You are on page 1of 16

ENERGY STAR Data Center Infrastructure Rating Development

Data Collection Form


Data Collection Guidelines
The data collection effort will focus on stand-alone data centers and data centers in larger buildings (e.g. office buildings) that
have submetering capability to isolate data center operations.
Report values that were valid for at least 12 consecutive months within a period from March 20, 2008 to June 1, 2009.
The facility must have been in normal operation for at least 12 months.
If data elements change over time (e.g. the number of racks, UPS utilization), provide the average of that element over the
12 month data collection period.
If you have any specific questions about the items listed below, or difficulty assessing data during this data collection period,
please send an email to ENERGYSTARdatacenters@icfi.com.

Data Elements List


The following table outlines the data elements of interest; each section of the table corresponds to a tab in this MS Excel Data
Template. This data template was created for your convenience, but we will accept the data in any form, provided all of
the listed information is included.

Data Element Name

Description/Question

Tab 1 Building Information


Data Center Name or ID

Please provide a unique name (or number) for each data center in your sample.

Zip Code

Please provide the five-digit zip code for each data center's location.

Type of Data Center

Please select among the following: 1 = Traditional Enterprise; 2 = On-Demand Enterprise; 3 =


Telecom; 4 = High Performance Computing Center (Scientific); 5 = Hosting; 6 = Internet; 7 = Hybrid

Type of Building

Please select between the following: 1 = Stand-alone, 2 = Enclosed in a larger building (i.e. office
building or other space type). NOTE: If the data center is enclosed within another building space,
it must be completely submetered in order to proceed with this data collection.

Building Square Footage

Provide the gross or total square footage of the building.

Data Center Square Footage

Provide the square footage of the data center space that includes the rack equipment, service
clearance and circulation, control console area, power distribution, and local air conditioning that is
encapsulated by the proper protective walls. Exclude administrative offices, storage, loading docks,
and other non-essential space that does not directly support the operation of the data center.

Building Earned the ENERGY STAR?

Has the building earned the ENERGY STAR? (Yes or No)

Building LEED Certified?

Has the building received the US Green Building Council LEED certification? (Yes or No)

Tab 2 Data Center Operations


For any element that may change over the course of the data collection period (e.g. number of racks, UPS utilization), please provide an
average figure for the 12 months of data.

Reliability (Tier Level)

Using the Uptime Institute's classification of four tiers of reliability (Tier I, II, III, IV), please provide the
level of the data center's reliability that describes the amount of required, active, redundant
infrastructure. When multiple tier levels exist, the reliability tier level should represent the majority, or
the highest percentage, of the data center's total load. When estimating tier levels, the fractional
estimates (i.e. 3+ or 3.5) should be rounded DOWN to the whole number for purposes of the data
input.
(See Uptime's Web site for more information on the tier classifications:
http://www.upsite.com/TUIpages/whitepapers/tuitiers.html)

Number of Racks

Please provide the number of racks in the data center that are typically in operation.

UPS Utilization

Based on your data center's tier level and corresponding UPS configuration, please enter the percent
utilization of your UPS, which is the amount of critical load compared with the redundant capacity of
the system. Please use the examples in the FAQs to see the calculations associated with each tier
level and UPS configuration. If you have multiple systems and multiple configurations, please use the
pro-rated average of all systems weighted by load and their individual system utilizations.

Total Capacity for Cooling

To help determine the Chiller Utilization, provide the data center's total capacity for cooling in tons.

Annual Chiller Runtime

To help determine the Chiller Utilization, please provide the annual runtime for the chillers in hours.

Average Chiller Demand

To help determine the Chiller Utilization, enter the average demand for the chillers in KW.

