation in fault current depending upon system operating condition


and selective relaying may be difficult.
4.2

Generator Earthing
The maximum stress, which a generator is normally designed to
withstand, is that associated with the currents of a three phase fault at
the machine terminals. Because of relatively low zero sequence
impedance inherent in most synchronous machines, a solid line to
earth fault at machine terminals results in a machine winding current
higher than three phase fault current. Therefore, some impedance in
the generator neutral earthing is necessary.This impedance will be
used to limit the generator ground fault currents within the safe limits
as specified /recommended by the generator manufacturer.

4.3

Multiple Power Source

4.3.1

When there are two or more major bus sections, each bus section
should have at least one earthed neutral point.

4.3.2

When there are two or more generators,without the generator


transformers at one station, which operate in parallel, only one neutral
earthing resistor is some times used. Each power source is then
connected to the resistor through a neutral bus and neutral switching
equipment (preferably load break switch). It is desirable in such cases
to operate with only one generator neutral switch closed at a time to
eliminate any circulating harmonic or zero sequence currents (Refer
fig 1 in Annexure-3). In the case of multiple transformers all neutral
isolating devices may be normally closed because presence of delta
connected windings (which are nearly always present on at least one
side of each transformer) minimises circulation of harmonic current
between transformers.However,in the case of an emergency DG
set,normally they do not operate in parallel,in which case seperate
neutral grounding resistor is necessary for each generator.

4.4

Artificial Grounding
Where one machine only is tied to a bus with feeders requiring a
permanent system earthing, generator neutral earthing of any type is
usually inadequate,as removal of the generator from service for any
reason also removes the only earth point. This also may be the case
with several machines on the bus where, for most economic
scheduling of generation or other reasons, all the generators on that
bus may at some time be shut down. In such cases, when generator
ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SYSTEM NEUTRAL EARTHING

SECTION: WRITE UP

SHEET 4

OF 16

neutral is inaccessible and for delta connected systems, an earthing


transformer should be provided on the generator bus(one for each
bus section/island). Either a zig-zag or wye-delta transformer may be
used. These grounding transformers provide a low impedance path
for the flow of zero sequence currents associated with ground fault
conditions.The impedance of grounding transformer to a normal 3
phase current is high so that when no fault exists on the system, only
small magnetising current flows in the transformer winding.
4.4.1

Zig Zag Transformers


Zig Zag transformers provide a stable neutral point which makes them
suitable for grounding an isolated system neutral. A commonly used
zig-zag transformer is a 3 phase transformer without a secondary
winding. The neutral of this transformer is then connected solidly or
through a resistance or reactance to ground. For a given short time
rating, a zig-zag earthing transformer is somewhat lower in cost and
more frequently used.Zig Zag transformers with a star connected
secondary winding can be used as a grounding cum substation
transformer.

4.4.2

Wye-delta earthing transformer


Wye-delta Earthing Transformer is also used for obtaining a neutral
point for delta connected systems and it is usually recommended for
existing systems. A more readily available star/delta transformer of
adequate rating (probably in stock) may be used.
In case of single phase to ground fault on non effectively earthed
systems, earthing transformer used on delta side of power system
shall be either 3 nos. of single phase transformers used in star/open
delta formation with secondary loading resistor or a 3 phase earthing
transformer with 5 limbed construction. As far as possible single
phase earthing transformer should be recommended for this
application. In case adequate space is not available then 3 phase, 5limb transformer should be specified. For secondary resistor loaded
on open delta side of start/open delta earthing transformer,Power loss
shall be made equal to 1.5 times the system. capacitive kVAR with a
10% positive tolerance on the capacitance of the system. This will
form the basis for arriving at the rating of grounding transformer and
associated loading resistor(Refer Annexure-1 for sample sizing
calculations). Each phase of the high voltage winding (i.e. Primary)
shall be designed to continuously withstand the system phase-phase
voltage. The calculated max. Zero sequence current in each phase
ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SYSTEM NEUTRAL EARTHING

SECTION: WRITE UP

SHEET 5

OF 16

(both in primary as well as in secondary) shall be clearly specified


instead of specifying kVA rating of the transformer. It is recommended
that broken delta winding shall have only two terminals.
4.5

Parallel Operation of Transformers


When an earthed star/star transformer with delta tertiary is operated in
parallel with similar transformer with neutral unearthed, the rating of
the tertiary of the former should be checked for being adequate to
carry zero sequence current under fault condition. The usual 33%
rating of the tertiary winding may not be adequate.

