Calculation Note

Design Of Sluice Valve Chamber

Rev.

Status
1

Date

2-Mar-16

Status Code (Status):

1 = issued for Approval

Prepared

Reviewed Approved Description

3 = issued for order

2 = issued for information

4 = issued for site fabrication

Document Acceptance Code


A

Approved

Approved as noted

Rejected

Revise and resubmit

Signature :

Date :

5 = issued for construction

6 = As-built

Design Of Sluice Valve Chamber For Pipe 300 Dia.


DESIGN CRITERIA
Design Code

BS 8110 & 8007

Compressive strength

Fcu

Live Load Surcharge

Fy

Steel yield stress

hGwt

Height of Ground water Table

gc

Concrete density
Floor

tf

Floor Thickness
Cover

Floor Depth

Base Length

Base Width

Walls

tw

Wall Thickness
Cover

Wall Depth

dw

Net Bearing Capacity

qnc

Hw

Wall clear Height

=
=
=
=
=
=
=
=
=
=
=
=
=
=

Dry Soil Density

gsd

Soil Height

Hs

=
=
=
=
=

K0

=
=
=
=
=
=

gw

Water Density

Angle of repose

Sever Exposure

Design Crack width

Es

Steel Modulus of Elasticity

Constant depends on the modulus of elasticity of aggregate


Direct tensile strength of concrete at 3 days (BS8007)

Fct

Hydration temperture to ambient tempreture for wall (BS8007)

T1w

Fs

Allowable Tensile stress in steel (BS8007)

T1f

Hydration temperture to ambient tempreture for floor (BS8007)

T2

Variation in temperture due to seasonal changes

gm

Partial safety factor

gf

Partial safety factor for load

=
=

40

N\mm

10

KN\m

KN\m

460
0

24
300

N\mm
mm

mm

1500

mm

700
300

mm

mm
mm

75

mm

1100

mm

225

mm

150

KN\m

18

KN\m

10

30

4100

0.2

mm

75

225

KN\m

degree
mm

200000

N\mm

1.6

N\mm

20

100

KN\mm
N\mm

35

degree

degree

35

1.25
1.4

degree

P.20

table 3.1 P.9

table A.2 P.24

table A.2 P.24

ANALYSIS

Loads :-

For External Walls

0.333

External Soil and Water Pressures

=
=

Ka (

3.333

KN\m

24.600

KN\m

18.000

KN\m

7.56

KN

22.968

KN

30.528

KN

1.050

29.074

KN\m

7.200

KN\m

21.874

KN\m

Ka

) =

Check of Bearing Capacity :Wf =


Ww =
Wtotal =

2
+

Wtotal
=

=
=

<

150 KN\m2

Reinforcement Design :For Walls

Vertical Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

mm

392.5

K =

0.156

174.7997 mm

200

<

Z=0.95 d =

213.75

mm

174.7997 mm

Mu =0.87 As Fy Z =
K=

As =

Z=

Take

10

27.45727 KN.m

M
=
2
b d Fcu

0.013559

<

0.156

No compression steel required.

Mdesign =

5.5

KN.m

<

27.45727137

KN.m

Accepted design.

Horizontal Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

K =

0.156

174.7997 mm

M
=
2
b d Fcu

Mdesign =

mm

392.5

Mu =0.87As Fy Z =
K=

As =

Z=

Take

10

200

<

Z=0.95 d =

213.75

174.7997 mm
27.45727 KN.m
0.013559

<

0.156

No compression steel required.


4.67

KN.m

<

Accepted design.

27.45727137

KN.m

mm

CONT'D
For Floor

Vertical Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

mm

392.5

K =

0.156

174.7997 mm

200

<

Z=0.95 d =

213.75

mm

174.7997 mm

Mu =0.87 As Fy Z =
K=

As =

Z=

Take

10

27.45727 KN.m

M
=
2
b d Fcu

0.013559

<

0.156

No compression steel required.

Mdesign =

7.6

KN.m

<

27.45727137

KN.m

Accepted design.

Horizontal Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

K =

0.156

174.7997 mm

M
=
2
b d Fcu

Mdesign =

mm

392.5

Mu =0.87As Fy Z =
K=

As =

Z=

Take

10

200

<

Z=0.95 d =

213.75

174.7997 mm
27.45727 KN.m
0.013559

<

0.156

No compression steel required.


7.52

KN.m

<

Accepted design.

27.45727137

KN.m

mm

CONT'D

Check of Shear Strength :For Walls

=
v=
= 0.8

11.3715

5.05E-05

N\mm

5.059644 N\mm

N\mm

Accepted design.

0.79

100

400

25

0.4769199 N\mm

Accepted design.
For Floor

=
v=
= 0.8

24.82

0.00011

N\mm

2.529822 N\mm

N\mm

Accepted design.