Data Element Name


Tab 3 IT Measurement

Total IT Plug Energy from UPS Meter


in KWh

Start Date
End Date

Total IT Plug Energy from PDU Meter


in KWh
(If Available)

Start Date
End Date

Description/Question
Please enter the annual total IT plug energy, as measured in KWh, from the output of a UPS meter, for
energy going into the computer room (not crac units, etc.). This can be entered as one value for the
year or as a series of meter/energy readings (i.e. monthly or periodic) that cover the entire calendar
year. It is preferable that these measurements are read at approximately the same period and
frequency as the utility meter for the building.
For each energy use value, enter a start and end date. You can provide an entry for each
meter/energy reading or one entry for the entire year.
Please enter the annual total IT plug energy, as measured in KWh, from the input of a PDU meter, for
energy going into the computer room (not crac units, etc.). This can be entered as one value for the
year or as a series of meter/energy readings (i.e. monthly or periodic) that cover the entire calendar
year. It is preferrable that these measurements are read at approximately the same period and
frequency as the utility meter for the building. If both the UPS and PDU meters are provided, an
estimate of the difference between the total UPS and the sum of the PDU's will be estimated as the
non-critical UPS load that might be serving the office, mechanical and non-data center loads.

For each energy use value, enter a start and end date. You can provide an entry for each
meter/energy reading or one entry for the entire year.

Tab 4 Electricity Data


Provide the annual electricity consumption for the building (if a stand-alone data center) or the submetered data center. You can provide this
as one value for the year or as a series of meter/energy bill entries that cover the entire year.
Meter ID

Enter a distinguishing name or number for each meter.

Start Date
End Date

For each energy use value, enter a start and end date. You can provide an entry for each bill or one
entry for the entire year.

Electricity Consumption in KWh

Enter the electricity consumption in KWh corresponding to the start and end date.

Data Element Name

Description/Question

Tab 5 Natural Gas Data


Provide the annual natural gas consumption for the building (if a stand-alone data center) or the submetered data center. You can provide this
as one value for the year or as a series of meter/energy bill entries that cover the entire year.
Meter ID

Enter a distinguishing name or number for each meter.

Start Date
End Date

For each energy use value, enter a start and end date. You can provide an entry for each bill or one
entry for the entire year.

Natural Gas Consumption

Enter the natural gas consumption corresponding to the start and end date.

Energy Units

Please enter the corresponding units for the natural gas consumption figure (i.e. therms, ccf, Mcf).

Tab 6 Other Energy Sources


For each fuel type and other sources of energy (i.e. diesel fuel, steam, chilled water, solar) provide the annual energy consumption for the
building (if a stand-alone data center) or the submetered data center. You can provide this as one value for the year or as a series of
meter/energy bill entries that cover the entire year. NOTE: Stand-by generator diesel fuel used less than 200 hours per year should not
be included.
Fuel Type/Other Energy Source

Please enter the type of energy that the following data represents.

Meter ID

Enter a distinguishing name or number for each meter.

Start Date
End Date

For each energy use value, enter a start and end date. You can provide an entry for each bill or one
entry for the entire year.

Energy Consumption

Enter the energy consumption corresponding to the start and end date.

Energy Units

Please enter the corresponding units for the energy consumption figure (i.e. gallons, therms, Kbtu,
Mbtu, lbs, ton hours).

Data Element Name

Description/Question

Tab 7 Optional Elements (To be used for future study purposes)


Year Constructed

Enter the 4 digit year the building was built.

HVAC "Economizer Cycle" Control


Strategy

Does the building utilize an HVAC "economizer cycle" control strategy? Yes or no?

Water-side or Air-side Economizer


Cycle?

If yes on "economizer cycle" is this on the water-side or air-side? Please select between the following:
1 = water-side, 2 = air-side

Does the building incorporate peak


shaving, demand response, thermal
storage or co-generation in its
operations?

Does the building incorporate peak shaving, demand response, thermal storage or co-generation in its
operations? Please select all operations/strategies that apply.

Percentage of Average IT Utilization

What is the current "average" IT processing load as a percentage of the total server processor
capacity? Enter this percentage as one average calculation for the entire year.

Percentage of Peak IT Utilization

What is the current "peak" IT processing load as a percentage of the total server processor capacity?
Enter this percentage as one average calculation for the entire year.

Mechanical System Type

Please select the type of mechanical system used for cooling the data center: 1 = Direct Expansion; 2
= Chilled Water; 3 = Condenser; 4 = Other

Liquid-Cooled IT Equipment/Racks

Please check the box if the data center employs liquid cooling for IT equipment and/or racks.