4.6

Expected Earth Fault Currents

4.6.1

The typical levels of available earth fault current that can be expected
from various types of system earthing are as follows :
(a) Solidly earthed, Effectively : Same order of fault current as is
earthed, Earthed for serving available for the three phase short
line to neutral loads
circuit current (more than 60% of
three phase fault current)
(b) Reactance earthed

: Nearly as high as the three phase


shortcircuit current (25% to 60% of
3 phase
fault current)

(c) Medium resistance earthed : 50A to several thousand amperes


depending on the value of
resistance
(d) High resistance earthed

4.6.2

Upto 15A level (current through


resistor more than system charging
current)

The medium resistance method has the advantage of immediate and


selective clearing of the earthed circuit but requires that the minimum
earth fault current be large enough, usually 400A or more, to
positively actuate earth fault relay. High resistance earthing is a
method that can be applied to limit transient over voltages without
requiring to add earth fault relays to each circuit.

ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SYSTEM NEUTRAL EARTHING

SECTION: WRITE UP

SHEET 6

4.7

Criteria for Limiting Transient Over-voltages

4.7.1

In resistance earthed systems, the resistor earth fault current should


be at least equal to, but preferably greater than the capacitive
charging current of the system.

4.7.2

In reactance earthed system the ratio X0/X1 < 10 where X0 is the


zero sequence inductive reactance of the system including that of the
neutral reactor.

4.7.3

Where a combination of earthing transformer and neutral earthing


resistor is used, the earthing transformer impedance should be low
relative to the neutral resistance.

OF 16

R0/X0 2, where R0 and X0 are inclusive of neutral resistor and


earthing transformer.
4.8

Arrester Application

4.8.1

Arrester application discussed below is only to bring out arrester


ratings required with adoption of different methods of system neutral
earthing. For actual selection of arrester reference should be made to
TCE.M6-SY-G-LA-6702.

4.8.2

The minimum required arrester rating is the maximum operating


voltage times coefficient of earthing, which is 80% for effectively
earthed systems, and more than 80% for non-effectively earthed or
unearthed systems. The earth fault current in this case is more than
60% of three phase fault current.

4.8.3

Systems, which employ some form of resistance system earthing, are


non-effectively earthed system having coefficient of earthing of 100%
for arrester application purposes.

4.8.4

Many high voltage systems may exhibit coefficients of earthing as low


as 70% and certain multi-earthed distribution systems may be even
slightly less.

4.8.5

It may not be practicable to provide an earthing transformer of the size


and impedance necessary to achieve an X0/X1 ratio of 3 or less.
However, if the generator neutral is also earthed by means of a
suitable reactor, the earthed neutral type (80%) of arrester may be
applied at the machine terminals.

ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

4.9

SYSTEM NEUTRAL EARTHING

SECTION: WRITE UP

SHEET 7

OF 16

System earthing in case of generator circuit breakers


In case of generator system having a generator circuit breaker and if
the generator circuit breaker is open for some reason, the zone
between generator circuit breaker and generator transformer primary
will be left ungrounded. In such cases a star-star voltage transformer
with an open delta tertiary winding loaded with resistor should be
used.(Refer fig-2 in Annexure-3)

5.0

EQUIPMENT RATING

5.1

Earthing Transformer
i)
Voltage - Line to Line voltage of the system
ii)
Reactance XET, Such that
(X0/X1) (System Line to Line voltage in kV)

XET = -----------------------------------------------------------------(System Symmetrical 3 phase short circuit level in MVA)


iii)

Current - Maximum neutral current

3E
Ie = ---------------------------X1 + X2 + X0 + 3 Xep

E = Line to Neutral voltage


Xep = Reactance of earth return
path

Note : Where resistor/reactor is inserted between the neutral and the earth
connection the transformer should be rated to carry the required
current for rated time.
iv)

Time Continuous rated if it is wired for Alarm


--10 or 60 Seconds if it is wired for Trip depending upon
fault clearing time.

5.2

Earthing Resistance

5.2.1

High Resistance
The resistor is designed to dissipate kW equal to 1.5 times charging
kVA of distributed capacitance continuously. In calculating the
capacitance to earth, the important items are the machine winding
capacitance, the surge protective capacitors and the load carrying
power cable and surge suppressor capacitance for HT Motor feeders,
if used. The capacitance to earth of bus duct, lightning arrester and
ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SYSTEM NEUTRAL EARTHING

SECTION: WRITE UP

SHEET 8

OF 16

transformer low voltage windings is relatively small (1 or 2 percent of


the total) and need not be considered.
Resistance Value
a) For direct connection to Neutral
RN = 706/C ohms for 50 Hz
b) For connection to secondary of distribution transformer
2