0.79

100

400

25

0.4769199 N\mm

Accepted design.

CONT'D

Check early thermal crack :For Walls

+ 0.2

=
=
=

=
2

= 0.5

+
1+2

785

mm

150

mm

1.20E-05

=
2

10

0.15

N\mm

14.286

=
.

28000

200

/C
0

0.000032
75

mm

123

mm

0.007088

mm

<

0.2 mm

CONT'D
For Floor

+ 0.2

=
=
=

=
2

= 0.5

+
=

1+2

=
2

10
785

mm

150

mm

0.15

1.20E-05

N\mm

14.286

=
.

28000

200

/C
0

0.000032
75

mm

123

mm

0.007088

mm

<

0.2 mm

SAP2000

3/2/16 8:27:32

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 300 DIA - Area Surface Pressure - Face Top (SD) - KN, m, C Units
9

SAP2000

-4.25

-3.40

3/2/16 8:28:40

-2.55

-1.70

-0.85

0.00

0.85

1.70

2.55

3.40

4.25

5.10

5.95

6.80

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 300 DIA - Resultant M11 Diagram (COMB1) - KN, m, C Units
10

SAP2000

-6.80

-5.95

3/2/16 8:29:25

-5.10

-4.25

-3.40

-2.55

-1.70

-0.85

0.00

0.85

1.70

2.55

3.40

4.25

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 300 DIA - Resultant M22 Diagram (COMB1) - KN, m, C Units
11

SAP2000

1.7

3.4

3/2/16 8:30:00

5.1

6.8

8.5

10.2

11.9

13.6

15.3

17.0

18.7

20.4

22.1

23.8

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 300 DIA - Resultant VMAX Diagram (COMB1) - KN, m, C Units
12

Design Of Sluice Valve Chamber For Pipe 200 Dia.


DESIGN CRITERIA
Design Code

BS 8110 & 8007

Compressive strength

Fcu

Live Load Surcharge

Fy

Steel yield stress

hGwt

Height of Ground water Table

gc

Concrete density
Floor

tf

Floor Thickness
Cover

Floor Depth

Base Length

Base Width

Walls

tw

Wall Thickness
Cover

Wall Depth

dw

Net Bearing Capacity

qnc

Hw

Wall clear Height

=
=
=
=
=
=
=
=
=
=
=
=
=
=

Dry Soil Density

gsd

Soil Height

Hs

=
=
=
=
=

K0

=
=
=
=
=
=

gw

Water Density

Angle of repose

Sever Exposure

Design Crack width

Es

Steel Modulus of Elasticity

Constant depends on the modulus of elasticity of aggregate


Direct tensile strength of concrete at 3 days (BS8007)

Fct

Hydration temperture to ambient tempreture for wall (BS8007)

T1w

Fs

Allowable Tensile stress in steel (BS8007)

T1f

Hydration temperture to ambient tempreture for floor (BS8007)

T2

Variation in temperture due to seasonal changes

gm

Partial safety factor

gf

Partial safety factor for load

13

=
=

40

N\mm

10

KN\m

KN\m

460
0

24
200

N\mm
mm

mm

1200

mm

700
200

mm

mm
mm

75

mm

1000

mm

125

mm

150

KN\m

18

KN\m

10

30

4000

0.2

mm

75

125

KN\m

degree
mm

200000

N\mm

1.6

N\mm

20

100

KN\mm
N\mm

35

degree

degree

35

1.25
1.4

degree

P.20

table 3.1 P.9

table A.2 P.24

table A.2 P.24

ANALYSIS

Loads :-

For External Walls

0.333

External Soil and Water Pressures

=
=

Ka (

3.333

KN\m

24.000

KN\m

18.000

KN\m

4.032

KN

12.480

KN

16.512

KN

0.840

19.657

KN\m

4.800

KN\m

14.857

KN\m

Ka

) =

Check of Bearing Capacity :Wf =


Ww =
Wtotal =

2
+

Wtotal
=

=
=

14

<

150 KN\m2

Reinforcement Design :For Walls

Vertical Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

mm

392.5

K =

0.156

97.11093 mm

200

<

Z=0.95 d =

118.75

mm

97.11093 mm

Mu =0.87 As Fy Z =
K=

As =

Z=

Take

10

15.25404 KN.m

M
=
2
b d Fcu

0.024406

<

0.156

No compression steel required.

Mdesign =

5.045

KN.m

<

15.25403965

KN.m

Accepted design.

Horizontal Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

K =

0.156

97.11093 mm

M
=
2
b d Fcu

Mdesign =

mm

392.5

Mu =0.87As Fy Z =
K=

As =

Z=

Take

10

200

<

Z=0.95 d =

118.75

97.11093 mm
15.25404 KN.m
0.024406

<

0.156

No compression steel required.


