Small Packaged Products

Electric Cooling and Heat Pump Units


Unit Sizes 018-060
Accessory Electric Heat and Single Point Box
50/60 Hz
Cancels: IIK 555A-18-27

IIK 555A-18-31
6/1/97

Installation Instructions
Part Numbers: CPHEATER001A00 thru CPHEATER020A00
CONTENTS
Page
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-20
Heater Installation (Horizontal Airflow
Configuration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Heater Installation (Vertical Airflow
Configuration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
High-Voltage Connection to Unit . . . . . . . . . . . . . . 4
WIRING HEATER SEPARATE FROM BASE UNIT
WIRING HEATER AS A SINGLE POINT POWER
CONNECTION
ADJUST THERMOSTAT . . . . . . . . . . . . . . . . . . . . . . 20
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

SAFETY CONSIDERATIONS
Installing and servicing air-conditioning equipment can be
hazardous due to system pressure and electrical components. Only trained personnel should install or service airconditioning equipment.
When working on air-conditioning equipment, observe precautions in the literature and on tags and labels attached
to unit. All electrical wiring should be done by a licensed
electrician.
Follow all safety codes. Wear safety glasses and work gloves.
Have a fire extinguisher available.

Before performing service or maintenance operations on


system, turn off all main power switches. There may be
more than one disconnect. Turn off accessory heater power
switch if applicable. Electrical shock can cause personal injury. TAG DISCONNECT SWITCH(ES) WITH
A SUITABLE WARNING LABEL.

GENERAL
These instructions cover the installation of field-installed
accessory electric heater packages for Electric Cooling Units
and Heat Pumps. Accessory electric heater packages are available from 5 to 20 kW. Consult Table 1 and Fig. 1 for package contents.

Table 1 Accessory Electric Heater Kit Contents


ITEM
Heater Assembly
Control Box
Wiring Label
Wire Tie
Screws
Safety Shield
Speed Nut Clips
Dual Ground Lug
Power Lugs

QTY
1
1
1
3
6
1
2
1
3

INSTALLATION
Heater Installation (Horizontal Airflow
Configuration)
1. Refer to unit Installation Instructions for complete unit
installation details. The minimum air quantity for safe electric heater operation is shown in Tables 2A and 2B.
IMPORTANT: When using accessory electric heat
and flexible ductwork, it is recommended that a sheet
metal sleeve be installed inside the first 12 in.
(304.8 mm) of the duct.
2. Remove blower/control box access panel. See Fig. 2.
3. Remove the electric heater and control box assembly from
packaging. Route the accessory electric heater lowvoltage control wires through the back of the unit control
box. See Fig. 3. Using wire tie provided in kit, route and
secure the accessory electric heater low-voltage wires with
the unit low-voltage wires.
4. Install electric heater control box by engaging the back
of the heater control box with the slots in the back of the
unit control box. Secure with the screws provided. See
Fig. 4.
5. Install heater assembly to blower-side plate. Ensure that
the tabs on the heater assembly engage the slots closest
to the indoor coil on the blower housing. See Fig. 5.
Secure heater assembly with screws provided in kit. See
Fig. 6.
6. Route and secure high-voltage wires as shown in Fig. 7.
7. Connect low-voltage control circuit wiring in the lowvoltage connection box on the unit by making proper electrical connections. See Fig. 8-11.

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 1 4 4
PC 111
Catalog No. 535-087
Printed in U.S.A.
Form 50H,S-10SI
Pg 1
6-97
Replaces: 50H,S-7SI
Tab 1b 5a 5a 6b

CONTROL BOX
CONTROL BOX

POWER
PLUGS
DUAL
GROUND
LUG
HEATER
ASSEMBLY

WIRE TIES

SPEED
NUT CLIPS

SECURING SCREWS

Fig. 4 Accessory Electric Heater Control Box


Installation

SCREWS

Fig. 1 Accessory Heater Package


SLOTS FOR HEATER ASSEMBLY

BLOWER HOUSING

Fig. 5 Blower Housing


HEATER
ASSEMBLY

Fig. 2 Blower/Control Box Access Panel

LOW-VOLTAGE
CONTROL WIRES

DUAL GROUND
LUG

CONTROL WIRING
HOLE

SECURING SCREWS

INSTALLATION SLOTS

NOTE: Blower in horizontal discharge application.

Fig. 3 Accessory Electric Heater Control Wiring

Fig. 6 Heater Assembly Installation


2

Table 2A Minimum Airflow for


Electric Heater Operation; 60 Hz
UNIT
TYPE
HEAT PUMP
ELECTRIC
COOLING

018
700*

MINIMUM AIRFLOW (Cfm)


Unit Size
024 030
036
042
048
800 1000 1300 1300 1600

060
1750

700*

700

1750

875

1200

1225

1400

10. Orient blower housing for vertical airflow and slide into
vertical opening, making sure the flanges on the blower
side plates engage the tabs in the unit basepan. When
the blower housing is near final position, resistance will
be felt as the blower housing contacts the basepan insulation. This resistance can be overcome by applying a
slight force to the base of the blower. Continue sliding
blower until hole in side plate flange aligns with the hole
in the basepan. Secure blower to unit using screws removed in Step 5.
11. Install electric heater control box by engaging the tabs
back of the heater control box with the slots in the back
of the unit control box. Secure the heater control box
using the screws provided.

*Not applicable to High Efficiency units.

