Istat 300

Electrical Transducers

How to Order
To order an Istat 300 transducer:1. Select Type Reference
2. Provide scaling details,
current and voltage inputs,
CT and VT ratios

Type Reference
A 6 character reference that designates the basic type of transducer.
Type of transducer
(From Selection Table, Page 3)

3WD

Code
Output
0 1 mA
0 5 mA
0 8 mA
0 10 mA
0 20 mA
4 20 mA
4 12 20 mA
0 5 10 mA
1 0 1 mA
10 0 10 mA
Relay Contacts
None of the above
(please specify)
Auxiliary supply
Self powered
63.5 V ac
69.3 V ac
100 V ac
110 V ac
115 V ac
120 V ac
208 V ac
220 V ac
240 V ac
380 Vac
415 V ac
440 V ac
24 V dc
32 V dc
48 V dc
110 V dc
125 V dc
From dc/dc converter
None of the above
(please specify)
Frequency
50 Hz
60 Hz
DC

A
B
C
D
E
F
G
H
J
K
R
Z
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T
U
X
Z
5
6
9

Example of required order information


Type 3WDKE5, Input 25 0 25 MW, CT Ratio 400/5 A, VT Ratio 33 kV/110 V
(Type reference indicates 2 El Watts transducer with 10 0 10 mA output,
auxiliary supply 110 V ac and operational frequency 50 Hz)
Type Reference for DC/DC Converters
Converter supply voltage
(See selection table over)
No. of outputs, 001 One, 002 Two
2

3BC

001

Transducer Selection Table


The following types of transducer are available in the Istat 300 range
Type

Type reference

Size of housing

Auxiliary power supply requirements

Mean Sensing Current Single


Triple

3CA
3CC

55 mm
150 mm

AC or DC, 4 20 mA output only


AC or DC, 4 20 mA output only

True RMS Current

Single
Triple

3CD
3CF

55 mm
150mm

AC or DC for all outputs


AC or DC for all outputs

Mean Sensing
Voltage

Single
Triple

3VA
3VC

55 mm
150 mm

AC or DC, 0 20 mA, 4 20 mA outputs only


AC or DC, 0 20 mA, 4 20 mA outputs only

True RMS Voltage

Single
Triple

3VD
3VF

55 mm
150 mm

AC or DC for all outputs


AC or DC for all outputs

3VX

55 mm

AC or DC for all outputs

Suppressed Zero
Voltage
Frequency

45 55 Hz (0.1%)
55 65 Hz (0.1%)
48 52 Hz (0.1%)
58 62 Hz (0.1%)
48 52 Hz (0.01%)
58 62 Hz (0.01%)
47 53 Hz (0.01%)

3FA
3FB
3FC
3FD
3FE
3FF
3FG

55 mm
55 mm
55 mm
55 mm
150 mm
150 mm
150 mm

Not Required
Not Required
Not Required
Not Required
AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs

Phase Angle

Single Phase
3ph 3w Balanced
3ph 4w Balanced
3ph 3w Unbalanced
3ph 4w Unbalanced
Phase difference

3PA
3PB
3PC
3PD
3PE
3PG

150 mm
150 mm
150 mm
150 mm
150 mm
150 mm

AC or DC for all outputs


AC or DC for all outputs
AC or DC for all output
AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs

Watts

Single Phase
3ph 3w Balanced (1 El)
3ph 4w Balanced (1 El)
3ph 3w Unbalanced (2 El)
1
3ph 4w Unbalanced (2 2 El)
3ph 4w Unbalanced (3 El)

3WA
3WB
3WC
3WD
3WE
3WF

150 mm
150 mm
150 mm
150 mm
150 mm
150 mm

AC or DC for all outputs


AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs
AC or DC via DC/DC Converter for all outputs

Vars

Single Phase
3ph 3w Balanced (1 El)
3ph 4w Balanced (1 El)
3ph 3w Unbalanced (2 El)
1
3ph 4w Unbalanced (2 2 El)
3ph 4w Unbalanced (3 El)

