You are on page 1of 10

MICOM P442 SETTING CALCULATION TEMPLATE

Please Enter the line parameter and required value in yellow coloums.
Length of the protected line
KM
156.5
Positive Sequence Resistance per KM
Ohms
0.01
Positive Sequence Reactance per KM
Ohms
0.30
Zero Sequence Resistance per KM
Ohms
0.26
Zero Sequence Reactance per KM
Ohms
1.05
Positive Sequence Resistance for prot. line
1.78
Ohm
Positive Sequence Reactance for prot. line
46.17
Ohm
Positive Sequence Impedance for prot. line
46.20
Ohm
Positive Sequence Impedance Angle
87.79
Degree
Zero Sequence Resistance for prot. line
Ohm
41.21
Zero Sequence Reactance for prot. line
164.79 Ohm
Zero Sequence Impedance for prot. line
169.87 Ohm
Zero Sequence Impedance Angle
75.96
Degree
Details of Adjacent Shortest line
Length of the adjacent shortest line
Pos. Seq. Resistance. Of Adj. Line
Pos. Seq. Reactance. Of Adj. Line
Pos. Seq. Impedance of Adj. Line
Pos. Seq. Impedance Angle of Adj. Line

17.00
0.03
0.31
5.24
84.62

KM
Ohm
Ohm
Ohm
Degree

Details of Adjacent longest line


Length of the adjacent longest line
Pos. Seq. Resistance. Of Adj. Line
Pos. Seq. Reactance. Of Adj. Line
Pos. Seq. Impedance of Adj. Line
Pos. Seq. Impedance Angle of Adj. Line

413.00
0.03
0.31
127.42
84.62

KM
Ohm
Ohm
Ohm
Degree

2000.00
1.00
400.00
110.00
0.55

Amp
Amp
Kilo Volt
Volt

CT & PT Details
CT Primary
CT Secondary
PT Primary
PT Secondary
CT / PT Ratio
Secondary Value impedance
Positive Sequence Impedance for prot. line
Pos. Seq. Impedance of Adj.Shortest Line
Pos. Seq. Impedance of Adj.Longest Line

25.411078 Ohm
2.8846615 Ohm
70.080306 Ohm

Magnitude of Grounding Factor Kg


Angle of Grounding factor Kg

0.9018806
-16.16974 Degree

Primary Full Load current


Zone 1 required % of Line
Zone 2 required % in Shortest Line

2000
80
50

Amp
%
%

Zone 3 required % in Longest Line


Zone 4(R) required % of Line
Enter the Required % of R3Ph for R & X

110
25
20

%
%
%

Relay Setting Value:


Load resistance in secondary
Resisitive Reach for all Zone Phase(80% Load
resistance)
Resisitive Reach for all Zone Ground (90% Load
resistance)

Z1
Z2
Z3
Z4
Magnitude of Grounding Factor Kg
Angle of Grounding factor Kg
Power Swing
R & X

25.40 Ohms
20.32 Ohms
22.86 Ohms

20.33
26.85
102.50
5.08
0.90
-16.17

Ohms
Ohms
Ohms
Ohms
Degree

4.06 Ohms

Note:
Decide the other related values (I.e) tZ1,tZ2,tZ3 and tZ4,Power swing,SOTF,O/C & E/Fsetting.

DONT TRY TO CHANGE ANY FORMULA.

setting.

MICOM P437 SETTING CALCULATION TEMPLATE


Please Enter the line parameter and required value in yellow
coloums.
Length of the protected line
KM
36.5
Positive Sequence Resistance per KM
Ohms
0.08
Positive Sequence Reactance per KM
Ohms
0.40
Zero Sequence Resistance per KM
Ohms
0.28
Zero Sequence Reactance per KM
Ohms
1.28
Positive Sequence Resistance for prot. line
2.96 Ohm
Positive Sequence Reactance for prot. line
14.60 Ohm
Positive Sequence Reactance for prot. line
14.60 Ohm
Positive Sequence Impedance Angle
78.55 Degree
Zero Sequence Resistance for prot. line
10.04 Ohm
Zero Sequence Reactance for prot. line
46.54 Ohm
Zero Sequence Impedance for prot. line
47.61 Ohm
Zero Sequence Impedance Angle
77.83 Degree
Details of Adjacent Shortest line
Length of the adjacent shortest line
Pos. Seq. Resistance. Of Adj. Line
Pos. Seq. Reactance. Of Adj. Line
Pos. Seq. Reactance of Adj. Line
Pos. Seq. Impedance Angle of Adj. Line

6.00
0.08
0.40
2.40
78.69

KM
Ohm
Ohm
Ohm
Degree

Details of Adjacent longest line


Length of the adjacent longest line
Pos. Seq. Resistance. Of Adj. Line
Pos. Seq. Reactance. Of Adj. Line
Pos. Seq. Reactance of Adj. Line
Pos. Seq. Impedance Angle of Adj. Line

132.00
0.08
0.40
52.80
78.69

KM
Ohm
Ohm
Ohm
Degree

800
1
220
110
0.4

Amp
Amp
Kilo Volt
Volt

CT & PT Details
CT Primary
CT Secondary
PT Primary
PT Secondary
CT / PT Ratio
Secondary Value Reactance
Positive Sequence Reactance for prot. line
Pos. Seq. Reactance of Adj.Shortest Line
Pos. Seq. Reactance of Adj.Longest Line

5.84 Ohm
0.96 Ohm
21.12 Ohm

Magnitude of Grounding Factor Kg


Angle of Grounding factor Kg

0.73
-1.05 Degree

Primary Full Load current


Zone 1 required % of Line
Zone 2 required % in Shortest Line

800 Amp
80 %
50 %

Zone 3 required % in Longest Line


Zone 4(R) required % of Line
Enter the Required % of R3Ph for R & X

100 %
13.6 %
10 %

Relay Setting Value:


Load resistance in secondary
Resisitive Reach for all Zone
Phase(80% Load resistance)
Resisitive Reach for all Zone Ground
(90% Load resistance)

25.40 Ohms

20.32 Ohms
Ohms
22.86

Z1
Z2
Z3
Z4
Magnitude of Grounding Factor Kg
Angle of Grounding factor Kg

4.67
6.32
26.96
0.64
0.73
-1.05

Ohms
Ohms
Ohms
Ohms

Power Swing
R & X

22.36 Ohms

Degree