Automatic Changeover
with Current Limiter (ACCL)
The intelligent start-up solution

Features
Microcontroller based DIN rail mountable automatic source changeover
with neutral isolation
Inbuilt SMPS for low power consumption
Operational status indication through LEDs
Manual reset provision for restoring supply, when in sleep mode
Automatic generator on/off facility (on special demand)
Staggered terminal design with bottom wiring for better isolation between
phase & neutral

Automatic Changeover with Current Limiter (ACCL)


An indispensable tool to automate power distribution, protect
expensive gensets and prevent fatal risks - The power instability in
developing countries along with the inefficient rationalized power
distribution creates a need for the alternative source of power,
to back up the utility supply, and hence, most of the commercial
and residential complexes set-up alternate power sources, such
as gensets, to provide efficient back-up for their power needs.
However, most of these users of alternate power still depend on
manual change-over, which leads to issues such as increased
downtime, disruption in key activities as well as critical damage
to the expensive equipment and could also prove fatal to the
operators.
HAVELLS INDIA LTD Nations leading player in power distribution
equipment and solutions, now offers HAVELLS ACCL, a
fully automatic high precision microcontroller based Source
Changeover device, which also has current limiting function and
offers easy and controllable changeover between main power
supply and generator supply.
With these inherent strengths, HAVELLS ACCL is being increasingly
adopted by leading power consumers, both at commercial as well
as residential levels, as a strong and proven power distribution
management tool.
So go ahead, and empower your premises and power distribution
with HAVELLS ACCL today!

Functions
- When the Mains Supply is available:
a. The ACCL allows unrestricted supply from Mains in case
current is in allowable limits.
b. If the current exceed the mains rating, the load is disconnected
after a delay of 5 seconds and it will remain disconnected for
8 seconds as a warning and then automatically reconnects it.
During this period, the consumer is expected to switch off the
non-essential loads and bring it within the limit.
c. In an unlikely event, if the consumer does not switch off the non
essential loads to reduce it to within the limit, supply to the load
from the mains is automatically disconnected after 5 cycles of
interruption.
d. The supply from mains to the load can be restored after
pressing the reset button present in the front of ACCL.
- When the Mains supply fails
Without AGS (automatic generator start features) - When the
mains supply goes OFF, a consumer is automatically connected
to the generator in case generator supply is available after a
time delay of 8 to 12 seconds in order to limit the sudden load
on the generator.
With AGS (automatic generator start features) - ACCL
Provides signaling through a potential free contact for starting
the Generator (Generator must have control unit for auto

Start/off) and then consumer is automatically connected to the


generator after a time delay of 8 to 12 seconds in order to limit
the sudden load on the generator.
Once the supply goes to generator side then:
a. ACCL limits the user from drawing excess load current beyond
the pre- set limit.
b. If the current exceeds the allowable limit, the ACCL will indicate
the overload condition by glowing its overload LED. Due to
this the load is disconnected after a delay of 5 seconds and
will remain disconnected for 8 seconds as a warning and then
automatically reconnects. During this period, the consumer is
expected to switch off the non-essential loads and reduce it
within the limit.
c. In an unlikely event, if the Consumer does not switch off the
non essential loads to reduce it to within the limit, supply to
the load from the mains is automatically disconnected after 5
cycles of interruptions.
d. The supply from Gen to the load can be restored only after
pressing the Reset button present in the front of ACCL.

Technical Specifications
Standard Conformity

IEC 60947-6-1

No. of Poles

1P+N

Rated current (In)

30A on mains, 1.5-20A on generator

Rated voltage (Ue)

240 Vac

Rated frequency

50 Hz

Rated insulation voltage

500V

Transfer time

8 to 12 sec

Restoring Time

2 to 4 sec

Utilization Category

AC 31B

Class of Equipment

PC

Environment

Indication

Mains, Generator, Load, Overload

Ambient Temp.

-5 to +55C

Electrical Life

6000 operations

Rated Impulse Voltage

1.5kV

Duty

Uninterrupted

2
Pollution Degree
Conditional Short Circuit
3kA
Current
IP20
Protection Class
Mounting

standard mounting RAIL (35x7.5 mm)

Mounting Position

Vertical /Horizontal

Terminal Capacity mm

10

Weight

350 gms.