3RA*
3RB
3RN*
3RD*
3RH*
3RF*

150 mm
150 mm
150 mm
150 mm
150 mm
150 mm

AC or DC for all outputs


AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs
AC or DC via DC/DC Converter for all outputs

Combined Watt/Var

3ph 3w Unbalanced (2 El)

3JD

150 mm

AC or DC via DC/DC Converter,


101mA output only

3DB
3DC
3DF (2 wire)
3DL (3 wire)
3DA
3DH/3DJ
3DD
3DG

150 mm
150 mm
150 mm
150mm
150 mm
150 mm
150 mm
150 mm

AC or DC for all outputs


AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs
AC or DC for all outputs
AC or DC via DC/DC Converter

DC Voltage
DC Current
Resistance
Tap Position
Temperature
Summation
mA/pulse Converter

DC/DC Converter (To provide isolated DC auxiliary power supply where required - see above)
24 V
3BA
55 mm
32 V
3BB
55 mm
48 V
3BC
55 mm
110 V
3BD
55 mm
125 V
3BE
55 mm
220V/48V
3BG
55 mm
*Var transducer utilises a phase shifter circuit to
derive vars.

Not Required
Not Required
Not Required
Not Required
Not Required
Not required

This unit steps down 220V dc for use with


3BC isolators. It can supply up to eight
3BC isolators.

Technical Specification
Istat 300 transducers are designed to comply with IEC 688-1, IEC 255-22-1 and BS 6253-1
Transducer Type
Current - mean
sensing - non
adjustable
(self powered)

Current - mean
sensing biased
(420mA
output)

RMS
Current

Voltage - mean
sensing
(self powered)

Voltage - mean
sensing
(420mA)

1 or 5
0200
4555 or
5565

1.5

1 or 5
0160
4555 or
5565

0.6

1 or 5
0200
4555 or
5565

1.0

63.5 to 440
0150

4555 or
5565
1.0

63.5 to 440
0150

4555 or
5565
0.3

AC Auxiliary (where applicable)


Voltage input (nominal) Vx
V
Operating range (1)
%Vx
Frequency range
Hz

63.5 to 440
80120
4555 or
5565
2.0

Power supply burden

63.5 to 440
80120
4555 or
5565
2.0

63.5 to 440
80120
4555 or
5565
2.0

DC Auxiliary (where applicable)


Voltage input (nominal) Vx
V
Operating range
%Vx
Power supply burden
VA

24 to 125
80140
2.0

24 to 125
80140
2.0

24 to 125
80140
2.0

Output
Accuracy (6)

0.2

0.2

0.2

0.2

0.2

Reference range (18)


Reference range (18)
Compliance voltage (8)
Open circuit voltage

%In
%Vn
V
V

0200

15(9)
25

0100

15
25

20200

15
25

20150
15
25

20100
15
25

Temperature
Temperature reference range
Temperature coefficient
Nominal range of use

C
%/C
C

050
0.008
1060

050
0.008
1060

050
0.008
1060

050
0.008
1060

050
0.008
1060

Miscellaneous
Frequency coefficient
%/Hz
Phase angle error
%/90
Ripple (rms)
%
Response time (0...99%)
s
Voltage overload:continuous
xVn
10s
xVn
Current overload:continuous (12) xIn
3s
xIn
1s
xIn
Humidity (noncondensing)
%RH
Waveform error
%
Peak factor (crest factor, CF)

0.02

<0.35
<0.5

3
25
50
93
0.4 (14)

0.02

<0.35
<0.5

3
25
50
93
0.4 (14)

0.02

<0.1
<0.5

3
25
50
93
0.4
1.2...1.8

0.02

<0.14
<0.5
1.5
2

93
0.4 (14)

0.05

<0.35
<0.5
1.5
2

93
0.4 (14)

Isolation (15)
Impulse test
Surge withstand
RFI/EMI

4kVrms 50 Hz for 60 seconds


5kV (1.2/50s) for BS923 and IEC 255221
IEC 255221 and ANSI C3790A IEEE Std 472 SWC where applicable
Tested to IEC 801

Figures in brackets
refer to notes

Unit

Input
Voltage input (nominal) Vn (1)
Nominal range of use
Current input (nominal) In (3)
Nominal range of use
Frequency range

V
%Vn
A
%In
Hz

Voltage circuit burden


Current circuit burden

VA
VA

VA

kV
kV

1. Maximum permissible auxiliary supply


and input voltage is 500V ac.

