You are on page 1of 27

g

GE T&D

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site
Acceptance Test Procedure

Document Number
Version
Revision
Date

:
:
:
:

P3405_SAT_Procedure_Rev0.doc
1
0
14 May 2008

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

NOTICE OF COPYRIGHT & PROPRIETARY RIGHTS

2008, General Electric All rights reserved.


The contents of this presentation are the property of General Electric No part of this work may
be reproduced or transmitted in any form or by any means, except as permitted in written
license agreement with General Electric
The information contained in this document is subject to change without notice.

TRADEMARK NOTICES

WESDAC is a registered trademark of General Electric Company, General Electric and/or GE


Harris Energy Control Systems Canada, Inc. All other brand and product names mentioned in
this document are trademarks or registered trademarks of their respective companies.

P3405_SAT_Procedure_Rev0.doc

ii

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Table of Contents
About This Document.............................................................................................................. vi
Purpose of this Document ....................................................................................................... vi
Definition of Terms ................................................................................................................. vii
Chapter 1 SAT Requirements................................................................................................. 1-1
1.1
Scope of Tests ............................................................................................................. 1-1
1.2
Hardware Environment ............................................................................................ 1-1
1.3
Software Environment............................................................................................... 1-1
1.4
System Availability Tests .......................................................................................... 1-2
1.5
Test Equipment .......................................................................................................... 1-2
1.6
Test Witness................................................................................................................ 1-2
Chapter 2 Communications Equipment and Time Synchronization Equipment Tests .... 2-3
2.1
LAN Communications Functional Check................................................................ 2-3
2.2
Network Management Software (NMS) Check ...................................................... 2-4
2.3
IEC 60870-5-101 Serial Communication Check ..................................................... 2-4
2.3.1 Gateway Communications to PLCC Modem .......................................................... 2-4
2.3.2 IEC 60870-5-101 Serial Communications Verification .......................................... 2-4
2.4
Time Synchronization Tests...................................................................................... 2-5
2.4.1 Time Synchronization Equipment Functional Check .............................................. 2-5
2.4.2 System Time Synchronization Check...................................................................... 2-6
Chapter 3 SAS Operational Tests........................................................................................... 3-1
3.1
System Data Retrieval ............................................................................................... 3-1
3.1.1 Digital Inputs Retrieval............................................................................................ 3-1
3.1.2 Digital Outputs......................................................................................................... 3-2
3.1.3 Analog Inputs........................................................................................................... 3-2
3.2
Software Interlock Logic........................................................................................... 3-3
3.3
Synchronizing Tests ................................................................................................... 3-3
3.3.1 Check Synchronization ............................................................................................ 3-3
3.4
220kV Auto-Sequencing ............................................................................................ 3-4
P3405_SAT_Procedure_Rev0.doc

iii

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

3.4.1

GE T&D

220kV Auto-Sequencing.......................................................................................... 3-4

Chapter 4 HMI/Server Tests................................................................................................... 4-1


4.1
HMI Functions Test................................................................................................... 4-1
4.1.1 Shutdown and Startup of Servers............................................................................. 4-1
4.1.2 HMI Security and Access Test ................................................................................ 4-1
4.1.3 HMI SLDs and Bay Details Screens........................................................................ 4-2
4.1.4 HMI Alarms and Events Processing ........................................................................ 4-2
4.1.5 HMI Trending Display............................................................................................. 4-3
4.1.6 HMI Reports Function ............................................................................................. 4-3
4.2
HMI Server Function Tests....................................................................................... 4-3
4.2.1 HMI Workstation Memory and Disk Utilization..................................................... 4-3
4.2.2 HMI Server Redundancy Checks............................................................................. 4-4
Chapter 5 Substation Controller/Gateway Function Tests.................................................. 5-5
5.1
Gateway IEC 60870-5-101 Data Retrieval............................................................... 5-5
5.1.1 Master Station Digital data Retrieval....................................................................... 5-5
5.1.2 Master Analog data Retrieval .................................................................................. 5-5
Chapter 6 Engineering Workstation (EWS) Tests............................................................... 6-1
6.1
Setting and Configuration of BCUs.......................................................................... 6-1
6.2
Setting of Protection Relays ...................................................................................... 6-1
6.2.1 Setting of UR Relays ............................................................................................... 6-1
6.2.2 Setting of Siemens 7SA522 Relays ......................................................................... 6-1
Chapter 7 Remote Workstation (RWS) Tests ....................................................................... 7-1
7.1
HMI
7-1

