These pages cover the current Inverter product range.
They also cover the ARY60U, ARY54U Single and AOY19/24F/U Multi Systems.
Trouble Shooting
Models with Wireless Controllers Trouble Shooting from the Indoor Unit
Wall Mounted Single Systems ASY, ASYA & ASYB
Includes AWYZ Nokria Models
Red Light
Operation
Green Light
Timer
Current Models
Off
Off
Off
Off
Off
2 Flashes
2 Flashes
2 Flashes
2 Flashes
3 Flashes
3 Flashes
3 Flashes
3 Flashes
3 Flashes
4 Flashes
4 Flashes
4 Flashes
4 Flashes
4 Flashes
5 Flashes
5 Flashes
5 Flashes
5 Flashes
6 Flashes
6 Flashes
7 Flashes
7 Flashes
7 Flashes
7 Flashes
7 Flashes
8 Flashes
8 Flashes
8 Flashes
Blinking
2 Flashes
3 Flashes
4 Flashes
5 Flashes
8 Flashes
2 Flashes
3 Flashes
4 Flashes
6 Flashes
2 Flashes
3 Flashes
4 Flashes
7 Flashes
8 Flashes
2 Flashes
3 Flashes
4 Flashes
7 Flashes
8 Flashes
2 Flashes
3 Flashes
5 Flashes
6 Flashes
2 Flashes
3 Flashes
2 Flashes
3 Flashes
4 Flashes
5 Flashes
6 Flashes
2 Flashes
3 Flashes
4 Flashes
Blinking
On
On
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
2 Pulses
2 Pulses
3 Pulses
3 Pulses
4 Pulses
5 Pulses
5 Pulses
6 Pulses
Slow Blink
Blinks
Blinks
2 Pulses
3 Pulses
4 Pulses
4 Pulses
5 Pulses
5 Pulses
6 Pulses
7 Pulses
9 Pulses
10 Pulses
11 Pulses
12 Pulses
13 Pulses
14 Pulses
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Slow Blink
Off
Blinks
Off
Off
Off
Blinks
Off
Blinks
Off
Off
Off
Off
Off
Off
Off
Off
Off
Blinks
Off
Blinks
Off
Off
Blinks
Off
Normal
Test
ID PCB Fail
OD PCB Fail
OD Power Connection Failure
OD Unit Pipe Sensor Fail
OD Unit Air Sensor Fail
OD Unit Air Sensor Short
OD Unit Disch Sensor Fail
OD Unit Disch Sensor Short
High Pressure
High Discharge or Compressor Temp
OD Unit Compressor Temp Sensor
IPM Error
CT Error
AFM Filter Error
Compressor Error
OD Fan Motor Fail
Air Sensor Open
Air Sensor Closed
Pipe Sensor Open
Pipe Sensor Closed
Drain Problem
Communication Error
OD PCB or Wiring Error
Indoor Fan Failure
Meaning
ID Sensor Failure
ID Sensor Failure
ID Control Error
ID Control Error
Comms Failure
Comms Failure
ID Fan Failure
ID Fan Failure
OD Thermistor Fail
OD Thermistor Fail
OD Thermistor Fail
OD Thermistor Fail
OD Thermistor Fail
OD Thermistor Fail
Pressure Switch
ID Units Incorrect
Inverter Failure
Inverter Failure
Red
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
2 Flashes
4 Flashes
6 Flashes
8 Flashes
9 Flashes
10 Flashes
2 Flashes
2 Flashes
2 Flashes
5 Flashes
Green
2 Flashes
3 Flashes
2 Flashes
4 Flashes
2 Flashes
3 Flashes
2 Flashes
3 Flashes
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Blinks
Meaning
ID Air Sensor
ID Pipe Sensor
Manual Auto Button Error
Power Source Failure
Reverse Comms Failure
Forward Comms Failure
Motor locked
Motor RPM Incorrect
OD Discharge Sensor Fail
OD Pipe Sensor Fail
OD Air Sensor Fail
Compressor Temp Sensor Fail
2 Way Valve Sensor Fail
3 Way Valve Sensor Fail
Pressure Switch
Incorrect Indoor Unit Index
IPM Failure
Compressor Failure
www.climatecenter.co.uk
ID to RC Comms Fail
ID to OD Comms Fail
ID Air Sensor Open
ID Air Sensor Close
ID Pipe Sensor Open
ID Pipe Sensor Close
OD Pipe Sensor Fail
Power Source Connection Failure
Drain Problem Float switch operated
OD Air Sensor Fail
Discharge sensor Fail
Outdoor High Pressure Heatsink error
OD PCB Fail
ID Fan Fail
OD Signal Abnormal ID signal error
OD EEPROM Fail
Compressor Temp Failure
Pressure Switch Error
IPM Error
CT Error
Active Filter Module Error
Compressor Failure
OD Fan Failure
Inverter to PCB Comms Fail
2 Way Valve sensor Fail
Expansion Valve Error
Connection ID Unit Error
Indoor manual switch abnormal
Excessive high pressure protection on cooling
25
26
27
28
29
2A
2B
2C
To Interrogate
When E:EE is displayed switch unit off and press the temp up and temp down
buttons simultaneously for 3 seconds.