Table 2B Minimum Airflow for


Electric Heater Operation; 50 Hz
UNIT
TYPE
HEAT PUMP
ELECTRIC
COOLING

024
338
330

MINIMUM AIRFLOW (L/s)


Unit Size
030
036
048
472
614
755
413

567

661

060
826
826

Heater Installation (Vertical Airflow


Configuration)

SECURE
HIGHVOLTAGE
BUNDLE
HERE

1. The unit must first be converted to vertical airflow configuration before the electric heater package is installed.
Refer to unit Installation Instructions.
NOTE: If heat pump units have already been factory converted to vertical airflow configuration, skip to Step 6.
2. Remove blower/control box access panel. See Fig. 2.
3. Disconnect indoor-fan motor leads from indoor-fan relay and unit contactor. Disengage wire tie securing wires
to the unit control box. See Fig. 12.
4. Remove indoor blower assembly. Remove screws
securing the filler bracket and relocate filler bracket to
vertical airflow application as shown in Fig. 13.
5. Remove the blower assembly support bracket. The screws
securing the support bracket can be accessed by removing the condenser side grille. Discard support bracket
and retain screws. Using the 2 speed nut clips provided
with the kit, reinsert the screws through the partition and
tighten to ensure watertightness. See Fig. 13.
6. Remove the electric heater and control box assembly from
packaging and remove safety shield from heater tray.
See Fig. 14.
7. Remove the plug holding the heater wiring bundle to
the heater tray, being careful not to damage wiring. Loosen
nuts on the heater terminals that hold the heater power
leads and ring terminals in place. See Fig. 15. Rotate the
wiring 180 degrees, so that the heater power leads now
leave in the opposite direction from the heater tray. Tighten
the nuts holding the heater power leads and ring terminals. Secure wire tie by inserting it into the engagement hole in heater tray.
8. Mount the safety shield over the limit switches using
2 screws provided. See Fig. 16.
9. Mount the electric heater assembly onto the indoor blower
housing. Insert the tabs on the heater assembly into the
slots closest to the blower wheel inlet. Secure to housing with 2 screws provided in kit. See Fig. 17.

LOWVOLTAGE
CONNECTION
SPLICE BOX

Fig. 7 Accessory Electric Heater


Low-Voltage Wiring

Fig. 8 Low-Voltage Wiring, Single-Stage


Electric Heaters

Fig. 9 Low-Voltage Wiring, Two-Stage


Electric Heaters

WIRE TIE TO BE
DISENGAGED

Fig. 12 Indoor-Fan Motor Leads


12. Reconnect indoor-fan motor leads (refer to Tables 2A
and 2B for minimum cfm [L/s] required for accessory
electric heater operation to determine indoor-fan motor
speed when connecting leads) and reinsert wire tie into
unit control box. Secure wires to control box. See
Fig. 18.
13. Connect low-voltage control circuit wiring in the lowvoltage connection box on the unit by making proper
electric connections. See Fig. 8-11.

High-Voltage Connection To Unit Unit wiring


must be in compliance with the National Electrical Code (NEC,
U.S.A. Standard) and any applicable local codes. Wiring label included with Accessory Electric Heater Kit should be
attached to base unit adjacent to base unit wiring label.
The accessory electric heater can be wired either separately from the unit, or as one single point connection.
Determine which wiring method will be used, and follow
the correct installation procedure.
WIRING HEATER SEPARATE FROM BASE UNIT
1. Size wire for base unit and heaters per NEC. Refer to
unit Installation Instructions for wire sizing. Refer to
Tables 3A and 3B for electric heater wiring sizing and
connection diagram.
2. Run high-voltage leads for the base unit and electric heat
through the appropriate inlet hole in the duct panel, and
through the high-voltage raceway to the control box.
3. Using lugs provided, connect power supply to leads from
unit and electric heater as shown in power connection
diagram. See Fig. 19. Insulate lug. Refer to Tables 3A
and 3B for the correct power connection diagram. (Refer
to proper connection diagram Fig. 20-25.)
4. Install dual ground lug using green ground screw in control box. See Fig. 3. Connect ground leads from base
unit power supply and electric heater supply to ground
lug.
5. Using field-supplied connectors, connect base unit power
supply to base unit power leads.
6. Replace blower/control box access panel and restore power
to the unit.

Fig. 10 Low-Voltage Wiring, Single-Stage


Heat Pump Units

Fig. 11 Low-Voltage Wiring, Two-Stage


Heat Pump Units

Fig. 16 Safety Shield Mounted

BLOWER ASSEMBLY
SUPPORT BRACKET

RELOCATED FILLER
BRACKET AND SCREWS

Fig. 13 Vertical Discharge Opening With


Insulation and Cover Removed

Fig. 17 Electric Heater Assembly Mounted on


Blower Housing

Fig. 14 Electric Heater and


Control Box Assembly

WIRE
TIE

RING TERMINAL
CONNECTIONS
ROTATED 180 DEGREES
FROM ORIGINAL

HEATER SAFETY SHIELD


(FOR VERTICAL AIRFLOW
INSTALLATION)

Fig. 15 Rotation of Heater Terminals

NOTE: Blower in vertical discharge application.

Fig. 18 Heater Assembly Installed in Unit


5

WIRING HEATER AS A SINGLE POINT POWER


CONNECTION
1. Size the wire gage for base unit and heater combinations
per NEC (U.S.A. Standard). Refer to Tables 4A-9B for
wire sizing and connection diagram.
2. Run the high-voltage and ground leads through the appropriate knockout. Run leads through the high-voltage
raceway to the electric heater control box.
3. Connect the ground lead to the ground lug attached to the
unit control box surface. See Fig. 3.
4. Units with fuses:
Connect the power leads to the fuse block and connect
the leads from the unit to the stripped leads from the
fuse block. (Refer to proper connection diagram
Fig. 20-33.)
Close door to electric heater control box making sure that
the door engages the dimple in the control box, which
will lock the door into place.
Units without fuses:
Connect power leads to heater and unit leads using connnectors provided. (Refer to proper connection diagram
Fig. 26-33.)
5. Install blower/control box access panel and restore power
to the unit.