P3405_SAT_Procedure_Rev0.doc

iv

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

MODIFICATION RECORD

VERSION

REV.

DATE

INITIALS

COMMENT

16-May-2008

Mahesh
Sathe

Created.

P3405_SAT_Procedure_Rev0.doc

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

About This Document


Purpose of this Document
This document defines the scope and procedure for the Site Acceptance Tests (SAT).
All the tests shall be carried out based on this document. The test results shall be recorded on
SAT Check List. (Refer P3405_SAT Checklist_Rev0)

P3405_SAT_Procedure_Rev0.doc

vi

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Definition of Terms
AI
ASE
BCU
BPU
DBX
DI
DO
COS
EWS
FOC
GDP
HMI
IEC
IED
IRCON
LAN
NMS
OWS
Powergrid
p.u.
SAS
SAT
SIT
SNMP
SNTP
SOE

Analog Input
Applied Systems Engineering Test Kit Manufacturer
Bay Controller Unit
Bay Protection Unit
Data Base Terminal
Digital Input
Digital Output
Change Of State
Engineering Work Station
Fiber Optic Cable
Graphic Display Panel
Human-Machine Interface
International Electrotechnical Commission
Intelligent Electronic Device
short name for IRCON International Limited, Ministry of Railways
Local Area Network
Network Management System
Operator Work Station
short name for Power Grid Corporation of India Limited
Power Units
Substation Automation System
Site Acceptance Test
Site Inspection and Test
Simple Network Management Protocol
Simple Network Time Protocol
Sequence Of Events

P3405_SAT_Procedure_Rev0.doc

vii

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

This page intentionally left blank.

P3405_SAT_Procedure_Rev0.doc

viii

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Chapter 1 SAT Requirements


1.1

Scope of Tests

The Site Acceptance Tests (SAT) will verify that the Substation Automation System (SAS)
functions are per the approved design.
It is not the scope of this SAT document to test the Protection portion of the substation.
The SAT tests have been divided into relevant sections in order to perform the tests
systematically. Upon successful verification of the tests in each section, pertinent forms and
test results shall be completed and signed for acceptance by the customer or its
representative.
After the SAT has been successfully verified, the System Acceptance document will be
signed by representatives from Powergrid, IRCON and GE.

1.2

Hardware Environment

The SAS hardware equipment consist of:


 Bay Control Units in respective Bay Panels in the Kiosks.
 Protection Relays in the Protection Panels.
 HMI/Operator Workstation system consisting of Redundant Servers.
 Engineering Workstation.
 Time Synchronization Equipment consisting of a GPS Receiver Unit, Time Display
Unit and IRIG-B/PPS Distribution Unit.
 Substation Controller/Gateway Subsystem.
 LAN Switch Equipment distributed in the Bay Panels/Kiosk.

1.3

Software Environment

The following Firmware and Software applications are used in the system:
 F650 Firmware Version 3.70 with IEC 61850 (Server) capability.
 F600 Substation Controller, with IEC 61850 (Client) capability.
 D200 Gateway Firmware with support for IEC 60870-5-101.
 UR Protection Relays Firmware Version 5.2, with IEC 61850 (Server) capability.
 Siemens 7SA522 Firmware Version 4.6, with IEC 61850 (Server) capability.
 Siemens DIGSI 4.7TM shall be used in the configuration of Siemens IED.
 HMI using Factory Link 7.5 Platform with IEC 61850 (Client) capability.
The Configuration files and applications are archived in the Engineering Workstation.

