You are on page 1of 5

STORAGE TANK SPECIFICATION

(English Units)

Morichal

Sheet

1 of 1

1 Service :
3 Manufacturer :

T 3101 B

Unit :

Model :

4 P&ID No.

T 3101 B

Equipment No. :

Diluent storage tank


Morichal

2 Location :

Design Engineer :

Mfr Ref. No. :


Plot Plan No. :

Rev. No.

Project No.

One

No. Req'd :

Other Ref. Dwg No. :

5
6
7
8
9
10

11
12

129.92

13

Ft

14

48.23 Ft

15
16

24" X 36"
FLUSH
CLEANOUT

17

18
19

20

21

N1

22

N2

23
24 Shell Diameter :
25 Roof Type :

129.92
Cone

26

Feet

48.23

Shell Height :

Feet

LUBE OIL

NOZZLES/CONNECTIONS

1.0000

Sp. Gr. :

28 This Tank Service is considered:

Cyclic

5.5

29 Vapor Pressure @ Max. Operating Temperature


30 Flash Point (Closed Cup) :

Mark

Service

Qty

Size

TH1

Roof Manway

24"

TH

Shell Manway

24"

Operating

Design

psia

TH2

Flush Cleanout MW

24"x36"
8"

31 Negative Pressure

oz/in.2

0.00

0.50

Stilling Vent

32 Positive Pressure

psig

1.00

2.00

Temperature Indicator

Outlet Nozzle

12"

Fill Nozzle

8"

Mixer Manway

Water Draw Nozzle

4"

Top Center Vent

4"

Sample Tap

3/4"
3/4"

----

33 (Hydro)test Pressure expressed in Psig


34 Minimum Fluid Temperature

35 Maximum Fluid Temperature

36 Emergency Vacuum Design ?


37

No

-25
200
Set @

0.0.3

oz/in.2

METALLURGY

38

Component

Barrels

Sloped

OPERATING/DESIGN DATA

27 Fluid Stored :

113,878

Nominal Volume :

Bottom Floor Type:

Material

CA, in.

Remarks

39 Shell & Bottom

A36

0.1250

Normalized

Sample Tap

40 Roof

A36

0.1250

Normalized

Roof Nozzle

4"

Spare

3/4"

41 Lining/Coating
42
43 Stress Relieve ?
44

No

for:

Rating
150#
125#
125#
150#
150#
150#
150#
150#
150#
150#
150#
150#
150#
150#
150#
150#

Face
F. F.
R. F.
R. F.
F. F.
L. J.
API
L. J.
F. F.
R. F.
API
R. F.
F. F.
L. J.
API
API
API

CONSTRUCTION/FABRICATION

API 650 LATEST EDITION

45 Code (as appl.):

Internals (attach separate sheet, as req'd):

46 Design Specifications:
47 Tank Insulation ?

No

48 Insulation Type:
49 Fireproofing ?

Others:

Sump
Thickness :

in.

Hot

No

Radiograph
Paint Spec.

2A

Seismic Zone
85

EmptyTank Weight

Design Wind Velocity


% Inspection Req'd ?

976,822 lb

55.92

mph

Yes

Full of Water

36,573,773 lb

50 Remarks
51

1. Items marked with an asterisk (*) to be completed by Vendor/Fabricator.

52

2. Rafter supported type cone roof

Approvals
Rev
0

Date

Description

By

Chk.

Appr.

Rev

Date

Description

By

Chk.

Appr.

04/14/2016
Rev: 0

API 650 Storage Tank

TANK T 3101 B SHELL PLATE DESIGN CALCULATION by ONE FOOT METHOD


D = Normal tank diameter , in feet

129.92

H = depth of tank , in feet


Shell Plate Design :

48.23

39.6 meters
14.7 meters

FROM ( BOTTOM COURSE) PLATE TO (TOP COURSE) PLATE

SG = design Specific gravity of liquid


Sd = allowable Stress for Design condition
E = joint efficiency
St = allowable stress A36 Hydro Test
CA = Corrosion Allowance
For First Course (Bottom) A36 Plate ;

Provided thickness:

1
23,200
1.00

160 Mpa

24,900
0.1180

171 Mpa
3.00 mm

20.000

As per API 5.6.3.2 In US Customary units;

td = 2.6(D)(H -1)(SG)/Sd =

0.688

17.47 mm

tt = 2.6(D)(H-1)/St =

0.641

16.27 mm

0.759
129.92
48.23
1.00
23,200
1.00

19.271 mm

td = Minimum shell course thickness plus C.A, in inches =


D = Normal tank diameter , in feet =
H = depth of tank , in feet =
SG = design Specific gravity of liquid =
Sd = allowable Stress for Design condition
E = joint efficiency
St = allowable stress A36 Hydro Test
CA = Corrosion Allowance
For Second Course A36 Plate

24,900
0.1180

Provided thickness:

3.000

18.000

As per API 5.6.3.2 In US Customary units;

td = 2.6(D)(H -1)(SG)/Sd =

0.688

17.47 mm

tt = 2.6(D)(H-1)/St =

0.641

16.27 mm

0.759
129.92
39.454
1.00
23,200
1.00
24,900
0.1180

19.27 mm

td = Minimum shell course thickness plus C.A, in inches =


D = Normal tank diameter , in feet
H = depth of tank , in feet
SG = design Specific gravity of liquid =
Sd = allowable Stress for Design condition
E = joint efficiency
St = allowable stress A36 Hydro Test
CA = Corrosion Allowance
For Third Course A36 Plate

Provided thickness:

16.000

As per API 5.6.3.2 In US Customary units;

td = 2.6(D)(H -1)(SG)/Sd =

0.560

14.22 mm

tt = 2.6(D)(H-1)/St =

0.522

13.25 mm

0.640
129.92
32.909
1.00
23,200
1.00
24,900
0.1180

16.25 mm

td = Minimum shell course thickness plus C.A, in inches =


D = Normal tank diameter , in feet
H = depth of tank , in feet
SG = design Specific gravity of liquid =
Sd = allowable Stress for Design condition
E = joint efficiency
St = allowable stress A36 Hydro Test
CA = Corrosion Allowance

Seth A. Duazo
Nass Mechanical

Page 2 of 5

FileName: 313805276.xls
WorkSheet: 11T-503A

04/14/2016
Rev: 0

API 650 Storage Tank

TANK T 3101 B SHELL PLATE DESIGN CALCULATION by ONE FOOT METHOD


D = Normal tank diameter , in feet

129.92

H = depth of tank , in feet


For Fourth Course A36 Plate

48.23
Provided thickness:

39.6 meters
14.7 meters

12.000

As per API 5.6.3.2 In US Customary units;

td = 2.6(D)(H -1)(SG)/Sd =

0.506

12.85 mm

tt = 2.6(D)(H-1)/St =

0.433

11.00 mm

0.551
129.92
26.3632
1.00
21,300
1.00
24,900
0.1180

13.99 mm

td = Minimum shell course thickness plus C.A, in inches =


D = Normal tank diameter , in feet
H = depth of tank , in feet
SG = design Specific gravity of liquid =
Sd = allowable Stress for Design condition
E = joint efficiency
St = allowable stress A36 Hydro Test
CA = Corrosion Allowance
For Fifth Course A36 Plate

Provided thickness:

10mm

As per API 5.6.3.2 In US Customary units;

td = 2.6(D)(H -1)(SG)/Sd =

0.402

10.22 mm

tt = 2.6(D)(H-1)/St =

0.344

8.74 mm

0.462
129.92
19.754
1.00
21,300
1.00
24,900
0.1180

11.74 mm

td = Minimum shell course thickness plus C.A, in inches =


D = Normal tank diameter , in feet
H = depth of tank , in feet
SG = design Specific gravity of liquid =
Sd = allowable Stress for Design condition
E = joint efficiency
St = allowable stress A36 Hydro Test
CA = Corrosion Allowance
For Sixth Course A36 Plate

Provided thickness:

8mm

As per API 5.6.3.2 In US Customary units;

td = 2.6(D)(H -1)(SG)/Sd =

0.268

6.80 mm

tt = 2.6(D)(H-1)/St =

0.254

6.46 mm

0.372
129.92
13.194
0.9
21,300
1.00
24,900
0.1180

9.46 mm

td = Minimum shell course thickness plus C.A, in inches =


D = Normal tank diameter , in feet
H = depth of tank , in feet
SG = design Specific gravity of liquid =
Sd = allowable Stress for Design condition
E = joint efficiency
St = allowable stress A36 Hydro Test
CA = Corrosion Allowance
For Seventh Course A36 Plate

Provided thickness:

8mm

As per API 5.6.3.2 In US Customary units;

td = 2.6(D)(H -1)(SG)/Sd =

0.193

4.91 mm

tt = 2.6(D)(H-1)/St =

0.165

4.20 mm

0.283
129.92
6.63
1
21,300
1.00
24,900
0.1180

7.20 mm

td = Minimum shell course thickness plus C.A, in inches =


D = Normal tank diameter , in feet
H = depth of tank , in feet
SG = design Specific gravity of liquid =
Sd = allowable Stress for Design condition
E = joint efficiency
St = allowable stress A36 Hydro Test
CA = Corrosion Allowance
Seth A. Duazo
Nass Mechanical

Page 3 of 5

FileName: 313805276.xls
WorkSheet: 11T-503A

04/14/2016
Rev: 0

API 650 Storage Tank

TANK T 3101 B SHELL PLATE DESIGN CALCULATION by ONE FOOT METHOD


D = Normal tank diameter , in feet

129.92

H = depth of tank , in feet

48.23

39.6 meters
14.7 meters

BOTTOM PLATE DESIGN:


As per API 650 11th Ed. 2009 Add. 2 Sect. 5.4.1;

Minimum Nominal Thickness excluding corrosion allowance, Inch


Corrosion Allowance for Bottom Plate
Required Thickness of Bottom Plate
Used bottom plate thickness
Minimum Nominal Width, Inch
Used bottom plate Width,in

0.25
0.125
0.25
0.375
70.866
78.74

6.35
6.00
6.35
10
1800.0
2000.0

mm
mm
mm
mm
mm
mm

ANNULAR BOTTOM PLATE DESIGN:


As per API 650 11th Ed. 2009 Add. 2 Sect. 5.5.2;

Minimum Annular plate Width shall be =

215 tb
( GH )

or a Minimum of
Annular Plate width provided; in

28.62

727 mm

23.622

600 mm

0.5

29.92
Where: tb = Annular plate thickness, mm
H = maximum Design Liquid level, Meter
G = liquid Specific gravity

760 mm

HENCE, OK.

ROOF PLATE DESIGN: ( Non Frangible roof Tank)


As per API 650 11th Ed. 2009 Add. 2 Sect. 5.10.2.2,

Minimum Nominal Thickness excluding corrosion allowance =


Corrosion Allowance for Roof Plate, =
Required Thickness of Roof Plate =
Used roof plate thickness =

0.1875
0.3125
0.1875
0.1875

5
8
5
5

mm
mm
mm
mm

SHELL STABILITY CHECK;


As per API 650 11th Ed. 2009 Add. 2 Sect. 5.9.7.1

The Maximum height for the unstiffined shell shall be calculated as follows:
H1 = 600,000*(t)*(((t/D)^3)^0.5)*(120 /V)^2 = , ft

23.82

7.26 Meters

Where;
H1 = Vertical Distance in ft, betwwen the intermediate wind girder and the top angle of the shell or the top wind girder of an open top tank

t = as built thickness, unless otherwise specified of the thinnest shell course (in Inches)
D = Nominal Tank height, Ft
V = Designed wind speed (3 sec gust)mph

Seth A. Duazo
Nass Mechanical

Page 4 of 5

FileName: 313805276.xls
WorkSheet: 11T-503A

04/14/2016
Rev: 0

API 650 Storage Tank

TANK T 3101 B SHELL PLATE DESIGN CALCULATION by ONE FOOT METHOD


D = Normal tank diameter , in feet

129.92

H = depth of tank , in feet

48.23

Equivalent stable height of


shell at ' t ' min. HE = sum He
He = W( ' t 'min / ' t 'actual)^2.5
As per API 650 11th Ed. 2009 Add. 2 Sect. V.8.1.4 (b)
Course
Width (M)
t' min (mm)
1
1.995
20.00
2
1.995
16.00
3
1.995
15.00
4
2.0
12.00
5
2.0
10.00
6
2.0
8.00
7
2.0
8.00
Minimum Shell Thickness = 8mm
Transformed shell height,
Maximum height of unstiffined shell=

W' tr

39.6 meters
14.7 meters

Wtr (Meter)
0.202
0.353
0.414
0.726
1.145
2.000
2.000

6.840

Meters

7.26 Meters

H1 > Wtr, hence intermediate wind girder is not required

Seth A. Duazo
Nass Mechanical

Page 5 of 5

FileName: 313805276.xls
WorkSheet: 11T-503A

You might also like