You are on page 1of 29

DANIELI

GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Revision

GS-S-01
XXXXAS90S80001

01
Sheet

of

28

Printed

ITALY

Job

Document n.

Contractual item

DANIELI item (TPC)

Title

INSTRUMENTATION
Approvals

Remarks

C
C
C
C
C
C
C
C
01

10.11.00

Revised as indicated

00

08.04.96

Issue for information

Date

Revisions description

Rev. File

D. Zorzi

ZOD

Compiled

A. Serafini

SEA

Checked

P. Iuri

IUP

Approved

According to law DANIELI & C. SpA considers this document to be a company secret and therefore prohibits any person to reproduce
it or make it known in whole or in part to other parties or to competitors without specific written authorisation of DANIELIs
Management.

File: GSS01_01.doc

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Document n.

GS-S-01
XXXXAS90S80001
Printed

ITALY

Revision

00
Sheet

of

28

INSTRUMENTATION AND CONTROLS


CONTENTS
1.0
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8

GENERAL
Scope
Standards
Design basis
Environmental conditions
Protection degree
Measurement units
Electric power and signals
Identification system

2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
2.9
2.10

FIELD INSTRUMENTS AND CONTROL EQUIPMENT


Flow
Pressure and differential pressure
Level
Temperature
Analyser
Weighing system
Encoders
Control drives and valves
Single loop controllers
Instrument panels and desks

3.0
3.1
3.2
3.3
3.4

INSTALLATION
Mounting of instruments
Instrument process connections
Instrument piping
Cabling

4.0

DRAWING AND DOCUMENTS

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

1.0

GENERAL

1.1

Scope

01

GS-S-01
XXXXAS90S80001
Printed

ITALY

1.2

Document n.

Revision

00
Sheet

of

28

This specification outlines the basic requirements covering the design,


selection, supply and installation of all process measuring instruments,
control equipment and associated accessories as required for
instrumentation and control systems.

The instrumentation and control system equipment shall be complete in all


respects and any device not included in the specification but is essential for
proper operation of equipment and process shall deem to be within the scope
of specification whether specifically mentioned or not.

When special instruments not covered by this specification are required,


Danieli shall choose and include them on the basis of technical specification
required for the technological areas.

Standards
All design, installation materials and equipment shall be in compliance with the
following standards.
IEC
International Electric Commission
ISA
Instrument Society of America (For coding system)
UNI
Unificazione Italiana
DIN
Deutsche Normen
ANSI/ASME American standard
Exclusion
These regulations shall not apply to electrical test instrumentation and controls of
generation, distribution and utilisation facilities of electrical power and energy.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

1.3

Document n.

Revision

00
Sheet

of

28

Design basis

01

The instrumentation and control system equipment included shall be sufficient


to monitor and control all significant variables in accordance with the process
requirements, provide all operating requirements and necessary safety
controls including alarms for abnormal conditions.

The instrumentation and control system components shall be suitable for a


continuous and reliable operation and due consideration shall be given to the
environmental conditions in steel plants, particularly the presence of fair
amount of conductive dust and hazardous areas requiring circuitry, except
where differently specified.

The number of different sizes and types of instruments and control equipment
adopted for instrumentation system design shall be oriented towards
maximising interchangeability and minimising maintenance as well as to
provide easy interfacing with the process control computers.

The design shall include all reasonable precautions and provisions for the
safety of operating and maintenance personnel.

All systems and equipment shall be designed for a fail-safe operation, as and
where applicable.

The instrumentation and control system equipment shall be so designed that


the selected instruments accuracy as well as overall accuracy of the system
meets the process requirements in order to achieve general performance of
the technological equipment on the basis of service conditions envisaged.

01

However the overall accuracy of different measurement loops, including the


measuring elements, shall be as follows:

1.4

flow:

- with magnetic flowmeter


- with vortex type flowmeter
- with differential pressure
pressure

1.0% span
1.5% span
2.5% span
1.0% span

level

1.5% span

temperature

1.0% span

Environmental conditions
-

All instruments and control equipment which have to be installed outdoor, not
in shadow or indoor shall be done for an ambient temperature of 40C unless
a higher ambient is specifically stated in the Technical Specification.

All equipment and accessories shall be designed to withstand the operating


conditions in the plant and the atmospheric conditions on site.

01

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

1.5

Document n.

Revision

00
Sheet

of

28

Protection degree
Local instruments shall be dust and weather proof, explosion proof if necessary,
suitable for use under ambient conditions prevalent in a specific plant.
Protection degree for instruments and control devices shall generally be:
.

inside the cabin, buildings

IP30

indoor installation

IP54

Outdoor installation

IP55

unless otherwise specified.