P3405_SAT_Procedure_Rev0.doc

1-1

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

1.4

GE T&D

System Availability Tests

The 1000 hours system availability test will be covered in another document.

1.5

Test Equipment

To conduct the test procedures outlined in this document, the following equipments are
required to be arranged by M/S IRCON and supplied at site.
- Digital Multimeter.
- 3 Phase Current and Voltage Injection kit - if the bays are not commissioned.
- Protocol Analyzer. (Optional item)

1.6

Test Witness

IRCON/Powergrid shall provide a Representative to witness and sign-off this SAT.

P3405_SAT_Procedure_Rev0.doc

1-2

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Chapter 2 Communications Equipment


and Time Synchronization Equipment
Tests
2.1

LAN Communications Functional Check

Purpose
1. To verify that LAN Switch Backbone redundancy is functional and running.
2. To verify that Ethernet LAN communications in the Substation Automation System
are functional and running.
Set up/Program
1.

In the HMI, navigate to Communication Network Architecture.

2.

Setup multiple Ping screens in the EWS to different devices in the system.

Procedure
LAN SWITCH BACKBONE - REDUNDANCY CHECK.
[ ] 1 Select LAN Switch SW-4A. On this LAN Switch, disconnect the LAN cable
connected to SW-01A. (i.e. Port 14 on SW-1A)
[ ] 2 Verify in the Ping screens and the HMI Communications Summary Screen
that there is no communication failure of the devices in the system.
[ ] 3 On LAN Switch SW-1A, disconnect the LAN cable connected to SW-02A
(i.e. Port 17 on SW-1A).
[ ] 4 Repeat step 2.
[ ] 5 Restore LAN cables on SW-1A.
[ ] 6 Select other Backbone switches and the network should remain undisturbed
for any 2 failures in the communication network.
[ ] 7 These link failures should be indicated in the Alarm List. Verify the same at
every step of the test.

P3405_SAT_Procedure_Rev0.doc

2-3

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

2.2

GE T&D

Network Management Software (NMS) Check

Purpose
1. To verify that NMS software is functional and running
Set up/Program
2. OWS-1, OWS-2 are running under normal conditions.
Procedure
NMS SOFTWARE.
[ ] 1 Start the NMS Viewer (iSNMP DataViewer)
[ ] 2 Verify that the LAN Port status and the Network Analyst Data is valid.
[ ] 3 This data is represented in the graphical form in the HMI.

2.3

IEC 60870-5-101 Serial Communication Check

2.3.1 Gateway Communications to PLCC Modem


Purpose
To verify Gateway communications to PLCC Modem.
Setup
1.

Using the EWS, connect to D200 Gateway.

2.

Ensure the communications cable to gateway to NSK5 modem is connected to


the correct ports of the NSK5 modem.

Procedure
[ ]1
[ ]2
[ ]3
[ ]4

On the Gateway Wesmaint screen, go to 68k Monitor.


In 68k Monitor, bring up the serial analyzer function by typing at the prompt
sa com 1.
Observe that IEC 101 transmit packets are captured in the screen.
This will test communications up to the output of the NSK5 modem.

2.3.2 IEC 60870-5-101 Serial Communications Verification


Purpose
To verify that the Gateway IEC 60870-5-101 communications to PLCC modem are
functional.
 Notes:
a) PLCC communication equipment is supplied by others. IEC 60870-5-101
communications shall be tested up to modem serial port.
b) To test IEC 60870-5-101 communications to RSCC, coordination is required.

P3405_SAT_Procedure_Rev0.doc

2-4

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Set up/Program
1.

If the LDC communication is up and running, the data can be verified with the
LDC. In absence of this connection, use an ASE Test Set to simulate IEC 608705-101 Master Station polling at the cable connection to PLCC modem.

