Professional Documents
Culture Documents
Contact Information
The following contact information is provided for those times when you cannot contact
your local representative:
Mailing Address
Telephone
Fax
Internet
ii
Additional Information
Notice:
This manual does not contain all the information required to operate and maintain
the product. Refer to the following manuals for other required information.
Guidelines for using the 3500 Rack Configuration software for setting the
operating parameters of the module.
Guidelines for using the 3500 test utilities to verify that the input and output
terminals on the module are operating properly.
iii
Contents
1. Receiving and Handling Instructions..........................................................1
1.1
1.2
Receiving Inspection........................................................................................................................ 1
Handling and Storage Considerations .................................................................................... 1
4. Configuration Information......................................................................... 23
4.1
Transient Data Interface Considerations .............................................................................23
4.1.1 3500 Rack Configuration ........................................................................................................23
4.1.2 System 1.........................................................................................................................................23
4.2
Configuration Process Overview ..............................................................................................24
4.3
Transient Data Interface Configuration ................................................................................25
4.3.1 Rear Port.........................................................................................................................................25
4.3.2 Ethernet (Rear Port) ...................................................................................................................25
4.3.3 Front Port .......................................................................................................................................26
4.3.4 Passwords .....................................................................................................................................27
4.3.5 Rack Mounting Option .............................................................................................................27
4.3.6 Power Supply................................................................................................................................28
4.3.7 Agency Approvals ......................................................................................................................28
4.4
Security Options Configuration.................................................................................................28
4.5
Software Switches ..........................................................................................................................29
4.5.1 General Information..................................................................................................................29
4.5.2 Configuration Mode ..................................................................................................................30
4.6
Hardware Switches ........................................................................................................................31
4.6.1 Key Switch .....................................................................................................................................31
4.6.2 Rack Reset .....................................................................................................................................31
4.6.3 Rack Address................................................................................................................................31
6. Maintenance ................................................................................................. 47
6.1
6.2
Verification .........................................................................................................................................47
Performing Firmware Upgrades...............................................................................................47
7. Troubleshooting........................................................................................... 49
7.1
7.2
7.3
7.4
Verification .........................................................................................................................................49
LED Fault Conditions......................................................................................................................49
System Event List Messages ......................................................................................................50
Management System Event List Messages.........................................................................69
v
8. Specifications ................................................................................................75
8.1
Inputs....................................................................................................................................................75
8.2
Outputs ................................................................................................................................................75
8.2.1 Front Panel LEDs.........................................................................................................................75
8.2.2 I/O Module OK Relay .................................................................................................................75
8.3
Controls................................................................................................................................................76
8.3.1 Front Panel ....................................................................................................................................76
8.3.2 I/O Module System Contacts.................................................................................................76
8.4
Data Collection .................................................................................................................................77
8.4.1 Startup/Coastdown Data........................................................................................................77
8.4.2 Alarm Data Collection ..............................................................................................................78
8.4.3 Static Values Data......................................................................................................................78
8.4.4 Waveform Sampling .................................................................................................................78
8.5
Communications .............................................................................................................................79
8.5.1 Protocols ........................................................................................................................................79
8.5.2 Front Panel ....................................................................................................................................79
8.5.3 10 Base-T/100 Base-TX Ethernet I/O.................................................................................80
8.5.4 100 Base-FX Ethernet I/O .......................................................................................................80
8.6
Environmental Limits .....................................................................................................................81
8.6.1 TDI Module, 10 Base-T/100 Base-TX I/O and 100 Base-FX I/O..............................81
8.7
Physical................................................................................................................................................81
8.7.1 TDI Module.....................................................................................................................................81
8.7.2 I/O Modules...................................................................................................................................81
vi
2. General Information
The Transient Data Interface (TDI) is the primary interface into the 3500 rack. It
supports a Bently Nevada* proprietary protocol that software uses to configure
the rack and retrieve machinery information. TDI has 2 primary functions:
configuration of the protection system and data retrieval for Bently Nevada
machine management systems.
You must place the TDI in slot 1 of the rack (next to the power supplies). Although
the TDI does provide certain functions common to the entire rack, the TDI is not
part of the critical monitoring path. The TDI's operation (or non-operation) does
not effect the proper, normal operation of the overall monitoring system.
5
8
9
6
10
1.
2.
3.
Main module
10 Base-T/100 Base-TX Ethernet input/output module
100 Base-FX Ethernet input output/module
4.
5.
6.
7.
8.
9.
Rack reset
Alarm inhibit
Trip multiply
OK relay
2.1.2 Security
Password
Key switch
2.3 Status
The Transient Data Interface returns both module and channel status. This
section describes the available statuses and where you can find them.
OK
This indicates if the Transient Data Interface is functioning correctly. The TDI
returns a Not OK status if it detects any of the following conditions:
If the Module OK status goes Not OK then the TDI will drive the system OK Relay
on the Rack Interface I/O Module Not OK.
