PL-RSA, PL-RSF and PL-RSC

Analog Wall Sensors for Prolon


PRODUCT OVERVIEW
The PL analog wall sensor family is specifically designed for Prolon VC500 and VC1000 controllers in
order to interface with fan coil, heat pump, rooftop & other terminal unit building automation controls.
The units provide precision indoors local temperature sensing. Local setpoint adjustment with various
scales is available.
The modern attractive low profile enclosure is suitable for classrooms, hotels, executive areas, office
spaces & other commercial areas.
Mounting hardware with a separate sub base is provided with the units for installation on dry wall or a
2x 4 electrical junction box.

MODELS, FEATURES & OPTIONS


Features

Benefits

Local temperature
Tenant override button

10K type 3 NTC Thermistor 3% precision


An embossed membrane momentary open switch can be provided
to act as a local override button to current system status The
override button operates in parallel with the temperature sensor
Standard set point potentiometer of 10K
7.26 K at 21 C, 70 F
Potentiometer is direct acting and has 20 % tolerance across the
range. Available frontal scales available are:

+/
40 to 90 F

5 to 30 C

Tenant set point

PLRSA
X
X

PLRSF
X
X

PLRSC
X
X

X
X
X

SPECIFICATIONS
Operating Conditions:
Storage Conditions:
Sensor:
Set point Potentiometer:

-20C to 50C (-4F to 122F) 0 % to 95 % R.H. non-condensing


-40C to 80C (-40F to 176F) 0 % to 95 % R.H. non-condensing
Local 10K type 3 NTC Thermistor 3% precision
Local 10K direct acting setpoint potentiometer. 20 % tolerance across the range
7.26 K at 21 C, 70 F

RESISTANCE -vs- TEMPERATURE CHART and DIMENSIONS


C
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0
22.0
23.0
24.0
25.0
26.0
27.0
28.0
29.0
30.0
31.0
32.0

F
41.0
42.8
44.6
46.4
48.2
50.0
51.8
53.6
55.4
57.2
59.0
60.8
62.6
64.4
66.2
68.0
69.8
71.6
73.4
75.2
77.0
78.8
80.6
82.4
84.2
86.0
87.8
89.6

Kohm
23.652
22.602
21.604
20.656
19.755
18.897
18.082
17.306
16.567
15.864
15.194
14.556
13.949
13.369
12.817
12.291
11.789
11.310
10.853
10.416
10.000
9.601
9.219
8.855
8.508
8.175
7.858
7.554

Fig.1 PL wall sensor dimensions

WIRING
Generic wiring all models

1
2

Normally open
Momentarily closed
Override button

10K type 3 NTC thermistor


3% precision

10K Ohms DA setpoint potentiometer


20% tolerance
7.26 K Ohms at 21 C, 70 F
Resistance increases on CW rotation

4
Fig.3 Generic PL wall sensor wiring

PL WALL SENSOR INSTALLATION


Important: All wiring must conform to local and national electrical code regulations.
To avoid problems, carefully follow the procedures below.
A) Location:
1- Should not be installed on an outside wall.
2- Must be installed away from any heat source.
3- Should not be installed near an air discharge grill.
4- Should not be affected by direct sun radiation.

Wiring terminal

5- Nothing must restrain vertical air circulation to the sensor.

Security screw
Fig. 3 PL wall sensor cover removal and wiring terminal location

B) Installation:
1- Remove security screw on the bottom of thermostat cover.
2- Open up by pulling on the bottom side of thermostat.
3- Pull out cables 6 out of the wall.
4- Wall surface must be flat and clean.
5- Insert cable in the central hole of the base.
6- Flip printed circuit board to access mounting hole
7- Align the base and mark the location of the two mounting
holes on the wall. Install proper side of base up.
8- Install anchors in the wall.
9- Insert screws in mounting holes on each side of the base.
DO NOT OVERTIGHTEN
10- Strip each wire 1/4 inch.
11- Insert each wire according to wiring diagram.
12- Gently push back into hole excess wring back into the wall.
13- Press back printed circuit board into place
Flip printed circuit
14- Install the cover, top side
board to access
15- Install security screw.

Wall Anchor

Pull on plastic tab


to release the
printed circuit board

Security Screw

mounting hole

Fig.4 PL wall sensor installation

All PL series controls are for use as operating controls only and are not safety devices. These instruments have
undergone rigorous tests and verifications prior to shipment to ensure proper and reliable operation in the field.
Whenever a control failure could lead to personal injury and/or loss of property, it becomes the responsibility of the
user / installer / electrical panel designer to incorporate safety devices (such as relays, flow switch, thermal
protections, etc) and/or alarm systems to protect the entire system against such catastrophic failures. Any
abusive use of the product will void the warranty.

028-0108

PL-RSC_E

Copyright 2006 Prolon. All rights reserved.

No part of this document may be photocopied or reproduced by any means, or translated to another language without prior written consent of Prolon.

All specifications are nominal and may change as design improvements are introduced.
Prolon shall not be liable for damages resulting from misapplication or misuse of its products.
All other trademarks are the property of their respective owners.