ACCL

Feature Benefits of Havells ACCL


Features

Advantage of Havells ACCL

Other Competitor Products

Requires less installation space, it can be fitted


in any DBs as dimension is same as 4 Pole MCB
(87.5 x 71.8 x 63)

108 x 72 x 68

Terminals for External Conductors

Prevent connection error


(Indirect pressure type )

Direct pressure type

Conditional Short Circuit Current

3 kA

Not mentioned

Compact Design

Thermoplastic, PA6 FR Grade

Thermoplastic

Local Reset Facility

Reset button provided, so no


extra switch required for restoring supply

Extra switching device required


for restoring supply

Overload Indication

Customer knows immediately in case of overload

Not provided

As per IEC 60947-6-1

No marking on product

Eco Friendly Housings

Standard Conformity

1.5kV

Not mentioned

80-300 Vac

180-240 Vac

Longer life product (>6000 ops.)

Not mentioned

Provided

Not provided

Longer contact life (AC 31B / IEC 60947-6-1)

Not mentioned

Low temperature rise

No vents

Rated Impulse Voltage


Operational Voltage
Electrical Life
Pre-Trip Indication Under
Overload Condition
Utilization Category
Vents Provided for Cool Running

ACCL Wiring Arrangement during Installation


ACCL

Main supply
N

SCPD 1

Terminals available in ACCL for


GEN. ON/OFF feature
Input from mains supply
Input from GEN supply
L

SCPD 2

Auto GEN start control unit

Ignition signal to remote GEN start terminals


GEN with auto start control unit

* SCPD can be 32A HRC FUSE or 32A MCB

MCB /
RCCB

N
Output

Load

45

36

87.5

Dimensions (in mm)

71.8

63

Front view

Side view

Price List
Mains Rating

Gen Rating

Product Code

Description

SPN 30 (6000 W)

SPN 1.5 (300W)

DHACOSN301X

30A/1.5A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 2.5 (500W)

DHACOSN302X

30A/2.5A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 3 (600W)

DHACOSN3003

30A/03A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 4 (800W)

DHACOSN3004

30A/4A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 5 (1000W)

DHACOSN3005

30A/5A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 6 (1200W)

DHACOSN3006

30A/06A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 9 (1800W)

DHACOSN3009

30A/09A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 12 (2400W)

DHACOSN3012

30A/12A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 15 (3000W)

DHACOSN3015

30A/15A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 20 (4000W)

DHACOSN3020

30A/20A ACCL W/O GEN START/STOP

SPN 30 (6000 W)

SPN 3 (600W)

DHACWSN3003

30A/03A ACCL WITH GEN START/STOP

SPN 30 (6000 W)

SPN 6 (1200W)

DHACWSN3006

30A/06A ACCL WITH GEN START/STOP

SPN 30 (6000 W)

SPN 9 (1800W)

DHACWSN3009

30A/09A ACCL WITH GEN START/STOP

SPN 30 (6000 W)

SPN 12 (2400W)

DHACWSN3012

30A/12A ACCL WITH GEN START/STOP

SPN 30 (6000 W)

SPN 15 (3000W)

DHACWSN3015

30A/15A ACCL WITH GEN START/STOP

SPN 30 (6000 W)

SPN 20 (4000W)

DHACWSN3020

30A/20A ACCL WITH GEN START/STOP

ACCL

Havells India Ltd.

Corp Office: QRG Towers, 2D, Sector-126, Expressway, Noida-201304 (U.P), Ph. +91-120-4771000,
Email: marketing@havells.com, www.havells.com Consumer Care No.: 1800 11 0303 (Tollfree),
011-4166 0303 (Landline), 1800 103 1313 (All Connections)
Join us on Facebook at www.facebook.com/havells and share your ways to save the planet!

SWI/ZHDLE00012/JUL11/APR12

ACCL with Generator ON/OFF

Introducing

Three Phase Automatic


Changeover with Current
Limiter (TPN ACCL)
The Intelligent start-up solution

Features
Microcontroller based automatic changeover with isolated neutral
Current limitation on generator side
Operational status indication through membrane keypad
Manual reset provision for restoring supply, when in sleep mode
Mode selection feature i.e automatic or manual
Automatic generator on/off facility (on special demand)

Three Phase Automatic Changeover with Current Limiter


(TPN ACCL)

The supply from mains to the load can be restored only after
pressing the Reset button present in the front of TPN ACCL.

