Specification for Survelliance System AD177-NSG-T-SPC-05723


Section No.
Section description
1
Introduction
1.1
Purpose
1.2
Scope
2
Abbreviations and Definitions
2.1
Abbreviations
2.2
Definitions
3
Reference documents
3.1
Project Specification and Guidelines
3.2
Industry codes and standards
3.3
Other codes and standards for Telecommunication
4
Requirements
4.1
General
4.1.1
Cabling
4.1.2
Electrical Power
4.1.3
Hazardous Area Classification
4.1.4
Expnadability
4.1.5
Reliablity
4.1.5.1

4.1.5.2

4.1.6
4.1.6.2

4.1.6.3
4.1.7
4.1.7.1
4.1.7.2
4.1.7.3
4.1.7.4
4.1.8
4.1.9
4.1.9.1
4.1.9.2
4.1.9.3
4.1.10
4.1.11
4.1.12

The Surveillance System designs shall be such that no single component or wiring failure
shall cause a complete malfunction of the system with resilience provided by automated
failover mechanisms.
The MTBF for the systems shall be more than 25,000 hours with project supply voltage,
temperature, and humidity. The provided Surveillance System shall include the capability
to replace faulty units without affecting the functionality of other healthy sub systems or
components.
Maintainability
The Surveillance System shall include self-diagnostic algorithms to continually monitor the
health and status of the entire system, including wiring, and provide alarm annunciation for
detected aberrations.
The MTTR of the system shall be less than one (1) hour with the spares and technician
available on site.
Availability
The Surveillance System design shall utilize high availability technologies with intrinsic
availability for the provided equipment not less than 0.99996 where:
Availability (Intrinsic) = MTBF / (MTBF + MTTR)
Operational Availability shall not be less than 0.99990 where:
Availability (Operational) = MTBM / (MTBM + MDT)
Serviceability
Software
General
Programming
Licenses and Installation
Comprehensive of Design
Enviromental Condition
Coatings

Compliance

Non- Compliance

Remarks

4.1.13
4.2
4.2.1
4.2.2
4.2.2.1

4.2.2.2

4.2.2.3

4.2.2.4

4.2.2.5

4.2.2.6

4.2.2.7
4.2.2.8

Standard measurement Units


Functional
Overview
General
The Surveillance System head end equipment electronics shall be installed on the
Accommodations Platform of the NSSC. Each well head tower will contain equipment that
will be controlled and monitored at the Accommodations Platform.
The system shall have redundant servers, one acting as a primary server and the other
acting as a hot standby server.
It shall be possible to remove one of the Surveillance System servers for maintenance
without interrupting system operation. After reconnecting the removed server, it shall
rebuild the databases and configurations automatically before returning to hot standby
mode of operation.
Surveillance System shall provide for daily backups of the Surveillance related data using
automatic backup devices and procedures.
Surveillance System servers and workstations shall be connected via the Surveillance
LAN (by others). The system shall extend to all platforms via SDH nodes connected by
single mode fiber optic cable. See AD177-NSG-T-SPC-05718, Local Area Network
Specification, for Surveillance LAN details.
It shall be possible to view, manipulate, and analyze data acquired from the various subsystems through a common operator interface at any of the Surveillance System Consoles
connected to the Surveillance System LAN.
The Surveillance System shall utilize video cameras of the CCTV System for the Intrusion
Detection System.
The system shall provide customized graphics of the facilities, as well as graphic displays
of Surveillance System status and performance.
The system functionality shall include but not be limited to the following:

system on Redundant Array of Independent Disk


images data on an First In, First Out basis.
4.2.2.9

time between changes

4.2.3
4.2.3.1
4.2.3.2

Access Control Readers


Access Control Readers shall be designed to allow employees, and visitors access to the
facility using an identification card at points of entry/exit.
The system will optionally be utilized for locating personnels physical locations on
platforms, buildings, and rooms.