POWER LUGS

Fig. 19 Power Supply Connections

Table 3A Power Connection Data; 60 Hz (Dual-Point Electric Heater Only)


HEATER
MODEL
NUMBER
CPHEATER
001A00
002A00
003A00
004A00
005A00
006A00

CONNECTION
DIAGRAM
(Fig. No.)

RATING
kW

20
21
21
22
22
23

3.75/5.0
5.6/7.5
7.5/10.0
11.3/15.0
13.1/17.5
15.0/20.0

007A00
008A00
009A00

24
24
24

7.5/10.0
11.3/15.0
13.1/17.5

030, 036, 042, 048, 060


030, 036, 042, 048, 060
036, 042, 048, 060

010A00
011A00
012A00

25
25
25

10.0
15.0
17.5

036, 042, 048, 060


036, 042, 048, 060
036, 042, 048, 060

BASE UNIT APPLICATION


(Unit Size)
018, 024, 030, 036,
018, 024, 030, 036,
018, 024, 030, 036,
030, 036, 042,
036
042, 048,

042,
042,
042,
048,

048, 060
048, 060
048, 060
060

060

MCA

MOCP

208/240-1-60*
22.5/26.0
25/30
33.7/39.1
35/40
45.1/50.8
50/60
67.9/78.1
70/80
82.0/93.8
90/100
90.1/104.2
100/110
208/240-3-60*
26.1/30.1
30/35
39.1/45.2
40/50
45.6/51.3
50/60
480-3-60*
15.3
20
22.6
25
26.3
30

Table 3B Power Connection Data; 50 Hz (Dual-Point Electric Heater Only)


HEATER
MODEL
NUMBER
CPHEATER
007A00
008A00
009A00

CONNECTION
DIAGRAM
(Fig. No.)

RATING
kW

BASE UNIT APPLICATION


(Unit Size)

24
24
24

8.4
12.6
14.7

024, 030, 036, 048, 060


036, 048, 060
048, 060

29.0
43.5
50.6

010A00
011A00
012A00

25
25
25

6.9
10.4
12.1

024, 030, 036, 048, 060


024, 030, 036, 048, 060
048, 060

13.1
19.8
23.1

MCA

MOCP
220-3-50*
30
50
60
400-3-50*

LEGEND FOR TABLES 3A AND 3B


MCA Minimum Circuit Amps
MOCP Maximum Overcurrent Protection
*V-Ph-Hz.

15
20
25

Table 4A Standard Efficiency Heat Pump Unit Electric Heater Packages 208/240 V, Single-Phase, 60 Hz
UNIT
SIZE

018

024

030

036

042

048

060

FLA
HACR
MCA
MOCP
NEC

ELECTRIC HEAT/ CONNECTION ELECTRIC HEAT


HEATER
SINGLE-POINT
(kW)
FLA
DIAGRAM
WIRING KIT
(Fig. No.)
CPHEATER
208 V
240 V 208 V 240 V

001A00
26
3.75
5.0
18.1
20.8
002A00
27
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7

001A00
26
3.75
5.0
18.1
20.8
002A00
27
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7

001A00
26
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.1
62.0

001A00
26
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.1
62.0
017A00
29
15.00
20.0
72.2
83.3

001A00
26
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.1
62.0
017A00
29
15.00
20.0
72.2
83.3

013A00
28
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.1
62.0
017A00
29
15.00
20.0
72.2
83.3

013A00
28
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.1
62.0
017A00
29
15.00
20.0
72.2
83.3
LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
National Electrical Code (U.S.A. Standard)

MIN CIRCUIT
MAX FUSE
AMPACITY FOR
OR HACR
MOCP
WIRE SIZING
BRKR
MCA MOCP 208 V
240 V 208 V 240 V 208 V 240 V
15.5
25

38.1
41.5
40
45

49.3
54.6
50
60

60.6
67.6

70
70
17.4
25

40.0
43.4
45
45

51.2
56.5
60
60

62.5
69.5

70
70
22.4
30

44.9
48.4
50
50

56.2
61.4
60

70

67.5
74.5

70
80

90.0
99.9

90
100
26.7
40

49.3
52.7
60
60

60.5
65.8

70
70

71.8
78.8

80
80

94.3
104.2

100
110

116.9
130.5

125
150
30.9
50

53.5
56.9
60
60

64.7
70.0

70
80

76.0
83.0

80
90

98.5
108.4

100
110

121.2
135.0

125
150
40.1
60

62.7
66.1

80
80

73.9
79.2

90
90

85.2
92.2

100
100

107.7
117.6

110
125

130.4
144.3

150
150
48.4
60

71.0
74.5

90
100

82.3
87.5

100
100

93.6
100.5

100
110

116.1
125.9

125
150

138.7
152.6

150
175
UNIT ONLY

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Table 4B Standard Efficiency Heat Pump Unit Electric Heater Packages 208/240 V, 3-Phase, 60 Hz
ELECTRIC HEAT/
UNIT SINGLE-POINT CONNECTION
DIAGRAM
SIZE
WIRING KIT
(Fig. No.)
CPHEATER

