VERIS INDUSTRIES

INSTALLATION GUIDE

environmental Sensors

T Series

T Series

Temperature Transmitters
Installers Specifications
Input Power

Temp Output

Sensor Type
Accuracy
Ranges
Wiring (TOA and TDDA)

TDDA
TOA

4-20mA version - Loop powered 12-30VDC only, 30mA max;


0-5/0-10V versions - 12-30VDC/24VAC, 15mA max
2-wire, loop powered 4-20mA or 3-wire, 0-5V/0-10VDC
(switch selectable in TWxA)
Solid-state, integrated circuit (Transmitter)
0.5C (1F) typical
0 to 50C (32 to 122F), -40 to 50C (-40 to 122F)
22AWG; 2-wire: 4-20mA;
3-wire: Voltage output models

TWxA/TW

quick install

NOTICE

TDDA

This product is not intended for life or safety applications.


Do not install this product in hazardous or classied locations.
Read and understand the instructions before installing
this product.
Turn o all power supplying equipment before working on it.
The installer is responsible for conformance to all applicable codes.

Range

Output

1 = -40 to 50 C
(-40 to 122F)
2 = 0 to 50C
(32 to 122F)

Range

1. Locate sensor in an outside area, out of direct sunlight (e.g. under an eave, north
side of building).

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

2. Mount the housing.


3. Wire as shown (see Wiring section).

Cal Certificate

TWxA and TW

TOA
M = 4-20mA
V = 0-5/10VDC

Local Display

TW

1 = -40to 50C
(-40 to 122F)
2 = 0 to 50C
(32 to 122F)

Sensor Type

3. Use screws to secure the junction box to the duct.

TOA

Cal Certificate

TDDA
M = 4-20mA
V = 0-5/10VDC

2. Insert the temperature probe, until the junction box is flat against the outer
surface of the duct.

4. Wire as shown (see Wiring section).

Product Identification
Output

1. Drill a hole in the duct.

1. Mount the housing vertically on an interior wall in the area to be monitored, in


a location where air circulates freely. Locate unit away from air outlets, corners,
exterior walls, windows, and doors.

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

2. Wire as shown (see Wiring section).

Setpoint/Override

Cal Certificate

A
L = LCD
X = No

Local Display

0 = None
2 = 1k Setpoint
3 = 10k Setpoint
4 = 1k Setpoint with override
5 = 10k Setpoint with override

= Transmitter
selectable
outputs

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

Setpoint/Override

Sensor Type

Cal Certificate

TW
L = LCD
X = No

Z201986-0N

B = 100R platinum, RTD


C = 1k platinum, RTD
D = 10k T2, Thermistor
E = 2.2k, Thermistor
F = 3k, Thermistor
G = 10k CPC, Thermistor
H = 10k T3, Thermistor
J = 10k Dale, Thermistor

PAGE 1

K = 10k w/11k shunt,Thermistor


M = 20k NTC, Thermistor
N = 1800 ohm, Thermistor
P = 10mV/C, Linitemp
R = 10k US, Thermistor
S = 10k 3A221, Thermistor
T = 100k, Thermistor

0 = None
2 = 1k Setpoint
3 = 10k Setpoint
4 = 1k Setpoint with override
5 = 10k Setpoint with override

0 = None
1 = 1 point Cal validation
2 = 2 point Cal validation

2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com

04101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris V logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

VERIS INDUSTRIES

INSTALLATION GUIDE

T Series

Dimensions

Wiring - TDDA and TOA


TDDA

TDDA/TOA 4-20mA

3.4"
(86 mm)

Veris #PS-24

0.5" Dia.
(13 mm.)

3.9"
(100 mm)

4.6"
(116 mm)

DIGITAL CONTROL

8.5"
(216 mm)

2.8"
(71 mm)

POWER SUPPLY
12 To 30 VDC

NGE

NGE

ORA

Temperature
4-20mA return

TOA

TDDA/TOA 0-5/0-10V

3.4"
(86 mm)

Veris #PS-24
0.9"
(22 mm)
3.9"
(100 mm)

4.6"
(116 mm)

ORA

+
POWER SUPPLY
12 To 30 VDC

9.3"
(237 mm)

DIGITAL CONTROL

2.8"
(71 mm)

RED

BLACK

ORAN
W
ELLO

Temperature
0-10V
0-5V

GE

TWxA
1.2"
(30 mm)

Wiring - TWxA
RIGHT
WIPER
LEFT

TWxA 4-20mA
Veris PS-24 Series, or Panel
POWER SOURCE +
12 to 24VDC Only -

DIGITAL CONTROL
3.5"
(89 mm)

Thermistor, RTD or Override

4.8"
(121 mm)

Temperature
4-20mA

Setpoint

TWxA 0-5/0-10V
Veris PS-24 Series, or Panel

Temperature
0-5/0-10V

Thermistor, RTD or Override

DIGITAL CONTROL

RIGHT
WIPER
LEFT

POWER SOURCE +
12 to 24VAC/DC -

Setpoint

NOTE: For 24VAC transformer powered applications, one side of transformer secondary is
connected to common. Isolation transformer or dedicated power supply may be required.

Z201986-0N

PAGE 2

2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com

04101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris V logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

VERIS INDUSTRIES

INSTALLATION GUIDE

T Series

Wiring - TW

Configuration - TW and TWxA

Current Output (2-Wire, 4-20mA)


+ POWER SUPPLY
-

12-24DC

CONTROL SYSTEM
- COMMON

Output Select
Volts

mA
Temp

RTD/THERMISTOR OVERRIDE
SETPOINT SLIDER
SLIDER RIGHT
SLIDER WIPER
SLIDER LEFT

PWR (4-20 SEND)

T OUT (4-20 RTN)


RTD/THERMISTOR OVERRIDE
RTD/THERMISTOR OVERRIDE

T RETURN

10V
Temp Range
50 to 95F
10 to 35C

32 to 122F
0 to 50C

5V
Temp

Voltage Output (3-Wire, 0-10V)


+ POWER SUPPLY
-

24 VAC/DC

CONTROL SYSTEM
- COMMON

Z201986-0N

RTD/THERMISTOR/OVERRIDE

PAGE 3

SLIDER LEFT

SETPOINT SLIDER
SLIDER RIGHT
SLIDER WIPER

T OUT
RTD/THERMISTOR/OVERRIDE
RTD/THERMISTOR/OVERRIDE

PWR
COMMON

T INPUT 0-10V

2010 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com

04101

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris V logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.