Procedure
[ ]1
[ ]2

[ ]3

2.4

Verify that communication is established with the ASE test set.


Verify that the ASE test set is sending request on the primary channel and that
the SAS Gateway is responding on both the primary and the secondary
channels.
Disconnect the ASE test set from the primary channel and connect it to the
secondary channel; verify that the SAS Gateway will respond on both
channels to requests received on the Secondary channel

Time Synchronization Tests

2.4.1 Time Synchronization Equipment Functional Check


Purpose
To verify that the following components of the Time Synchronization Equipment are
functional and receiving satellite time updates:
1.

GPS Receiver

2.

External Time Display Unit

Procedure
[ ]1
[ ]2

[ ]3

[ ]4
[ ]5

[ ]6

[ ]7

Disconnect the GPS Receiver Antenna. Set the GPS Receiver to send Local
Time. Change the value of this local time to 00:00:00.
Verify that the External Time Display Unit displays this local time. This
confirms that the IRIG-B signal from the GPS unit to the Time Display Unit is
functional.
Verify that the IEDs, Operator Workstations and Substation Gateway times
match this local time. This confirms that the SNTP packets are broadcasted by
the GPS receiver and received by the end devices.
Verify that GPS Receiver Out-of-Lock Alarm is received in the OWS.
Restore the GPS Receiver Antenna connection. Verify that the GPS Receiver
is locked up to at least 3 satellites. Verify that the GPS is updated to satellite
time.
Verify that the IEDs, Operator Workstations and Substation Gateway times
match this satellite time update. This confirms that the time updates are
broadcasted by the GPS receiver and received by the end devices.
Confirm that the External Time Display Unit is also updated to the new time.

P3405_SAT_Procedure_Rev0.doc

2-5

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

2.4.2 System Time Synchronization Check


Purpose
To verify that the GPS System time is received by all SAS devices and working
according to the time synchronization requirements of IEC 61850.
Procedure
SAS IED TIME SYNCHRONIZATION
[ ] 1 Change the time on one Bay control unit (BCU) by a few minutes.
[ ] 2 The device will get synchronized over SNTP and the time will automatically
adjust to the correct time
[ ] 3 Repeat Step 3 for a few sample BCUs.
HMI EQUIPMENT
[ ] 4 Set the Primary or the secondary server to an incorrect time.
[ ] 5 The machine will automatically synchronize over SNTP with the GPS clock.
[ ] 6 Repeat the procedure on the Engineering workstation.

P3405_SAT_Procedure_Rev0.doc

2-6

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Chapter 3 SAS Operational Tests


3.1

System Data Retrieval

3.1.1 Digital Inputs Retrieval


Purpose
To verify that:
1. The change of state and SOEs of Digital Input points are updated in the BCU GDP
and the Substation HMI Operator Workstations.
2. That selected SOEs according to the IEC 60870-5-101 mapping table are updated in
the Master Station.
Setup
1.

On the GDP of the BCU under test, go to the Digital Inputs display screen.

2.

On the Operator Workstation 1 (OWS-1), go to the Point Detail Screen

3.

On the Operator Workstation 2 (OWS-2), go to the Alarm Screen.

Procedure
[ ]1
[ ]2

[ ]3
[ ]4
[ ]5
[ ]6

Select a BCU to test.


From the field, simulate the Digital Input points on the BCU under test by
changing their states from OFF to ON (single points) or from OPEN to
CLOSED (double points).
Verify that the change of state in the BCU GDP.
Verify the same in both the servers.
For points configured with alarm, verify that alarms are displayed in the
Alarm Screen with correct time stamps.
Repeat steps 1 to 5 for sample Digital Input points on the BCU.

P3405_SAT_Procedure_Rev0.doc

3-1

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

3.1.2 Digital Outputs


Purpose
To verify that digital output operations are successfully executed.
Setup
1.

On the GDP of the BCU under test, go to the single line display.

2.

On the Operator Workstation 1 (OWS-1), go to the bay detail under test.

