Overview of features
Digital
PLC system
Analog
PLC system
Feature
Digital interface
Synchronous X.21 (max. 2)
G703.1 64 kbit / s
Analog interface
VF (VFM, VFO, VFS), max. 8 for voice,
data and protection signal
Unterstation
RTU
Substation
Substation
RTU
RTU
RTU
Phone (ISDN
or analog)
Fax
Remote terminal
unit
Computer (data
transmission)
Protection
relay
Router
CFS-2
VF
PLPA
CSP
VFO
VFS
8x
VFM
VF
DSP system
AMP50
A
AMP50 TXF LT100
vMUX
D
X21-1
A
AGC
X21-2
TCP/IP
G703.1
DP
RS232
RS232
8x
iSWT1
iSWT2
TXF
D
D
fE1
Modem
connection
MUX
ATT
RXF
VF
VFO
VFS
VFM
X.21-x
RS232
iSWT
vMux
iFSK
DP
AGC
ATT
E1
CFS-2
PLPA
CSP
AMP50
RXF
TXF
TCP/IP
Voice frequency
Voice frequency interface FXO
Voice frequency interface FXS
Voice frequency interface E & M
Synchronous digital interface
Asynchronous digital interface
Integrated SWT 3000
Versatile multiplexer
Integrated FSK channel
Data Pump
Automatic Gain Control
Attenvator
Fractional E1 2 Mbit / s
Carrier Frequency Section
PowerLink Power Amplifier
Central Signal Processor unit
50 W power amplifier
Receive filter
Transmit filter
LAN interface
PowerLink
highlights in the package
As a power system operator, your emphasis is on
system performance. Thanks to a comprehensive
service portfolio, PowerLink can help you optimize
communications in your system, utilize bandwidth efficiently, and permanently improve the
reliability of your network operations. The most
important aspect of PowerLink is flexibility,
always offering you the best possible transmission
performance under all operating conditions.
Traditional
PLC
Traditional
PLC
MUX
MUX
CSP
vMUX
CSP
vMUX
PowerLink
your advantages at a glance
iFSK
iFSK
up to 2400 Bd
RTU
RTU
vMUX
vMUX
up to 19.2 kbit/s
RTU
RTU
*
vMUX
vMUX
vMUX
FSK
Modem
RTU
FSK
Modem
RTU
AF
Modem
RTU
Modem
RTU
Substation A
vMUX
vMUX
Substation C
Substation D
StationLink
Point-to-multipoint connection for asynchronous data
(RTU polling)
vMUX
Substation B
vMUX
Local
RTU
Power system control center
The functions of a power system control center include the regular retrieval of the event data from the telecontrol units,
which are usually combined into groups. This point-to-multipoint retrieval of data is implemented in a substation between
the PowerLink systems by means of the StationLink function
StationLink
Max. 8 x RS232
RTU connection PtP, PtMP
Optionally 4 RS232 with
FSK modulation in analog
operation
vMUX
Ethernet TCP / IP
e.g. router
10
LAN connection
PowerLink permits establishing a LAN connection
between substations in the high-voltage network.
As well as connecting routers via the X.21 interface,
PowerLink also provides an integrated Ethernet interface. This allows IP-enabled data terminal equipment
to be connected directly at low cost.
Transparent analog data transfer
When PowerLink is used in analog mode, a maximum
of four conventional asynchronous data channels up
to 2400 bit / s can be transmitted transparently by
means of FSK modulation.
a/b
PABX
E&M
PowerLink
PowerLink
Analog interface
Analog connection of individual telephones
PABX
Analog interface
Analog connection of telephone systems
E1
TCP / IP
PowerLink
PowerLink
TCP / IP interface
Connection of telephone or telephone systems via TCP / IP
Digital interface
Digital connection of telephone systems
Power system
control center
PowerLink
PABX
Substation A
PowerLink
Substation B
PowerLink
PABX
PowerLink
Substation C
PowerLink
PABX
PowerLink
PABX
11
Fiber-optic link
SWT 3000
SWT 3000
SWT 3000
SWT 3000
Integrated in PowerLink
SWT 3000
SWT 3000
SWT 3000
SWT 3000
SDH / PDH
Multi-purpose mode:
In this mode voice and data are transmitted
parallel to protection signals.