Rs = 706/C.N ohms for 50 Hz


c) Resistor kW rating
2

P = 0.472V C for 50 Hz
Where V = Line to line voltage
C = Distributed capacitance to earth in
f N = Turns ratio of distribution
transformer
iii)

Temperature rise of grounding resistors shall be specified as


per IEEE-2

iii)

Distribution transformer Voltage rating :


HV : Standard rating near generator Line to Line voltage
LV : 240 Volts

iv)

Distribution transformer kVA rating :


3 X Resistor kW rating.

v)

5.2.2

Time : Continuous rated ,if it is wired for alarm


10 or 60 seconds, if it is wired for trip depending upon
fault clearing time
Medium Resistance : (Earth fault current equal to full load current-I
of largest feeder or machine).
i)

Resistor

EL
R = --------3.I

EL.I
ohms, P = -------- Watts
3
ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SECTION: WRITE UP

SHEET 9

SYSTEM NEUTRAL EARTHING

OF 16

Where, EL= Line to Line voltage


ii)

Time 10 or 60 seconds depending upon fault clearing time

5.3

Reactor

5.3.1

X 1 X0 X 1 = Generator positive sequence sub


Reactance Xn = ---------transient reactance
3
X0= Generator zero sequence reactance

5.3.2

Thermal Current Rating

IE =
Note:

3E
-----------------------------------X1 + X2 + X0 + 3 (Xn + Xep)
For X1 of generators and synchronous motors use
subtransient reactance. For X2 of generators, synchronous
and induction motors, use transient reactance (X1, X2, X0 etc.
refer to source to point of fault reactances).

5.3.3

Time 10 or 60 seconds depending upon fault clearing time.

5.4

Earth Fault Neutralizer

5.4.1

Voltage : Line to Neutral voltage

5.4.2

Current I = 3E/XCO

5.4.3

Time 10 or 60 seconds depending upon fault clearing time.

6.0

REFERENCES

6.1

IEEE Standard 142-1982 (Revision)

E = Line to neutral voltage


XCO = Zero sequence capacitive reactance per
phase

IEEE Recommended Practice


Commercial Power System.

for

Grounding

of

Industrial

6.2

CET 1941 A (Xerox 261b) Generator neutral grounding

6.3

IEEE Standard-2.

&

ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SYSTEM NEUTRAL EARTHING

SECTION: TABLE

SHEET 10 OF 16

TABLE-I
Sl. System
No.
1.

Ref.
Fig.

Remarks

Industrial Plants
a) Upto 415V

2.

Recommended
Method of
Earthing

Solidly earthed

Earth connector should be of


adequate capacity

b) Above 415V up Medium


to 11 kV
resistance
earthed

Limit earth fault current to


largest feeder current rating &
permit tripping of circuit

c) Above 11 kV

Solidly earthed

Earth connector should be of


adequate capacity

d) For
diesel High resistance
generator sets earthed
of
voltage
rating
above
415V
and
emergency DG
sets
of
all
voltages

High resistance grounding is


recommended for emergency
DG sets to enable continued
operation.

e) For
diesel Solidly earthed
generator sets
of
voltage
rating of 415V

Earth connector should be of


adequate capacity

Power Plants

Adequate earth fault current


helps to locate faults and
isolating the faulty section by
means of residually connected
earth fault relays or fuses.

a) 415V Auxiliary
systems (New)

Solidly earthed

b) 415V Auxiliary
systems
(Extension)
c) Above 415V &
upto11 kV

Retain the existing system of


earthing
High resistance
earthed

Limit earth fault current to 1.5


times
capacitive
charging
ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS


TCE.M6-EL-GL-8166307

SYSTEM NEUTRAL EARTHING

SECTION: TABLE

SHEET 11 OF 16

Current & permit tripping of the


circuit

3.

Synchronous
Generators

i) High
resistance
Earthed

Current limited to 1.5 times


capacitive
charging current
(usually distribution transformer
and secondary resistor)

a) Unit system &


TG rating up
to 120 MW
Or
b) General
ii) Reactor
machines and /
earthed
or feeders on
the bus & TG
rating
above
200 MW
4.

Transmission
system

Earth fault current to be limited


to 25%-60% of three phase
fault current to prevent serious
transient over voltages (X0 <
10X1) and permit selective
relaying

a)Effectively
earthed
b) Earth
fault
neutralize
r

5.