The Power instability in developing countries along with the


inefficient rationalized power distribution creates a need for the
alternative source of power, to back up the utility supply. This further
necessitates the automation, in the distribution system as the rate
of power outage & low voltage output becomes predominantly high.
Most of the Residential & commercial processes are dependent
on power supply & if the process of changeover is manual, this
will not only create the hindrance in important activities but it may
also damage the device or machine from human error during the
changeover.

3. When Mains supply is restored


As soon as the main supply restores, the load is automatically
transferred to the mains supply after a delay of 2-4 sec.
With AGS, TPN ACCL itself generates the signal to automatically
stop the generator

Technical Specifications
Standard Conformity

IEC 60947-6-1

No. of Poles

Rated voltage (Ue)

3P+N
40A/63A/100A on mains,
10-100A on generator
415 / 220 Vac

Functions

Rated frequency

50 Hz

1. When the Mains Supply is available:


Automatic mode:
The TPN ACCL allows full load current on each phase when all
the 3 phases of mains supply is available, and when any one of
the phase fails, TPN ACCL will automatically senses and actuates
the inbuilt changeover mechanism to the generator supply.
Manual mode:
If R phase is available, it will countinue to run the load on main
supply irrespective of the availability of other phases. But if R
phase fails, the TPN ACCL will automatically senses and actuates
the inbuilt changeover mechanism to the generator supply.
Note: It is recomended to connect all essential load to R phase.
2. When the Mains supply fails
With AGS (automatic generator start feature):
TPN ACCL provides signaling through a potential free contact
for starting the Generator.

Transfer Time

8-12 sec

Restoring Time

2-4 sec

Rated Impulse Voltage


(Uimp)

6kV

Utilization Category

AC 31A

Class of Equipment

PC

Environment

Indication

Mains, Generator, Load, Overload


(R,Y,B), mode of operation
(auto/manual)

Pollution Degree

II

Conditional Short Circuit


Current

5kA

Without AGS (automatic generator start feature):


When the mains supply goes OFF, a consumer is automatically
connected to the generator in case generator supply is available,
after a time delay of 8-12 seconds in order to limit the sudden
load on the generator.
The TPN ACCL has a current limiting feature on the generator
side. If the load exceeds the allowable limit, TPN ACCL will give a
pre-trip indication and after a delay of 5 second, TPN ACCL will
trip and goes on hold. After a predetermined time delay (say 8
sec), it will again check the connected load and gives the supply
if the load is under the allowable limit. During this period, the
consumer is expected to switch off the non-essential loads and
reduce it within the limit. The overloaded phase will be indicated
through LED.
In an unlikely event, if the consumer does not switch off the nonessential loads to reduce it to within the limit, supply to the load
is automatically disconnected after 5 cycles of interruption.

Ambient Temp.

- 5 to + 55 C

Electrical Life

6000 operations

Mounting

Surface mounting

Mounting Position

Vertical

Terminal Capacity

16 mm2 / 35 mm2

Duty

Uninterrupted

Weight

4.5 Kg / 9.4 Kg
260 x 243 x 115 mm3
260 x 243 x 150 mm3
383 x 333 x 150 mm3

Havells TPN ACCL is a fully automatic high precision microcontroller


based device and is ideally suited for proper/efficient utilization of
standby generator used in multi-storied apartments, commercial
complexes, etc.

Rated current (In)

Dimensions

ACCL TPN/SPN Wiring Arrangement during Installation


In TPN/SPN, the ACCL will restrict the load if the cumulative current of all the 3 phases (ie R+Y+B) exceeds rated generator current.