Air Management Techniques

Please check off all of the following air management techniques that are in operation at the data
center:
Blanking Plates in Racks
Hot Aisle/Cold Aisle Equipment
CFD Modeling
High Delta "T" Cooling
Air Separation Chambers
Racks with Air Management Control
Static Pressure Control
Static Pressure Boundaries
Dynamically Managed Air-Flow

Operating Set Points

Please check off all of the following operational practices employed at the data center: New ASHRAE
Humidity Set Points; Dynamic Temperature Change; Automatic Chiller Water Reset

Frequently Asked Questions (FAQ)


Review the additional information for select questions below. If you need further clarification, email your questions to: ENERGYSTARDatacenters@icfi.com

Tab 1 - Building Information


Type of Data Center
1 - Traditional Enterprise: Processes data requirements for data center owner
2 - On Demand Enterprise: Processes and expands data processing capacity, when needed, for numerous customers (this would include batch processing and
manufacturing type data processing facilities)
3 - Telecom: Telecom Switching Center
4 - High Performance Computing: Scientific and high density data processing
5 - Hosting: Sells data processing services to numerous Customers
6 - Internet: Provides high capacity processing for large numbers of web clients
7 - Hybrid: Combination of two or more of the above

Tab 2 Data Center Operations


UPS Utilization
There are various configurations of UPS support. Some of the redundancy of the UPS system design will be indicated by the Tier Level already collected in the data
elements. Efficiency is also affected by the load on the UPS system (a lightly loaded UPS is less efficient than a system operation in the peak efficiency above 90% depending on the system manufacture). The formal definition of the % of UPS capacity is the amount of critical load compared with the redundant capacity of the system.
For illustrative purposes, examples of the utilization calculation could be any of the following:
Example # 1 Tier One Stand-Alone UPS (No redundancy): The percent of utilization would be calculated by noting a fully loaded UPS should not exceed 85% of the rated
capacity - for transients harmonic and temporary loads with equipment swap. Therefore the percent utilization calculation in this example is a 500 kVA unit has 425 kVA of
capacity (85%) and a 150 kVA IT load on this unit would represent a 35.3% loaded unit. (150 / 500 x 0.85 = 35.3%)
Example # 2 Tier Two N+1 Redundant UPS: The percent of utilization in this example would be noted as a three module 500 kVA UPS system (three modules of 500 +
500 + 500 = 1000 kVA (plus a redundant module)) since all modules share load and 1500 kVA will be on line a full 850 kVA of capacity of redundant system. A 150 kVA IT
load in this system would NOT be 10% of 1500 kVA installed but 17.6% of system utilization (150 / (1500 - 500 (redundant module) X 0.85 = 17.6%). The "normal-mode"
UPS loading of each module is 150 / 1500 = 10%, but the system is utilized to 17.6%.
Example # 3 Tier Three N+N UPS modules: The percent utilization would be calculated be noting the redundant UPS (N) system will not need a de-ration factor of 85%
since the system will share load between the "A & B" side UPS systems. In this example the systems would be configured in two 500 kVA modulate (1000 kVA - "A") + two
additional 500 kVA modules ( 1000 kVA - "B") for a total installed 2000 kVA of UPS modules. This configuration can support 850 kVA redundant load while being fully
maintained on the "A" side, while the "B" side is supporting the load (concurrent maintainability). The load calculation for 150 kVA of IT load is ( 150 / (2000 - 1000
(redundant N system)) x .85 = 17.6%). The "normal-mode" UPS load shared across all modules would be 7.5% each but the system utilization in the redundant
configuration would still be 17.6% loaded.
Example # 4 Tier Four N+1 + N+1 UPS System: The difference between Tier Three and Tier Four configurations is the redundant module to offer redundancy when the
system is in the maintenance mode. If the total load was being supported by the "A" side while the "B" side is being maintained, the "A-side +1" module will still be in
reserve for a module failure. In this example the modules installed would be three 500 kVA modules (N+1) for the "A" side and three 500 Kva modules for the "B" side UPS
and a system redundant capacity of 1000 kVA. Since each system has reserve when supporting the total load, the 85% de-rating factor is not necessary. Therefore the
utilization load for this configuration is [ 150 / (3000 - (1500 (redundant system) + 500 (redundant second system module))] = (150 / 1000 ) = 15.0%

Chiller Utilization
These three elements (total capacity for cooling, annual chiller runtime, and average chiller demand) will be factored into an equation to determine the total IT load being
cooled compared to the chiller capacity.