3.

On the Operator Workstation 2 (OWS-2), go to the Alarm/Event Screen.

Procedure
[ ]1
[ ]2

From the Operator Work Station, initiate digital output requests to the BCU
under test.
Verify that the corresponding outputs are activated.

3.1.3 Analog Inputs


Purpose
To verify that the Analog Input points are updated in the BCU GDP, the Operator
Workstations.
Setup
1.

Select Bay under normal operations

2.

Go to the BCU GDP Display screen.

3.

Go to the bay detail screen on the Operator Workstations.

Procedure
AC ANALOG INPUTS

[ ]1
[ ]2

Verify that the correct readings are presented in the BCU GDP display screens
and the HMI Point Detail Screens for the injected voltage and current values.
Confirm that the corresponding readings are updated.

3.
DC ANALOG INPUTS

 Note that only the Transformer and Reactor Bays have BCUs to monitor DC
Analogs.
[ ]1

Verify that the correct readings and accuracy are presented in the BCU GDPs
and the HMI Point Detail Screens for the s4-20mA transducer outputs.

P3405_SAT_Procedure_Rev0.doc

3-2

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

3.2

GE T&D

Software Interlock Logic

Purpose
To verify that software interlock logic for CBs and Isolators are operational based on
actual field conditions.
 If all interlock conditions cannot be set during SAT, the interlock inputs (auxiliary
contacts) shall be simulated in the field.
Procedure
[ ]1
[ ]2

3.3

Select a bay to test.


Refer to protection schematic drawings. For each interlock condition, attempt
to operate controls related to the interlock logic being tested. Verify that the
interlock is successful.

Synchronizing Tests

3.3.1 Check Synchronization


Purpose
1. To verify that Incoming and Running (Reference) voltages are within the
synchronizing range before the circuit breaker can close. The circuit breaker will not
close if any of the limiting parameters is not within the check synchronizing range.
2. To verify that the running voltage reference is properly selected (voltage selection)
depending on isolator switch conditions.
Procedure
[ ]1
[ ]2
[ ]3
[ ]4
[ ]5

Select a BCU and corresponding Circuit Breaker to test.


Verify the voltage selection based on the isolator status.
Verify the voltage reading in the Enervista F650 setup software for the
synchrocheck function.
Initiate a Close request on this Circuit Breaker.
Verify that the Circuit Breaker closes only when configured settings are met.

P3405_SAT_Procedure_Rev0.doc

3-3

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

3.4

GE T&D

220kV Auto-Sequencing

3.4.1 220kV Auto-Sequencing


Purpose
To verify that the 220kV Auto-Sequencing logic functions correctly.
Setup
Ensure that the HMI Servers are running.
Procedure
[ ]1
[ ]2
[ ]3
[ ]4
[ ]5
[ ]6

Select a Feeder to test.


Turn ON the Auto-sequencing controls.
Click Transfer to TBC or the Transfer Bus sequence.
Verify the Transfer Logic Status as well as the actual isolators being
controlled.
The sequence can be aborted at any given time by using the abort Set
button.
Repeat above tests with negative conditions e.g. another Feeder is already on
Transfer Bus. Verify that the appropriate alarms are indicated and operation is
not permitted.

P3405_SAT_Procedure_Rev0.doc

3-4

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Chapter 4 HMI/Server Tests


4.1

HMI Functions Test

4.1.1 Shutdown and Startup of Servers


Purpose
To verify that the HMI Redundancy is operational during shutdown of the active server.
Setup
1.

Ensure that the HMI Servers are running.

Procedure
[ ]1
[ ]2
[ ]3

With both Servers running, and the HMI client is running under normal mode.
Shutdown the Active Server. (say OWS-1)
Observe that the Standby server takes over and becomes the Stand-alone
HMI server.
[ ] 4 Restore the machines (Startup OWS-1). Observe that there is no interruption
to the Bay level devices.
[ ] 5 Observe that Viewer clients attach to OWS-1 and remote devices are still
normal and communicating with OWS-2.
Observe that the system is back to normal.

