Professional Documents
Culture Documents
Research Article
Integrating STATCOM and Battery Energy Storage System for
Power System Transient Stability: A Review and Application
Arindam Chakraborty,1 Shravana K. Musunuri,2
Anurag K. Srivastava,3 and Anil K. Kondabathini4
1 Philips
1. Introduction
The principal benefit of the STATCOM for transient stability
enhancement is direct through rapid bus voltage control. In
particular, the STATCOM may be used to enhance power
transfer during low-voltage conditions, which typically predominate during faults, decreasing the acceleration of local
generators. An additional benefit is the reduction of the
demagnetizing eects of faults on local generation. STATCOMs behave analogously to synchronous compensators,
except that STATCOMs have no mechanical inertia and
are therefore capable of responding much more rapidly
to changing system conditions. When compared to synchronous machines, they do not contribute to short circuit
currents and have no moving parts. However, the system has
a symmetric lead-lag capability and can theoretically go from
full lag to full lead in fraction of cycles [1, 2].
2
(decreasing) the power transfer capability when the machine
angle increases (decreases). In Figure 1, which shows the
single line diagram of a STATCOM, if the DC capacitor
voltage, Vdc , is increased from its nominal value, the
STATCOM is overexcited (capacitive mode) and generates
reactive power. If the voltage of the DC capacitor bank is
decreased below the nominal value, the STATCOM is under
excited (inductive mode) and absorbs reactive power from
the system. This is completely analogous to increasing or
decreasing the field voltage of a synchronous compensator
[2].
In this paper, review and application of using STATCOM
in network with BESS are presented. Next section provides
review in greater details and Sections 35 provide application
demonstration of STATCOM + BESS. For test cases, a
power transmission system with a single machine generator
connected to an infinite bus is considered. For simplification
purpose the classical model of a generator is assumed
with an infinite bus as a constant voltage source. The
model is implemented in MATLAB/Simulink and computer
simulation results under dierent fault (3-phase to ground
fault) clearing times are analyzed for transient stability.
The results are then compared with STATCOM placed in
the system. The analysis is then extended by adding an
energy storage device (battery) to the STATCOM. The final
results show that the addition of energy storage allows the
STATCOM to inject and/or absorb active and reactive power
simultaneously and, therefore, provides additional benefits
and improvements in the system.
The paper is organized as follows. Section 2 gives a
comprehensive review and brief introduction of STATCOM
and battery, applications as well as financial aspects. Sections
3, 4, and 5 provide modeling and a practical case study
of STATCOM being used in interface with BESS and the
corresponding results based on the transient analysis of such
system are discussed. Finally, in Section 6 conclusions are
drawn.
V -bus
Coupling
transformer
V -VSC
Voltage
sourced
converter
+
DC source
V -DC
Energy
storage
system
(ESS)
Power
electronic
interface
Power
regulation
network
Voltage
source
inverter (VSI)
DC bus
Utility grid
Isolation tr.
STATCOM +
BESS
RT1
LT1
RTL1
LTL1
RT2
LT2
RTL2
LTL2
RT3
LT3
RTL3
LTL3
PS1
Utility
PS2 power
system
PS3
Transformer
parameters
Transmission
line parameters
Feeder lines
Sensors
and
regulation
power
unit
+
VS
P S1
P S2
P S3
Cb
Feedback
V, I
VS
Cb
Synchronizing port 2
Figure 4: Structure of a BESS connected FACTS in a complete control interface for maintaining stability.
5
does not compromise the voltage quality of the system. In
terms of dynamic performance for damping oscillations, it
is observed in practical cases that if ESS is connected to the
AC system, it would provide better performance for a seriesconnected voltage source inverter (static synchronous series
compensator) compared to a shunt-connected voltage source
inverter. However, this is not a pragmatic solution due to the
additional cost involved.
The pulsating torque at blade-passing frequency varies
the slip of the wind power generator about the normal
operating point. Terminal voltage of the wind turbine varies
significantly with its slip. There is also a variation in the
terminal voltage with active power output of the wind
turbine. The large variation is due to the power flow, causing
a change in voltage drop in the distribution circuit. The
voltage drop can be separated into a horizontal and a
vertical component of the voltage drop across the grid
impedance. These voltages are the components in phase and
in quadrature with the network voltage, respectively.
In summary, STATCOM + BESS unit can be applied
to load leveling, saving energy at peak demand, minimizing subsynchronous oscillations, enhancing transient and
dynamic stability. Another advantage of using STATCOM
+ BESS is that the DC link capacitor value can be reduced
enormously. For certain applications, only a small capacitor
would be sucient to smooth the battery DC current which
is an eminent feature of integrating battery energy storage
system (BESS) with STATCOM.
