Professional Documents
Culture Documents
MASONRY DESIGN
2.1 Structural design of masonry
The structural design of masonry is carried out in accordance with the guidance given in BS
5628 Code of practice for use of masonry. This is divided into the following three parts:
BS 5628 Part 1 - Structural use of unreinforced masonry.
BS 5628 Part 2 - Structural use of reinforced and prestressed masonry.
BS 5628 Part 3 - Materials and components, design and workmanship.
The design of masonry dealt with in this manual is based on Part 1, which gives design
recommendations for unreinforced masonry constructed of bricks, concrete blocks or natural
stone.
2.2 Design Philosophy
The design approach employed in BS 5628 is based on limit state philosophy. In the context of
load bearing masonry its objective is to ensure an acceptable probability that the ultimate limit
state will not be exceeded. Thus for a masonry member, which will be either a wall or a column,
Ultimate design strength ultimate design load
Partial safety factors are applied separately to both the loads and the material stresses in limit
state design.
2.3 Loads
The basic or characteristic load is adjusted by a partial safety factor to arrive at the ultimate
design load acting on a wall.
Characteristic loads
The characteristic loads applicable to masonry design are the same as those defined for concrete
design:
Values of f are given in BS 5628 Part 1 for the following load combinations:
(a) Dead and imposed load
(b) Dead and wind load
(c) Dead imposed and wind load
(d) Accidental damage.
Those for the dead and imposed load combination which would usually apply to vertically
loaded walls are as follows:
Design dead load: 1.4Gk
Design imposed load: 1.6Qk
BS 5628-1:2005 Page 16
Ex 02:
Determine the characteristic compressive strength, fk, of a wall constructed in hollow blocks (as
shown in Figure) of gross area compressive strength 7 N/mm2, if the blocks are filled with
concrete having a 28 day compressive strength equal to that of the blocks and a mortar
designation (iii) is used.
Manufacturing Control
(a) Category I: This category is used when suppliers can meet a specified strength limit (known
as the acceptance limit) when not more than 2.5% of the test results will fall below the
acceptance limit, and also when the suppliers quality control scheme can satisfy the buyer that
the acceptance limit is consistently met.
(b) Category II: This category is used when the supplier can meet the compressive strength
requirements of the appropriate British Standard.
Construction Control
(a) Normal category: Normal category should be assumed whenever the work is carried out
following the recommendations for workmanship in Annex A of BS 5628-3:2001, or BS 8000-3
including appropriate supervision and inspection.
(b) Special Category
Ex 03:
1. Determine the design strength of the brickwork in Example 2, if the manufacturing
control is category I and construction control is normal category.
2. Determine the design strength of the brickwork in Example 2, the manufacturing control
is category I and the construction control is special category.
(b) The clear distance between lateral supports which only provide simple resistance.
10
Ex 04: Determine the slenderness ratio for the wall as shown in Figure, assuming tef = 102.5 mm.
11
Ex 05: Determine the effective thickness of the wall shown in Figure 1-4.
(1)
(2)
(3)
(4)
12
A load applied eccentrically will increase the tendency for a wall or column to buckle and
reduce the load capacity further. This is catered for by using a modified capacity reduction
factor from Table which depends on the ratio of the eccentricity ex to the member thickness.
Design Strength = Capacity Reduction Factor () Characteristic compressive strength (fk)
Partial safety factor for materials (m)
k
m
t
b
The design vertical resistance of a wall per unit length is given by: fk t
13
(a)
Requirement
hef or lef
tef
Slenderness ratio,
Eccentricity of loading
Brick/Block type,
Shape factor,
Mortar designation
Manufacturing control,
Construction control
, k , m , t, b
Page
23
30
Table/Section
Section 4
24.1
Table 7
16
Table 2
22
Table 4(a)
29,30
32.2
Ex 06: A wall has an effective height of 2.25 m and an effective thickness of 102.5 mm. The brick
strength is 15 N/mm2 and the mortar mix is 1 : 1 : 6.
1. The manufacturing control is category II and the construction controls are special.
Determine:
(a) The design strength of the wall,
(b) The loadbearing capacity of the wall.
2. Determine the loadbearing capacity of the wall, when both the manufacturing control is
category II and construction controls is normal.
Ex 07: Determine the design compressive strength of a column, 440 mm 440 mm, 4.4 m clear
height between concrete floors giving enhanced lateral restraint. The bricks have a compressive
strength of 35 N/mm2, and the mortar is designation (ii). The manufacturing control is category
II and construction controls is normal.
Ex 08: A 102.5 mm thick single skin brick wall, as shown in Figure, is built between the concrete
floors of a multi-storey building. It supports an ultimate axial load, including an allowance for
the self-weight, of 250 kN per metre run. What brick and mortar strengths are required if
category II manufacturing and normal construction control apply and the wall is first 10 m long
and secondly only 1 m long?
14
Ex 09: The brick cavity wall shown in Figure supports an ultimate axial load of 150 kN/m
shared equally by both leaves. Select suitable bricks and mortar if both the manufacturing and
construction control are to be normal.
Ex 10: The wall shown in Figure is built of 50 N/mm2 clay bricks set in grade (i) mortar.
Calculate the vertical design strength of the wall if it is 2.4 m high and is provided with simple
lateral support at the top. The category of manufacturing control is to be category II and that for
construction is special.
15
16
The eccentricity is assumed to vary from the value ex at the top of the wall to zero at the
bottom of the wall, subject to an additional eccentricity being considered to cover
slenderness effects.
No slenderness effect need be considered for walls or columns where the slenderness
ratio is less than or equal to 6.
The additional eccentricity may be assumed to vary linearly from zero at top and bottom
of the wall, to a value ea over the central fifth of the wall height where ea is given by:
t
tef
hef
ex
Eccentricity is calculated as:
max
0.6 ex
+ ea
17