2.3.1.2
Configuration Fault
This indicates whether the Transient Data Interface configuration is invalid.
OK
This indicates whether or not the TDI has detected a fault on the channel or within
the module. If the Channel OK status goes Not OK then the TDI will drive the
system OK Relay on the Rack Interface I/O Module Not OK.
Table 2-1 shows where you can find the statuses.
Table 2-1: Location of Channel OK Statuses
Status Locations
Communications
Gateway Module
Rack
Configuration
Software
Module OK
Operator
Display
Software
X
X
1
2
3
4
1.
2.
3.
OK: Indicates that the Transient Data Interface and the I/O modules are operating correctly.
TX/RX: Flashes at the rate that messages are sent.
TM: Indicates that the rack is in Trip Multiply mode.
4.
CONFIG OK: Indicates that ANY module in the rack is not configured or has a configuration error, that the stored
configuration of the Transient Data Interface does not match the physical configuration of the rack, or that a
security option was not met.
2.5 Requirements
The TDI has 2 levels of requirements:
1. functioning as the interface module for interfacing with 3500 Rack
Configuration and 3500 Data Acquisition software, and
2. collecting data for interfacing with System 1* software.
2.5.1 Hardware
TDI requires a management-ready 3500/05 rack. The presence of an Orbit symbol
on the left-hand size of the bezel, as shown in Figure 2-3, identifies the
management-ready racks.
1.
2.5.2 Software
TDI support requires the following software revisions:
2.5.3 Limitations
The TDI will not support the following:
TDI will not permit 3500 Configuration software to access the rack
through a 3500/92 Communications Gateway.
3. Data Collection
The Transient Data Interface is an integral communication processor that collects
and stores information from the 3500 monitors and transmits this information to
a host computer. This section describes how the data collection functions.
3.1 Overview
Data collected from a machine has several forms. This data includes static data,
dynamic data, status information and speed data. The TDI acquires all of these
forms of data as a result of various stages of operation for a machine: steady
state, transient (start-up & coast-down) and when alarms occur. The TDI collects,
stores, and transmits the data sets from the 3500 monitors to the data
acquisition computer. The data acquisition computer, in turn, provides the data
to the database and display stations.
The TDI uses structures called Collection groups to organize data collection. You
should place channels (measurement points) that are related to each other in the
same collection group. You create groups and add channels to them until you
associate all of the channels of the monitoring system with their respective
collection group. The TDI collects all of the channels data within the collection
group together and synchronizes them with each other. You use System 1
configuration software to create Collection Groups.
The TDI attempts to move data to the host computer at the earliest opportunity,
so it identifies data that it collects as part of an event as being related to the
event and then sends the data using its network connections. If TDI is unable to
send the data it will store the data and send it when it is able to do so.
3.2 Definitions
Channels
The connection of a transducer to the system.
Collection Group
A group of channels (transducers) that are collected together. This is used
for collection of data for alarms and during transient events.
Collection Group Enabler
A speed region that the user configures and that the TDI uses to enter into
transient collection mode.
Collection Control Parameter
A parameter that defines when to collect transient data.
9
3.3 Communication
The TDI communicates with the data acquisition computer using Ethernet. It can
support the following physical media: 10 Base-T, 100 Base-TX or 100 Base- FX.
The TDI is designed to work as a standard network device and should be
compatible with any Ethernet structure.
Protection Values
All of the static values that you configure or enable using 3500 monitor
configuration are available through the TDI. The TDI does not re-compute or
replace any values that the monitors measure. All of the 3500 monitors can
provide these static values regardless of the monitor type and whether the
monitor design supports the TDI (M vs. non-M series). Although both monitor
types support static values, one difference between non-M series and M series
monitors is that the M series can update static value faster than their
non-management ready counterparts.
3.4.1.2
Management Values
The 3500 TDI takes the dynamic waveform from the management ready (M
series) monitors and processes it to provide additional static values. These values
that the TDI computes are nX static values that return amplitude and phase
information of the vibration that relate to an order (nX) of running speed. The TDI
can calculate up to 4 nX values, which are available through the System 1
software.
Application Advisory
The TDI will mark phase information for
nX values derived from 360x or 720x
synchronous sample rates as invalid.
The nX values require a speed input to the 3500 rack. The nX options available are
based on the synchronous sampling rate used for waveform sampling. You can
adjust nX values in 0.01x steps.
Table 3-1: nX Available Options
nX Range
Synchronous Sampling
Rate
16x
100,000 rpm
32x
60,000 rpm
64x
30,000 rpm
128x
15,000 rpm
256x
7,500 rpm
11
3.4.1.3
nX Range
Synchronous Sampling
Rate
5,333 rpm
512x
3,750 rpm
2,666 rpm
1024x
1,875 rpm
Software Variables
Software variables augment the static variables that the monitor and TDI provide.
