Professional Documents
Culture Documents
Experiment No.: 1
OBJECTIVE:
Study the Vapour Compression System (Test Rig).
INTRODUCTION:
The process of refrigeration is most commonly accomplished by the evaporation
of a liquid refrigerant, thereby extracting heat from the medium to be cooled. The
refrigeration cycle is then composed chiefly of four further steps, whose purpose
is to remove this heat from the evaporating refrigerant by again putting it in the
liquid state in order that it may be used repeatedly in a continuous process.
The standard vapour compression cycle consists of the following processes.
Process: 1-2
Reversible adiabatic compression from the saturated vapour to the condenser
pressure.
Process: 2-3
Reversible heat rejection at constant pressure de-superheating and condensation.
Process: 3-4
Irreversible constant enthalpy expansion from saturated liquid to evaporator
pressure.
Process: 4-1
Reversible heat addition at pressure (evaporation to saturated vapour.)
STANDARD VAPOUR COMPRESSION CYCLE:
Refrigerants such as R-12 / R-22 (commonly known as Freon) are used as the
working medium because of their properties, which are required as refrigeration
cycles.
Performance of Standard Vapour Compression Cycle:
Process 1-2 is the compression process wherein mechanical work is to be
supplied (usually in the form of electrical energy) to a compressor. This is the
quantity to be spent.
Process 4-1 represents the useful refrigeration effect.
The index of performance is defined as co-efficient of performance (not as
efficiency, as for heat engines).
C.O.P. is defined as follows:
C.O.P. =
= 30 minutes
= 17 PSI
= 132 PSI
= -5 o C
= 49.3 o C
=33.3 o C
= 9.5 LPH
= 750 rev/Kwh
=123 sec
= 12.5 kg
= 24.1o C
= 9.9o C
Drop in temperature
= 14.2o C
= 0.39 KW
Mw cp T = kW
Time taken fro drop in initial to final temp.
Refrigeration effect
= Work done by the compressor
0.412
= 0.390
THEORETICAL C.O.P.
= 0.412 KW
= 1.056
Locate 1, 2, 3, and 4 on P.h Chart for R-12 / 143a using (P1 T1), (P2 T2) T3 & T4
read specific enthalpy values at 1, 2, 3 & 4
h1
= 190 kj / kg
h2
= 215 kj / kg
h3
h4 = 80 kj / kg
h1 - h4
Theoretical C.O.P. = h2 - h1
190 - 80
= 215 180
= 4.40
OPERATIONAL INSTRUCTIONS:
Before starting the unit please observe and not the following points:
a. All the hand shut valves should be opened except charging line valve which
should not be touched.
b. P1/P2 indicates suction and discharge pressure gauges.
c. Provide a single- phase 15 amp 3-pin socket power supply close to the unit.
d. Now put the main switch on.
e. Decide which system you are going to use first. For thermostatic expansion
valve (TEV) close any one capillary operated valve.
NOTE:
Only one system of expansion can be used at a time.
(Rotate thermostat in clockwise direction to start the compressor, in an anticlockwise direction to stop the compressor).