4. For single phase var transducers the


frequency coefficient is 0.02.

2. Below 1% Vn or In causes
unpredictable output (below 10% In
for unbalanced load).

5. For a 3 phase unbalanced system,


frequency reference range 48...52 or
58...62 Hz.
Frequency coefficient = 0.33 deg/Hz.

3. Other inputs available on request.

6. Accuracy of full scale output unless


stated.
7. Accuracy of centre scale frequency.

8. The output loading (k) can be


obtained by dividing the compliance
voltage (V) by the maximum rated
output (mA). Examples are shown in the
table below.
Compliance
Voltage(V)

Value of output load ()


by output rating
1 mA

5 mA

10 mA

20 mA

11

11k

12

12k

15

15k

3k

1.5k

750

RMS
Voltage

Suppressed
Zero
Voltage

Watts

Vars (16)

Phase Angle (17)

Frequency 0.1

63.5 to 440
0150

4555 or
5565
0.1

63.5 to 440
0133

4555 or
5565
0.3

63.5 to 440
0150
1 or 5
0...160
4555 or
5565
0.1
0.3

63. 5 to 440
0150
1 or 5
0160
4555 or
5565
0.1
0.3

63.5 to 440
1...150 (2)
1 or 5
1160 (2)
4555 or
5565 (5)
0.1
0.3

63.5 to 440
63.5 to 440
0120
0120

refer to selection table, page 3

63.5 to 440
80120
4555 or
5565
2.0

63.5 to 440
80120
4555 or
5565
2.0

63.5 to 440
80120
4555 or
5565
4.0

63.5 to 440
80120
4555 or
5565
4.0

63.5 to 440
80...120
4555 or
5565
4.0

24 to 125
80140
2.0

24 to 125
80140
2.0

24 to 125
80140
2.0

24 to 125
80140
2.0

0.2

0.5 of span (19)

25150
15
25

67133
15
25

0.19 reading
+0.01 FS
10160
40150
15 (10)
25

0.19 reading
+0.01 FS
10160
40150
15
25

050
0.008
10+60

050
0.04
10+60

050
0.008
10+60

0.02

<0.1
<0.5
1.5
2

93
0.4
1.3...1.7

0.05

<0.35
<0.5
1.5
2

93
1
1.3...1.7

0.02
0.2
<0.35
<0.5
1.5
2
3
25
50
93
0.4
1.2...1.8

9. Compliance voltage for the 0...1 mA


output version is 12V.
10. Compliance voltage for combined
watt/var transducer is 11V.
11. Output ripple depends upon input
range chosen.
12. At 25C.
13. This applies to current inputs only.

Frequency 0.01

1.5

0.1

63.5 to 440
80...120
4555 or
5565
4.0

24 to 125
80140
2.0

24 to 125
80140
2.0

1 degree

0.1 (7)

0.01 (7)

10160
20150
15
25

80120
15
25

20120
15
25

050
0.008
10+60

050
0.02 deg/C
10+60

050
0.004
10+60

540
0.001
5+50

0.3 (4)
0.2
<0.35
<0.5
1.5
2
3
25
50
93
0.4 (13)
1.2...1.8

0.1 deg/Hz (5)

<0.35 (11)
<0.6
1.5
2
3
25
50
93
2
1.2...1.6

<0.35
2
1.5
2

93

<0.35
1
1.5
2

93

15. For 3 phase systems isolation = 500V


50Hz for 60s between CT inputs. All
triple element transducers have 2kV
isolation between elements but 4 kV
between input and output.
16. This specification applies when phase
shifter circuit used to derive vars.