The software computes these variables after retrieving a waveform from the TDI
and performing a series of calculations on the data. The software may drive
Alarm data capture based on the values of these variables, but cannot issue a
protection alarm (relay closure).
3.4.2.1
Number of Channels
1 to 16
1 rpm
100,000 rpm
17 to 32
1 rpm
60,000 rpm
33 to 48
1 rpm
30,000 rpm
Synchronous Data
Synchronous data requires a once-per-turn input to the rack. The TDI samples
data relative to this once-per-turn reference signal and uses a supporting
predictive algorithm to sample systems in which speeds are changing. You
configure the TDI to collect a defined number of samples for each rotation of the
shaft, generally trading off between spectral resolution and waveform detail. The
speed of the machine limits the upper sampling rates available. Table 3-3 lists the
sampling rates and the maximum machine speed supported by the sampling
rate.
12
3.4.2.2
Sampling Rate
16x
128
100,000 rpm
32x
64
60,000 rpm
64x
32
30,000 rpm
128x
16
15,000 rpm
256x
7,500 rpm
360x
5,333 rpm
512x
3,750 rpm
720x
2,666 rpm
1024x
1,875 rpm
Asynchronous Sampling
In addition to synchronous data, the TDI uses a fixed-frequency sampling rate to
simultaneously collect asynchronous waveforms. The TDI will collect a
2048-sample data set that you can display as a waveform or an 800 line
spectrum. The data collected in this manner is anti-alias filtered. The TDI
synchronizes sampling of channel pairs within a monitor, except for the 64kHz
sampling rate, and you can use full spectrum plots to view the data. The following
table shows the sampling rate, corresponding spectral frequency span and the
number of spectral lines.
Application Advisory
The TDI limits the number of channels in
a collection group to 24 for 51.2kHz and
64kHz sampling rates.
Frequency Span
Spectral Resolution
25.6 Hz
10 Hz
800
0.0125 Hz
51.2 Hz
20 Hz
800
0.025 Hz
128 Hz
50 Hz
800
0.0625 Hz
256 Hz
100 Hz
800
0.125 Hz
512 Hz
200 Hz
800
0.25 Hz
1.28 kHz
500 Hz
800
0.625 Hz
13
3.4.2.3
Sample Rate
Frequency Span
Spectral Resolution
2.56 kHz
1 kHz
800
1.25 Hz
5.12 Hz
2 kHz
800
2.5 Hz
12.8 kHz
5 kHz
800
6.25 Hz
25.6 kHz
10 kHz
800
12.5 Hz
51.2 kHz*
20 kHz
800
25 Hz
64 kHz*
30 kHz
960
31.25 Hz
Integration
You can configure the TDI to return integrated waveform data. The TDI will return
all of the waveform and nX values as integrated data if you select integration in
the protection system configuration.
14
Note
Waveform data collection and storage is
an optional software feature that you
must purchase and then activate in TDI.
The TDI returns static values and waveforms when the host computer requests
them. The software uses this data to provide both real-time data displays and to
establish historical trend and reference data. The software collects the static
values at 1-second intervals across the machine train to build historical trend
plots. The host computer collects and stores historical waveform data at a
user-defined interval. The system uses this collection in static, steady state and
transient software operation.
a software alarm occurs for one of the points within the collection
group, or
The TDI does not collect alarm data when the point leaves the alarm state, such
as when going from Danger to Alert, or from Alert to no alarm.
The data set for an alarm event on a dynamic point will typically consist of the
following:
10 minutes of 1-second interval static data from before the event (580
static data points);
2.5 minutes of 10-second interval waveforms from before the event (15
wave- forms);
10 seconds of 0.1-second interval static data from after the event (100
static data points);
1 minute of 1-second interval static data from after the event (50 static
data points);
1.
2.
3.
4.
5.
6.
7.
8.
9.
NOTE
Transient data collection is an optional
software feature that you must
purchase and then activate in TDI.
The TDI has a special mode of operation for collecting data during transient
operation of the machine. The TDI collects transient data based on changes in
machine speed and at a configurable time interval. The TDI is always collecting
speed-based and time-based data. The TDI temporarily saves data but does not
send it to the host until the TDI detects that the machine is entering a transient
mode of operation. When this happens the TDI transmits the last 200 data
collection sets to the host and continues to send new data sets until the end of
transient conditions are met.
17
3.7.4.1
Define the Collection Group Enablers. These determine how the TDI
can determine that a machine is in transient operation.
12000
10000
8000
1
6000
4
4000
2000
5
6
1.
2.
3.
4.
5.
6.
19
1
2
3
4
1.
Delta time
2.
3.
4.
20
1
2
3
5
6
10
9
8
8
10
5
4
2
1
2
3
4
5
1.
2.
3.