2.4. Economic Aspect of the ESS System Connected to STATCOM. The cost of such an integrated system can be broken
down into three major segments, namely, the energy storage
system, the supporting systems such as refrigeration for
SMES, and the power conversion system. The amount of
energy to be stored primarily determines the cost of the
energy storage system. For the high-power low-energy storage applications, the configuration and the size of the power
conversion system may become a dominant component.
In order to establish a realistic cost estimate, the following
steps must be considered.
(i) Identification of the system issue(s) to be addressed.
(ii) Study of preliminary system characteristics.
(iii) Define basic energy storage, power, voltage, and
current requirements.
(iv) Define utility financial benefits from the integration
of the systems to determine adequacy of utilitys
return on investment.
(v) Model system performance in response to system
demands to establish eectiveness of the BESS.
(vi) Optimize integrated system specifications and determine system cost.
(vii) Study and compare various energy storage systems
performance and costs.
In terms of per unit active or reactive power, the cost of
energy storage in feasible range is possible to be achieved by
Synchronizing
signal
PLL
t++
t++
q +
Instantaneous
power theory
Switching
logic
Driving signal
for the switches
Lead/lag
voltage controller
PI
controller
Feedback
currents, I
Re
+
Eeq
Vt
3. System Modeling
3.1. STATCOM Modeling. A STATCOM regulates voltage
on a three-bus system. It is modeled as 48-pulse power
converter which uses a voltage-sourced converter (VSC) built
of four 12-pulse three-level GTO inverters. During steadystate operation the STATCOM control system keeps the
fundamental component of the VSC voltage in phase with
the system voltage. If the voltage generated by the VSC is
higher (or lower) than the system voltage, the STATCOM
generates (or absorbs) reactive power. The amount of
reactive power depends on the VSC voltage magnitude and
on the transformer leakage reactance.
The fundamental component of VSC voltage is controlled by varying the DC bus voltage. In order to vary
the DC voltage, and therefore the reactive power, the VSC
voltage angle (alpha) which is normally kept close to zero
is temporarily phase shifted. This VSC voltage lag or lead
produces a temporary flow of active power which results in
an increase or decrease of capacitor voltages. The control
used for this model of STATCOM is a very simple one. It uses
measurements of voltages and currents at the point where the
STATCOM is connected to the AC system bus.
(1)
(2)
Eeq = E0 +
SOC
RT
.
ln
nF
1 SOC
(3)
(4)
4. Test Case
The test case system is considered as two-area system, area1 and area-2 as shown in Figure 7. The two areas are
connected by two parallel connected long transmission lines.
The direction of real power flow is from area-1 to area-2. The
STATCOM is placed on one of the transmission lines and
near to the generator being analyzed (area-1).
For a long transmission line, having a series impedance
of z ohm/km and shunt admittance of y mho/km, the
relationship between the sending end and the receiving end
VS
VM
VR
Receiving end
Area-2
Area-1
Section 1
Section 2
STATCOM
(5)
(6)
5. Simulation Analysis
5.1. Wind Energy Integration. Simulation analysis is performed in order to investigate the impact of STATCOM on
Gate
Vq
Vstab
Cm
B1
STATCOM
500 kV, 5000 MVA
100 MVA
Vf
200 MVA
13.8 kV
Y9 c
C
Transmission line 1
B2
210 MVA
13.8 kV/500 kV
Vf
5000 MVA
500 kV
B3
Transmission line 2
A
B
C
Vref
Vd
Cp
m
Pm
HTG
Pulses VdcP
A
N
B
VdcM
C
Pulses
VdcPN
Pm
Pref
we
dw
Iabc
STATCOM
controller
wref
Peo
Vabc
Iabc B1
A
B
C
1
0.7516
Vabc B1
A
B
C
3-phase fault
5 MW
Excitation
system
10 MW
P bus (pu)
10
5
O STATCOM
1
0
1
O bus
Figure 8: MATLAB/SIMULINK simulation model for test case system with STATCOM.
15
10
5
0
10
12
14
16
18
20
14
16
18
20
14
16
18
20
12
14
16
18
20
12
14
16
18
20
10
12
V STATCOM
1
0
1
V bus
1.5
1
0.5
0
10
12
STATCOM voltage
10
Bus voltage
10
Time (seconds)
Figure 9: Wind Farm simulation without STATCOM connected to power transmission system.
remain stable after the fault is cleared. For the fault clearing
time 0.235 sec, which is greater than the critical clearing time
0.2315 sec, the rotor angle of the generator becomes unstable
after the fault is cleared. Since this case does not have any
compensator attached to the AC system, STATCOM real and
reactive powers are zero.