Generator
Auto GEN start control unit

Main supply

R Y B N

L N

SCPD 1

SCPD 2

R Y B N R Y B N L N X1 X2

MAINS

LOAD

GEN IGN

MCB/RCCB

* SCPD can be - 40A MCB or fuse for 40A TPN ACCL



- 63A MCB or fuse for 63A TPN ACCL

- 100A MCB or fuse for 100A TPN ACCL

Load

ACCL TPN/TPN Wiring Arrangement during Installation


In TPN/TPN, the ACCL will restrict the load if the current in any of the phase (ie R or Y or B) exceeds rated generator current.

Generator
Auto GEN start control unit

Main supply

R Y B N

SCPD 1

R Y B N

R Y B N R Y B N R Y B N X1 X2

MAINS

LOAD

MCB/RCCB

* SCPD can be - 40A MCB or fuse for 40A TPN ACCL



- 63A MCB or fuse for 63A TPN ACCL

- 100A MCB or fuse for 100A TPN ACCL

Load

GEN

IGN

SCPD 2

ACCL

Feature Benefits of Havells TPN ACCL


Features
Mode Selection
Separate LED indication for individual
overloaded phase
Local reset facility

Advantage of Havells TPN ACCL

Other Competitor Products

can be operated in two different modes ie


automatic or manual as per customer requirement

not provided

customer immediately comes to know the


overloaded phase & can easily reduce the load
running on that phase

not available

reset button provided, so no extra switch required


for restoring supply

extra switching device required for restoring


supply

6kV

not mentioned

provided

not provided

as per IEC 60947-6-1

no marking on the product

5kA

not mentioned

150 - 415 Vac

150 - 360 Vac

available (on special demand)

not available

Rated impluse voltage


Pre-trip LED indication under overload
condition
Standard conformity
Conditional short circuit Current
Operating range
Automatic gen ON/OFF

Dimension (in mm)


B
C

Side

Rating

Front

40A TPN ACCL

115

243

205

224

260

63A TPN ACCL

150

243

205

224

260

100A TPN ACCL

150

333

293

337

383

TPN ACCL
TPN ACCL (TPN/SPN)

(Automatic Source Changeover with Current Limiter)


Description

Cat. No.

20A

Gen Rating

40A/20A TPN/SPN ACCL

DHACOTN4020

Cat. No. with GEN Start/Stop


DHACWTN4020

25A

40A/25A TPN/SPN ACCL

DHACOTN4025

DHACWTN4025

30A

40A/30A TPN/SPN ACCL

DHACOTN4030

DHACWTN4030

40A

40A/40A TPN/SPN ACCL

DHACOTN4040

DHACWTN4040

20A

63A/20A TPN/SPN ACCL

DHACOTN6320

DHACWTN6320

25A

63A/25A TPN/SPN ACCL

DHACOTN6325

DHACWTN6325

30A

63A/30A TPN/SPN ACCL

DHACOTN6330

DHACWTN6330

40A

63A/40A TPN/SPN ACCL

DHACOTN6340

DHACWTN6340

TPN ACCL (TPN/TPN)

(Automatic Source Changeover with Current Limiter)


Gen Rating

Cat. No.

Cat. No. with GEN Start/Stop

40A/20A TPN/TPN ACCL

DHACOTT4020

DHACWTT4020

25A

40A/25A TPN/TPN ACCL

DHACOTT4025

DHACWTT4025

30A

40A/30A TPN/TPN ACCL

DHACOTT4030

DHACWTT4030

40A

40A/40A TPN/TPN ACCL

DHACOTT4040

DHACWTT4040

20A

63A/20A TPN/TPN ACCL

DHACOTT6320

DHACWTT6320

25A

63A/25A TPN/TPN ACCL

DHACOTT6325

DHACWTT6325

30A

63A/30A TPN/TPN ACCL

DHACOTT6330

DHACWTT6330

40A

63A/40A TPN/TPN ACCL

DHACOTT6340

DHACWTT6340

SWI/ZHDLE00015/SEP11/APR12

Description

20A

Havells India Ltd.

Corp Office: QRG Towers, 2D, Sector-126, Expressway, Noida-201304 (U.P), Ph. +91-120-4771000,
Email: marketing@havells.com, www.havells.com Consumer Care No.: 1800 11 0303 (Tollfree),
011-4166 0303 (Landline), 1800 103 1313 (All Connections)
Join us on Facebook at www.facebook.com/havells and share your ways to save the planet!

You might also like