3.79

KN.m

<

Accepted design.

15

15.25403965

KN.m

mm

CONT'D
For Floor

Vertical Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

mm

392.5

K =

0.156

97.11093 mm

200

<

Z=0.95 d =

118.75

mm

97.11093 mm

Mu =0.87 As Fy Z =
K=

As =

Z=

Take

10

15.25404 KN.m

M
=
2
b d Fcu

0.024406

<

0.156

No compression steel required.

Mdesign =

7.53

KN.m

<

15.25403965

KN.m

Accepted design.

Horizontal Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

K =

0.156

97.11093 mm

M
=
2
b d Fcu

Mdesign =

mm

392.5

Mu =0.87As Fy Z =
K=

As =

Z=

Take

10

200

<

Z=0.95 d =

118.75

97.11093 mm
15.25404 KN.m
0.024406

<

0.156

No compression steel required.


7.45

KN.m

<

Accepted design.

16

15.25403965

KN.m

mm

CONT'D

Check of Shear Strength :For Walls

=
v=
= 0.8

11.3715

9.1E-05

N\mm

5.059644 N\mm

N\mm

Accepted design.

0.79

100

400

25

0.6719771 N\mm

Accepted design.
For Floor

=
v=
= 0.8

21.78

0.000174 N\mm

2.529822 N\mm

N\mm

Accepted design.

0.79

100

400

25

0.6719771 N\mm

Accepted design.

17

CONT'D

Check early thermal crack :For Walls

+ 0.2

=
=
=

=
2

= 0.5

+
1+2

785

mm

100

mm

1.20E-05

=
2

10

0.15

N\mm

14.286

=
.

28000

200

/C
0

0.000032
75

mm

123

mm

0.005930

mm

18

<

0.2 mm

CONT'D
For Floor

+ 0.2

=
=
=

=
2

= 0.5

+
=

1+2

=
2

10
785

mm

100

mm

0.15

1.20E-05

N\mm

14.286

=
.

28000

200

/C
0

0.000032
75

mm

123

mm

0.005930

mm

19

<

0.2 mm

SAP2000

3/2/16 8:39:30

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 200 DIA - Area Surface Pressure - Face Top (SD) - KN, m, C Units
20

SAP2000

-4.25

-3.40

3/2/16 8:40:07

-2.55

-1.70

-0.85

0.00

0.85

1.70

2.55

3.40

4.25

5.10

5.95

6.80

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 200 DIA - Resultant M11 Diagram (COMB1) - KN, m, C Units
21

SAP2000

-6.80

-5.95

3/2/16 8:40:27

-5.10

-4.25

-3.40

-2.55

-1.70

-0.85

0.00

0.85

1.70

2.55

3.40

4.25

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 200 DIA - Resultant M22 Diagram (COMB1) - KN, m, C Units
22

SAP2000

1.7

3.4

3/2/16 8:39:51

5.1

6.8

8.5

10.2

11.9

13.6

15.3

17.0

18.7

20.4

22.1

23.8

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 200 DIA - Resultant VMAX Diagram (COMB1) - KN, m, C Units
23

Design Of Sluice Valve Chamber For Pipe 150&100 Dia.


DESIGN CRITERIA
Design Code

BS 8110 & 8007

Compressive strength

Fcu

Live Load Surcharge

Fy

Steel yield stress

hGwt

Height of Ground water Table

gc

Concrete density
Floor

tf

Floor Thickness
Cover

Floor Depth

Base Length

Base Width

Walls

tw

Wall Thickness
Cover

Wall Depth

dw

Net Bearing Capacity

qnc

Hw

Wall clear Height

=
=
=
=
=
=
=
=
=
=

Direct tensile strength of concrete at 3 days (BS8007)

Fct

Hydration temperture to ambient tempreture for wall (BS8007)

T1w

Fs

Allowable Tensile stress in steel (BS8007)

T1f

Hydration temperture to ambient tempreture for floor (BS8007)

