TSHK 670...672: Fan-coil room-temperature controller, heating-cooling sequence
For flexible individual-room control in residential and business premises. For quasi-continuous
temperature control of air-conditioning systems (fan-coil). Gradual change-over from heating to cooling
via a sequence characteristic. For 2-point pulsed operation. Suitable for thermal drives, ventilators or
cooling equipment in air-conditioning systems.
Housing 127 75 mm of pure-white (RAL 9010), flame-retardant thermoplastic (fire class as per
UL94 HB). Black baseplate with NTC sensor, electronic evaluation unit and switching relay. Setpoint
adjuster with scale and rear mechanical min./max. limitation of the setting range. Suitable for mounting
onto walls or recessed junction boxes. Cable inlet at rear. Separate terminal compartment with screw
terminals (for wire of max. 2,5 mm2).
Type

TSHK 670 F001


TSHK 671 F001
TSHK 672 F001

Operating mode

Number of
switches

Power

Weight
kg

Heating-cooling sequence; 4-pipe


Heating-cooling sequence; 4-pipe
Heating-cooling sequence; 4-pipe

1
2

230 V~
230 V~
230 V~

0,18
0,18
0,18

Mains switch, on/off


Mode switch
Fan speeds
Indicator
Wiring diagram

T
Y01938

E (control factor)
1

TSHK 670

TSHK 671

TSHK 672

1 LED

A09161

A09162

A09163

Power supply 1)
Switch rating
Ventilator

10%, 50...60 Hz
10(4) A, 230 V~
6 (3) A, 230 V~

Setting range
P-band Xp
Sequence dead zone
Hysteresis1)
Shortest switching period

5...30 C
23K
2 K 0,7
approx. 0,1...0,5 K
approx. 19 min (E = 0,5)

0,5

0
Xp

Time behaviour in air:


still
moving (0.2 m/s)
Ambient temperature
Degree of protection
Protection class

Dead time Time constant


2 min
20 min
1 min
15 min
0...55 C
IP 30 (EN 60529)
II (IEC 60730)

Wiring diagram
Dimension drawing
Fitting instructions

see table
M09206
MV 505680

Xs

Xp
E=0,25

E=0,50

E=0,75

B09204

Accessories
0362239 001* Intermediate cover plate in pure white; fits various recessed junction boxes
*)

Dimension drawing for accessory is available under the same number

1)

The device is electronically made to pulse. The control factor initially falls to nought at the heating output as the temperature rises. After a
dead zone, the control factor rises at the cooling output. The pulsing causes a small temperature deviation of 0,1...0,5 K, depending on
the time constant of the room.

Operation
The room temperature is measured using an internal NTC temperature sensor and then compared
with the setpoint. An electric switching relay is operated in relation to the temperature deviation. When
the setpoint has been reached, the switch moves to the mid-position (OFF). The controllers operating
points are determined by the setpoint, the dead zone and the proportional band.

Sauter Components

7121165003 02

21.165/2 TSHK

Engineering and fitting notes


Fitting position: horizontal on walls, avoiding draughts and insolation, at a height of approx. 1,5 m.
The mechanical restriction on the setpoint adjuster permits adjustment but prevents extreme settings
and, therefore, energy wastage.

Wiring diagrams

TSHK 670

TSHK 670
T

30

25
N

20

15
10

5
B09201

N
L

A09161

TSHK 671

TSHK 671
T

ON

30

C
N

25
OFF

20
15
10

N
L

B09202

A09162

TSHK 672

TSHK 672
T
T

ON

ON

30

C
N

25

5
I

OFF

4
II

3
III

20
15
10

5
B09203

Sauter Components

A09163

7121165003 02

TSHK

21.165/3

Dimension drawing

28,6

75

127

M09206

Accessories
135,5

11,5

83

362239

M09152

Sauter Components

Printed in Switzerland
Right of amendment reserved