007A00
019A00

007A00
019A00
020A00

007A00
019A00
020A00

007A00
019A00
020A00

018A00
019A00
020A00

030

036

042

048

060

FLA
HACR
MCA
MOCP
NEC

ELECTRIC HEAT
(kW)
208 V

240 V

7.5
11.3

7.5
11.3
13.1

7.5
11.3
13.1

7.5
11.3
13.1

7.5
11.3
13.1

10.0
15.0

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

30
31

30
31
31

30
31
31

30
31
31

30
31
31

HEATER
FLA

UNIT ONLY

Max
208 V 240 V MCA Fuse/
HACR

16.6
25
20.8
24.1

31.3
36.1

18.5
25
20.8
24.1

31.3
36.1

36.5
42.1

22.9
30
20.8
24.1

31.3
36.1

36.5
42.1

25.9
40
20.8
24.1

31.3
36.1

36.5
42.1

32.4
50
20.8
24.1

31.3
36.1

36.5
42.1

LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
National Electrical Code (U.S.A. Standard)

MIN CIRCUIT
AMPACITY FOR
WIRE SIZING
208 V

240 V

42.7
55.7

44.5
57.5
64.0

49.0
62.0
68.5

51.9
64.9
71.4

58.5
71.5
78.0

46.7
61.7

48.5
63.6
71.1

53.0
68.0
75.5

55.9
71.0
78.5

62.5
77.5
85.0

MAX FUSE
OR HACR
BRKR

MOCP

208 V 240 V 208 V 240 V

45
60

50
60

50

60

50

50

60

60

70

70
70

70
80

70
80
80

70

70
80

70
80

80
80

70
80
90

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Table 4C Standard Efficiency Heat Pump Unit Electric Heater Packages 480 V, 3-Phase, 60 Hz

UNIT
SIZE

ELECTRIC HEAT/
SINGLE-POINT
WIRING KIT
CPHEATER

CONNECTION
DIAGRAM
(Fig. No.)

010A00
011A00
012A00

010A00
011A00
012A00

010A00
011A00
012A00

010A00
011A00
012A00

32
32
32

32
32
32

32
32
32

32
32
32

036

042

048

060

FLA
HACR
MCA
NEC

ELECTRIC HEAT
(kW)

HEATER
FLA

480 V

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

UNIT ONLY
MCA

12.0
18.0
21.0

12.0
18.0
21.0

12.0
18.0
21.0

12.0
18.0
21.0

LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
National Electrical Code (U.S.A. Standard)

9.0

10.8

13.7

16.8

Max
Fuse/HACR
10

15

20

25

MIN CIRCUIT
AMPACITY FOR
WIRE SIZING

MAX FUSE
OR HACR BRKR

480 V

480 V

24.0
31.5
35.3

25.8
33.4
37.1

28.7
36.2
40.0

31.8
39.4
43.1

25
35
40

30
35
40

30
40
40

35
40
45

2. This unit must be supplied from a 480 v, 3-phase power supply


with a maximum voltage to ground of 300 v.

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.

Table 5A High Efficiency Heat Pump Unit Electric Heater Packages 208/240 V, Single-Phase, 60 Hz
UNIT
SIZE

024

030

036

042

048

060

FLA
HACR
MCA
MOCP
NEC

ELECTRIC HEAT/ CONNECTION ELECTRIC HEAT


HEATER
SINGLE-POINT
(kW)
FLA
DIAGRAM
WIRING KIT
(Fig. No.)
CPHEATER
208 V
240 V 208 V 240 V

001A00
26
3.75
5.0
18.1
20.8
002A00
27
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7

001A00
26
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.1
62.0

001A00
26
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.3
62.0
017A00
29
15.00
20.0
72.2
83.3

001A00
26
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.1
62.0
017A00
29
15.00
20.0
72.2
83.3

013A00
28
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.1
62.0
017A00
29
15.00
20.0
72.2
83.3

013A00
28
3.75
5.0
18.1
20.8
014A00
28
5.60
7.5
27.1
31.3
015A00
28
7.50
10.0
36.1
41.7
016A00
29
11.30
15.0
54.1
62.0
017A00
29
15.00
20.0
72.2
83.3
LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
National Electrical Code (U.S.A. Standard)

MIN CIRCUIT
MAX FUSE
AMPACITY FOR
OR HACR
MOCP
WIRE SIZING
BRKR
MCA MOCP 208 V
240 V 208 V 240 V 208 V 240 V
19.5
30

42.1
45.6
50
50

53.4
58.6
60
60

64.7
71.6

70
80
22.8
30

45.3
48.8
50
50

56.6
61.8
60

70

67.9
74.8

70
80

90.4
100.3

100
110
25.7
40

48.3
51.7
60
60

59.5
64.8
60

70

70.8
77.8

80
80

93.3
103.2

100
110

116.0
129.9

125
150
29.5
45

52.1
55.5
60
60

63.3
68.6

70
80

74.6
81.6

80
90

97.1
107.0

100
110

119.8
133.7

125
150
39.4
60

62.0
65.4

80
80

73.2
78.5

90
90

84.5
91.5

100
100

107.0
116.9

110
125

129.7
143.6

150
150
49.4
60

72.0
75.5

90
100

83.3
88.5

100
100

94.6
101.5

100
110

117.1
126.9

125
150

139.6
153.5

150
175
UNIT ONLY

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Table 5B High Efficiency Heat Pump Unit Electric Heater Packages 208/240 V, 3-Phase, 60 Hz
ELECTRIC HEAT/
UNIT SINGLE-POINT CONNECTION
DIAGRAM
SIZE
WIRING KIT
(Fig. No.)
CPHEATER