4.1.2 HMI Security and Access Test


Purpose
To verify that the OWS/HMI system has Security Classes; that these are enabled and
configured properly.
Setup
1.
Procedure
[ ]1
[ ]2

Ensure that the HMI Servers are running.


At Primary Server, Login as the observer user.
Verify that this user class has proper access level as per HMI Security
P3405_SAT_Procedure_Rev0.doc

4-1

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

[ ]3
[ ]4
[ ]5

GE T&D

Classification.
Go to any bay detail screen. Verify if access to tool bar and object controls are
according to the allowed in the access level logged in.
Repeat steps 1 to 4 for the other HMI Usernames (Operator and
Administrator).
Repeat steps 1 to 4 on Secondary Server.

4.1.3 HMI SLDs and Bay Details Screens


Purpose
To verify that the Single Line Diagram and Bay Detail Screens in the OWS/HMI system
are configured properly and are in correct operating condition.
Setup
1.

Ensure that the HMI Servers are running.

2.

Log in as an Operator.

Procedure
[ ]1
[ ]2
[ ]3
[ ]4
[ ]5
[ ]6

Verify the layout of each One-Line screen.


Verify the device number and device description for each device.
Verify all displayed analog and digital values in One-Line screens.
Click on each device object and confirm that the correct pop up screen or
bay/device detail screen is displayed.
Repeat steps 1 to 4 for each One-Line screens.
Repeat steps 1 to 5 for each Workstation.

4.1.4 HMI Alarms and Events Processing


Purpose
To verify that the Alarm and Event Points are configured properly and are in correct
operating condition.
Setup
1.

Ensure that the HMI Servers are running.

2.

Display the Alarm Logger Screen.

Procedure
[ ]1
[ ]2
[ ]3
[ ]4
[ ]5

Select a Digital Input point from one of the BCUs configured as an Alarm.
Change the state of the selected point.
Confirm that an Alarm is displayed in the Active Alarm Logger screen with
proper description and Time Stamp.
Acknowledge this alarm.
Locate the Event History screen and verify that this alarm is displayed and that
it is acknowledged.
P3405_SAT_Procedure_Rev0.doc

4-2

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

[ ]6

GE T&D

Repeat steps 1 to 5 for several Digital Input points that are configured as
Alarms (Events).

4.1.5 HMI Trending Display


Purpose
To verify that the trending in the OWS/HMI system are configured properly and are in
correct operating condition.
Setup
1.

Ensure that the HMI Servers are running.

2.

Go to the trending screen.

Procedure
[ ]1
[ ]2
[ ]3
[ ]4

Select Pen Editor Form.


Verify that a Pen Select screen pops up.
Assign a point to the selected pen.
Repeat step 3 for other pens.

4.1.6 HMI Reports Function


Purpose
To verify that the Reports Function in the OWS/HMI system are configured properly and
are in correct operating condition.
Setup
Ensure that the HMI Servers are running.
Procedure
HISTORICAL REPORTS
[ ] 5 Go to the Statistical Report Screen.
[ ] 6 Select an analog value to print. Select the range of date by selecting the start
and stop dates.
[ ] 7 Save the report as a CSV file.
[ ] 8 Print CSV file. Confirm that the file is printed.
DAILYREPORTS
[ ] 9 Verify that the daily reports are prepared in the Reports folder.
[ ] 10 Verify the validity of the data in the report.

4.2

HMI Server Function Tests

4.2.1 HMI Workstation Memory and Disk Utilization


Purpose
P3405_SAT_Procedure_Rev0.doc

4-3

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

To verify that the Operator Workstation/HMI Computers have Memory and Disk usage and
allocation that are within specification requirements.
Setup
1.

Ensure that the HMI Servers are running.