To Return to Normal Operation
Press Temp Up and Temp Down Buttons together for 3 seconds.
To Initiate Test Operation
Switch Unit Off & Press Master & Fan Buttons together for 3 seconds.
Press Start/Stop to Initiate.
Changing the Sensor Position
The unit can sense the air temperature at the unit or controller
Turn Unit Off
To change press THERMOSENSOR button for 5 seconds to unlock
Toggle the THERMOSENSOR button & controller is displayed
Set to desired setting (unit or controller)
Press THERMOSENSOR button for 5 seconds to lock
Two Handsets/1 Unit set on RC DIP SWs
Single handset DIP SW1 is On & 2 is Off
Dual Handset Master Both On & Slave both Off
Group Control up to 16 Unit from 1 RC Handset
Set DIP SW3 on RC to ON
Set Each ID Unit Rotary SW to Unit Address (0-15) in series
Auto Restart on Power Failure
DIP SW2-3 on ID Unit. Off is autorestart (std)/On is Manual Restart
Auto Changeover
DIP SW5 on RC. On is autochangeover (std)/Off is Manual
Memory Retention on Power Failure
Dip SW6 on RC. On is Memory/Off is no memory
OD PCB LED
Pulses
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Slow Blink
Models 9-30
Comms Failure
Disch Sensor Fail
Pipe Sensor Fail
Air Sensor Fail
2 Way Valve Sensor
3 Way Valve Sensor
Compressor Thermistor
Pressure Switch
Indoor Comms Error
Current Trip
CT Fail
Compressor Position Fail
Compressor Start Fail
Timer Failure
Models 36-54
Comms Failure
Disch Sensor Fail
Pipe Sensor Fail
Air Sensor Fail
Compressor Thermistor
Heatsink Sensor Fail
Pressure Switch
LED 1
LED 2
Blinks
1 Pulse
2 Pulses
3 Pulses
4 Pulses
5 Pulses
6 Pulses
7 Pulses
8 Pulses
9 Pulses
10 Pulses
Blinks
Lift
Lift
Lit
Lit
Lit
Lit
Lit
Lit
Lit
Lit
OD PCB Fail
Power Source Failure
OD Disch Temp Sensor
OD Pipe Sensor
OD Air Sensor
Comms Failure
Indoor Unit Error
High Discharge Temp
High Pressure
Compressor Temp Abnormal
Compressor Temp Sensor Fail
IPM Error
Compressor Position Fail
Compressor Start Fail
OD Upper Fan Fail
OD Lower Fan Fail
Protect Operation
Interconnecting Wiring
This has 4 LEDs A,B, C & D to denote which circuit has the fault
Up to 8 flashes - faults are identical to above 9-30 Single System
This has 4 LEDs A,B, C & D to denote which circuit has the fault
Up to 8 flashes - faults are identical to above 9-30 Single System
9
10
11
12
13
14
15
16
17
Pressure Switch A
Pressure Switch B
Indoor Unit Indexing Problem
IPM Fail
Compressor Position Fail
Compressor Fail
OD Fan Upper Fail
OD Fan Lower Fail
PCB Fail
www.climatecenter.co.uk
CO Multis
HP Multis
AOY90T
ALL OTHERS
Live
2
1
3
1 or L
Neutral
1
2
2
2 or N
Comms
3
3
1
3
Trouble Shooting
Outdoor Unit
Indoor Unit
Controller
Wiring
EE:EE on LCDhandset
fault diagnostics see over
Trouble Shooting
ASY7-12A
Wire
Earth
Neutral
Comp+Fan
Unused
Unused
Unused
Unused
Unused
Unused
ASY7-12R
