ZXDU68 W201 (V4.0R06M03/V4.0R06M04) DC Power System

Document number/version:
SJ-20101011152815-004 / 2015-03-11 (R1.1)

1 /2

Caution: The ZXDU68 W201 is outdoor power


supply equipment with direct air ventilation, but
cannot be used in a harsh outdoor environment.

System Structure

Monitoring Software
For more information about the software operations, refer to the
ZXDU58/ZXDU68 B121-CSU (V2.20) Monitoring Unit Operation Manual.

Power equipment unit

Record the parameter modification in the


Modified column of the table below.

Setup Para

15

The following table lists the key parameters that need to be


checked. Those marked with
must be modified according to the
actual configuration of the system (wrong parameter settings will
cause improper system operation and alarm errors)!

Operation Instruction:
7

1. Press Enter to enable the modification of the value.


10

2. Press or to modify values.

Real Msg

3. Press Ent to save the modification or press Esc to cancel the


modification.

Msg Alm Ctrl Rec


2

12

11
5

13

14

Ent

1. Communication equipment space (21 U)


2. Communication box
8

Parameter List

DC out
Battery
AC In
SMR
Work Mode
ENV
IN-Relays
Next Equal Time
Version

3. Power equipment unit


4. Batteries terminals
5. Working ground busbar (GND)
6. Batteries (4*12V DC per rack)

Ent

Sys Para.

Turn pages/move the cursor

7. Communication equipment space (26 U)


8. DC distribution unit (LLVD2)
6

9. ZXD2400 rectifiers
11. AC SPD
12. DC output breakers (LLVD1)
13. Battery breakers (1-2)

100

Bat.2 Cap. (Ah)

100

RS232 Bauds

9600

RS485 Bauds

9600

Device No.

Passw ord

0000

Language

Chinese

AuxSw itch Set

On
No

Alm 1-n
Alm 2-n

Auto Alarm

Enabled

SMR Pulled Alm

Enabled

Alm n-n

Current Date

Current Time

Msg Alm Ctrl Rec


Ent

Default

Bat.1 Cap. (Ah)

Buzz Sw itch

Real Alm.

10. AC input breaker

Param eter

14. DC SPD
15. Monitoring unit

His.Record
Primary Cabinet
(V4.0R06M03

Msg Alm Ctrl Rec

Secondary Cabinet
V4.0R06M04

Alm Rec.
Operate Rec.
Discharge Rec.
Peak Rec.
Maintain Rec.

Ent

(The configuration of DC output branches is subject to the


contract. This image is for reference only.)

Description

AC input voltage

Rated: 100 ~ 240 VAC

Rectifier
(ZXD2400)

Msg Alm
CtrlSetupRec
Para
Ent

Monitoring Unit

Range: 80 ~ 300 VAC


AC input mode

Three-phase five-w ire (L1/L2/L3/N/PE)

Rated DC output voltage

-53.5 VDC

ZXD2400 rectifier

Rated current: 50 A

Rectifier quantity

Three at most

Caution: The ventilation holes cannot


be blocked! Maintain good ventilation!
OAM
The rectifier in each slot is powered by a single phase
cable. The corresponding relations of the slots and the
phase cables are as shown below:

REC1
L1

REC2
L2

REC3
L3

REC4

1. Sys Para
2. Batt Para
3. Alarm Para

1. SMR ON
2. SMR OFF
3. FlOAT
4. EQUAL...
5.TEST
6. Auto Save
7. Temp Nonsave
8. Perm Nonsave
9. Manual Detect

CSU

L1

ZTE Corporation Address: No. 55, Hi-tech Road South, ShenZhen, P.R.China

Postcode: 518057

Website: http://ensupport.zte.com.cn

Email: 800@zte.com.cn

53.5

Equal Vol.

56.4

Cur. Limited
Equal Func.
Period
(Day)

Ctrl. (initial password:0000)

Safe Mode

Float Vol.
Test Vol.
Batt Para.

Electrical Characteristics of the System


Item

Work Mode

46
0.125
Enabled
180

BatVol Min.

47

1-Shut Vol.

