Adjusting the measuring range on Micaflex


P, PD och FD fr.o.m ver 3.x

P/PD/FD
Mi-274gb / 2008-10-20

FM1

R18
R13
R16

LEDT2D102

SW1

C8

DEC

LED1
ZERO

R44

J2

K3
VDR1

C21

DIL1

R43

DIL1 *
1 RANGE
2 TEST
3 OUTPUT
4 DAMPING
5 DAMPING
* see cover

G G0G0OutOut
(+)(-) (-) V mA
FM2

AB Micatrone
P3778 v3.01
Top Silk

PL2

Connect the necessary instruments for adjustment


acc. to figure below for best results.
Remove the front cover on the transmitter to access
the adjustment keys on the printed circuit board
(PCB) inside the unit.

PL1

AB MICATRONE 2008-10-20 [H:\ Apps \ Typeset \ Mima \ mi-274gb_081020.vp]

R20
D101

R101

C18

R15
R12

ESC
R19
R22
LED102R17
T1
D2
C5

SW2

D104

IC4

INC

R48

C7

C17

C10

R21

D103

C11
R27 R28

R11 C9

R23

PGM

LED101
IC5

SW3

SNAP1

D3
Miniature
switch
D4

C6

IC1

R47

C3

R8
R10
C23

C13

C15
FM3 R24 T3

AC1

DIG4

R14 D1

R45

K4

C4 R9 R7
AB Micatrone
C101 P3761
R112
C24 Top Silk

R5
DIG3
C1 C2

AC7D

R1

K1

H2

8888
AC7A

LED103

DIG2 AC3

TG1

C14
C16

R46

D105R26SW4

IC6

R41

R111

J101
R25

C12 R29

R38

LED105

RGND

LED104
R2

RP102

J1

DIG1

C102

R6

K101
R39

C19
IC101
D5

IC3 R4

AC8

R42

R31

FM2

R110

K2

Depending on the set measuring application, the


adjustment is carried out in different ways using
transmitters with a measuring range that begin at
zero (0) Pa, eg. 0...500 Pa, or transmitters that uses
zero-crossing ranges, eg. -50...+50 Pa.

R109

FM1
R40

AC2

IC2

Adjustment keys
5 6.
R30

R34

IC7
R102

H1

IC8

R32
R37

C22 C20

AC9 IC9 R33

RP101

Note! This adjustment should not be used for


changing the measuring range of the unit.

D7

D6

R35

R36

General
The measuring range can be adjusted to correct a
measuring deviation on Micaflex PD/FD ver 3.x if
the transmitter no longer remain within specifications.

Zero-set key

FM3

Turn off any set damping during adjustment.

Reference transmitter

Micaflex ver 3.x

8888

Micaflex
P/PD/FD

Pressure pump

8888

PVM

V/mA-instrument

ZERO

Adjusting a transmitter with a measuring range


passing 0 Pa, i.e. zero-crossing.
1 Remove the pressure tubes on the transmitter and

connect a V/mA-instrument to the selected output.


If the miniature switch no 3 is in position "OFF", the
voltage output should be connected. If the miniature
switch is in position "ON" the mA-output should be
connected.

connect a V/mA-instrument to the selected output.


If the miniature switch no 3 is in position "OFF", the
voltage output should be connected. If the miniature
switch is in position "ON" the mA-output should be
connected

Take a note of how the damping is set (miniature


switch no 4 and 5) and then place both switches in
position "OFF".

Take a note of how the damping is set (miniature


switch no 4 and 5) and then place both switches in
position "OFF".

Press and keep down the zero-setting key until the


LED goes off. Release the key and the zero-adjustment is done.

Connect a pressure pump together with a reference


transmitter to the negative [-] connection.

Connect a pressure pump together with a reference


transmitter to the positive [+] connection.

Place the miniature switch no 2 in position "ON" to


activate the adjustment keys.

Place the miniature switch no 2 in position "ON" to


activate the adjustment keys.