4.
Delta time
Delta rpm (increasing)
Delta rpm (decreasing)
5.
Waveform collection
Figure 3-4: Sample Delta Time and Delta RPM Data Collection
3.7.4.3
22
4. Configuration Information
Configuring the 3500/22M consists of 2 steps:
1. configuring the TDI to function as the Rack Interface Module, and
2. configuring the data collection system.
This manual covers configuring the Rack Interface Module. The System 1 help
system covers configuring data collection.
This section describes how to use the 3500 Rack Configuration Software to
configure the Transient Data Interface. It also describes configuration restrictions
that are associated with this module. Refer to the 3500 Monitoring System Rack
Configuration and Utilities Guide and the Rack Configuration Software for the
details on how to operate the software.
4.1.2 System 1
If a collection group contains more than 24 channels then that group will not offer
20 kHz and 30 kHz as asynchronous frequency spans. Smaller collection groups
can still use 20 kHz or 30 kHz.
23
10 Base-T/100 Base-TX
100 Base-FX
Application Advisory
IP Addresses of 0.0.0.0 and
255.255.255.255 are not valid.
When configuring a new TDI, see your network administrator to obtain a
valid IP Address.
Rack Subnet Mask
This is a string that the system uses to mask against the IP Address. The
Rack Subnet Mask takes the form 255.255.0.0, 255.255.255.0, etc.
Gateway Address
The Gateway Address is the IP Address of the Gateway server. The system
uses the Gateway server to access addresses outside the local network.
Networks in which the Host Computer and the TDI are on the same local
area network do not need a Gateway. Contact your network administrator
to obtain the gateway address.
26
None
US Robotics 56k
Custom
Initialization String
The Initialization String is the command that sets up and starts the
modem. If you select a modem from the list, the software will display the
default initialization string in this field. If you select Custom, enter an
initialization string from information in the modem's documentation.
Byte Timeout
The Byte Timeout is the number of byte times for which the
communication line must be idle before the rack considers a
communication to be complete. One byte time is a function of the baud
rate selected. The range of values is 3 to 255.
4.3.4 Passwords
Connect Password
The Connect Password provides read-only access to the 3500 rack. If the
password entered in this field does not match the password entered in the
Rack Configuration Software "Connect" screen or in the Data Acquisition/
DDE Server Software "Setup" screen, the 3500 rack will not allow you to
communicate with it. The rack stores this password in non-volatile
memory in the Transient Data Interface.
Configuration Password
The Configuration Password provides configuration write access to the
3500 rack. If the password in this field does not match the password you
entered in the Rack Configuration Software "Download" screen, the 3500
rack will not accept new configurations. The 3500 rack requires you to
also enter this password to change setpoints in the 3500 rack from the
Operator Display Software. The rack stores this password in non-volatile
memory in the Transient Data Interface.
27
No Power Supply
AC High Voltage
AC Low Voltage
DC High Voltage
DC Low Voltage
Bottom
You can install the following power supplies in the lower 3500 Power
Supply Slot:
No Power Supply
AC High Voltage
AC Low Voltage
DC High Voltage
DC Low Voltage
None
CSA-NRTL/C
CE Approval
Select this box if the CE mark applies to the racks installation.
28
29
Application Advisory
No changes will take effect until
you press the Set button.
30
Switch Name
Configuration Mode
Application Advisory
You must insert an I/O module for the
Rack Reset switch to function correctly.
When you press the Rack Reset switch is pressed, any monitors in the rack will
clear latched alarms and reset Timed OK Channel Defeat indications. If the
Configuration LED is blinking at 5 Hz, it will stop blinking. This switch performs the
same function as the Rack Reset contact on the Rack Interface I/O Module.
NOTE
This does not apply to the 3500/53
Overspeed Monitors which can only be
reset by the methods listed in section
3.3.2 Basic Configuration Options (Page
33) of the 3500/53 manual.
1.
2.
