You are on page 1of 6

Vector Group = Dyn11

During Earth fault voltage between Ne


Earth Fault current will be limited to = 5
N.G.R. value in ohm = V / I = (
Value of N.G.R.
NGR are inserted On Higher vo

Vector Group = Dyn11


During Earth fault voltage between Ne
Earth Fault current will be limited to = 5
N.G.R. value in ohm = V / I = (
Value of N.G.R.
NGR are inserted On Higher vo

Typical shunt calculations fro 5 MAV 20/6.

Vector Group = Ynd1


Vector Group = Dyn11
During Earth fault voltage between Neu
Earth Fault current will be limited to = 5
N.G.R. value in ohm = V / I =

Value of N.G.R.
NGR are inserted On Higher vo

200 to 400 A rated Neutral Grounding Resistors are generally used in 6.9 kV to 34.5 k

During Earth fault voltage between Neu


Earth Fault current will be limited to = 5
N.G.R. value in ohm = V / I
Value of N.G.
NGR are inserted On Higher vo

http://cr4.globalspec.com/thread/6144

iT IS ISMILAR TO THE GROUND RESITOR CALCULATION FOR TRANSFOM


THE TYPICAL EXAMPLE WAS ANSWERED EARLIER FOR TRANSFORMER D
Neutral of transformer can be grounded solidly earthed OR with Neutral

Typical shunt calculations fro 5 MAV 11/6.6 kv transformer neutral are as


Transformer rating = 5 MVA
Voltage ratio = 11/6.6 KV
Vector Group = Dyn11 (6.6 KV ground through Resistor)
During Earth fault voltage between Neutral & Earth = 6.6/3 = 3.81 KV
Earth Fault current will be limited to = 5 x 10 /(3 x 6.6) = 437.38Amp
N.G.R. value in ohm = V / I = (3.81 x 10) / 437.38 = 8.71 Ohm
Value of N.G.R. is 437.38 Amp, 8.71 Ohm., 10 Sec
NGR are inserted On Higher voltage to restrict earth fault current

Transformer rating = 5 MVA


Voltage ratio = 11/6.6 KV
Vector Group = Dyn11 (6.6 KV ground through Resistor)
ault voltage between Neutral & Earth = 6.6/3 = 3.81 KV
ent will be limited to = 5 x 10 /(3 x 6.6) = 437.38Amp.
value in ohm = V / I = (3.81 x 10) / 437.38 = 8.71 Ohm
Value of N.G.R. is 437.38 Amp, 8.71 Ohm., 10 Sec
e inserted On Higher voltage to restrict earth fault current

Transformer rating = 5 MVA


Voltage ratio = 11/6.6 KV
Vector Group = Dyn11 (6.6 KV ground through Resistor)
ault voltage between Neutral & Earth = 6.6/3 = 3.81 KV
ent will be limited to = 5 x 10 /(3 x 6.6) = 437.38Amp.
value in ohm = V / I = (3.81 x 10) / 437.38 = 8.71 Ohm
Value of N.G.R. is 437.38 Amp, 8.71 Ohm., 10 Sec
e inserted On Higher voltage to restrict earth fault current

lations fro 5 MAV 20/6.6 KV transformer neutral are as :_


Transformer rating = 5 MVA
Voltage ratio = 20/6.6 KV
Vector Group = Ynd11 (20 KV ground through Resistor)
Vector Group = Dyn11 (6.6 KV ground through Resistor)
ult voltage between Neutral & Earth = 20.0/3 = 11.5 KV
nt will be limited to = 5 x 10 /(3 x 20.0) = 144.3 Amp.
value in ohm = V / I = (11.5 x 10) / 144.3 = 80.0 Ohm

Perhitungan NGR Sisi 6.6 KV


3.8 KV
437.4 Amp
8.7 Ohm

Perhitungan NGR Sisi 11.0 KV


6.4 KV
262.4 Amp
24.2 Ohm

Perhitungan NGR Sisi 20 KV


11.5 KV
144.3 Amp
80.0 Ohm

Value of N.G.R. is 144.3 Amp, 80.0 Ohm., 10 Sec


e inserted On Higher voltage to restrict earth fault current

d in 6.9 kV to 34.5 kV systems (Se note below).

ult voltage between Neutral & Earth = 20.0/3 = 11.5 KV


nt will be limited to = 5 x 10 /(3 x 20.0) = 144.3 Amp.
R. value in ohm = V / I = (11.5 x 10) / 200 = 57.7 Ohm
Value of N.G.R. is 200 Amp, 60.0 Ohm., 10 Sec
e inserted On Higher voltage to restrict earth fault current

Ref.
spec.com/thread/61442/Earthing-Resistor-Calculation

Perhitungan NGR Sisi 20 KV


11.5 KV
144.3 Amp
80.0 Ohm

R CALCULATION FOR TRANSFOMER


EARLIER FOR TRANSFORMER DT.19-06-2009
solidly earthed OR with Neutral Grounded with Resistance.
.6 kv transformer neutral are as :_

hrough Resistor)
ral & Earth = 6.6/3 = 3.81 KV
x 10 /(3 x 6.6) = 437.38Amp.
0) / 437.38 = 8.71 Ohm

estrict earth fault current

an NGR Sisi 6.6 KV

an NGR Sisi 11.0 KV

an NGR Sisi 20 KV

an NGR Sisi 20 KV
11.5 KV
200 Amp
57.7 Ohm

Input Amp ~ 200 Amp