Alternate multi-purpose mode:
In this mode, the entire transmission capacity is
used for voice and data as long as it is not needed
for protection purposes. The PowerLink pilot tone
is used as the guard tone in this mode. If a protection command needs to be transmitted, voice
transmission is interrupted for the duration of
transmission of the protection command. Data
transmission may also be interrupted if the relevant parameter is set.
Easy to operate
the PowerLink management system
When analyzing the costs of an infrastructure investment, the expense
of training employees cannot be disregarded. The gratifyingly low
costs for training in PowerLink are due to the easy-to-learn, intuitive
user interface, standard for all system components. All applications in
PowerLink, such as the versatile multiplexer and the integrated and
external SWT 3000 devices, use a standard user interface. Your employees
everywhere can familiarize themselves quickly, so training times and
costs are minimized.
13
Station B
Station C
PowerLink
PowerLink
PowerLink
PowerLink
RM Addr. 1
RM Addr.
RM 2
RM Addr. 3
RM Addr. 4
SSF
RM
RM
Local
PowerSys
The administration of remote PowerLink systems can be carried out from the local operator console
at little cost or effort via a service channel which can be set up.
Station A
PowerLink
Station C
Station B
PowerLink
PowerLink
PowerLink
SSF
SSF
SSF
SSF
RM2
RM2
RM2
RM2
RM1
RM1
RM1
RM1
RAS RS232
RM channel
RM channel
Modem
Modem
RAS
IP network
The modems are connected via remote access servers (RAS) that also control the dial up or termination of the connections.
14
Station B
Station C
PowerLink
PowerLink
PowerLink
PowerLink
SWT 3000
SWT 3000
SWT 3000
SWT 3000
Terminal
Server
Terminal
Server
Terminal
Server
Terminal
Server
PowerLink helps you simplify your operating processes thanks to the latest technologies. Administration can be carried out
easily via the corporate LAN network using
the common TCP / IP network protocol.
The system can be connected with its
own network protection equipment and
a firewall to ensure the necessary security
level in the company.
Switch / Hub
IP network
PowerLink
PowerLink
PowerLink
SNMP
SNMP
SNMP
SNMP
IP network
The SNMP (Simple Network Management Protocol) function allows the integration
of PowerLink and SWT 3000 with network management systems on the basis of
SNMP V2.
Joint SNMP interface for PowerLink and the integrated SWT 3000
15
Technical data
HF transmission
Analog interface
Method
Modulation
VF interface (general)
Amplitude modulation with single-sideband
transmission, multicarrier modulation (OFDM),
single stage frequency conversion
HF frequency range
HF bandwidth
TX / RX band
Number of channels
up to 8
Telephone signaling
channel
Compander
Compression-expansion ratio k = 2
Bandwidth
Return loss
> 14 dB
Control wire in
Optocoupler
(7 V DC < V in < 72 V DC, Imax = 7 mA)
Interface
Output power
Rated output
impedance
75 ohms unbalanced
150 ohms balanced
Spurious emission
At a distance of:
60 dB
14 dBm
70 dB
24 dBm
80 dB
34 dBm
Return loss
Tapping loss
Properties
Receiver sensitivity
Receiver selectivity
Automatic crosstalk
cancellation AXC
Automatic frequency
control AFC
* Release P3.4
16
Number of channels
up to 5
Impedance
input / output
Input level
Output level
Control wires
Balance to ground 50 Hz
Balance to ground 60 Hz
Number of channels
up to 3
Impedance
600 ohms
Feeding current
48 V / max. 40 mA
Loop resistance
1500 ohms
Ringing current
Input level
26 dBm to + 5 dBm
Output level
11 dBm to + 14 dBm
up to 3
Impedance
600 ohms
Ringing detection
Loop resistance
Loop current
max. 70 mA
Input level
26 dBm to + 5 dBm
Output level
11 dBm to + 14 dB
Number of channels
up to 3
Input level
26 dBm to + 1 dBm
Output level
7 dBm to + 14 dBm
Number of voice