007A00
019A00

007A00
019A00
020A00

007A00
019A00
020A00

007A00
019A00
020A00

007A00
019A00
020A00

030

036

042

048

060

FLA
HACR
MCA
MOCP
NEC

ELECTRIC HEAT
(kW)
208 V

240 V

7.5
11.3

7.5
11.3
13.1

7.5
11.3
13.1

7.5
11.3
13.1

7.5
11.3
13.1

10.0
15.0

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

30
31

30
31
31

30
31
31

30
31
31

30
31
31

HEATER
FLA

UNIT ONLY

Max
208 V 240 V MCA Fuse/
HACR

16.6
25
20.8
24.1

31.3
36.1

18.5
25
20.8
24.1

31.3
36.1

36.5
42.1

21.9
30
20.8
24.1

31.3
36.1

36.5
42.1

25.2
40
20.8
24.1

31.3
36.1

36.5
42.0

33.4
50
20.8
24.1

31.3
36.1

36.5
42.0

LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
National Electrical Code (U.S.A. Standard)

MIN CIRCUIT
AMPACITY FOR
WIRE SIZING
208 V

240 V

42.7
55.7

44.5
57.5
64.0

47.9
61.0
67.5

51.2
64.2
70.7

20.8
31.3
36.5

46.7
61.7

48.5
63.6
71.1

51.9
67.0
74.5

55.2
70.3
77.8

24.1
36.1
42.1

MAX FUSE
OR HACR
BRKR

MOCP

208 V 240 V 208 V 240 V

45
60

50
60

50

60

50

50

60

60

70

70
70

70
80

70
80
80

70

70
80

70
80

80
80

70
80
90

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Table 5C High Efficiency Heat Pump Unit Electric Heater Packages 480 V, 3-Phase, 60 Hz

UNIT
SIZE

ELECTRIC HEAT/
SINGLE-POINT
WIRING KIT
CPHEATER

CONNECTION
DIAGRAM
(Fig. No.)

010A00
011A00
012A00

010A00
011A00
012A00

010A00
011A00
012A00

32
32
32

32
32
32

32
32
32

036

042

048

ELECTRIC HEAT
(kW)

HEATER
FLA

480 V

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

MCA

12.0
18.0
21.0

12.0
18.0
21.0

12.0
18.0
21.0

LEGEND
FLA
HACR
MCA
NEC

UNIT ONLY

9.3

10.9

13.4

Max
Fuse/HACR
15

15

20

MIN CIRCUIT
AMPACITY FOR
WIRE SIZING

MAX FUSE
OR HACR BRKR

480 V

480 V

24.4
31.9
35.6

25.9
33.5
37.2

28.4
35.9
39.7

25
35
40

30
35
40

30
40
40

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. This unit must be supplied from a 480 v, 3-phase power supply
with a maximum voltage to ground of 300 v.

Full Load Amps


Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
National Electrical Code (U.S.A. Standard)

10

Table 6A Standard Efficiency Electric Cooling Unit Electric Heater Packages


208/240 V, Single-Phase, 60 Hz
UNIT
SIZE

018

024

030

036

042

048

060

FLA
HACR
MCA
MOCP
NEC

ELECTRIC HEAT/ CONNECTION ELECTRIC HEAT


HEATER
SINGLE-POINT
(kW)
FLA
DIAGRAM
WIRING KIT
(Fig. No.)
CPHEATER
208 V
240 V 208 V 240 V

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.3
62.5

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.3
62.5
005A00
33
13.10
17.5
65.6
75.0

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.3
62.5
006A00
33
15.00
20.0
72.1
83.3

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.3
62.5
006A00
33
15.00
20.0
72.1
83.3

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.3
62.5
006A00
33
15.00
20.0
72.1
83.3
LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
National Electrical Code (U.S.A. Standard)

MIN CIRCUIT
MAX FUSE
AMPACITY FOR
OR HACR
MOCP
WIRE SIZING
BRKR
MCA MOCP 208 V
240 V 208 V 240 V 208 V 240 V
12.9
15

24.8
28.3
25
30

35.9
41.3
40
45

47.3
53.0
50
60

18.2
30

25.0
28.5
30
30

36.2
41.6
40
45

47.6
53.3
50
60

21.8
30

25.0
28.5
30
30

36.2
41.6
40
45

47.6
53.3
50
60

70.4
80.6

80
90
26.7
40

26.7
29.5
40
40

37.2
42.6
40
45

48.6
54.3
50
60

71.4
81.6

80
90

85.5
97.3

90
100
30.9
50

30.9
31.0
50
50

38.7
44.1
50
50

50.1
55.8
60
60

72.9
83.1

80
90

95.1
109.2

100
110
40.1
60

40.1
40.1
60
60

40.1
45.3
60
60

51.3
57.0
60
60

74.2
84.4

80
90

96.4
110.4

100
125
49.0
60

49.0
49.0
60
60

49.0
49.0
60
60

53.6
59.3
60
60

76.4
86.6

80
90

98.7
112.6

100
125
UNIT ONLY

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

11

Table 6B Standard Efficiency Electric Cooling Unit Electric Heater Packages 208/240 V, 3-Phase, 60 Hz
ELECTRIC HEAT/
UNIT SINGLE-POINT CONNECTION
DIAGRAM
SIZE
WIRING KIT
(Fig. No.)
CPHEATER