45

2-Shut Vol.
Auto Test
Test Period

44
Disabled
30

Test StartTime

10:00

Set relays out

A1-A6

Alarm Para

Actual

User Guide

Symptoms and Troubleshooting

Status Indication
IN

The Rectifier (ZXD2400)

OUT

CL

ALM

CSU Symptoms and Troubleshooting

Indicator

Status

Description

Sym ptom

IN

Lit (green)

AC input is normal

OUT

Lit (green)

DC output is normal

Disorderly LCD display (1) Re-install the CSU to reset it.


(2) If the symptom persists, take out the CSU to troubleshoot it.

CL

Lit (yellow )

Current limit occurs

ALM

Lit (red)

Alarm occurs

Status

Description

PWR

Lit (green)

The unit is pow ered

Invalid keypad
operation

RUN

Lit (green)

EQU

Lit (green)

The Unit is running normally


The system is inequalized
charge mode
The unit is sommunicating
w ith the background PC
A fault occurs to the system

The CSU indicates that Query the real-time alarm information and take measures according
an alarm occurs
to the specific alarm.

Lit (yellow )

&

Lit (red)

PWR

Premise for the running of the monitoring unit: The input DC power
is normal and the power indicator is ON.

RUN

EQU

COMM

ALM

It might be the hardw are or softw are fault of the CSU.


(1) Re-install the CSU to reset it.
(2) If the symptom persists, take out the CSU to troubleshoot it and
install a new CSU.

Rectifier Symptoms and Troubleshooting


Sym ptom

Cause and Solution

Rectifier pow er-on


fails, and thus the
pow er indicator of the
rectifier is not ON.

(1) Make sure that the AC input breaker of the rectifier is turned on.
(2) Make sure that the AC input voltage is w ithin the w orking voltage
of the rectifier.
(3) If the above tw o items are not the causes, re-install the rectifier
or replace the installation slot and then re-install the rectifier.
(4) If the symptom persists, troubleshoot the faulty rectifier and
install a new rectifier in the slot.

Rectifier alarm

Rectifier fault

ZTE Corporation Address: No. 55, Hi-tech Road South, ShenZhen, P.R.China

Warning: The system shutdown will cause power


1. Turn off the loads (or switch to another power supply system to
power the loads), to make the system free of loads.
2. Turn off the DC output breakers.
3. Turn off the monitoring unit.
4. Turn off the battery breakers.
5. Turn off the AC input breaker of the cabinet
6. Turn off the external AC input breaker powering the cabinet.

Emergency Shutdown
Warning: The emergency shutdown can be
performed only when there is an emergency!
1. Turn off the external AC input breakers of the system.
2. Turn off the battery breakers in the cabinet.

The possible cause might be that the AC input voltage is too high or
too low , the temperature is too high, the load-sharing quality is bad
or the addresses conflict. The alarm might be caused by the
surrounding conditions or the other equipment and might not be
caused by the rectifier itself. Check the alarm information through
the CSU and take measures accordingly.
The possible cause might be that the AC output voltage/current is
too high, the fan is faulty or the output fuse is blow n.
(1) Re-install the rectifier to reset it.
(2) If the fault persists, troubleshoot the faulty rectifier and install a
new rectifier in the slot.

Postcode: 518057

Shutdown
supply interruption to the loads connected. Be cautious!

Indicator

ALM

&

Cause and Solution

Communication
(1) Make sure that the communication cable (serial port cable or
interruption w ith the
netw ork cable) is firmly connected to the corresponding
monitoring background communication interface.
(2) Make sure that the communication parameters of the CSU are
correctly set according to the netw orking requirement.
(3) If the symptom persists, take out the CSU to troubleshoot it.
Remark: The communication parameters include RS232 Bauds,
RS485 Bauds, and Device No.. For specific parameter values,
consult the netw ork management engineer.

The Monitorng Unit (CSU)

COMM

2 /2

ZXDU68 W201 (V4.0R06M03/M04) DC Power System

Website: http://ensupport.zte.com.cn

Startup
Prerequisites: This equipment has passed the electrical
check and is qualified for the debugging. The Quick Installation and
Commissioning Guide (V4.0R06M03/M04) describes the check and
debugging in detail.
1. Turn on the battery breakers.
2. Wait for the CSU startup. Proceed to the next step after the CSU displays
the main menu interface.
3. Turn on the external power switch.
4. Turn on the AC input breaker in the cabinet.
5. If any loads need to be powered-on, turn on the DC output breakers
connected to these loads.