17. Not suitable for use with thyristor


waveforms. Please ask for advice
on other products available for this
application.
18. Reference range of 4...20mA output is
only >4mA and <20mA.
19. The accuracy class and other
parameters depend on the voltage input
range chosen.

14. +1.7 class index per 1% 3rd harmonic


distortion.

Technical Specification
Istat 300 transducers are designed to comply with IEC 688-1, IEC 255-22-1 and BS 6253-1
Transducer Type
Figures in brackets
refer to notes

Unit

DC voltage
or current

Summation
Amplifier (6)

Tap Position
& Resistance

Thermocouple

mA pulse
Converter

Input
Voltage input (nominal) Vn
Nominal range of use
Current input (nominal) In (2)
Nominal range of use
Frequency range
Resistance input (3)
Input impedance (10mV to 1V dc)
Input impedance (1V to 1500V dc)

V
%Vn
A
%In
Hz
Ohms
M
Ohms/V

10mV to 1500V
0120
10mA...10A
0120
DC

1.0
10k

10mA...20mA
0120
DC

1.0

DC
50...10k
1.0

5mV50mV
0120

DC

1.0

1mA...20mA
0125
DC

800 ohms at 1mA

AC Auxiliary (where applicable)


Voltage input (nominal) Vx
Operating range (1)
Frequency range
Power supply burden

V
%Vx
Hz
VA

63.5 to 440
80120
4555 or 5565
5

63.5 to 440
80120
4555 or 5565
5

63.5 to 440
80120
4555 or 5565
5

63.5 to 440
80120
4555 or 5565
5

63.5 to 440
80120
4555 or 5565
3

DC Auxiliary (where applicable)


Voltage input (nominal) Vx
V
Operating range
%Vx
Power supply burden
VA

24 to 125
80140
3.5

24 to 125
80140
3.5

24 to 125
80140
3.5

24 to 125
80140
3.5

24 to 125
80140
2.0

Output
Accuracy (4)
Reference range
Reference range
Compliance voltage (5)
Open circuit voltage
Relay contact rating
Pick up (pulsed output)
Drop off (pulsed output)
Maximum pulses per hour

pph

0.2
0120
0120
15
25

0.5
0120

15
25

0.5

15
25

1.0
0100
0100
15
25

0125

15
25
1A at 50V dc
3.33.9
1.42.0
4000

Temperature
Temperature reference range
Temperature coefficient
Nominal range of use

C
%/C
C

050
0.008
10+60

050
0.008
10+60

050
0.008
10+60

050
0.008
10+60

050
0.008
10+60

Miscellaneous
Ripple (rms)
Response time (0...99%)
Voltage overload: continuous
10s
Current overload: 3s
1s
Humidity (noncondensing)

%
s
xVn
xVn
xIn
xIn
% RH

0.35
0.5
1.2
1.5
2
10
93

0.35
0.5

2
10
93

0.35
0.5

93

0.35
0.5

93

0.35
0.5

1.25

93

%
%In
%Vn
V
V
A

%
%

Isolation
Impulse test
Surge withstand
1. Maximum permissible auxiliary
supply voltage is 500V ac.
2. Other inputs available on request.
3. Tap Position transducer has a
maximum of 33 taps.
4. Accuracy of full scale output unless
stated.

4kVrms 50 Hz for 60 seconds


5kV (1.2/50s) for BS923 and IEC 255221
IEC 255221 and ANSI C3790A IEEE Std 472 SWC where applicable
5. The output loading (kV) can be
obtained by dividing the compliance
voltage (V) by the maximum rated
output (mA). Examples are shown in
the table below.
Compliance
Voltage(V)

Value of output load ()


by output rating
1 mA

5 mA

10 mA

20 mA

11

11k

12

12k

15

15k

3k

1.5k

750

1kVrms

6. A maximum of 12 inputs can be


summated.

Phase Angle

Istat 300 Wiring Arrangements

Current lagging for output


polarity shown

The diagrams below indicate the


connections required for various types
of transducer.

Output
+

Correct polarity must be observed for


dc auxiliary supply.