Tab 3 IT Measurement
Total IT Plug Energy
In general the calculation is attempting to capture the energy used by the IT equipment (this will include the IT equipment fan systems and all other devices: KVM, cabinet
monitoring and cabinet circulation fans) that are connected into the plug strip serving the computer room. If the UPS system is only providing load to the computer
equipment in the data center, and NOT providing Computer room fans, pumps, telecommunication closets and desktop services outside the data center, then the UPS
readings over time can be recorded. The best case in this circumstance is to read a KWH meter at approximately the same period and frequency as the utility meter for
the building. If a KWH meter is not available on the UPS then the instantaneous meter reading can be measured on a periodic basis to predict how load on the UPS
changes with the data center processing load. A comparison with the known processing peak and the lowest utilization would be good times to record instantaneous meter
readings to capture the range of UPS output. If it is greater than 5%, a more detailed (greater frequency) of recording would be used to estimate the total KWH provided
by the UPS over time.

Tab 6 Other Energy Sources

Generally these systems provide maintenance start-up testing and battery re-fresh run-time exercise cycles that do not sustain actual data center operations for extended
periods (defined as less than 200 hours per year). Since the on-line status is not significant you can ignore the make-up diesel fuel as a captured energy source.

Tab 7 - Optional Elements


Does the building utilize an HVAC "economizer cycle" control strategy?
Economizer Cycle is a mechanical device that uses any type of system that eliminates the mechanical refrigeration cycle by using outside atmosphere to cool the interior
spaces that are normally cooled by an energy intensive refrigerant system. These would include free cooling with economy coils using cooled water from the cooling tower
or dry coolers, replacement air used directly from the outside (with exhaust air being flushed to the outside), or a heat exchanger process that transfers heat to the
atmosphere without the use of a mechanical input to change a refrigerant state.
If yes on "economizer cycle" is this on the water-side or air-side?
A Water-side economizer cycle uses water as the key fluid in the transfer of heat to the atmosphere and does not introduce a large quantity of outside air directly into
cooled interior spaces. Usually coils and/or heat exchangers are used with these types of systems.
An Air-side economizer cycle generally uses the induction of outside air (when conditions of that air can cool) for the direct conditioning of the space. There is a need to
monitor humidity and contaminates when this type of cooling is provided with attention to filtering and the moisture content of the air.
Does the building incorporate peak shaving, demand response, thermal storage or co-generation in its operations?
Peak shaving is a technique that stores heating or cooling generated in an alternate (cheaper cost) time of day to be used when the utility system is experiencing a high
demand on their system and charges customers for energy use at a higher cost during that period. The shaving provides the utility with higher system utilization and less
capacity peaks they typically provide customers with a reduced rate of cost for this benefit. Systems can include chilled water storage, ice storage, heated material, solar
heated storage and other processes. The utility rate reduction may lower total utility cost, but total energy usage is generally displaced but not reduced with these systems.
Demand response (partial) and co-generation (continuous) processes provide removal of utility load from the utility when their system is stressed. For the ability to
temporarily remove or self-generate power, the utility will typically provide a reduced utility rate. These processes may or may not save total energy used.
The ENERGY STAR data collection effort is interested in large energy input to the data center. If the peak shaving, demand response and storage processes do not save
energy and are primarily used for utility cost reduction, the effect on an energy rating will be minimal on the calculated rating. Co-generation however would by its
continuous nature use a large quantity of energy and therefore would need to be included in the other energy tab 6&7 collection.