1.6

01

Measurements units
The measurement units adopted shall be:
-

pressure
gauge pressure
vacuum
temperatures
mass flow (gas)
volume flow (gas)
flow (liquids)
level
density
dynamic viscosity
speed
weight
electric conductivity

bar-mbar
barg - mbarg
mbar - torr
C
kg/h
3
m /h
3
m /h
m
3
kg/dm
Pa*s
m/s
kg - t
S/cm

The other not listed measurement units shall be in accordance with the
International System of Units.
1.7

Electric power and signals


01

The instrument and control system equipment shall be suitable for:


- power supply
- generally 110V + 5% single phase 50 Hz + 1,5 Hz
or according to particular project requirements
- 24 V d.c.
Transfer of the measurement signal:
- output
standardised 4-20mA current signal
- connection
2 wire technique

01

Switches:
- switches shall be either contact or two-wires proximity switches
( three wires switch can be used for particular instruments)
- contact shall be snap-action micro-switches type, 2A minimum rate at
220/230 V a.c. (resistive load)
- contacts shall also be capable to operate with low voltage and low current
systems (PLC inputs)

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

1.8

Document n.

Revision

00
Sheet

of

28

Identification system
The identification system is based on the standard ISA S5.1.
Every instrument is identified by a tag consisting of a series of letters which
define the functional features and of a number which identifies the loop the
instrument is part of. A letter suffix can be added to this number in order to
identify several of similar instruments.
LL(LL)

01

(NN)

NNN(N)

L
suffix letter (if necessary)
loop identification number
plant unit (see remarks)
functional identification

Functional identification
It consists of a series of letters (usually not more than 4), as TAB 1, where the
first letter indicates the process variable, and the following ones identify the
functions of the instruments. A modification letter may be added to the first or
following cases. All letters must be capital.
LOOP identification
The identification of the loop consists of a maximum number of 6 digits, where
the first two identify the plant unit and the following ones the number of the loop.
Loop numbering is parallel. Parallel number involves starting a numerical
sequence for new first letter. The loop number sequence may incorporate coded
information. The number is identical for all the instruments involved on the loop.

01

Suffix letter (if necessary)


If a given loop has more than one instrument with the same functional
identification, a suffix letter may be added to a loop number.
Remarks
-

For instruments, which are part of machine, the number identifying the plant
unit is omitted. In this case, for complete identification of instrument within the
plant, the tag number is preceded by the equipment code of the machine.
The loop number sequence restarts for each machine. On the P&ID diagrams
the machine is represented inside a box indicating the machine take over
point.

For instruments, which are part of production and distribution plants or


complex plants, the plant unit identification must be always included on tag
number. The loop number sequence restart for each plant unit, number
sequence shall be fixed during detail design considering quantity of
instrument included on each part of plant unit.

01

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

Document n.

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

Revision

00
Sheet

of

28

Tab. 1 - Meaning of identification letters


01

A
B
C
D
E
F

01

Measure or
initiating variable
Analysis (1)
Flame detector
Conductivity
Density
Voltage
Flow

Modifier

Read out or
passive function
Alarm
Users choice (6)

Output function

Modifier
Users choice (6)

Control
Differential
Primary element
Ratio
Glass,
viewing device(5)

Users choice (6)

H
I
J
K
L

Hand
Current (electrical)
Power
Time
Level

Scan

Moisture

Momentary

High (2)
Indicate
Control station
Light

Low (3)

Users choice (6)

Users choice (6)

Middle or
intermediate
Users choice

Users choice (6)

Orifice (restriction)

Pressure, vacuum

Point
(test connection)

Q
R
S
T
U
V
W
X

Quantity
Radiation
Speed, frequency
Temperature
Multivariable
Vibration
Weight, force
Unclassified

Event,
state or presence

Relay, compute,
convert (4)

Position, dimension

Driver, actuator

Users choice (6)

Integrate, totalize
Record
Safety
Multifunction
Well
Unclassified

Switch
Transmit
Multifunction
Valve
Unclassified

Multifunction

Unclassified

Note
(1) - Type of analysis is indicated outside the instrument symbol
(2) - Limit switch valve open (ZSH), limit switch high position, motor running; HH = very high
(3) - Limit switch valve closed (ZSL), limit switch low position, motor stop; LL = very low
(4) - The compute function is indicated outside the instrument symbol
(5) - Direct reading or viewing devices
(6) - The meaning of chosen letters are defined in a legend of a diagram

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

01

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.0

Document n.

Revision

00
Sheet

of

28

FIELD INSTRUMENTS AND CONTROL EQUIPMENT


General
All instruments shall be supplied with name plate with identification tag number.
The name plate shall be attached permanently to all casing.
Generally the name plate shall be of stainless steel.

2.1

Flow

2.1.1

Flow elements
In general, the concentric type orifice shall be used. Eccentric or segmental
types shall be used for measurement of dirty gases or fluids carrying suspended
matter which might tend to cause build-up.
Flow nozzle shall be used when fluid velocities and temperatures in pipelines are
very high.
Venturi tubes shall only be used when operating economy requires low
permanent pressure losses.
Orifice plates shall be sized according to ISO5167.

