Outdoor Unit
RAC-50WX8
SAFETY PRECAUTION
No.
Item
0.9m
WARNING
(4.1x32)
Make sure that the units are mounted at locations which are able to provide full support to the weight of the units. If not, the
units may collapse and impose danger.
Observe the rules and regulations of the electrical installation and the methods described in the installation manual when
dealing with the electrical work. Use power cables approved by the authorities of your country.
Please use the specified components for installation work. Otherwise, the units may collapse or water leakage, electric shock
and fire may occur.
Be sure to use the specified piping set for R-410A. Otherwise, this may result in broken copper pipes or faults.
When installing or removing an air conditioner, only specified refrigerant (R410A) shall be allowed, do not allow air or moisture
to remain in the refrigeration cycle. Otherwise, pressure in the refrigeration cycle may become abnormally high so that a rupture
may be caused.
2
Screw for holder of
Remote Controller
Be sure to ventilate fully if a refrigerant gas leak while at work. If the refrigerant gas comes into contact with fire, a poisonous
gas may occur.
After completion of installation work, check to make sure that there is no refrigeration gas leakage. If the refrigerant gas leaks
into the room, coming into contact with fire in the fan-driven heater, space heater, etc., a poisonous gas may occur.
(3.1x16)
Remote Controller
(unit : mm)
50
10
500
35
No.
Item
The draining of the water container inside the indoor unit can be done from the left.
Therefore the hanger must be fixed horizontally or slightly tilted towards the side
of drain hose. Otherwise, condensed water may overflow the water container.
295
Protection
Pipe
Drain Hose
2
Connecting
Cord
Projection
Pipe
! CAUTION
Pipe
! CAUTION
HORIZONTAL PIPING
Preparation
0.85m
4.8mm
above 50mm
1 Hanger
Plug
2 Screw
32mm
Exchange the location of drain hose and drain cap during horizontal piping as shown in
figure below. Be sure to plug in the drain hose until the insulating material folds upon
itself.
Wall
4.1 x 32 Screw
Wall
3 Remote
Control
Holder
Drain cap
5 Screw
20mm
Drain hose
<IA438: A >
Hang the Indoor unit onto the hanger. Use the temporary
stand at the back of the Indoor unit to push its lower part Projection
15cm forwards.
Hook
Place the drain hose through the hole on the wall.
Wrap the refrigerating pipes with insulation pipe after
connecting refrigerating pipe.
Connect the connecting cord after removing electrical cover.
(Refer to Connection of Power Cord)
After adjustment, the connecting cord and refrigerating pipes
about 15cm
are placed into the space available under the Indoor unit.
The projection of Indoor unit must hook to the hanger.
Heat insulation pipe
Protection pipe
Indoor
Outdoor
2 ~ 5mm
Seal with
putty
Protection
pipe
Seal with
putty
WALL
Sleeve of
protection
pipe
! WARNING
Be sure that the wire is not
in contact with any metal
in the wall. Please use the
protection pipe as wire
passing through the
hollow part of the wall so
as to prevent the
possibility of damaged by
mouse.
Unless it seals completely,
any air with high humidity
flows from outdoor and
any dew may drop.
! CAUTION
Connecting
cord
Drain hose
Refrigerating pipe
Please insert
until here
Please insert
until here
Installation
Plug
Drain cap
below
5mm
Ceiling
Wall
4.4mm
INDOOR UNIT
Connecting
cord
Drain hose
! CAUTION
Please pull the lower part of
the Indoor unit outwards to
check if the unit is hooked
onto the hanger. Improper
installation may cause
vibration and noise.
Hanger
Level
Mark
Hanger
55
100
55
65
above
200mm
above 100mm
Hanger
82
above 50mm
give clearance
as wide as
possible
Preparation
795
77
50
Plug
65
6
4
Installation
80
2,300mm or more
above 200mm
above 100mm
above 50 mm when
installed on the
ceiling of balcony
! CAUTION
above 100mm
above 200mm
Do not install the unit near a location where there is flammable gas. The outdoor unit may
catch fire if flammable gas leaks around it.
Piping shall be suitable supported with a maximum spacing of 1m between the supports.
above 50mm
Qty
A circuit breaker or fuse (16A time delay) must be installed. Without a circuit breaker or fuse the danger of electric shock
exists.
A main switch with a contact gap of more than 3mm has to be installed in the power supply line to the outdoor unit.
! CAUTION
Bush
CAUTION
Please ensure smooth flow of water when installing the drain hose.
12
125
Drain Pipe
Mounting
Stand
Unauthorized modifications to the air conditioner may be dangerous. If a breakdown occurs please call a qualified air conditioner
technician or electrician. Improper repairs may result in water leakage, electric shock and fire, etc.
Be sure to
completely
seal any
gap with
putty.
Purifying Filter
Connection
Be sure to use the specified wire for connecting the indoor and outdoor units. Please ensure that the connections are tight
after the conductors of the wire are inserted into the terminals. Improper insertion and loose contact may cause over-heating
and fire.
(10)
Please observe the instructions stated in the installation manual during the process of installation. Improper installation may
cause water leakage, electric shock and fire.
1.6m
330
310
Horizontally
perpendicular
to the unit
Please request your sales agent or qualified technician to install your unit. Water leakage, short circuit or fire may occur if you
do the installation work yourself.
Direction of Piping
CAUTION
Be sure that the unit operates in proper condition after installation. Explain to customer the proper way of operating
the unit as described in the users guide.
Qty
Hanger
CAUTION
! WARNING ........ Incorrect methods of installation may cause death or serious injury.