32
Switch
Settings
7654321
Rack
Address
Switch
Settings
7654321
Rack
Address
Switch
Settings
7654321
Rack
Address
Switch
Settings
7654321
See note
0000001
0000010
0000011
0000100
0000101
0000110
0000111
0001000
0001001
10
0001010
11
0001011
12
0001100
13
0001101
14
0001110
15
0001111
16
0010000
17
0010001
18
0010010
19
0010011
20
0010100
21
0010101
22
0010110
23
0010111
24
0011000
25
0011001
26
0011010
27
0011011
28
0011100
29
0011101
30
0011110
31
0011111
32
0100000
33
0100001
34
0100010
35
0100011
36
0100100
37
0100101
38
0100110
39
0100111
40
0101000
41
0101001
42
0101010
43
0101011
44
0101100
45
0101101
46
0101110
47
0101111
48
0110000
49
0110001
50
0110010
51
0110011
52
0110100
53
0110101
54
0110110
55
0110111
56
0111000
57
0111001
58
0111010
59
0111011
Switch
Settings
7654321
Rack
Address
Switch
Settings
7654321
Rack
Address
Switch
Settings
7654321
Rack
Address
Switch
Settings
7654321
60
0111100
61
0111101
62
0111110
63
0111111
64
1000000
65
1000001
66
1000010
67
1000011
68
1000100
69
1000101
70
1000110
71
1000111
72
1001000
73
1001001
74
1001010
75
1001011
76
1001100
77
1001101
78
1001110
79
1001111
80
1010000
81
1010001
82
1010010
83
1010011
84
1010100
85
1010101
86
1010110
87
1010111
88
1011000
89
1011001
90
1011010
91
1011011
92
1011100
93
1011101
94
1011110
95
1011111
96
1100000
97
1100001
98
1100010
99
1100011
100
1100100
101
1100101
102
1100110
103
1100111
104
1101000
105
1101001
106
1101010
107
1101011
108
1101100
109
1101101
110
1101110
111
1101111
112
1110000
113
1110001
114
1110010
115
1110011
116
1110100
117
1110101
118
1110110
119
1110111
120
1111000
121
1111001
122
1111010
123
1111011
124
1111100
125
1111101
126
1111110
127
1111111
NOTE
Rack address 0 is reserved for the host.
Settings the switches to 0000000 will set
the rack address to 1, just as setting the
switches to 0000001 will.
33
35
1.
2.
OK relay. The OK relay is normally energized and indicates whether the 3500 Monitoring System is OK.
RJ-45 Ethernet connector. This allows you to connect the TDI to a host computer using Ethernet.
3.
4.
5.
MT-RJ Male fiber optic connector. This allows you to connect the TDI to a host computer using Ethernet.
Activity LED. This amber LED will flicker if the TDI detects network activity.
Link LED. This green LED will illuminate if the network to which the TDI connects is active.
6.
Eternal contacts. These consist of Trip Multiply, Rack Alarm Inhibit, and Rack Rest.
5.1.1 OK RELAY
The OK Relay will go Not OK under any of the following conditions:
36
You remove the Transient Data Interface from the 3500 rack
You configure any of the following security options and the rack meets
their conditions:
-
You change the rack address while the TDI is in Run mode.
You insert any module into or remove any module from the rack.
You change the key switch from Run mode to Program mode.
The following diagrams show the different ways that you can wire the OK Relay.
Note that NC means Normally Closed, ARM means Armature, and NO means
Normally Open.
NC
NC
NC
ARM
ARM
ARM
NO
NO
NO
2
1.
2.
3.
NOTE
The OK relay is normally energized.
37
100 Base-FX
The MT-RJ Male fiber optic port connects the TDI to the host computer through an
Ethernet network. This connection requires MT-RJ Female Multi-mode fiber optic
network cabling. The TDI supports a maximum length of 400 m (1312 ft).
NOTE
The 3500/22M has a MT-RJ Male
connector on the unit for Fiber Optic 100
Base-FX cabling therefore you MUST use
a MT-RJ Female connector on the fiber
optic cable to ensure proper
connectivity.
5.1.3.2
5.1.3.3
38
Application Advisory
Do not remove more than 6 mm (0.25
inches) of insulation from the wires.
39
COMMON
COMMON
TX
TX
RX
TX
RTS
RTS
CTS
CTS
DCD
DCD
DTR
20
DTR
1.
2.
40
RX
TX
COM
COM
TX
RX
NC
NC
NC
NC
NC
NC
4
1.
2.
3.
4.
Figure 5-5: Host Computer to 3500 Rack RS-232 Cable (P/N 130118-XXXX-XX)
41
1.
2.
3.
4.
NOTE
The Buffered Signal Output module
does not support connection to
DDIX, TDIX, or TDXnet.
42
Common
Channel
Pin Number
14
18
16
11
21
25
23
20
19
24
10
13
12
15
22
17
All channels
Channel
Pin Number
14
18
16
43
10
11
12
13
Common
44
11
21
25
23
20
19
24
10
13
12
15
22
17
All channels
14
15
Common
Channel
Pin Number
16
14
17
15
All channels
Channel
Pin Number
Upper - Keyphasor
1 (1 Upper KPH)
Upper - Keyphasor
2 (2 Upper KPH)
Lower - Keyphasor
3 (1 Lower KPH)
Lower - Keyphasor
4 (2 Lower KPH)
Common
All channels
45
Section 6 - Maintenance
6. Maintenance
This section shows how to verify that the Transient Data Interface and the I/O
modules are operating correctly.
When performed properly, you may install this module into or remove this module
from the rack while power is applied to the rack. Refer to the Rack Installation and
Maintenance Manual (part number 129766-01) for the proper procedure.