007A00
008A00

007A00
008A00
009A00

007A00
008A00
009A00

007A00
008A00
009A00

007A00
008A00
009A00

030

036

042

048

060

FLA
HACR
MCA
NEC

30
30

30
30
30

30
30
30

30
30
30

30
30
30

ELECTRIC HEAT
(kW)
208 V

240 V

7.5
11.3

7.5
11.3
13.1

7.5
11.3
13.1

7.5
11.3
13.1

7.5
11.3
13.1

10.0
15.0

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

HEATER
FLA

UNIT ONLY

208 V 240 V MCA

20.9
31.3

20.9
31.3
36.5

20.9
31.3
36.5

20.9
31.3
36.5

20.9
31.3
36.5

LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
National Electrical Code (U.S.A. Standard)

24.1
36.1

24.1
36.1
41.0

24.1
36.1
41.0

24.1
36.1
41.0

24.1
36.1
41.0

15.5

18.8

22.9

25.9

33.0

Max
Fuse
HACR
25

30

35

40

50

MIN CIRCUIT AMPACITY


MAX FUSE
FOR WIRE SIZING
OR HACR BRKR
208 V

240 V

208 V

240 V

28.6
41.6

29.6
42.6
49.1

31.1
44.1
50.6

32.3
45.4
51.8

34.6
47.6
54.1

32.6
47.7

33.6
48.7
54.8

35.1
50.2
56.3

36.3
51.4
57.5

38.6
53.7
59.8

30
45

30
45
50

35
45
60

40
50
60

50
50
60

35
50

35
50
60

40
60
60

40
60
60

50
60
60

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Table 6C Standard Efficiency Electric Cooling Unit Electric Heater Packages 480 V, 3-Phase, 60 Hz
UNIT
SIZE

ELECTRIC HEAT
MIN CIRCUIT AMPACITY
MAX FUSE
ELECTRIC HEAT/
UNIT ONLY
(kW)
FOR WIRE SIZING
OR HACR BRKR
SINGLE-POINT CONNECTION
HEATER
DIAGRAM
FLA
WIRING KIT
Max
(Fig. No.)
480 V
MCA Fuse/HACR
480 V
480 V
CPHEATER

010A00
011A00
012A00

010A00
011A00
012A00

010A00
011A00
012A00

010A00
011A00
012A00

036

042

048

060

FLA
HACR
MCA
NEC

32
32
32

32
32
32

32
32
32

32
32
32

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

12.2
18.1
21.1

12.2
18.1
21.1

12.2
18.1
21.1

12.2
18.1
21.1

LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
National Electrical Code (U.S.A. Standard)

9.2

10.8

13.7

16.8

10

15

20

25

17.0
24.3
28.1

17.8
25.1
28.8

18.1
25.5
29.2

19.3
26.6
30.3

20
25
30

20
30
30

20
30
30

25
30
35

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. This unit must be supplied from a 480 v, 3-phase power supply
with a maximum voltage to ground of 300 v.

12

Table 7A High Efficiency Electric Cooling Unit Electric Heater Packages 208/240 V, Single-Phase, 60 Hz
UNIT
SIZE

024

030

036

042

048

060

FLA
HACR
MCA
MOCP
NEC

ELECTRIC HEAT/ CONNECTION ELECTRIC HEAT


HEATER
SINGLE-POINT
(kW)
FLA
DIAGRAM
WIRING KIT
(Fig. No.)
CPHEATER
208 V
240 V 208 V 240 V

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.3
62.5

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.3
62.5
005A00
33
13.10
17.5
65.6
75.0

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.3
62.5
006A00
33
15.00
20.0
72.1
83.3

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.3
62.5
006A00
33
15.00
20.0
72.1
83.3

001A00
26
3.75
5.0
18.0
20.8
002A00
27
5.60
7.5
26.9
31.3
003A00
27
7.50
10.0
36.1
40.6
004A00
33
11.30
15.0
54.5
62.5
006A00
33
15.00
20.0
72.1
83.3
LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
National Electrical Code (U.S.A. Standard)

MIN CIRCUIT
MAX FUSE
AMPACITY FOR
OR HACR
MOCP
WIRE SIZING
BRKR
MCA MOCP 208 V
240 V 208 V 240 V 208 V 240 V
19.5
30

25.0
28.5
30
30

36.1
41.6
40
45

47.6
53.3
50
60

22.8
30

25.8
29.8
30
30

36.9
42.3
40
45

48.4
54.0
50
60

71.1
81.4

80
90
25.1
30

26.0
29.5
40
40

37.1
42.6
40
45

48.6
54.3
50
60

71.4
81.6

80
90

85.5
97.3

90
100
29.4
45

29.4
29.9
45
45

37.5
42.9
45
45

49.0
54.6
50
60

71.8
82.0

80
90

94.0
108.0

100
110
39.4
60

39.4
39.4
60
60

39.9
45.3
60
60

51.4
57.0
60
60

74.1
84.4

80
90

96.4
110.4

100
125
49.4
60

49.4
49.4
60
60

49.4
49.4
60
60

54.1
59.8
60
60

76.9
87.1

80
90

99.1
113.2

100
125
UNIT ONLY

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

13

Table 7B High Efficiency Electric Cooling Unit Electric Heater Packages 208/240 V, 3-Phase, 60 Hz

UNIT
SIZE

ELECTRIC HEAT/
SINGLE-POINT
WIRING KIT
CPHEATER

CONNECTION
DIAGRAM
(Fig. No.)