Artificial grounding

a) Solidly
earthed
b) Resistance
earthed
c) High
resistance
earthed
d) Reactance
earthed

When it is desired to limit the


earth fault current and to
reduce switching surges to safe
value.
1
2
3

When generator neutral


inaccessible or for
Delta connected systems.

is

ISSUE
R2
FORM NO. 020R2

TCE.M6-EL-GL-8166307

TATA CONSULTING ENGINEERS

SECTION:ANNEXURE

SYSTEM NEUTRAL EARTHING

SHEET 13 OF 16

ANNEXURE-1
CALCULATION OF SIZING OF GROUNDING TRANSFORMER FOR
PSEUDO GROUNDING FOR DELTA CONNECTED SYSTEM (3 NOS. OF
1
TRANSFORMERS)
System phase to phase voltage

= V Volts

System phase to earth capacitance


(Value of `C shall be inclusive of
10% +ve tolerance)

=C

Micro farads/phase

Capacitive charging current

IC = 3V/XC ,Where, XC = 1/2fC


= 3V2fC
-6
= 544.36 * 10 VC
Ampere

Required resistive current

IG = 1.5 * IC
-6
= 816.54 * 10 VC

Ampere

Zero sequence earth fault current/phase IO = IG/ 3 (Refer Fig-1) Ampere


-6
= 272.18 * 10 VC
Ampere
Grounding transformer voltage ratio
Voltage across Open Delta during

N = V/VS

Phase to ground fault

Vod = 3VS

Volts

Required secondary current

IS

Ampere
Ampere

Value of resistance across Open-Delta

RS = 3VS/ IS

= IO * N
-6
= 272.18 * 10 VCN

Ohms
2

Ohms

-3

kW

RS = 6364/(C * N )
Power rating of the resistor

PS = 3VSIS * 10
-6

PS = 0.471 * 10 CV
Rating of the transformer

= VSIS * 10

-3
-6

P = 0.272 * 10 CV

kW
kVA

kVA

Note : Where value of C ie system to earth capacitance also includes


capacitance of cables, surge suppressor capacitance for HT motor
feeders, if any.
ISSUE
R2
FORM NO. 020R2

TCE.M6-EL-GL-8166307

TATA CONSULTING ENGINEERS

SECTION:ANNEXURE

SYSTEM NEUTRAL EARTHING

SHEET 14 OF 16

ANNEXURE-1 CONTINUED

ISSUE
R2
FORM NO. 020R2

TATA CONSULTING ENGINEERS

SECTION

ANNEXURE

SHEET

15 OF 16

TCE.MS-EL-GL-816-

6307

SYSTEM NEUTRAL EARTHING

ANNEXURE-2
ARTI FICIAL GROUNDING

METHODS

N/ B

A
-

A
-

N/

cA

c-

B C

-s

N /

\-

cA

fl_.,

C
A

8 C

B
N

B C

6.

c
A

A
A

N/

-----

DISTRIBUTION
TRANSFORME R

B
N

fl

RESISTOR
A

B C

-s

N/ ,

\c-

c
-

HIGH RESISTANCE
RESISTOR

ISSUE

R2
TCE FORM 120 R1

TATA CONSULTING ENGINEERS

TCE.MS-EL-GL-8166307

SYSTEM NEUTRAL EARTHING

SECTION

TABLE

SHEET

12 OF 16

TABLE - II
SUMMARY OF GENERATOR GROUNDING APPLICATIONS
REACTOR

RESISTOR

GENERATOR
GROUNDING
METHOD

INHERANTLY HIGH
FAULT CURRENT
PERMITS USE OF
GROUNDED NEUTRAL
ARRESTORS IF

GENERATOR
SYSTEM

GENERAL
COMMENTS

Xo/X1 :!> 3.

LOW VOLTAGE BUS NO DIRECT


NO LOW VOLTAGE
FEEDERS

LOW VOLTAGE
BUS OVER HEAD LOW
VOLTAGE FEEDERS

tLOW

VOLTAGE
BUS

CABLE FEEDERS

t-

PREFERRED.

GENERALLY NOT
APPLICABLE BUT MAY
USED IF SELECTIVE
RELAYING OF
MACHINES IS NOT
REQUIRED OR IF
SPECIAL RELAYING IS
USED TO OBTAIN
SEl..ECTM1Y.

DIRECT EXPOSURE
TO LIGHTNING.
GROUND CURRENT
FOR SELECTIVE
RELAYING REQUIRED.
SUFFICIANT
MACHINES TO
PROVIDE
PERMANENT
GROUND.

PREFERRED WHERE
LIGHTNING
EXPOSURE IS
SLIGHT
MAY BE PREFERRED.
FOR VERY LARGE
MACHINES BECAUSE
OF DESIRE TO
RESTRICT FAULT
CURRENT.

NOT SUITABLE
BECAUSE OF LACK
OF RELAYING
SELECTMTY.