01

The orifice ratio (ratio or orifice inside diameter to process pipeline internal
diameter) shall, in general, be between 0.3 and 0.75 for metering accuracy.
Orifice plates shall be made of suitable grade stainless steel, unless process
conditions require some other material.

01

Orifice plates shall be complete of annular chamber or flanges with pressure


tapping.
Orifice taps will be 1/2 G (Female) (or NPT according to plant standard)
Annular chambers shall be of the same material of the pipe unless otherwise
specified.
The following items will be permanently marked on the orifice plate:
1)
2)
3)
4)

orifice diameter
flange size and pressure rating
inlet (+ - indication)
tag number

When the pipe size is 12 mm or smaller and the fluid is clean, integral orifice i.e.
orifice with integral differential pressure transmitter shall be considered.
Generally orifice plates shall be designed for flange taps, however venacontracta taps (D and D/2 taps) may be used.
Recommended lengths of straight pipe will be designed in accordance with
ISO5167 requirements.
The flow measurement of gas will be pressure and temperature compensated if
necessary.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Document n.

GS-S-01
XXXXAS90S80001
Printed

ITALY

Revision

00
Sheet

of

28

For particular measures other primary elements such as pilot tubes or others
may be used.
2.1.2

Flow transmitters
Differential pressure transmitters shall be used with flow element previously
described, materials for measuring element and internal part according to
process fluid. Transmitters shall be complete with equalising valve manifold and
mounting bracket.
The overpressure capacity shall not be less than the maximum pressure to which
the instrument will be exposed during normal operating conditions without giving
rise to calibration errors.
For measurements with higher accuracy and for wide range of measurement,
magnetic type flow sensors shall be used to measure the flow rate of electrically
conductive, viscous and/or corrosive fluids. Interior lining shall be of hard rubber
neoprene or teflon or other suitable material. Electrodes shall generally be of
stainless steel but in case of highly corrosive fluid electrodes with suitable
material shall be provided.
Transmitters shall met the following minimum requirements:
- accuracy
+ 0,5% of span or better
- adjustment
zero, span
- accessories
built in local indicator, when
required.
The measuring range shall be selected such that the maximum flow condition
remains at/within 90% of measuring range.
Vortex type flowmeters may be used on gas measurements

2.1.3

2.1.4

01

Flow indicators
-

Flow indicators shall be rotameters.

Rotameters, when used, shall be of metal type with magnetic indicator or


glass type.

For large and very large flow calibrated orifice plate flowmeters with off-take
flowmeter shall be used.

Scales shall be linear or square root direct reading type.

Flow switches
-

Flow type switches shall be of either hot wire principle or orifice or variable
area or target type.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Document n.

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.2

Pressure and differential pressure

2.2.1

Pressure and differential pressure transmitters


-

Revision

00
Sheet

10

of

28

Pressure and differential pressure transmitters shall be of semi-conductor,


capacitance or inductive type sensor. The transmitter shall have oil filled
bellows/diaphragm as measuring element. Differential pressure type shall be
provided complete with equalising valve manifold.
Transmitters shall have easily accessible span and zero adjustment facilities
and shall also meet the following minimum requirements:

Accuracy

0.25% span or better

Repeatability

0.1 % span

Dead band

0.1% span

Ambient temperature effect

0.5% span per 10C change

Mounting

universal type bracket


suitable for horizontal or vertical support

Accessories

built in local indicator when required

Connection to process

1/2 G or flange DIN 19213


(or NPT according to plant standard)

Material

case, measuring element and internal


parts shall be made of material that is
corrosion resistant to process fluid and
ambient atmosphere. Sealing oil shall be
used wherever required.

01

In all cases the overpressure capacity shall not be less than the maximum
pressure to which the instrument will be exposed during normal operating
conditions without giving rise to calibration errors.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

00
Sheet

11

of

28

Pressure and differential pressure indicators

01

2.2.3

GS-S-01
XXXXAS90S80001

Revision

Printed

ITALY

2.2.2

Document n.

01

Dials shall generally be 100 mm diameter, calibrated dial and shall be of


either bellow of diaphragm of Boudon tube types and shall be provided with
stainless steel case.

Accuracy shall be as per class 1.6 or better.

Scale shall be white with black lettering

Connection process G (or NPT according to plant standard)

Differential pressure indicators shall be completed with equalising valve


manifolds

Pressure gauges shall be completed with needle valve to isolate instrument


from pressure medium or to throttle and to dampen pressure pulses.

Overload protection of the instruments shall be at least 1,3 times the


maximum static operating pressure

Gauges for steam service shall be connected with siphon.

Gauges shall be also of diaphragm type or fluid filled manometers.

Pressure and differential pressure switches


-

Pressure switches shall be of either bellows or diaphragms or piston type.

Differential pressure type switches shall be of either gauge pointer detectors


or DP-cells type.

Accuracy:
. dP-cell
. gauge pointer detector

0,5% of span up to 16 bar


Class 1,6

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.3
2.3.1

Document n.