6.1 Verification
Before running the TDI Host Port Test Utility, connect the host to the rack with
either a RS-232 cable to the front of the TDI. Then use the TDI Host Port Test
Utility to verify that the HOST ports on the Transient Data Interface and the TDI I/O
Module are operating properly.
Refer to the 3500 Monitoring System Rack Configuration and Utilities Guide and
the Rack Configuration Software for the details of this utility.
Application Alert
During the following procedure the rack
must not lose power and you must not
remove the TDI from the rack. If either
of these occurs the TDI may become
inoperable.
1. Close System 1 Data Acquisition.
2. Start the 3500 Configuration software and connect to the rack. Use the
Ethernet port to upgrade the firmware, due to the length of the files that
you must download.
3. Upload and save the current configuration of the module. Although the
module retains the current configuration during the upgrade, saving the
present configuration will help if any problems arise during the upgrade
process.
4. Under the Utilities menu option select Update Firmware.
47
48
Section 7 - Troubleshooting
7. Troubleshooting
This section describes how to use the information that verification screen, the
LEDs, the System Event List, and the Alarm Event List provide to troubleshoot a
problem with the Transient Data Interface or the I/O modules. You can use the
Rack Configuration Software to display the verification screen and the 2 event
lists.
7.1 Verification
To verify the operation of the Transient Data Interface:
1. Connect a computer running the Rack Configuration Software to the 3500
rack (if needed).
2. Select Utilities from the main screen of the Rack Configuration Software
3. Select Verification from the Utilities menu.
4. Select the Transient Data Interface and select the channel that you want
to verify.
5. Press the Verify button.
6. Select the Front Port or the Rear Port to get the status.
7. The Module OK State will show the Transient Data Interface's status and
the Channel OK State will show the channel's status.
TX/RX
Condition
Solution
1 Hz
1 Hz
5 Hz
Dont
Care
ON
Flashing
No action is required.
Dont
Care
Not
flashing
49
Condition
Solution
ON
No action is required.
OFF
No action is required.
Condition
Solution
ON
No action is required
5 Hz
Event
Information
Event
Number
Class
Event Date
DDMMYY
Event Time
0000000123
Device not
communicating
32
02/01/90
12:24:31:99
Event
Specific
Slot
5L
Sequence Number: This is the number of the event in the System Event List (for
example 123).
50
Event Information:
This provides the name of the event (for example Device Not
Communicating).
Event Number:
Section 7 - Troubleshooting
This indicates the severity of the event. The following
classes are available:
Class:
Classification
Severe/Fatal Event
Reserved
Event Date:
Event Time:
Event Specific:
Slot:
The Transient Data Interface may place the following messages, which are listed
in numerical order, in the System Event List. Note that if an event marked with an
asterisk (*) occurs, the host link on the back of the Rack Interface I/O Module that
supplied the message will not communicate with the host computer
If you are unable to resolve a problem, contact your nearest Bently Nevada, Inc.
office.
Device Is Communicating:
Event Number: 33
Event Classification: Potential Problem
Action:
52
Section 7 - Troubleshooting
Config Token Acquired (Configuration Token Acquired):
Event Number: 50
Event Classification: Typical logged event
Event Specific:
- Front,
- Back,
The specified port can download configuration, change setpoints, set
software switches, enable/disable Rack Alarm Inhibit, enable/disable
Trip Multiply, or perform Rack Reset.
Action:
No action required.
No action required.
53
No action required.
Verify that the Rack Interface I/O Module installed matches the Rack
Interface I/O Module selected in the Rack Configuration Software. If
the correct Rack Interface I/O Module is installed, there could be a fault
with the installed Rack Interface I/O Module.
Section 7 - Troubleshooting
Event Classification: Potential Problem
Action:
Verify that the rack selection jumper, installed on the rack backplane,
matches the rack type selected in the software. If the jumper is
installed in the correct position, there could be a fault with the rack
backplane.
No action required.
No action required.
No action required.
No action required.
No action required.
55
No action required.
No action required.
No action required.
No action required.
No action required.
No action required.
Section 7 - Troubleshooting
SW Trip Mult Inactive (Software Trip Multiply Inactive):
Event Number: 81
Event Classification: Typical Logged Event
Action:
No action required.
No action required.
No action required.
No action required.
No action required.
Fail Main Board +5V-A (Fail Main Board +5V - upper Power Supply):
Event Number: 100
Event Classification: Potential Problem
57
Pass Main Board +5V-A(Pass Main Board +5V - upper Power Supply):
Event Number: 101
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface, or
- the Power Supply installed in the upper slot
Fail Main Board +5V-B (Fail Main Board +5V - lower Power Supply):
Event Number: 102
Event Classification: Potential Problem
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface, or
- the Power Supply installed in the lower slot
Pass Main Board +5V-B (Pass Main Board +5V - lower Power Supply):
Event Number: 103
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
Action:
58
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
Section 7 - Troubleshooting
- the Transient Data Interface, or
- the Power Supply installed in the lower slot
* Fail Main Board +5V-AB(Fail Main Board +5V - upper and lower Power
Supplies):
Event Number: 104
Event Classification: Severe / Fatal Event
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface,
- the Power Supply installed in the lower slot, or
- the Power Supply installed in the upper slot.