Case II (system with STATCOM). Now, the 500 KV,
100 MVAR STATCOM is connected to bus-B2. When only
the STATCOM is connected, the response of the system is
given in Figures 13 and 14.
Figure 13 shows the plots for the fault clearing of 0.23 sec
with and without STATCOM. It is observed that the system
10
5
0
10
12
14
16
18
20
14
16
18
20
14
16
18
20
12
14
16
18
20
12
14
16
18
20
O STATCOM
O bus (pu)
10
V STATCOM
1
0.8
0.6
V bus (pu)
P bus (pu)
2
0
10
12
5
0
10
12
10
Bus voltage
1
0
10
Time (seconds)
Figure 10: Wind Farm simulation with STATCOM connected to power transmission system.
Z-grid-1
S1
CB1
CB11
Filter
network
S2
S3
CB22
CB2
Wind power
generator
Z-grid-2
Z1
BESS
STATCOM
Z2
10
100
50
Rotor angle (degrees)
50
0
50
100
26.5
50
100
150
150
200
200
27
27.5
28
28.5
29
29.5
26.5
30
27
27.5
Time (s)
Tcr = 0.235
Tcr = 0.23
28
28.5
Time (s)
29
29.5
30
W/o fault
Figure 12: Rotor angle response for dierent values of faultclearing time (fault applied at t = 27 sec).
100
150
50
Rotor angle (degrees)
100
0
50
100
26.5
0
50
100
150
200
50
150
200
27
27.5
28
28.5
Time (s)
29
29.5
30
26.5
27
27.5
28
28.5
Time (s)
29
29.5
30
6. Conclusions
This paper is majorly divided into two sections. In the first
section, thorough reviews of the benefits of using STATCOM
in conjunction with battery energy storage systems are
discussed. The importance and technical significance of BESS
with STATCOM is elaborated here. Advantages of using
BESS in connection to STATCOM in the power system for
11
2
0
2
4
26.5
27
27.5
28
28.5
29
29.5
30
29
29.5
30
Time (s)
2
0
2
4
26.5
27
27.5
28
28.5
Time (s)
4
2
0
2
26.5
27
27.5
28
28.5
29
29.5
30
29
29.5
30
Time (s)
3
2
1
0
1
2
26.5
27
27.5
28
28.5
Time (s)
power flow path for battery, but the operation of the battery
is independent of the STATCOM controller. While the
STATCOM is controlled to absorb or inject reactive power,
the battery is controlled to absorb or inject real power.
References
[1] IEEE power engineering society. FACTS application task force,
FACTS applications, IEEE Publication 96-TP116-0.
[2] N. G. Hingorani and L. Gyugyi, Understanding FACTS:
Concepts and Technology of Flexible AC Transmission Systems,
IEEE press, New York, NY, USA, 2000.
[3] J. J. Paserba, How FACTS controllers benefit AC transmission
systems, in Proceedings of the IEEE Power Engineering Society
General Meeting, pp. 12571262, June 2004.
12
[21]
[22]
[23]
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[34]
[35]
International Journal of
Rotating
Machinery
Engineering
Journal of
Volume 2014
The Scientific
World Journal
Hindawi Publishing Corporation
http://www.hindawi.com
Volume 2014
International Journal of
Distributed
Sensor Networks
Journal of
Sensors
Hindawi Publishing Corporation
http://www.hindawi.com
Volume 2014
Volume 2014
Volume 2014
Journal of
Control Science
and Engineering
Advances in
Civil Engineering
Hindawi Publishing Corporation
http://www.hindawi.com
Volume 2014
Volume 2014
Journal of
Robotics
Hindawi Publishing Corporation
http://www.hindawi.com
Volume 2014
Volume 2014
VLSI Design
Advances in
OptoElectronics
International Journal of
Navigation and
Observation
Hindawi Publishing Corporation
http://www.hindawi.com
Volume 2014
Chemical Engineering
Hindawi Publishing Corporation
http://www.hindawi.com
Volume 2014
Volume 2014
Antennas and
Propagation
Hindawi Publishing Corporation
http://www.hindawi.com
Aerospace
Engineering
Volume 2014
Volume 2010
Volume 2014
International Journal of
International Journal of
International Journal of
Modelling &
Simulation
in Engineering
Volume 2014
Volume 2014
Volume 2014
Advances in
Volume 2014