Revision

00
Sheet

12

of

28

Level
Level transmitters
The level transmitter will be selected to meet the different requirements of
process. the following level detection methods are used:
-

capacitive

hydrostatic

ultrasonic

electromechanical

radiometric

Transmitters shall meet with standard materials for construction that are suitable
for process and ambient conditions.
01

2.3.2

Radiometric radiation type transmitter shall have adequate shielding to limit the
radiation field. Safety source holder shall have adequate rotary shutter for
complete shielding during shipping, storage and installation.
Level indicators
-

Gauge glasses, in general, shall be flat glass type with bolted cover, except
that tubular gauge shall be used in non-hazardous service. It generally shall
be directly installed on the tank.

Level coverage shall be in accordance with the operating requirements.

Reflex type gauge glasses shall be used for colourless liquid and transparent
type gauge glasses shall be used for all liquids having colour.

Gauge glass shall be complete with a pair of offset valves and drainage valve
for tank connection.

01

2.3.3

Level switches
The level switch will be selected to meet the different requirements of process.
The following detection methods are used:
-

floating

conductive

vibration

electromechanical

counter weight

ultrasonic

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Document n.

Revision

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.4

Temperature

2.4.1

Temperature elements

00
Sheet

13

of

28

The primary elements for temperature service shall consist of resistance bulb,
thermocouples, filled-in system or radiation pyrometers depending upon the
range of measurement as follows:
Object
Fluids

Measuring Range
up to 1600C
up to 1200C
up to 900C

Measuring Element
Thermocouple
Type: "S
Thermocouple
Type: "K"
Thermocouple
Type: "J"

-200 to 500C
Solids

iron-costantan
Resistance bulb for
high temperature use
(Pt - 100)

Radiation pyrometer

The resistance bulb thermometer shall be made of high purity platinum wire
wound on ceramic or glass core. This shall be connected by three-leads
method.

Resistance winding material shall be stable and shall posses a linear


resistance - temperature relationship over the temperature range covered by
the application.

Stainless steel tubes shall be used as protective sheaths for all types of
resistance thermometers.

Duplex type thermocouples shall be provided wherever specified.

Thermocouple temperature and emf calibration shall conform to relevant DIN


standards. Suitable signal conditioners and/or linearization compensator,
located in control room, may be used if minimum range has to be extended.

For thermocouples, stainless steel, inconel or ceramic tubes, Mg0 filled, shall
be used as protective sheath.

Special extendable thermocouple will be used for the liquid steel temperature
measurements

Thermocouples shall be provided with cold junction compensation devices

Thermowells shall be used for all temperature elements and pressure


application. Material of construction of thermowells shall be of suitable
stainless steel, inconel or ceramic, unless some other material is required
due to process conditions.

For measuring temperature of high pressure process fluid tapered protection


sheath made solid bar stock shall be used.

01

01

Material
platinum -10% rodium
platinum
chromel - alumel

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GS-S-01
XXXXAS90S80001
Printed

ITALY

Revision

00
Sheet

14

of

28

Radiation pyrometers shall be used when:


.
.
.
.

2.4.2

Document n.

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

temperatures are above practical operating range of thermocouples


environmental will contaminate or seriously limit the life of thermocouples
the target is not easily accessible and
an average temperature of a large area is required.

Temperature transmitters
Temperature transmitters shall be used when receiver instrument or control loop
require signal conversion.
Temperature transmitters shall have either fluid, resistance, or thermocouple
type measuring systems.
Transmitters shall meet the following minimum requirements:

2.4.3

Accuracy

+ 0.5 % of span or better

Ambient temperature effect

Less than 0.5 % of span per 10C change

Adjustment

zero and span

Temperature indicators

2.4.4

Temperature gauges shall generally be 100 mm diameter calibrated dial, bimetallic or gas filled type with thermowell suitable for application

The gauges shall be provided with stainless steel case

Material of construction for thermowell shall be a suitable stainless steel,


unless some other material is required due to process conditions.

The measuring element and other internal parts shall be suitable for ambient
temperature and for the environmental conditions of the plant.

Scales shall be white with black lettering. Accuracy shall be Class 2 or better.

The gauges shall be provided with an over range protection of 25 percent of


span.

Gas filled type indicators shall be either rigid stem or capillary tubing type.

Capillary tubing shall be properly protected.

Stem or bulb shall be of a suitable stainless steel with welded joints.

Temperature switches

01

Temperature type switches shall be of either gas-filled or gauge pointer


detector or bimetallic detector type.

Capillary tubing shall be properly protected.

Material of construction for thermowell shall be a suitable stainless steel,


unless some other material is required due to process conditions.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.5

Document n.

Revision

00
Sheet

15

of

28

Analyser instruments
-

Instruments measuring pH, conductivity, concentration or other properties of


process streams shall consist of a suitably designed primary element to
convert or transduce the measured variable into an electrical signal which
shall be fed to a suitable indicator, recorder or controller.