Pass Main Board +5V-AB (Pass Main Board +5V - upper and lower Power
Supplies):
Event Number: 105
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface,
- the Power Supply installed in the lower slot, or
- the Power Supply installed in the upper slot.
Fail Main Board +15V-A (Fail Main Board +15V - upper Power Supply):
Event Number: 106
Event Classification: Potential Problem
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty
59
Pass Main Board +15V-A (Pass Main Board +15V - upper Power Supply):
Event Number: 107
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface, or
- the Power Supply installed in the upper slot.
Fail Main Board +15V-B(Fail Main Board +15V - lower Power Supply):
Event Number: 108
Event Classification: Potential Problem
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface, or
- the Power Supply installed in the lower slot.
Pass Main Board +15V-B (Pass Main Board +15V - lower Power Supply):
Event Number: 109
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface, or
- the Power Supply installed in the lower slot.
60
Section 7 - Troubleshooting
* Fail Main Board +15V-AB (Fail Main Board +15V - upper and lower Power
Supplies):
Event Number: 110
Event Classification: Severe / Fatal Event
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface,
- the Power Supply installed in the lower slot, or
- the Power Supply installed in the upper slot.
Pass Main Board +15V-AB (Pass Main Board +15V - upper and lower Power
Supplies):
Event Number: 111
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface,
- the Power Supply installed in the lower slot, or
- the Power Supply installed in the upper slot.
Fail Main Board +3V-AB (Pass Main Board +3V - upper and lower Power
Supplies):
Event Number: 162
Event Classification: Severe / Fatal Event
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface,
61
Pass Main Board +3V-AB (Pass Main Board +3V - upper and lower Power
Supplies):
Event Number: 163
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface,
- the Power Supply installed in the lower slot, or
- the Power Supply installed in the upper slot.
Fail Main Board +2.5V-AB (Pass Main Board +2.5V - upper and lower Power
Supplies):
Event Number: 164
Event Classification: Severe / Fatal Event
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface,
- the Power Supply installed in the lower slot, or
- the Power Supply installed in the upper slot.
Pass Main Board +2.5V-AB (Pass Main Board +2.5V - upper and lower Power
Supplies):
Event Number: 165
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
62
Action:
Section 7 - Troubleshooting
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface,
- the Power Supply installed in the lower slot, or
- the Power Supply installed in the upper slot.
Fail Low Rough Supply A (Fail Main Board Rough Supply - upper Power Supply):
Event Number: 174
Event Classification: Potential Problem
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface, or
- the Power Supply installed in the upper slot.
Fail Low Rough Supply B (Fail Main Board Rough Supply - lower Power Supply):
Event Number: 175
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface, or
- the Power Supply installed in the upper slot.
Pass Low Rough Supply A (Pass Main Board Rough Supply - upper Power
Supply):
Event Number: 176
Event Classification: Potential Problem
Description: Unit has recovered from a node voltage error.
63
Pass Low Rough Supply B (Fail Main Board Rough Supply - lower Power Supply):
Event Number: 177
Event Classification: Potential Problem
Action:
Verify that noise from the power source is not causing the problem. If
the problem is not caused by noise, check to see if one of the following
components is faulty:
- the Transient Data Interface, or
- the Power Supply installed in the lower slot.
Device Configured:
Event Number: 300
Event Classification: Typical Logged Event
Action:
No action required.
Configuration Failure:
Event Number: 301
Event Classification: Severe/Fatal Event
Action:
Configuration Failure:
Event Number: 301
Event Classification: Potential Problem
Action:
64
Section 7 - Troubleshooting
Module Entered Cfg Mode (Module Entered Configuration Mode):
Event Number: 302
Event Classification: Typical Logged Event
Action:
No action required.
If the rack configuration is TMR, verify that the rack has 2 power
supplies and that the jumper on the backplane is set to the lower
position.
Verify that you have installed a TMR TDI in a TMR rack and properly set
the jumper in the rack. If problems persist, contact Technical Support.
Module Reboot:
Event Number: 320
Event Classification: Typical Logged Event
Action:
No action required.
No action required.
No action required.
Supply OK/Installed:
Event Number: 330
Event Classification: Potential Problem
66
Action:
Section 7 - Troubleshooting
Determine if a power supply has been installed. Verify that there is not
a problem with the power source. If there are no problems with the
power source, replace the power supply as soon as possible.