T2

Variation in temperture due to seasonal changes

gm

Partial safety factor

gf

Partial safety factor for load

24

1050

mm

700

mm

0.2

=
=

mm

75

mm

750

mm

75

10

30

mm

3750

=
=
=
=
=
=

Constant depends on the modulus of elasticity of aggregate

mm

75

mm

75

K0

Es

150

KN\m

Steel Modulus of Elasticity

24

mm

18

Design Crack width

KN\m

Hs

Sever Exposure

KN\m

Soil Height

KN\m

N\mm

150

gsd

Angle of repose

10

460

150

Dry Soil Density

gw

N\mm

=
=
=
=
=
=
=
=
=

Water Density

40

mm

KN\m

degree
mm

200000

N\mm

1.6

N\mm

20

100

KN\mm
N\mm

35

degree

degree

35

1.25
1.4

degree

P.20

table 3.1 P.9

table A.2 P.24


table A.2 P.24

ANALYSIS

Loads :-

For External Walls

0.333

External Soil and Water Pressures

=
=

Ka (

3.333

KN\m

22.500

KN\m

18.000

KN\m

2.646

KN

6.615

KN

9.261

KN

0.735

12.600

KN\m

3.600

KN\m

9.000

KN\m

Ka

) =

Check of Bearing Capacity :Wf =


Ww =
Wtotal =

2
+

Wtotal
=

=
=

25

<

150 KN\m2

Reinforcement Design :For Walls

Vertical Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

mm

392.5

K =

0.156

58.26656 mm

200

<

Z=0.95 d =

71.25

mm

58.26656 mm

Mu =0.87 As Fy Z =
K=

As =

Z=

Take

10

9.152424 KN.m

M
=
2
b d Fcu

0.040677

<

0.156

No compression steel required.

Mdesign =

3.32

KN.m

<

9.152423791

KN.m

Accepted design.

Horizontal Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

K =

0.156

58.26656 mm

M
=
2
b d Fcu

Mdesign =

mm

392.5

Mu =0.87As Fy Z =
K=

As =

Z=

Take

10

200

<

Z=0.95 d =

71.25

mm

58.26656 mm
9.152424 KN.m
0.040677

<

0.156

No compression steel required.


1.94

KN.m

<

Accepted design.

26

9.152423791

KN.m

CONT'D
For Floor

Vertical Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

mm

392.5

K =

0.156

58.26656 mm

200

<

Z=0.95 d =

71.25

mm

58.26656 mm

Mu =0.87 As Fy Z =
K=

As =

Z=

Take

10

9.152424 KN.m

M
=
2
b d Fcu

0.040677

<

0.156

No compression steel required.

Mdesign =

3.81

KN.m

<

9.152423791

KN.m

Accepted design.

Horizontal Reinforcement

Proposed steel RFT.

= Z 0.5 +

0.25

K =

0.156

58.26656 mm

M
=
2
b d Fcu

Mdesign =

mm

392.5

Mu =0.87As Fy Z =
K=

As =

Z=

Take

10

200

<

Z=0.95 d =

71.25

mm

58.26656 mm
9.152424 KN.m
0.040677

<

0.156

No compression steel required.


3.79

KN.m

<

Accepted design.

27

9.152423791

KN.m

CONT'D

Check of Shear Strength :For Walls

=
v=
= 0.8

7.0875

9.45E-05

N\mm

5.059644 N\mm

N\mm

Accepted design.

0.79

100

400

25

0.9052452 N\mm

Accepted design.
For Floor

=
v=
= 0.8

12

0.00016

N\mm

2.529822 N\mm

N\mm

Accepted design.

0.79

100

400

25

0.9052452 N\mm

Accepted design.

28

CONT'D

Check early thermal crack :For Walls

+ 0.2

=
=
=

=
2

= 0.5

+
1+2

785

mm

75

mm

1.20E-05

=
2

10

0.15

N\mm

14.286

=
.

28000

200

/C
0

0.000032
75

mm

123

mm

0.005097

mm

29

<

0.2 mm

CONT'D
For Floor

+ 0.2

=
=
=

=
2

= 0.5

+
=

1+2

=
2

10
785

mm

75

mm

0.15

1.20E-05

N\mm

14.286

=
.

28000

200

/C
0

0.000032
75

mm

123

mm

0.005097

mm

30

<

0.2 mm

SAP2000

3/2/16 8:52:30

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 150DIA - Area Surface Pressure - Face Top (SD) - KN, m, C Units
31

SAP2000

-3.00

-2.50

3/2/16 8:53:33

-2.00

-1.50

-1.00

-0.50

0.00

0.50

1.00

1.50

2.00

2.50

3.00

3.50

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 150DIA - Resultant M11 Diagram (COMB1) - KN, m, C Units
32

SAP2000

-3.60

-3.20

3/2/16 8:55:00

-2.80

-2.40

-2.00

-1.60

-1.20

-0.80

-0.40

0.00

0.40

0.80

1.20

1.60

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 150DIA - Resultant M22 Diagram (COMB1) - KN, m, C Units
33

SAP2000

0.9

1.7

3/2/16 8:58:35

2.6

3.4

4.3

5.1

6.0

6.8

7.7

8.5

9.4

10.2

11.1

11.9

SAP2000 v15.1.0 - File:Sluice Valve Chamber For pipe 150DIA - Resultant VMAX Diagram (COMB1) - KN, m, C Units
34