Measuring pH electrode shall be of toughened all purpose glass electrode


giving accurate pH reading with long electrode life.

In application where variations in sample temperature may occur, automatic


temperature compensation device shall be provided.

The reference and glass electrode including the automatic temperature


compensator shall be housed in a compact sensor holder assembly provided
with terminal block, cable glands, silicagel desiccator and screened top cap to
prevent against spurious pick-ups.

Electrode assembly shall be provided with either flow type, in-line type or dip
type version depending upon application complete with all associated
accessories and fixing brackets.

The conductivity cell shall in general be of insertion type or flow type


depending upon the area of application.

Cell construction shall ensure that the cell constant remain precise and stable
even after a reasonable period of operation.

Conductivity transmitter shall have provision for automatic temperature


compensation.

Analysers shall be capable of operating in the ambient conditions that


generally prevail in the specific plant.

Sufficient sample conditioning equipment shall be provided.

For calibration purpose, the analysers shall be provided with supply of


certified calibration, sample gas cylinders or buffer solutions and all
equipment necessary for field installation including valves, pipe fittings etc. A
calibration curve for each analysers shall be provided.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

2.7

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.6

Document n.

Revision

00
Sheet

16

of

28

Weighing system (electronic type)

01

The characteristics of load cells such as temperature compensation,


operating temperature, capacity, sensitivity, drift, linearity, accuracy, input
and output resistance, maximum overload and recommended insulation
resistance shall be conform to process requirements.

The mechanical design shall make provision for load cell protection against
overload, shock load and plant vibration. It shall also take into consideration
the prevention of excessive bear loads being transmitted to the load cell
without affecting the accuracy of the scale.

Dynamic weighing system accuracy shall be specified on the relevant


specification where used.

Weighing equipment shall be supplied with electronic unit for calibration


system. The calibration system shall have the function of checking the zero
point and at least another print in the scale range.

Encoders
Please refer to machine or automation specification.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.8

Document n.

Revision

00
Sheet

17

of

28

Control drives and valves

01

Control drives for fan dampers, control valves and miscellaneous modulating
dampers shall be either electrical or pneumatic or hydraulic type.

All control drives shall have a start torque rating of at least 150 percent of the
maximum required torque for the driven element.

Electric drives shall operate generally on 110 V or 230 V single-phase or 400


V, 3-phase, 50 Hz AC power supply system. Other voltages can be applied
according to particular plant standardisation.

Pneumatic drives shall be fed, via air pressure filter reducers, by compressed
air with instrument quality features, such as:

filtration degree

0.5 micron

oil content

1.0 ppm

dew point

+ 3C at 6 bar

Pneumatic cylinders shall be able to withstand a line pressure of 7 bar.

All drives shall have a minimum repeatability of + 0.5 percent of full travel.

Hysteresis effect shall not exceed + 1 percent of full scale travel.

Electric drives shall have end-limit switches and torque limit switches.
Regulating drives shall have position transmitter within feedback signal and
end-limit switches if required by control system. Manual operating handle and
air look-up system may be provided, where required.

Pneumatic drives may be provided complete with line filter, lubricator,


positioner, manual operating handle and air lock-up system and position
feedback, where required.

Stroking speed of electrical drive shall be compatible with requirements of


driven element.

Control valves for modulation services shall be pneumatically or electrically


operated. Hydraulic types shall be used, where specified.

Wafer types valves may be used for on/off and modulating services where
specified.

Butterfly valves may be used for modulating service and for shut-off service,
where specified.

Flange facing and drilling generally shall be according to DIN standard, other
standards can be applied according to plant standardisation.

In general types of end connection shall be used following piping


specification.

Materials shall be selected according to process fluid or specific operating


conditions

For flow control valve the KVs-value has to be selected so as to obtain for KV
min a valve opening approx. more than 15% of the total valve stroke and for

01

01

01

01

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Document n.

GS-S-01
XXXXAS90S80001
Printed

ITALY

Revision

00
Sheet

18

of

28

KV max. a valve opening approx. less than 85% of the total. If necessary two
separate control valves in split-range mode can be inserted.

01

Valves topworks shall be sized so that the valve will operate properly when
upstream pressure is 10 percent above maximum inlet pressure and
downstream pressure is atmospheric.

Extended bonnets and high temperature packing shall be used for high
temperature applications.

Valve, trim for most application shall be stainless steel for pressure drops of
up to 7 bar . For pressure drops above 7 bar hard trim shall be used. Other
alloys shall be substituted, if required, for corrosion conditions.

Minimum valve size shall be DN 25 for line size DN 25 and larger, using
reducers, if necessary.

Isolating valves and by-pass valves shall in general be provided for each
control valve application.

For on-off control in small pipe lines below DN 50, 2-way or 3-way solenoid
valves may be provided. Coil voltage shall be 24 V d.c. rating and shall be
suitable for continuous operation. Coil voltage 110V/115V rating may be
used, where specified.