The Outdoor unit must be mounted at a location which can support heavy weight. Otherwise, noise and vibration will increase.
WARNING
Indoor Unit
RAS-50WX8(W)
RAS-50WX8(B)
WARNING
INDOOR UNIT
above 300mm
OUTDOOR UNIT
Drain hose
Ditch
Openings
Connected section
! CAUTION
Pipe
support
Holder
Connecting cord
Bending
upwards
Condensed
water pond
Condensed
water pond
You are free to choose the side (left or right) for the installation of drain
hose. Please ensure the smooth flow of condensed water of the Indoor
Pull downward
OUTDOOR UNIT
CAUTION
Do not touch the suction port,
bottomsurface, or aluminum
fin of the outdoor unit.
Failure to do so may cause
an injury.
Push
above
100mm
8 BUSH
Push
8 BUSH
DRAIN HOLE
9 DRAIN PIPE
Install the outdoor unit horizontally and make sure that condensate drains away.
In case of using in cold weather area
Especially, in case that there are heavy snows in cold weather area, condensed
water freezes on the base and may result not to drain. In this case, please
remove the bush and the drain pipe at the bottom of unit. (Left and center near
discharge portion of air, each 1 place). It becomes smooth drain.
Ensure that the distance from the drain hole to the ground is 250 mm or more.
! WARNING
CD
Copper pipe
1
! CAUTION
Die
Recommend to use
R410A flaring tool.
Copper pipe
A (mm)
Outer
Diameter (mm)
~
0.0 ~ 0.5mm
0.0 ~ 0.5mm
6.35
0.0
9.52
12.7
0.5mm
Closed
Lo
Hi
R410A
Manifold valve
Charge hose
Valve
Vacuum
pump
Valve
Vacuum pump
adapter
1.0mm
The body of
service valve
Cap of
valve core
Hexagonal
Wrench Key
1.0mm
Pipe Connection
4
! CAUTION of small diameter side, or a seal cap of big diameter side will fly
out. Prevent water from entering into the piping when working.
Wrench
Torque
wrench
Outer
dia.of pipe
Torque Nm
(kgf cm)
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
6.35 (1/4")
9.52 (3/8")
12.7 (1/2")
Procedures of Wiring
Indoor Unit
Trimming tool
Power supply shall be connected at the rated voltage, otherwise the unit will
be broken or could not reach the specified capacity.
Preparation of Pipe
AIR REMOVAL
Please mount the Outdoor unit of stable ground to prevent vibration and increase
of noise level.
Decide the location for piping after sorting out the different types of pipe available.
When removing side cover, please pull the handle after undoing the hook by
pulling it downward. Reinstall the side cover in the reverse order of the removal.
Outdoor Unit
L NCD
1.6 or
2.0
RAC Adapter
Weekly timer/
Wired remote controller
Connect the
earth cord
Connecting Cord
Connecting Cord
2.0
AC 220 - 230V
1 50Hz
Strip wires
100mm
160mm
Outdoor Unit
10mm
10mm
Power line
30mm
Detail of cutting the connecting cord
10mm
70mm
GRN + YEL
Be sure to use only power cables approved from the authorities in your
country. For example in Germany: Cable type: NYM 3x1.5mm2 (Fuse = 16A
time delay).
Sleeve of
protection pipe
Putty
Wire cross-section
up to 16m
1.5mm2
up to 15m
2.5mm2
Fuse Capacity
up to 25m
4.0mm2
Holder for
Remote Controller
Operation Test
Please use a new socket. Accident may occur due to the use of old
socket because of poor contact.
Please plug in and then remove the plug for 2 3 times. This is to
ensure that the plug is completely plugged into the socket.
Keep additional length for the power cord and do not render the
plug under external force as this may cause poor contact.
Do not fix the power cord with U-shape nail.
<IA438: A >
IMPORTANT
[For all optional part, please refer catalog for part number]
As for connecting to H-Link, a separately purchased
RAC Adapter is required.
To install the wiring the electrical box cover must be opened.
Connect the connector of RAC adapter to CN7.
Assemble back the cover of electrical box.
Please refer to the respective user manual of RAC Adapter
for further details.
Please be careful not to damage lead wires by edge of
plate when connecting the optional parts.
After installing the front cover onto the unit, hook three
claws at upper side of the cover securely. Then, push the
center of the front cover to lock the claws.
Slide the shafts of the right and left arms on the washable
panel along the steps to insert the shafts into the holes till
they stop. After checking that the shafts are securely
inserted, close the panel.
Locking mechanism
! CAUTION
Screw (2 pieces)
Remote
Controller
Power Source
Cable length
Putty
H-LINK
Earth terminal
IMPORTANT
You may not be able to close the side cover due to the
connecting cord, under such situation, please press
against the wall of side cover to fix it.
Be sure that the hooks (2 places) are plugged in.
Otherwise, water leakage may occur and this causes
short circuit or faults.
The connecting cord should not touch to service valve
and pipes. (It becomes high temperature in heating
operation.)
Please refer to the installation manual for wire connection to the terminals of
the units. The cabling must meet the standards of electrical installation.
The naked part of the wire core should be 10 mm and fix it to the terminal
tightly. Then try to pull the individual wire to check if the contact is tight.
Improper insertion may burn the terminal.
Weekly timer
cord/
Wired remote
controller
cord
Cover
WARNING
Strip wires
! WARNING
RAC Adapter
cord
Control line
Indoor Unit
10mm
10mm
160mm
GRN + YEL
Fix the
weekly timer/
wired remote
controller
cord and
RAC adapter
cord by
band.
Arm
Terminal cover
Slot
Step
Slot