PREFERRED
WHERE PRIMARY
OBJECTIVE IS TO
KEEP FAULT
CURRENT TO
MINIMUM.

NOT SUITABLE
BECAUSE OF LACK
OF RELAYING
SELECTMTY.

DOES NOT
PROVIDE
PERMANENT
GROUND

DOES NOT
PROVIDE
PERMANENT
GROUND.

DOES NOT
PROVIDE
PERMANENT
GROUND.

NO DIRECT
EXPOSURE TO
LIGHTNING.
NO SELECTIVE
RELAYING
REQUIRED.

SATISFACTORY
BUT HIGH
GROUND FAULT
CURRENT.

SATISFACTORY
BUT HIGH
GROUND FAULT
CURRENT.

PREFERRED.

NO DIRECT
EXPOSURE TO
LIGHTNING.
NO SELEC1l\IE
RELAYING IS
REQUIRED.
GENERATOR NEUTRAL
NEED NOT BE
GROUNDED IF AUTO
TRANSF. l""5
TERTIARY AND

REQUIRED WHERE
AUTO-TRANS. HAS
NO TERTIARY
GENERATOR AND
AUTO-TRANS
SHOULD BE
CONNECTED TO
COMMON GROUND
POINT.

IMPEDANCE
UNDESIRABLY
HIGH, IF USED
WITH AUTO-TRANS .
HAVING NO
TERTIARY.

IMPEDANCE
UNDESIRABLY
HIGH, IF USED
WITH AUTO-TRANS.
HAVING NO
TERTIARY .

PREFERRED WHERE
LIGHTNING
EXPOSURE SEVERE.
REQUIRED FOR 4
WIRE SYSTEMS.

PREFERRED WHERE
NO DIRECT
PRIMARY OBJECTIVE
EXPOSURE TO
IS TO KEEP
LIGHTNING.
GROUND CURRENT
DYNAMIC OVER
FOR SELECll\IE
VOLTAGE ON CABLE
RELAYING REQUIRED. NETWORK TO
SUFFICIENT MACHINES MINIMUM.
TO PROYIDE
PERMANENT GROUND.
DESIRABLE TO KEEP
DYNAMIC VOLTAGES
AS WELL AS FAULT
CURRENTS LOW.

t-

o-1t-o-

GROUND FAULT
CURRENT VERYLOW.
NO CURRENT FOR
SELEC1l\IE RELAYING
UNGROUNDEDNEUTRAi.. ARRESTERS
REQUIRED.

SATISFACTORY
EXPOSURE TO
BUT FAULT
LIGHTNING.
CURRENT HIGH.
GROUND CURRENT
FOR SELECTIVE
RELAYING REQUIRED.

CANNOT DEPEND ON
SINGLE MACHINE
MACHINE NElJTRAL
LOW VOLTAGE FEEDERS FOR PERMANENT
GROUND.
GENERATOR NEUTRAL
GROUNDING DESIRABLE
TO
DETECT MACHINE
FAULTS BEFORE
SYNCHRONISING

UNIT SSYTEM

GROUND FAULT
CURRENT RESTRICTED
TO THAT REQUIRED
FOR RELAYING
UNGROUNDEDNEUTRAL ARRESTERS
REQUIRED.

610 d
DISTR TRANS. WITH
SEC. RESISTOR

GROUNDING TRANSF.

PROVIDES PERMANENT
GROUND SOURCE
GROUND FAULT CURREN!
RESTRICTED TO THAT
REQUIRED FOR RELAYING
UNGROUNDED-NEUTRAL
ARRESTERS USUALLY
REQUIRED

PREFERRED IN
ADDmON TO
REACTOR OR
DISTRIBUTION
TRANSF. GROUNDING
OF GENERATOR
NEUTRAL

b. ""'

STEP UP THROUGH
AUTO TRANSFORMER

o--1
=

Xo/)(1S.10.

ISSUE

R2

TCE.M6-EL-GL-816- i----6307

s_E_C_T_lO_N_A_N 1
SYSTEM NEUTRAL EARTHING

SHEET

16 OF 16

ANNEXURE-3

NOTE:
1. EITHER 89N 1, OR 89N2 SHALL BE
OPEN TO AVOI D CIRCULATION OF
ZERO SEQUENCE CURRENTS
LOAD BREAK
SWITCH

89N1

THROUGH GENERATOR WINDINGS.

89N2

RN

FIG.-1

RN - NEUTRAL RESISTOR
Rs - SECONDARY
LOADING RESISTOR

GENERATOR
TRANSFORMER
Rs

UAT

FIG.-2

ISSUE

R2

You might also like