Percentage of Average IT Utilization


Typically the data center monitors the processor, network and storage processes that occur in the data center. There are peaks in production that when reached, tend to
determine if additional processing equipment is required to support the data center applications. The active measurement of the IT equipment is usually automated and
monitored. What it being asked in this data element is not the peak, but the average estimate over time of the IT equipments utilization (compared to the processor being
100% utilized). It is a value that currently will not affect the index but is the first step in data capture that will allow correlation the actual IT processing work with efficiency.
Although there is no standard to measure IT work being processed with energy input, this one measurement of the processor activity verses a dormant state will provide
an estimation of the potential for energy saving features, if activated, that could achieve even better efficiencies.
Percentage of Peak IT Utilization
If the console operator can run their capacity or processor monitoring programs, the peak utilization is used for alerting management when more IT equipment is
necessary to sustain business application processing. Since this is measured in most data centers, the historical capture should be accurate. The reason for this data
element is to provide an understanding of the maximum equipment that will be necessary for peak periods and then, depending on the variability of the enterprise
processing needs, be dormant during the non-peak times. By understanding the peak and average utilization characteristics of the data center, analysis with the tracking
of input energy and the extent of dormant equipment sitting in reserve for the peak. If these processes are tracked for the data center, the use of devices that can slow
down processor clock speed and turn off redundant processors can then be estimated. These concepts are the start of understanding IT work efficiency. For where the
data is captured, ask your console operator or check the measurement in the IT utility program available in the processor equipment.

Tab 1 - Building Information


Data Center
Name / ID
Example #1

Zip Code
21045

Type of Data Center


1 - Traditional Enterprise

Type of Building
1 - Stand-Alone

Building Square
Footage
36,000

Data Center
Square Footage
21,600

Building Earned
the ENERGY
STAR?
No

Building LEED
Rated?
No

Tab 2 - Data Center Operations


Data Center
Name / ID
Example #1

Reliability
(Tier Level)
Tier II

Number of Racks
420

UPS Utilization (%)


60%

Total Capacity for


Cooling
(tons)
950

Annual Chiller
Runtime
(hours)
8760

Average Chiller
Demand
(KW)
550

Tab 3 - IT Measurement

Data Center
Name / ID
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1

Total IT Plug
Energy from UPS
Meter (KWh)
1,824,270
1,814,000
1,723,300
1,723,278
1,723,222
1,723,168
1,723,111
1,723,056
1,723,000
1,722,944
1,722,889
1,722,833

Start Date
(MM/DD/YYYY)
02/21/2008
01/21/2008
12/21/2007
11/21/2007
10/21/2007
09/21/2007
08/21/2007
07/21/2007
06/21/2007
05/21/2007
04/21/2007
03/21/2007

End Date
(MM/DD/YYYY)
03/20/2008
02/20/2008
01/20/2008
12/20/2007
11/20/2007
10/20/2007
09/20/2007
08/20/2007
07/20/2007
06/20/2007
05/20/2007
04/20/2007

Total IT Plug
Energy from PDU
Meter (KWh)
If Available
1,806,028
1,795,860
1,706,067
1,706,045
1,705,990
1,705,936
1,705,880
1,705,825
1,705,770
1,705,715
1,705,660
1,705,605

Start Date
(MM/DD/YYYY)
02/21/2008
01/21/2008
12/21/2007
11/21/2007
10/21/2007
09/21/2007
08/21/2007
07/21/2007
06/21/2007
05/21/2007
04/21/2007
03/21/2007

End Date
(MM/DD/YYYY)
03/20/2008
02/20/2008
01/20/2008
12/20/2007
11/20/2007
10/20/2007
09/20/2007
08/20/2007
07/20/2007
06/20/2007
05/20/2007
04/20/2007

Tab 4 - Electricity Data


Data Center
Name / ID
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1

Meter ID
Electric 45389
Electric 45389
Electric 45389
Electric 45389
Electric 45389
Electric 45389
Electric 45389
Electric 45389
Electric 45389
Electric 45389
Electric 45389
Electric 45389

Start Date
(MM/DD/YYYY)
02/21/2008
01/21/2008
12/21/2007
11/21/2007
10/21/2007
09/21/2007
08/21/2007
07/21/2007
06/21/2007
05/21/2007
04/21/2007
03/21/2007

End Date
(MM/DD/YYYY)
03/20/2008
02/20/2008
01/20/2008
12/20/2007
11/20/2007
10/20/2007
09/20/2007
08/20/2007
07/20/2007
06/20/2007
05/20/2007
04/20/2007

Electricity
Consumption
(KWh)
3,283,686
3,265,200
3,102,000
3,101,900
3,101,800
3,101,700
3,101,600
3,101,500
3,101,400
3,101,300
3,101,200
3,101,100