channels
up to 8 via E1 interface,
up to 5 via analog VF telephone interface
Number of data
channels
up to 14 (synchronous, asynchronous,
ETH, VF data)
Selectable,
5.3 kbps as per G.723.1
6.3 kbps as per G.723.1
8 kbps as per G.729
Voice compression,
signaling
up to 3
Input level
26 dBm to + 1 dBm
Output level
7 dBm to + 14 dBm
Control wire
Alarm out
F6 supervision
Transmission time
7 ms
Digital interface
Transparent narrow band data for aPLC
Selectable
Cross connection
switching matrix
(StationLink)
Multiplex method
Transmission capacity
Number of channels
up to 4, asynchronous
Modulation scheme
Minimum bandwidth
Interface
Number of channels
up to 8
Interface
Bit rate
Number of channels
up to 8 x asynchronous, 2 x synchronous,
8 x voice, 2 x VF data, 2 x ETH*
UART mode
Modulation scheme
Multicarrier
Multiplex method
DP data rates
max. 64 kbps
max. 256 kbps*
Transmission capacity
Bandwidth
Versatile multiplexer
Fallback mode
Required minimum
signal-noise ratio
* Release P3.4
Interface
X.21
Bit rate
1*
Bit rate
64 kbps
Clock timing
Contra directional
17
Ethernet interface
Number of ports
2*
Contact type
Relay, NO
Interface
250 VA
Bandwidth
350 V AC / DC
Application
Insulation dielectric
strength
2.5 kVrms
Number of voice
channels
2 Mbps
Signaling
CAS
* Release P3.4
Contact type
AC 1250 VA,
DC 150 W
Insulation dielectric
strength
2.5 kVrms
Transmission time
Properties
Number of systems
Operating modes
Single-purpose, multi-purpose,
alternate multi-purpose
Number of commands
Modulation
F6 or Coded tripping
Broadband frequencies
for operating equipment
Narrow band
frequencies for
operating equipment
Broadband equipment
Single purpose mode
Alternate multi-purpose
mode (F2 + AMP)
Alternate multi-purpose
mode (DP + AMP)
Simultaneous
multi-purpose mode
< 15 ms (F6)
The stated values apply for the IFC-P module. If the IFC-D module is used all stated
signal transmission times are about 4 ms longer. An optical link between SWT 3000
and PowerLink prolong the transmission time by 1 ms.
FOS1
Local range
Single-mode
Digital
Optical module
Connection
SFP transceiver
Duplex LC connector as per industrial standard
Wavelength (nm)
Command input IFC-P / IFC-D
Nominal input voltage
24 V 250 V DC ( 20 % to + 15 %)
Threshold value
Polarity independence
Yes
Pulse suppression
1 ms to 100 ms
(programmable in 1-ms steps)
1310
850
8
15
3
10
28
17
max.
min.
18
FOS2
Local range
Multimode
1310 nm:
0.38 dB / km
850 nm:
3.5 dB / km
13
34
Security
PUC
Ambient conditions
< 10-6
Reliability
PMC
Miscellaneous
0 C to + 55 C
5 C to + 55 C (hot boot)
40 C to + 70 C
Relative humidity
5 to 95 %
Absolute max.
air humidity
29 g / m3 (non-condensing)
Maintenance interfaces
Element Manager
Operation
Ethernet TX 10 / 100*,
RS232 19.2 kbps
Service phone
Headset
(2 x 3.5-mm telephone jack)
Expansion port
USB*
HF immunity
Electrostatic discharge
EN 61000-6-2, 61000-4-2
4 kV (contact discharge)
8 kV (direct air discharge)
EN 61000-6-2
10 V / m (80 MHz 1 GHz)
3 V / m (1.4 GHz 2 GHz)
1 V / m (2 GHz 2,7 GHz)
Network management
Element Manager
Event memory
EMC emissions
Emission of HF
interference
International standards
Terminals for single
sideband carrier frequency communication
via high-voltage lines
IEC 60495
Recording capacity
4000 events
Product safety
EN 60950-1 : 2001
Real-time clock
1 ms resolution,
synchronization per sync. pulse, IRIG-B, NTP
EMC
Climatic conditions
IEC 60870-2-2
Alarm output
Number of alarm
outputs
3 or 6
Contact type
300 W (DC)
1000 VA
Carry current
Power supply
Input voltage
38 to 72 V DC
93 to 264 V AC (47 to 63 Hz) / 88 to 264 V DC
Power consumption
Mechanical conditions
Protection class
IP20
Vibrations
5 9 Hz : amplitude 1.5 mm
9 200 Hz : acceleration 0.5 g
Shock
Acceleration 10 g
21 kg
26 kg
* Release P3.4
19