15 14
1 2

6 7

12 13

Current, Voltage and Frequency

Note: Auxiliary required for:

Current 4...20mA

S1

S2

P1

P2

Aux
To load

Voltage 420mA & 020mA

7 Single Phase or 3 Phase 4 Wire

RMS Current

Balanced Load Phase Angle


Output
+

RMS Voltage
Suppressed zero voltage

15 14

Frequency 0.01%

8 9 10

1 2

12 13
+

Output
+

Output
A+

Output
B+

Output
C +

21 20

18 17

15 14

S1

S2

P1

P2

Aux

B
To load

7 6
1 2

4 5

S1

S2

P1

P2

1 2 3 4 5 6

12 13

+
Aux (If required)
To load

Means Sensing Current


or RMS Current

8 3 Phase 3 Wire Balanced Load

Phase Angle

+
Aux (If required)
Input
A

Input
B

Input
C

15 14
1 2

3 Element Mean Sensing Current


or RMS Current
Output
A+

Output
B+

Output
C +

S1

S2

21 20

2 3 4 5

V1

L
or

15 14

P1

P2

Aux

S1
P1

To load

S2
P2

9 3 Phase 3 Wire Unbalanced

8 9 10 11 12 13

+
Aux (If required)

Load Phase Angle

Output
+

+
Aux
(If required)

To load

Input
A

V2

6 7

18 17

Input
B

15 14

Input
C

1 2 3 4 5 6

11 12 13
+

4 3 Element Mean Sensing Voltage


Mean Sensing Voltage
or RMS Voltage or Suppressed Zero Voltage
or RMS Voltage

A
B

Output
+

12 13

B
C

7 6

8 9 10

5 6

+
A

Output
+

Output
+

Output
+

S1

S2

P1

P2
S1
P1

Aux
S2
P2
S1
P1

To load

S2
P2

N
7 6

15 14

4 5

6 7

12 13

10 3 Phase 4 Wire Unbalanced

Load Phase Angle

+
V1
V2

V1

L
or
N

5 0.1% Frequency

L
or

To load
V2

Output
+

Aux
15 14

To load

6 7

10 11 12 13
+

6 0.01% Frequency
L
N
L
N

Incoming

Aux

Running

11 Phase Difference

Watts and Vars

Combined Watts and Vars

Watts export/vars lagging for output


polarity shown

Watts export/vars lagging for output


polarity shown

15 14
1 2

6 7

S1

S2

P1

P2

15 14

12 13
Aux

Outputs

Output
+

+ Vars
Common
+ Watts

Output
+

1 2

8 9 10

+
A

To load

S1

S2

P1

P2

16 15 14

12 13
Aux

1 2

To load

12 13

13 3 Phase 3 Wire Balanced Load Watts ()

S1

S2

P1

P2

Aux

12 Single Phase Watts or Vars

8 9 10

+
A

5 6

S1

S2

P1

P2

To load

19 3 Phase 3 Wire Unbalanced Load Watts

1 2

9 10

S1

S2

P1

P2

Output
+

Output
+

15 14

15 14

12 13
Aux

5 6

1 2

12 13

S1

S2

P1

P2

Aux

B
To load

14 3 Phase 3 Wire or 3 Phase 4 Wire

1 2 3 4 5 6

P1

P2
S1

S2

P1

P2
S1

S2

P1

P2

B
C

P2

To load

Output
+

Output
+

15 14

15 14

Aux

S2

S2

P1

Watts or Vars 2 Element

8 9 10 11 12 13

S1

S1

15 3 Phase 3 Wire Unbalanced Load

Balanced Load Vars ()

8 9 10

1 2 3 4 5 6

+
A

To load
B
C

10 11 12 13
Aux

S1

S2

P1

P2
S1

S2

P1

P2
S1

S2

P1

P2

To load

16 3 Phase 4 Wire Unbalanced Load Watts

or Vars 3 Element (*)

17 3 Phase 4 Wire Unbalanced Load Watts

or Vars (21/2 Element)

Output
+
15 14
1 2

6 7

S1

S2

P1

P2

12 13
Aux

B
To load
C
N

18 3 Phase 4 Wire Balanced Load Watts

or Vars ()

: Alternative 2 CT connection for 3 phase balanced load available on request.