Tab 5 - Natural Gas Data


Data Center
Name / ID
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1
Example #1

Meter ID
Gas 2624
Gas 2624
Gas 2624
Gas 2624
Gas 2624
Gas 2624
Gas 2624
Gas 2624
Gas 2624
Gas 2624
Gas 2624
Gas 2624

Start Date
(MM/DD/YYYY)
02/05/2008
01/05/2008
12/05/2007
11/05/2007
10/05/2007
09/05/2007
08/05/2007
07/05/2007
06/05/2007
05/05/2007
04/05/2007
03/05/2007

End Date
(MM/DD/YYYY)
03/04/2008
02/04/2008
01/04/2008
12/04/2007
11/04/2007
10/04/2007
09/04/2007
08/04/2007
07/04/2007
06/04/2007
05/04/2007
04/04/2007

Natural Gas
Consumption
7,715
8,000
2,700
2,500
2,300
2,200
1,800
1,750
1,900
2,100
2,400
2,600

Energy Units
therms
therms
therms
therms
therms
therms
therms
therms
therms
therms
therms
therms

Tab 6 - Other Energy Sources


Data Center
Name / ID
Example #1

Fuel Type/
Other Energy Source
N/A

Meter ID

Start Date
(MM/DD/YYYY)

End Date
(MM/DD/YYYY)

Energy
Consumption

Energy Units

Tab 7 - Optional Elements

Data Center
Name / ID

Year
Constructed

HVAC
"Economizer Water-side or Does the building incorporate
Cycle"
Air-side
peak shaving, demand
Percentage of Percentage of
Control
Economizer
response, thermal storage, or
Average IT
Peak IT
Mechanical System
Strategy?
Cycle?
co-generation in its operations? Utilization
Utilization
Type

Example #1

1998

No

63%

76%

2 = Chilled Water

Operating Set Points

Liq
Eq uid
uip -Co
me ole
nt/ d I
Ra T
Bla
ck
n
Ra ki
s
c k ng
s
Pl a
tes
Ho
in
Ais t Ais
l
le
Eq e/ Co
ui p l d
CF
me
D
nt
Mo
de
lin
g
Hig
Co h-D
oli elt
ng a "
T"
Air
Ch Sep
am a r
be atio
rs
n
Ra
Mg cks
w
mt
Co ith A
ntr ir
Sta
ol
Co tic
ntr Pre
ol
ss
ur
e
Sta
Bo tic
P
un
r
e
da ss
rie ur
Dy
e
s
Ma nam
na ica
ge lly
dA
irFl o
Ne
w
w
Hu A
mi S H
dit RA
yS E
et
Dy
Pt
s.
Ch nam
an i c
ge Te
mp
.
Au
Wa tom
ter atic
Re Ch
se ile
t
r

Air Management Techniques

Data Center
Name / ID
Year
Constructed
Liq
Eq uid
uip -Co
me ole
nt/ d I
Ra T
Bla
ck
n
Ra ki
s
c k ng
s
Pl a
tes
Ho
in
Ais t Ais
l
le
Eq e/ Co
ui p l d
CF
me
D
nt
Mo
de
lin
g
Hig
Co h-D
oli elt
ng a "
T"
Air
Ch Sep
am a r
be atio
rs
n
Ra
Mg cks
w
mt
Co ith A
ntr ir
Sta
ol
Co tic
ntr Pre
ol
ss
ur
e
Sta
Bo tic
P
un
r
e
da ss
rie ur
Dy
e
s
Ma nam
na ica
ge lly
dA
irFl o
Ne
w
w
Hu A
mi S H
dit RA
yS E
et
Dy
Pt
s.
Ch nam
an i c
ge Te
mp
.
Au
Wa tom
ter atic
Re Ch
se ile
t
r

HVAC
"Economizer Water-side or Does the building incorporate
Cycle"
Air-side
peak shaving, demand
Percentage of Percentage of
Control
Economizer
response, thermal storage, or
Average IT
Peak IT
Mechanical System
Strategy?
Cycle?
co-generation in its operations? Utilization
Utilization
Type

You might also like