007A00
008A00
009A00

007A00
008A00
009A00

007A00
008A00
009A00

007A00
008A00
009A00

30
30
30

30
30
30

30
30
30

30
30
30

036

042

048

060

FLA
HACR
MCA
NEC

ELECTRIC HEAT
(kW)

HEATER
FLA

UNIT ONLY

208 V

240 V

208 V

240 V

MCA

7.5
11.3
13.1

7.5
11.3
13.1

7.5
11.3
13.1

7.5
11.3
13.1

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

10.0
15.0
17.5

20.9
31.3
36.5

20.9
31.3
36.5

20.9
31.3
36.5

20.9
31.3
36.5

24.1
36.1
41.0

24.1
36.1
41.0

24.1
36.1
41.0

24.1
36.1
41.0

17.8

20.0

25.2

33.4

LEGEND
Full Load Amps
Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
National Electrical Code (U.S.A. Standard)

Max
Fuse/
HACR
25

30

40

50

MIN CIRCUIT
AMPACITY FOR
WIRE SIZING

MAX FUSE
OR HACR
BRKR

208 V

240 V

208 V

240 V

29.6
42.6
49.1

30.0
43.0
49.5

32.4
45.3
51.8

35.1
48.1
54.6

33.6
48.6
54.8

33.9
49.0
55.1

36.3
51.4
57.5

39.1
54.1
60.3

30
45
50

30
45
50

40
50
60

50
50
60

35
50
60

35
50
60

40
60
60

50
60
60

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Table 7C High Efficiency Electric Cooling Unit Electric Heater Packages 480 V, 3-Phase, 60 Hz
UNIT
SIZE

036

042

048

ELECTRIC HEAT
MIN CIRCUIT AMPACITY
MAX FUSE
ELECTRIC HEAT/
UNIT ONLY
(kW)
FOR WIRE SIZING
OR HACR BRKR
SINGLE-POINT CONNECTION
HEATER
DIAGRAM
WIRING KIT
FLA
Max
(Fig. No.)
480
MCA Fuse/HACR
480 V
480 V
CPHEATER

9.0
10

010A00
32
10.0
12.2

17.0
20
011A00
32
15.0
18.1

24.4
25
012A00
32
17.5
21.1

28.1
30

10.4
15

010A00
32
10.0
12.2

17.3
20
011A00
32
15.0
18.1

24.6
25
012A00
32
17.5
21.1

28.4
30

13.4
20

010A00
32
10.0
12.2

18.1
20
011A00
32
15.0
18.1

25.5
30
012A00
32
17.5
21.1

29.3
30
LEGEND

FLA
HACR
MCA
NEC

NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the
overcurrent protective device for the unit shall be fuse or HACR
breaker.
2. This unit must be supplied from a 480 v, 3-phase power supply
with a maximum voltage to ground of 300 v.

Full Load Amps


Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
National Electrical Code (U.S.A. Standard)

14

Table 8A Standard Efficiency Heat Pump Unit Electric Heater Packages 220 V, 3-Phase, 50 Hz
ELECTRIC HEAT/
SINGLE-POINT
WIRING KIT
CPHEATER

007A00

007A00

007A00
008A00

007A00
008A00
009A00

007A00
008A00
009A00

UNIT
SIZE
024
030
036

048

060

CONNECTION
DIAGRAM
(Fig. No.)

ELECTRIC
HEAT (kW)

30

30

30
30

30
30
30

30
30
30

8.4

8.4

8.4
12.6

8.4
12.6
14.7

8.4
12.6
14.7

220 V

23.2

23.2

23.2
34.8

23.2
34.8
40.5

23.2
34.8
40.5

LEGEND
FLA
HACR
MCA
MOCP
NEC

MCA

MOCP

MIN CIRCUIT
AMPACITY FOR
WIRE SIZING

17.7

19.5

22.7

35.2

30.7

25

30

35

50

45

46.7

48.5

51.7
66.2

64.2
78.7
85.9

59.7
74.2
81.4

UNIT ONLY

HEATER
FLA

MAX FUSE
OR HACR
BRKR

MOCP

550

30

60

60

70

70
80
90

80
90

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Full Load Amps


Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
National Electrical Code (U.S.A. Standard)

Table 8B Standard Efficiency Heat Pump Unit Electric Heater Packages 400 V, 3-Phase, 50 Hz
ELECTRIC HEAT/
SINGLE-POINT
WIRING KIT
CPHEATER

010A00
011A00

010A00
011A00

010A00
011A00

010A00
011A00
012A00

010A00
011A00
012A00

UNIT
SIZE
024
030
036

048

060

CONNECTION
DIAGRAM
(Fig. No.)

ELECTRIC
HEAT (kW)

32
32

32
32

32
32

32
32
32

32
32
32

6.9
10.4

6.9
10.4

6.9
10.4

6.9
10.4
12.1

6.9
10.4
12.1

400 V

HEATER
FLA

10.5
15.8

10.5
15.8

10.5
15.8

10.5
15.8
18.5

10.5
15.8
18.5

LEGEND
FLA
HACR
MCA
MOCP
NEC

MCA

MOCP

MIN CIRCUIT
AMPACITY FOR
WIRE SIZING

9.0

9.0

11.0

18.5

17.9

10

10

15

25

25

22.1
28.7

22.1
28.7

24.1
30.7

31.6
38.3
41.6

31.0
37.6
41.0

UNIT ONLY

MAX FUSE
OR HACR
BRKR

25
30

25
30

25
35

35
40
45

35
40
45

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Full Load Amps


Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection (fuses or HACR-type
circuit breaker)
National Electrical Code (U.S.A. Standard)

15

Table 9A Standard Efficiency Electric Cooling Unit Electric Heater Packages 220 V, 3-Phase, 50 Hz
ELECTRIC HEAT/
SINGLE-POINT
WIRING KIT
CPHEATER

007A00

007A00

007A00
008A00

007A00
008A00
009A00

007A00
008A00
009A00

UNIT
SIZE
024
030
036

048

060

CONNECTION
DIAGRAM
(Fig. No.)