Supply Faulted/Removed:
Event Number: 331
Event Classification: Potential Problem
Action:
Determine if a power supply has been removed. Verify that there is not
a problem with the power source. If there are no problems with the
power source, replace the power supply as soon as possible.
No action required.
No action required.
Modem Reinitialized:
Event Number: 350
Event Classification: Typical Logged Event
Action:
No action required.
No action required.
67
No action required.
No action required.
No action required.
No action required.
No action required.
No action required.
Section 7 - Troubleshooting
Incompatible Backplane:
Event Number: 402
Event Classification: Potential Problem
Action:
No action required
No action required
No action required
Clctn Group Enter Transient (Collection Group Entered into Transient Mode):
Event Number: 1006
Event Classification: Typical Logged Event
Action:
No action required
Clctn Group Exit Transient (Collection Group Exited from Transient Mode):
Event Number: 1007
Event Classification: Typical Logged Event
Action:
70
No action required
Section 7 - Troubleshooting
Management Sys. Halted:
Event Number: 1008
Event Classification: Potential Problem
Action:
If the event occurred when you started System 1 DAQ or changed the
configuration of the TDI configuration no action is required. Otherwise,
replace the TDI.
If the event occurred when you started System 1 DAQ or changed the
configuration of the TDI configuration no action is required. Otherwise,
replace the TDI.
Management Configured:
Event Number: 1012
Event Classification: Typical Logged Event
Action:
No action required
71
No action required
No action required
No action required
No action required
No action required
72
Action:
Section 7 - Troubleshooting
Determine which M series monitor does not meet the requirements
for the TDI (monitor PWA revision of G or higher, or Mod 162183) and
replace the monitor.
Communication
Gateway
Entered not OK
Left not OK
Keyphasor
Module
Entered not OK
Left not OK
Transient Data
Interface
Entered not OK
Left not OK
Entered not OK
Left not OK
Relay Activated
Relay Deactivated
Relay Module
73
Section 8 - Specifications
8. Specifications
8.1 Inputs
Power Consumption
10.5 Watts
Data
Front panel
115.2 kbaud maximum RS232 serial communications
10 Base-T/100
Base-TX I/O
10 Base-T or 100 Base-TX Ethernet, auto-sensing
100 Base-FX I/O
100 Base-FX Fiber-Optic Ethernet
8.2 Outputs
8.2.1 Front Panel LEDs
OK LED
Indicates when the 3500/22M is operating properly.
TX/RX LED
Indicates when the 3500/22M is communicating with
other modules in the 3500 rack.
TM LED
Indicates when the 3500 rack is in Trip Multiply
mode.
CONFIG OK LED
Indicates that the 3500 rack has a valid
configuration.
8.3 Controls
8.3.1 Front Panel
Rack reset button
Clears latched alarms and Timed OK Channel Defeat
in the rack. Performs same function as the Rack
Reset contact on I/O module.
Address switch
Used to set the rack address; 127 possible addresses.
Configuration Key Switch
Used to place the 3500 rack in either RUN mode or
PROGRAM mode. RUN mode allows for normal
operation of the rack and locks out configuration
changes. PROGRAM mode allows for normal
operation of the rack and also allows for local or
remote rack configuration. The key can be removed
from the rack in either position, allowing switch to
remain in either RUN or PROGRAM positions. Locking
switch in the RUN position allows you to restrict
unauthorized rack reconfiguration. Locking switch in
PROGRAM position allows remote configuration of
the rack at any time.
Section 8 - Specifications
Maximum Current
<1 mA dc, Dry Contact to Common.
Minimum
Speed
Maximum
Speed
1 to 16
1 rpm
100,000 rpm
17 to 24
1 rpm
60,000 rpm
25 to 48
1 rpm
30,000 rpm
Section 8 - Specifications
Asynchronous Sampling
Asynchronous data sampled to support an 800-line
spectrum at the following frequency spans:
10 Hz
20 Hz
50 Hz
100 Hz
200 Hz
500 Hz
1000 Hz
2000 Hz
5000 Hz
10 kHz
20 kHz
30 kHz
Asynchronous data is anti-aliased filtered.
Channel Pair Support
You can split a Channel Pair among multiple
monitors to provide Orbit or synchronous full
spectrum presentations.
For asynchronous full spectrums the channels must
be within a monitor channel pair (the TDI will not
phase correlate 30 kHz frequency span data
between channel pairs).
8.5 Communications
8.5.1 Protocols
BN Host Protocol
Communications with 3500 Configuration Software
and 3500 Data Acquisition and Display Software.
BN TDI Protocol
Communications with System 1 Asset Management
and Data Collection Software.
80
Section 8 - Specifications
8.7 Physical
8.7.1 TDI Module
Dimensions (Height x
Width x Depth)
241.3 mm x 24.4 mm x 241.8 mm (9.50 in x 0.96 in x
9.52 in)
Weight
0.91 kg (2.0 lbm)