*: Auxiliary connection to dc supply is via dc converter.
8

and Vars Combined 2 Elements (*)

mA/Pulse Converter

DC Amplifiers

Input
+

Output
+

15 14

"Flo"

AC
Aux Input

"Pos"

"Pos" Relay: This indicates polarity of mA flow.


Contacts as shown in the negative
flow state.
"Flo" Relay:

15 14

15 14
6 7

12 13

Input

Aux.

12 13

4 5 6 7 8 9

Output
+

12 13

5 6 7

Hi

Lo

Aux.

Tap

22 Current or Voltage Input

23 Tap Position Indicator

Pulse rate indication

Output
+

20 AC Auxiliary

Output
+

15 14

Input
+

15 14

12 13

6 7

12 13

5 6 7

15 14
+
4 5 6 7 8 9 10 11 12 13
+
"Flo"

24 2 Wire Resistance Input

25 3 Wire Resistance Input

Isolated DC Aux
Inputs From Converter
"Pos" Relay: This indicates polarity of mA flow.
Contacts as shown in the negative
flow state.
"Flo" Relay:

+
Aux.

Aux.

"Pos"

Output
+

Output
+

15 14

Pulse rate indication

12 13

6 7

15 14
3 4

12 13

6 7

21 DC Auxiliary
+

Aux.

Thermocouple

26 Thermocouple Input

Aux.

CJC Thermocouple

27 Thermocouple Input with Cold Junction

Compensation (CJC)
AC Aux.

Output
+

25 24

15 14

1 2 3 4

+
1

+
2

+
3

5 6 7

+
4

+
5

+
6

Input

28 Summation

DC Converters

10 9

7 6

10 9

4 5

4 5

DC Supply

29 Two Output

DC Supply

30 Single Output

Case Outline and Fixing Details


Detachable terminal covers

All dimensions in mm

1,5

120

55

Notes:
i)

Terminal screws are M4


35

ii) Washers on terminal screws


are captive
iii) Unused terminal positions are
blanked off
iv) Terminals suitable for ring tags to
9.5mm outside diameter

Terminal
No.1

Terminal
pitch

10,7

78

55

74

DIN rail fixing


35 x 7,5 DIN rail
to spec EN 50 022
(B.S. 5584)

3
2 Holes 5,4 to accept M5 stud fixing
as alternative to DIN rail
9

60

128

40

7,5

Outline of 55mm case

Detachable terminal covers


120

150

55
35

10,7

Terminal No.1

Terminal
pitch

78

1,5

74

DIN rail fixing


35 x 7,5 DIN rail
to spec EN 50 022
(B.S. 5584)
4 Holes 5,4 to accept M5 stud fixing
as alternative to DIN rail
9

128

60

7,5

135
Outline of 150mm case

Packed Dimensions
Individual Units
55mm Housing

180 x 115 x 70mm

150mm Housing 250 x 165 x 90mm

10

Shipping Weights
The following applies to single units.
Multiple units will be supplied shrink
wrapped together.
In practice, export orders will have
additional secondary packaging consult factory for details.
Transducer
Type

Housing
(mm)

Weight (kg)
Nett
Gross

Single Current

55

0.51

0.66

Triple Current

150

1.50

1.70

Single Voltage

55

0.50

0.65

Triple Voltage

150

1.50

1.70

Suppressed Zero Voltage

55

0.60

0.75

Frequency 0.1%

55

0.33

0.48

150

0.64

0.84

Phase Angle

150

0.82

1.02

Watt

150

1.00

1.20

Var

150

1.00

1.20

Combined Watt/Var

150

1.10

1.30

DC Amplifier

150

0.80

1.00

mA/pulse Converter

150

0.70

0.90

55

0.50

0.65

0.01%

DC/DC Converter

11