4.2.3.3

4.2.3.4
4.2.3.5
4.2.3.6
4.2.3.7

4.2.3.8

The Access Control Readers Head End equipment (Enrollment Scanner / Badge Printer /
Surveillance PIN Workstation) shall be on the Accommodations Platform, located in the
associated security personnel office area.
The Access Control Reader software shall include Visitor Management and Time &
Attendance applications.
The system shall support anti-pass back function.
The Access Control Readers shall not affect the mechanical locking or panic bar exit
operation.
All information included in access card shall be configurable by an operator with
appropriate access level from the card detail display.
Based on IN and OUT logged status of personnel, during an emergency evacuation, the
access control system shall be able to generate reports identifying the presence of
personnel at various locations.
Access Control Readers shall be located as a minimum at:

4.2.3.9

An Access Card printer shall be provided at the accommodations platform that can be
used to produce fully functional photo identification access cards. The printer shall have
the following features as a minimum:
4.2.3.10

4.2.4

4.2.4.1
4.2.4.2

4.2.4.3

4.2.4.4

4.2.4.5

Personnel location Monitoring(RFID)


The system will make identification checks invisible and eamless to employees, visitors,
and guests inside specific designated areas. The system components consist of badge
tags and readers with antennas.
The system will be transparent to employees and visitors, and have no impact on access
to the facility.
The system will be utilized for determining physical locations of personnel throughout the
NASR FFD facilities.
The Personnel Location Monitoring Head End equipment (workstation with software) shall
be on the Accommodations Platform, located in the associated security personnel office
area.
All information included in tags shall be configurable by an operator with appropriate
access level
from the workstation.
The Personnel Location Monitoring system shall not affect the operation of any other
system.

4.2.4.6

During an emergency evacuation, the Personnel Location Monitoring system shall be able
to generate reports identifying presence of personnel at predetermined locations.

4.2.4.7

Badge Tags
Minimum requirements are as follows

4.2.4.8

4.2.4.9

4.3

4.3.1

Reader
Minimum requirements are as follows:
Antenna
The antenna type controls where tags are read, detects tags in any orientation relative to
the antenna with minimal impact on RSSI. Antenna shall be designed for indoor or outdoor
use and
conform to ETS 300 019.
Intrusion Detection
Intrusion Detection Radar
The small target detection radar shall be X-band frequency Radar with 16NM (29km)
range. Each
well head tower, the accommodations and the gas treatment platforms will be equipped
with a
minimum of two radars. Locations shall be on diagonal corners of decks to encompass a
full field
of detection.
Intrusion Detection Cameras
Intrusion detection cameras shall be integral with intrusion detection radar systems and
each shall
have the following capabilities as a minimum:

4.3.2

CCTV Cameras for the Surveillance System


The CCTV cameras shall be installed with visible coverage of the following as a minimum:
4.3.3

These CCTV cameras are specified in the CCTV Specification AD177-NSG-T-SPC05715.

4.3.4

Intrusion Detection Acoustic Hailer


The hailing equipment will be a directional beam used to communicate verbal warnings to
deter
accidental or inadvertent intruders.
The hailer will produce a warning tone.
Each wellhead tower will include a minimum of two devices located in the same area as
the
Surveillance Radar and cameras.
The speakers connected to the intrusion system shall be also used to convey messages
from the
CCR operator if he notices any intrusion through cameras.

Operator Console
The Surveillance System operating console functionality is integrated with the ICSS HMI
consoles
and shall include the following features and capabilities:

4.4

The Surveillance System and ICSS CONTRACTORs are responsible for integrating
Surveillance
System operating features and capabilities into the ICSS HMI consoles.
The Surveillance System servers, switches, workstations, and system software shall be in
accordance with ADMA-OPCO standards prevailing at the time of purchase.
5
5.1
5.1.1
5.1.2
5.1.3
5.1.4
5.2

Testing
FAT
Perface
Contract / Purchase Order
FAT
Punch Lists
Site Acceptance Test