Control valves used in safety shut-off service shall be single seated tight shutoff valve.

Noise level of the control valves shall be less than 85 dB (A) at one meter
distance and shall be specified, exceptions can be accepted for particular
service conditions.

Leakage class of the control valves/shut-off valves shall be selected as per


applicable standards and on the basis of the process requirements.

01

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.9

Document n.

Revision

00
Sheet

19

of

28

Single loop controllers


-

Single loop controllers shall be capable of programming the set point in the
following ways from:
.
.
.

Local key pad of the controller


Operator console
Computer

Single loop controllers shall have bumpless transfer feature in the event of
mode selection either from controller face plate, operator console or
computer.

Control schemes in controllers shall be configured using a friendly


conversational technique from controller. It shall include extensive selfdiagnostic software.

The tuning of the controller shall be carried out either from operator console
or locally from face plate. Tuning parameters shall form the part of the
configuration data and hence also saved in the tape drive of operator
console.

During the failure of controller its output value shall either be driven the flank
or to the selectable value as per process requirement.

The technical characteristics of the controller shall conform to the following:


.
Remote set-point input
1-5 V d.c.
.
Process input
4-20 mA d.c.
.
Controller output
4-20 mA d.c.
.
Transmitter power supply
110V/115 V a.c., 24 V d.c..
other power supply voltage can be used according to plant requirements

01

Control point accuracy

0.25%

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.10

Document n.

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Revision

00
Sheet

20

of

28

Instrument panel and desk


This specification outlines the basic requirements for local, separate control
panels and instrument panels, for PLC or centralised control system referred to
GSA01.

2.10.1

Structure
-

In general, instrument cabinets, control desks or control consoles shall be


totally enclosed and self standing.

Design and dimensions of panels and desks shall be based on human


engineering.

Dimensions and surface finishing of panels or desks shall be the same in


case that they are placed in a line.

Panels and desks shall be of welded construction throughout and all welds
shall be ground smooth, all corners shall be rounded and all weld spatters
shall be cleaned.

Panel painting shall be in accordance with the General Specification for


Painting.

Where necessary panels/desks shall be mounted with suitable antivibration


pad.

Name plates shall be installed on the panels face to identify the instrument
and the function.

The instruments will be located on control boards according to the sequence


of the technological process, taking into consideration the argonomic
requirements

All instrument cut-outs and drilling shall be straight and true. If provisions are
to be made for further instrument installation, cut-outs shall be made and
blanks shall be provided. Blank shall be 1.5 mm thick with 12 mm overlap
around all edges. Blanks shall be painted with same colour as panel and
shall be installed after panel finish coat has properly hardened or dried. A
minimum of 4 anchors shall be used to attach blank to panel board.

Mounting angle, flush with bottom of panel, shall be provided. All panels shall
be supported on suitably sized vibration isolators, designed for bolting to
panel frame and flooring.

Protection degree
.
.
.

for control room and cabin installation


for indoor installation
for outdoor installation

IP 30
IP 54
IP 55

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

2.10.2

Document n.

Revision

00
Sheet

21

of

28

Electrical accessories and wiring


-

All electrical accessories, e.g. circuit-breakers, control switches, pushbuttons,


panel lighting fixtures, light switches, receptacles, horns or sirens etc.
required for the panel shall be provided.

Electrical accessories shall be of heavy duty type suitable of the environment


of the specific location. Devices mounted on control room panels shall be
flush mounted. Devices mounted in locations where dust laden atmosphere
is prevalent shall be surface mounted in dust-tight enclosure.

Copper wires will be used for panels, pulpits and cabinets assembling

All terminal blocks shall include at least 20 percent spare terminals.

Wires shall run in suitable plastic wiring sleeves/ducts between terminal ends.
The signal wiring shall be isolated from the power wiring as much as
possible.

All wires shall be plainly and durably labelled at both ends with a nonconducting material for easy identification. Terminal of connection shall be
indicated on the label.

Thermocouple cables from the field shall be connected directly to the terminal
strip of the relevant instruments unless otherwise specified. Intermediate
terminal strips shall be used for all other cables, including the
interconnections among auxiliary cubicles for the electric power supplies for
remote motor controls.

Electric lighting and maintenance socket shall be provided inside cabinets.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

3.0

INSTALLATION

3.1

Mounting of instruments

3.1.1

General

3.1.3

Revision

00
Sheet

22

of

28

Devices should be located at the most suitable position for operation and
maintenance.

Instruments requiring maintenance work shall not be installed in hot places,


narrow places or places which may impede proper servicing/maintenance at
site. Suitable space shall be provided around the instrument.

In general, equipment to be installed outdoors in dusty or corrosive


environments shall be provided with covers or boxes.

The transmitters should be located at an optimum distance from the sensing


elements/detectors so that there will be no problem for safe and reliable
operation of measurement and control.

If there remains no other alternative but to keep the transmitters in dusty and
high temperature zones, proper cooling apparatus and purging system shall
be installed.