ELECTRIC
HEAT (kW)

30

30

30
30

30
30
30

30
30
30

8.4

8.4

8.4
12.6

8.4
12.6
14.7

8.4
12.6
14.7

220 V

HEATER
FLA

23.2

23.2

23.2
34.8

23.2
34.8
40.5

23.2
34.8
40.5

LEGEND
FLA
HACR
MCA
MOCP
NEC

MCA

MOCP

MIN CIRCUIT
AMPACITY FOR
WIRE SIZING

17.7

19.5

22.7

35.2

30.7

25

30

35

50

45

32.5

32.5

32.5
47.0

38.1
52.6
59.8

38.1
52.6
59.8

UNIT ONLY

MAX FUSE
OR HACR
BRKR

35

35

35
50

50
60
60

45
60
60

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Full Load Amps


Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code (U.S.A. Standard)

Table 9B Standard Efficiency Electric Cooling Unit Electric Heater Packages 400 V, 3-Phase, 50 Hz
ELECTRIC HEAT/
SINGLE-POINT
WIRING KIT
CPHEATER

010A00
011A00

010A00
011A00

010A00
011A00

010A00
011A00
012A00

010A00
011A00
012A00

UNIT
SIZE
024
030
036

048

060

CONNECTION
DIAGRAM
(Fig. No.)

ELECTRIC
HEAT (kW)

32
32

32
32

32
32

32
32
32

32
32
32

6.9
10.4

6.9
10.4

6.9
10.4

6.9
10.4
12.1

6.9
10.4
12.1

400 V

HEATER
FLA

10.5
15.8

10.5
15.8

10.5
15.8

10.5
15.8
18.5

10.5
15.8
18.5

LEGEND
FLA
HACR
MCA
MOCP
NEC

MCA

MOCP

MIN CIRCUIT
AMPACITY FOR
WIRE SIZING

9.0

9.0

11.0

18.5

17.9

10

10

15

25

25

15.1
21.8

15.1
21.8

15.1
21.8

18.5
24.8
28.1

18.1
24.8
28.1

UNIT ONLY

MAX FUSE
OR HACR
BRKR

20
25

20
25

20
25

25
25
30

25
25
30

NOTE: In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.

Full Load Amps


Heating, Air Conditioning and Refrigeration
Minimum Circuit Amps
Maximum Overcurrent Protection
National Electrical Code (U.S.A. Standard)

16

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

Fig. 20 Dual-Point Connection Diagram;


Part No. CPHEATER001A00

Fig. 22 Dual-Point Connection Diagram;


Part No. CPHEATER004A00, CPHEATER005A00

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

Fig. 21 Dual-Point Connection Diagram;


Part No. CPHEATER002A00, CPHEATER003A00

Fig. 23 Dual-Point Connection Diagram;


Part No. CPHEATER006A00

17

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

Fig. 26 Single Point Connection Diagram;


Part No. CPHEATER001A00

Fig. 24 Dual-Point Connection Diagram;


Part No. CPHEATER007A00, CPHEATER008A00,
CPHEATER009A00

LEGEND
LEGEND

EQUIP GND Equipment Ground


NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

EQUIP GND Equipment Ground


NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

Fig. 27 Single Point Connection Diagram;


Part No. CPHEATER002A00, CPHEATER003A00

Fig. 25 Dual-Point Connection Diagram;


Part No. CPHEATER010A00, CPHEATER011A00,
CPHEATER012A00

18

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

Fig. 28 Single Point Connection Diagram;


Part No. CPHEATER013A00, CPHEATER014A00,
CPHEATER015A00

Fig. 30 Single Point Connection Diagram;


Part No. CPHEATER007A00, CPHEATER008A00,
CPHEATER009A00, CPHEATER018A00

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

Fig. 29 Single Point Connection Diagram;


Part No. CPHEATER016A00, CPHEATER017A00

Fig. 31 Single Point Connection Diagram;


Part No. CPHEATER019A00, CPHEATER020A00

19

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

LEGEND
EQUIP GND Equipment Ground
NEC
National Electrical Code (U.S.A.)
Factory Wiring
Field-Supplied Wiring

Fig. 32 Single Point Connection Diagram;


Part No. CPHEATER010A00, CPHEATER011A00,
CPHEATER012A00

Fig. 33 Single Point Connection Diagram;


Part No. CPHEATER004A00, CPHEATER005A00,
CPHEATER006A00

ADJUST THERMOSTAT

SERVICE

To adjust thermostat for electric heat, refer to Table 10 for


heat anticipator settings for room thermostats. These settings may be changed slightly to provide a greater degree of
comfort for particular installations.

Limit switch provides overtemperature protection. Switch


malfunction, a result of improper handling, may prevent heating element from operating. Replace switch if malfunction
occurs.

Table 10 Heat Anticipator Settings


HEATER
PART NO.
CPHEATER---A00
001, 002, 013, 014
003, 005, 006, 007, 009,
010, 011, 012, 015,
017, 018, 020

ELECTRIC COOLING AND


HEAT PUMP UNITS
SINGLE STAGE
.26
.42
TWO STAGE

004, 008, 016, 019

1ST
.26

2ND
.26

Copyright 1997 Carrier Corporation