Increase the pressure to the transmitters max.


range and adjust the output signal using the adjustment keys 6 and 5 until the signal is 10 Volt or 20
mA.
The factory settings can be restored if both adjustment keys 6 and 5 are pressed down simultaneous for approx. 1 second.

Increase the pressure to the transmitters min. pressure.


i.e.. -50 Pa if the measuring range of the transmitter
is -50...+50 Pa.
The pressure reference transmitter will indicate a
positive pressure of +50 Pa.
Press the 6-key to store the value.

Adjust the pressure to 50% of the measuring range.


With a measuring range of -50...+50 Pa or other
similar symmetric range, 50% will correspond to
zero (0) Pa, i.e. deflated transmitter.

Press down the zero-set key to store the value.

Connect the pressure pump together with the reference transmitter to the positive [+] connection. Increase the pressure to the transmitters max. pressure acc. to the example.

Press the 5-key to store the value.

After finished adjustment, place the miniature


switch no 2 in position "OFF" and reset the damping
to earlier.
A less precise adjustment can be performed if a
pressure pump is not available using only a reference transmitter to adjust against. This adjustment
can be performed over the entire measuring range
but it is recommended that the pressure used is
more than half the measuring range. The adjustment is done in the same way as described above
using the adjustment keys.

Note ! Any adjustments will result in a no longer


valid certification protocol.
D7

FM1

R110

K2

R18

C3

R13
R16

R15
R12

DEC

LEDT2D102

SW1

C8

LED1
ZERO

R44

J2

K3
VDR1

C21

FM2

AB Micatrone
ldermansvgen 3
SE-171 48 SOLNA
SWEDEN
2

G G0G0OutOut
(+)(-) (-) V mA

AB Micatrone
P3778 v3.01
Top Silk

PL2

DIL1 *
1 RANGE
2 TEST
3 OUTPUT
4 DAMPING
5 DAMPING
* see cover

R43

PL1

DIL1

Note ! Any adjustments will result in a no longer


valid certification protocol.

R20
D101

R101

C18

INC

R48

D104

IC4

R21

C7

C17

C10

ESC
R19
R22
LED102R17
T1
D2
C5

SW2

SNAP1

LED101
IC5

C11
R27 R28

IC1

R47

R11 C9

R23

PGM

D103

C16

C6

C13

C15
FM3 R24 T3

D3
Miniature
switch
D4

8888
SW3

C14

R45

D105R26SW4

R25

IC6

DIG4

R8
R10
C23

R14 D1

LED105

C12 R29

DIG3
C1 C2

TG1

R1

J101

DIG2 AC3

R5

11 After finished adjustment, place the miniature

K4

H2

C4 R9 R7
AB Micatrone
C101 P3761
R112
C24 Top Silk
AC1

R111

DIG1

R46
LED103

AC7D

R41

AC7A

RP102
RGND

R38

LED104
R2

R39

R42

C102

R6

K101

IC3 R4

AC8

J1

C19
IC101
D5

ment keys 6 and 5 are pressed down simultaneous for approx. 1 second
switch no 2 in position "OFF" and reset the damping
to earlier.

K1

FM2

RP101

R109

FM1
R40

AC2

IC2

R31
Adjustment
keys
5 6.
R30

R34

IC7
R102

H1

IC8

R37

R36

AC9 IC9 R33

R32

C22 C20

D6

R35

10 The factory settings can be restored if both adjust-

ZERO

Note ! Do not misstake the arrow keys,


65, on the display unit in Micaflex PD
and FD with the adjustments keys on
the main PCB which are referred to in
the instruction.

Zero-set key

FM3

Telephone:
Fax:
Internet:
E-mail:

+46 8-470 25 00
+46 8-470 25 99
www.micatrone.se
info@micatrone.se

web reference - http://www.micatrone.se/prod_detail.php?secID=2&lang=gb&id=60

AB MICATRONE 2008-10-20 [H:\ Apps \ Typeset \ Mima \ mi-274gb_081020.vp]

Adjusting a transmitter with measuring range


that begin on 0 Pa
1 Remove the pressure tubes on the transmitter and

You might also like