2 inches nominal size pipes may be considered for mounting transmitters.

Safe and permanent access (walkways, platform and access ladders) to all
instruments such as pressure tapping points, thermocouples, control and
safety shut-off valves, actuators, sampling points etc. shall be provided so
that safe and effective preventive maintenance can be carried out.

01
01

GS-S-01
XXXXAS90S80001
Printed

ITALY

3.1.2

Document n.

Temperature sensors
-

When nozzle is inclined, nozzle length shall be sufficient for unbolting and
replacement work.

When a temperature sensor is installed near the pressure tap, it shall be


downstream the pressure tap.

Flow meters
-

The length of straight and other features and factors have to be considered
for flow orifices design run of process pipe, required for metering accuracy,
according to ISO 5167 standard, for other devices according to
manufacturers standard.

Straightening vanes may be used to lessen the straight run requirements.

Flow elements and transmitters shall be installed upstream of the control


valves, in general: however, in specific applications it may be different.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

Revision

00
Sheet

23

of

28

In general, tapping points for flow elements of differential pressure type


installed in horizontal piping are to be located as follows:
.
.
.
.

3.1.4

Document n.

For gas and air lines


For fuel oil
For water lines
For steam lines

0 to 45 from the vertical centre


0 to 30 below the horizontal centre line
0 to 45 from the horizontal centre line
0 to 90 from the vertical centre

A condensation pot shall be provided for the flow measurement of steam.

Mounting of the magnetic flowmeters shall be executed to ensure "filled-in


liquid" condition all the time.

Magnetic flowmeters shall be away from the electro-magnetic noise source.

Gas sampling system


-

Samples for gases containing a large quantity of dust should be prepared as


follows, according to the process requirements:
.
Manual and/or automatic blow-back system
.
Multiple sampling ports, if the ports are in danger of clogging. In this
case, stand-by ports shall be switched on automatically.

Filtering elements shall be easily dedustable and changeable.

When condensation in sampling piping is in danger, those pipes shall be


insulated and/or heat-traced.

When sampled gas is hazardous, it shall be returned to the main facilities or


discharged into the atmosphere after directing it to a place where nobody will
approach. "Keep out" signs shall be set up in the vicinity of the discharging
points.

Proper monitoring system of leakage of the hazardous gas in analyser room


shall be provided.

If samples and/or analysers are installed at difficult access locations,


platforms, housing tools, etc. shall be considered.

Cylinders for calibration gauges and carrier gases shall not be exposed to the
direct sunlight or heat radiation.
They shall be also installed at easily accessible locations for replacement.

3.2

Instrument process connection


The following items indicate DC major used process connection. Particular cases
shall be taken in consideration following process and instrument requirements.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Revision

00
Sheet

24

of

28

Flow connections
01

3.2.2

Orifice flanges for use at normal pressure generally shall be tapped 1/2 G
(15 mm) or NPT tapping according to plant standard.

Orifice connections for Vena-Contracta taps or pipe taps at normal


temperature shall be 1/2 G (15 mm) connection or NPT tapping
according to plant standard.

Pressure and sample connections


01

3.2.3

Pressure and sample connections on process lines for most applications


operating at normal temperature and pressure shall be 1/2 G (15 mm) or
NPT tapping according to plant standard.

Pressure connections for vessels shall be 1/2 G (15 mm) or NPT tapping
according to plant standard.

Temperature connections
01

3.2.4

GS-S-01
XXXXAS90S80001
Printed

ITALY

3.2.1

Document n.

Temperature connections on process lines for most applications operating at


normal temperature and pressure shall be 1/2 G min. (15 mm) or NPT
tapping according to plant standard.

Operating at normal pressure and temperature shall be 1/2G min. (15 mm)
or NPT tapping according to plant standard.

Operating at temperature above 100C shall be flanged DN 50

Level connections
-

Connections for use with external float chamber, ball float or displacer type at
normal pressure shall be DN 25.

Connections for use with top or side flange mounted displacer type or
transmitters at normal pressure shall DN100.

Connections for gauge glass shall be DN20.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Document n.

GS-S-01
XXXXAS90S80001
Printed

ITALY

3.3

Instrument piping

3.3.1

General

Revision

00
Sheet

25

of

28

The term instrument piping shall apply to all valves fittings, tubing and piping
used to connect instruments to main piping or to other instruments and
apparatus.
The term control piping shall apply to all valves, fittings, tubing and piping used
to interconnect air operated control apparatus, as well as to connect instrument
transmitters and receivers.
The term sampling piping shall apply to all valves, fittings, tubing and piping
used for the collection of samples of steam, liquid and gas.
Wherever required impulse piping and sample piping shall be insulated and/or
heated with steam or an electrical heater.
PTFE tape may be used as a thread sealant for screwed fittings up to 200C.
Piping and tubing shall be adequately supported and fixed.
Galvanised cable trays shall be used for continuously supporting PVC tubes and
copper tubes.
The tray shall be provided with additional supports to prevent sagging and
securely fixed to the structural steel work or masonry as per normal practice.
Capillaries of filled systems shall be laid independently of all other lines and shall
be supported continuously by using mild steel angle with clips.
3.3.2

