Document/Clause Reference

GTS/Clause 1.0

GTS/Clause 7.0

GTS/Clause 8.0

GTS/Clause 6.0

GTS/Clause 7.0

System Configuration

Alarms and alarm


management

Reporting and data


logging

Description

Clarification

System configuration

Dot matrix printer and A4


colour laser Printer shall have
single link to network via
ethernet as per OEM standard.

The use of multi-media system in HMI shall be envisaged for audio-visual


signaling for faults & alarms.
- There shall be dedicated key as a provision for acknowledging the faults.
The usability of the operator interface shall be further enhanced with
features such as sound cards, touch screen, track balls etc.
- Alarm list / event list and operator action list and its logging for minimum
one month .
Alarm Performance Irrespective of Operator activity and choice of display,
an alarm situation shall always have priority and shall be brought to the
attention of the Operator,
quickly and automatically.The display containing the alarm shall be
selected by
a single keystroke action. Alarms shouldautomatically update in the event
of an alarm
operating i.e. it should not require operatorintervention to update alarms
either on process mimics or alarm summary format.

Automation System shall have


following diagnostic alarm
information which shall be used
to identify the faulty device at
Please go as per Contracts TS for Alarms
card level:
& Interlocks Page 7 to 9 of 17
1) Card fault
2) per channel diagnostic for
Analog Input

Summary of faults with description, date and time of occurrence .


- Shift wise, daily, monthly, yearly report with process values / production
figures and other process data.However, same shall be finalised by the
Purchaser during detailed engineering process.
- Logging & reports of events
- Historical data storage & trending.

RDBMS software out of scope


and also pls. note we will offer
our standard report format.

Input Units

Output units

High density, modular.


- Insulation level of 500 / 1500 V AC/DC
- Individual DP MCB shall be provided in power supply for each card
- Cards shall have diagnostic features
- Cards shall have hot swapping features

Insulation level of offered


Digital Output Module is 500V
DC and 1500 V AC

Separate earthing bus for power / panel earthing and electronic earthing
shall be provided. Minimum two numbers of electronic earth pits shall be
provided for each set of PLC .
- Electronic earthing bus shall be suitably insulated. Earthing
requirements / earthing schemes for the equipment supplied shall be
clearly indicated in appropriate drawings.

Earthing pit,Earthing bus


outside PLC panel,Cabling
excluded

HART

HART is not applicable for the


scope. Hence not Considered.

Earthing

CTS/Clause 8

HART

Accepted if OEM standard

Please go as per Contracts TS clause


6.03 ( xxxiii,xxxiv Page 5 of 17 )

Historical data storage for 3


months considered

High density, modular.


- Insulation level of 500 / 1500 V AC/DC
- Input interrogation voltage 24 V DC.
- Individual DP MCB shall be provided in power supply for each card
- Cards shall have diagnostic features
- Cards shall have Hot swapping features

GTS/Clause 14.0

Request for Remarks from Blue Star

Insulation level of offered


Digital Input Module is 500V
DC and 1500 V AC

OK and accepted

OK and accepted

It is not in your scope

It is a part of Instrumentation