Earth
Neutral
Comp
Unused
Unused
Rev Valve
OD Fan
Unused
Unused
ASY13PS
Earth
Neutral
Line to OD
Unused
Unused
Signal
Unused
Unused
Unused
Earth
Unused
Unused
Neutral
Comp+Fan
Unused
Unused
Unused
Unused
ASY17-30A
Earth
Unused
Unused
Live to In
Neutral
Comp+Fan
Unused
Unused
Unused
Earth
Unused
Unused
Neutral
Comp
Rev Valve
OD Fan
Unused
Unused
Earth
Unused
Unused
Neutral
Comp
Fan Hi
Rev Valve
Fan Low
Unused
AUY12-18AG
Earth
Unused
Unused
Neutral
Comp
Fan Hi
Fan Low
Unused
Unused
AUY12-18RG
Earth
Unused
Unused
Neutral
Comp
Fan Hi
Rev Valve
Fan Low
Unused
Earth
Unused
Unused
Comp
Neutral
Live to In
Unused
Unused
Unused
Earth
Unused
Unused
Signal
Neutral
Live to In
Unused
Unused
Unused
Technical Support:
08705 218218
www.climatecenter.co.uk
Code
Fault
Diagnosis
E:0
E:01
E:02
E:03
E:04
E:05
E:06
E:07
E:08
E:09
E:0A
E:0C
E:0D
E:0F
E:11
E:12
E:13
E:14
Model Abnormal
Indoor Fan Failure
O/D Signal Abnormal
Outdoor PCB Fail
Fault
LED1
Signal Failure
Indoor Unit Failure
Discharge Sensor Fail
O/D Pipe Sensor Fail
O/D Air Sensor Fail
Power Source Error
PCB
PCBFailure
High Pressure Trip
Discharge Temp Trip
LED2
LED3
LED4
LED5
LED6
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
Flash
All Flashing Very Rapidly
Flash
Flash
Flash
Flash
Flash
Unit
Code Means:-
Red
Green
Yellow
All
All
All
All
All
D,E,F
All
G
A,B,G
D,E,F
E,F
C
D,E,F
E,F
D,E,F
F
G
B,E,F
F
C
F OD
F OD
F OD
F OD
F
F
F
F
Power On
Timer Mode
Louvre On
HP Defrost Cont.
Test
Power Fail
PCB Failure
Room Sensor Fault
Sensor Fault
Room Sensor Open/Fail
Room Sensor Short
Room Sensor Fault
Pipe Sensor Open
Pipe Sensor Short
High Water
Comms Failure
High Water
Fan Failure
3ph Reversal
Pipe Sensor Fault
Pipe Sensor Open
Pipe Sensor Short
Temp Sensor Open
Temp Sensor Short
Discharge Sensor Open
Discharge Sensor Short
High/Low Pressure
High Discharge Temp
On
On
On
Long pulses
Cont. Pulse
On
Cont. Short Pulse
1 Short Pulse
2 Short Pulses
2 Short Pulses
2 Short Pulses
3 Short Pulses
3 Short Pulses
3 Short Pulses
4 Short Pulses
5 Short Pulses
6 Short Pulses
6 Short Pulses
Rapid Pulse
Long Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse 7
Off
On
On or Off
Off
Cont. Pulse
Cont Long
Cont. Short Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Long Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
Rapid Pulse
2 Short Pulses
3 Short Pulses
3 Short Pulses
3 Short Pulses
4 Short
4 Short Pulses
5 Short Pulses
5 Short Pulses
6 Short Pulses
Short Pulses
Off
Off
On
Off
Off
Pulses Off
Off
Off
Off
Off
Rapid Pulse
Off
Off
Rapid Pulse
Off
Off
Off
Off
Off
Off
Off
Rapid Pulse
Pulses Off
Rapid Pulse
Off
Rapid Pulse
Off
Off
www.climatecenter.co.uk
At 10C
At 20C
At 30C
20K Ohms
103K Ohms
10K Ohms
646K Ohms
13K Ohms
63K Ohms
6K Ohms
395K Ohms
8K Ohms
40K Ohms
4K Ohms
250K Ohms
Trouble Shooting