Procedure
[ ]1
[ ]2
[
[
[
[
[

]3
]4
]5
]6
]7

On the Primary HMI (OWS-1), open the WindowsTM Operating System Task
Manager. Note that the OWS Computers have server grade operating system.
Select the Performance tab, take note of the Total and Available
Physical Memory information.
Calculate the percentage of available memory. Close the Task Manager.
Open Windows Explorer. Check the properties of the Hard Drive volume.
Calculate the current usage.
Record the information.
Repeat for the rest of the workstations.

4.2.2 HMI Server Redundancy Checks


Purpose
To verify that the HMI Redundancy is operational during simulated loss of Level 2
communications.
To verify that the HMI Workstations support redundant LAN communications.
Setup
1.

Ensure that the HMI Servers are running.

2.

The OWS-1 (Primary Server) is the active server.

3.

The OWS-2 (Secondary Server) is in Standby Mode.

Procedure
[ ]1
[ ]2
[ ]3
[ ]4
[ ]5

Verify that the devices are online with the HMI.


On OWS-1 (Primary Server), disconnect LAN-A cable. Observe that Viewer
clients and remote devices are still normal and communicating with OWS-1.
On OWS-1, now disconnect LAN-B cable. Observe that all the devices go
Offline.
Initiate a switchover to make OWS-2 (Secondary Server) the active HMI
Server.
Restore the LAN connections and system is back to normal operation.

[ ]6

P3405_SAT_Procedure_Rev0.doc

4-4

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Chapter 5 Substation
Controller/Gateway Function Tests
5.1

Gateway IEC 60870-5-101 Data Retrieval


 Note: This section of tests will need coordination with the Master Station

5.1.1

Master Station Digital data Retrieval

Purpose
To verify that the Substation Gateway correctly responds to polls for Digital Input and
SOE data by the Master Station.
Procedure
[ ]1
[ ]2
[ ]3

Select a Bay to test.


Verify the Switchgear Status with the Master Station.
Verify that SOE and COS data are received and updated in the Master Station.

5.1.2 Master Analog data Retrieval


Purpose
To verify that the Substation Gateway correctly responds to polls for Analog data
from the Master Station.
Procedure
[ ]1
[ ]2

Select a Bay to test.


Verify the analog values with the Master Station.

P3405_SAT_Procedure_Rev0.doc

5-5

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

This page intentionally left blank.

P3405_SAT_Procedure_Rev0.doc

5-6

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Chapter 6 Engineering Workstation


(EWS) Tests
6.1

Setting and Configuration of BCUs

Purpose
To verify that the BCUs can be configured online or offline using Enervista Software.
Setup
Ensure that the EWS is running.
Procedure
[ ]3
[ ]4
[ ]5

6.2

Run the Enervista F650 Setup application in the EWS.


Change some parameters on this BCU. Store the configuration. Observe that
the parameter changed is now active.
Download the original configuration file for this BCU. Observe that the
parameters changed in the previous step are now changed to the original
values.

Setting of Protection Relays

6.2.1 Setting of UR Relays


Verify the software functionality in the EWS

6.2.2 Setting of Siemens 7SA522 Relays


Verify the software functionality in the EWS.

P3405_SAT_Procedure_Rev0.doc

6-1

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

This page intentionally left blank.

P3405_SAT_Procedure_Rev0.doc

6-2

400/220kV Ludhiana/Gwalior Substation


Substation Automation System - Site Acceptance Test Procedure

GE T&D

Chapter 7 Remote Workstation (RWS)


Tests
7.1

HMI

Purpose
To verify that the Remote HMI function.
Setup
The Remote HMI computer is on the Local Area Network in the control Room.
Procedure
[ ]1
[ ]2
[ ]3
[ ]4

Run the HMI Client.


Log-in the HMI using different user name like Operator, Admin to verify
the access rights
Navigate through the various screens in the HMI along with the
Alarms/Events screen.
Initiate control commands to verify the functionality.

P3405_SAT_Procedure_Rev0.doc

7-1

You might also like