Instrument piping
Process piping specification shall be used in selecting the material employed for
valves, fittings and piping for lines directly connecting instruments to process
variables unless otherwise specified.
Tubing requirements shall be as follows:
- Tubing from process isolation valve to instrument for pressure up to 50 bar
shall be 12 mm outside diameter of suitable steel material according to
process requirements.
- Fittings shall be compression type of suitable steel material.
- In the measurement of the pressure or flowrate of a liquid, transmitters shall
be placed below the measuring taps, with a continuous fall in the connection
tubes. If transmitters are to be placed above the measuring taps, air bleeders
shall be put at the highest point in the connection tubes.
- In the measurement of the pressure or flowrate of wet gas or steam,
transmitters shall also be placed above the measuring taps. If they are placed
lower, condenser vessels shall be mounted directly to the sockets and on the
same level.
- All impulse piping to the transmitters shall in general be given with slope of
not less than 1 : 15 except otherwise stated.

3.3.3.

Control piping

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

Document n.

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

GS-S-01
XXXXAS90S80001
Printed

ITALY

Revision

00
Sheet

26

of

28

Control and signal transmission lines shall be min. 8 mm outside diameter, PVC
or copper tubing.
Compression type of fittings shall be used.
Multi-tube bundles shall be used whenever practical to run from field to Control
room. Tubing shall be of high density polythene material of 6 mm outside
diameter. Multi-tube bundles shall be jacketed with two layers of PVC and in
between galvanised steel armouring.
3.3.4

Sampling piping
The materials used for sampling lines shall conform to the piping specification for
the main line or process variable to which they connect.
Process piping specification shall be used in selecting valves and fittings.

3.4

Cabling
For cabling and connection refer to GS-E-04.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

00
Sheet

27

of

28

DRAWING AND DOCUMENTS


The following types of drawing/documents shall
drawing/documents are common to other disciplines):

4.1

Revision

GS-S-01
XXXXAS90S80001
Printed

ITALY

4.0

Document n.

be

provided

(same

Process flow diagram (PFD)


The process flow diagram (PFD) illustrates all essential elements of entire
process conditions. The process flow diagram generally shows the following:
-

All major equipment

Equipment identification number and names

Control valves

Valves required to demonstrate routing for all modes

Pipe sizes if required

Interconnections to other systems with related references

Process data like flowrates, pressure and temperature

Flow direction by arrows


For same cases process flow diagram can be substitute or implemented by a
lay-out of the process plant.

4.2

Piping and instrumentation diagram (P&ID) (where applicable)


The piping and instrumentation diagram (P&ID) provides a schematic
representation of the piping, process control, instrumentation which shows the
functional relationship among the system components.
In particular it is shown:
-

mechanical equipment

rating of capacity of main equipment

all valves associated with the process piping, including identification

instrument designation including:


.
control and alarming functions
.
interlocks (marked with the proper symbol I) explained with a short
written notice
all size transition in line (reducers, increasers etc.)

direction of flow

interfaces for class change

main interconnection references

manual switches (where it is necessary to understand the control functions)

MMI indication where necessary

Identification of components and sub-systems by others with reference to


package drawing for details not shown on P&ID.

For simple plants P&I and PFD diagram can be incorporated in one drawing.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

DANIELI
GROUP
Buttrio (UD)

GS-S-01
XXXXAS90S80001
Printed

ITALY

4.3

Document n.

GENERAL SPECIFICATION
(GS)
INSTRUMENTATION (S)

Revision

00
Sheet

28

of

28

Instrument list and data sheet


The document contains the list of the instruments related to the plant section and
the collection of the instruments data sheets (instrument specification). The
document contains the following information:

4.4

instrument tag number

device description

service involved

name of the manufacturer

model number and type

instrument data sheet number

instrument data and settings for filed instruments

Hook UPs
The document represents the collection of the assembly sketches and erection
diagram for instruments including the relevant material necessary

4.5

Catalogue for instruments


It includes the copies of the collection of the catalogues of instruments used on
the plant with relevant catalogue list for identification.

4.6

Instrument panel drawing


Instrument panel drawings showing front panel instrument layout and panel
internal wiring and piping details.

4.7

Lay-out drawings
Lay-out drawings show location of various instruments (Documents are common
to piping and electrical disciplines)

4.8

Cabling and connections


For cabling and connection refer to GS-E-04.

4.9

Instruction and maintenance manuals


It includes the copies of the collection of instruction and maintenance manuals
for instruments used with relevant list for identification.

File: GSS01_00/882
THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF DANIELI & C. SPA NOT DISCLOSABLE, NOT REPRODUCIBLE. ALL RIGHTS RESERVED.

You might also like