RW ID : RWR1

0.50

Concrete Strength, f'c =


Steel Yield Strength, fy =
Allow. Soil Bearing Capacity, qa =
Soil Unit Weight, s =
Concrete Unit Weight, c =
Angle of Internal Friction, =
Inclination of ground surface, =
sin =
cos =
Backfill Pressure Hor. Coeff., kh =
Pa =
Pv = Pa sin =
Ph = Pa cos =

21
414
250
18.50
23.6
40
10
0.175
0.985
0.450
111.7
19.50
110.0

MPa
MPa
kN/m2
kN/m3
kN/m3

W1
3.90
4.50
W2
W3

kN/m
kN/m
kN/m

0.60
C

0.70

0.70

Factor of Safety Against Overturning (consider 1-m strip)


-Tabulation to determine Righting Moment, MR
Section
No.
W1
W2
W3
W4
W5
Pv

Weight/unit
length
(kN/m)

Area
(m2)
3.90
0.20
1.80
3.90
1
/2 x 1.80
1

/2 x

x
x
x
x
x

0.50
4.50
0.60
1.80
0.681

=
=
=
=
=

1.95
0.45
1.08
7.02
0.613

23.60
23.60
23.60
18.50

x
x
x
x
18.50 x

1.95
0.45
1.08
7.02
0.613

Moment arm
from point C
(m)

Moment
(kN-m)

1.15
0.83
1.60
2.30
2.60
3.20

52.92
8.85
40.78
298.70
29.47
62.40

=
=
=
=
=

46.02
10.62
25.49
129.87
11.3333
= 19.50

R = 242.83

MR =

493.12

-Overturning Moment, MO

Ph
h/3

FSoverturning =

MR
MO

2.59

> 2, safe against overturning

MO = Ph (h/3)
= 190.0

-Soil Pressure
B
CL

R
x

x=

MR - MO
R

e=

= 1.248
qmax

qmin

qmax
qmin

m
<

=
B/6 =

<

250

= R/B(1 6e/B)

qmax = 179.16 kN/m2


qmin = 15.11 kN/m2
-Design of Wall (consider 1-m strip)
Coeff. of Active Pressure, kh =
Moment, MU =
deff =
P
z
3.90

reqd =
min =
As =
using
A1bar =
spacing =

0.217
66.46
625
0.0005
0.0034
2114
20
314.2
0.149

kN-m
mm

mm2
mm bar
mm2
m

-Design of Heel
W3 = 25.49 kN
W4 = 129.87 kN
W5 = 11.333 kN

qmin

q'
R2
R1
R1 =
R2 =

41.34
27.19

kN
kN

Moment, MU =
deff =
qmax = 179.16 kN/m2
qmin = 15.11 kN/m2
q' = 61.0405 kN/m2

reqd =
min =
As =
using
A1bar =
spacing =

W5

RW ID : RWR2
0.681

W4

Concrete Strength, f'c =


Steel Yield Strength, fy =
Allow. Soil Bearing Capacity, qa =
Soil Unit Weight, s =
Concrete Unit Weight, c =

Pv
Pa

Angle of Internal Friction, =


Inclination of ground surface, =
sin =
cos =
Backfill Pressure Hor. Coeff., kh =

Ph

Pa =
Pv = Pa sin =
Ph = Pa cos =

1.80

21
414
150
18.50
23.6
40
10
0.175
0.985
0.450
111.0
19.37
109.3

MPa
MPa
kN/m2
kN/m3
kN/m3

kN/m
kN/m
kN/m

Factor of Safety Against Overturning (consider 1-m strip)


-Tabulation to determine Righting Moment, MR
Moment
(kN-m)

Section
No.

52.92
8.85
40.78
298.70
29.47
62.40

W1
W2
W3
W4
W5
Pv

Weight/unit
length
(kN/m)

Area
(m2)
3.80
0.30
1.90
3.80
1
/2 x 1.90
/2 x

x
x
x
x
x

0.50
4.50
0.70
1.90
0.663

=
=
=
=
=

1.90
0.68
1.33
7.22
0.630

MR
MO

3.05

23.60
23.60
23.60
18.50

x
x
x
x
18.50 x

493.12
-Overturning Moment, MO

Ph (h/3)
kN-m

FSoverturning =

> 2, safe against overtu

-Soil Pressure
B
CL

R
B/2 - x
0.35
0.42

m
m
qmax

kN/m2

qmin

SAFE

-Design of Wall (consider 1-m strip)

Coeff. of Active Pres

P
z
3.80

-Design of Heel
164.4
525
0.0016
0.0034
1775
20
314.2
0.177

W3 = 31.39 kN
W4 = 133.57
W5 = 11.656 kN

kN-m
mm

mm2
mm bar
mm2
m

qmin

q'
R2
R1
R1 =
R2 =

29.76
80.22

kN
kN

0.50

W5

RW ID :
0.663

Allow. Soil Bearing Ca


W1

W4

Pv
Pa

3.80
4.50

Angle of Internal
Inclination of ground

Ph
W2
W3

Backfill Pressure Hor


0.70
C

0.80

0.80

ider 1-m strip)

1.90

Factor of Safety Against O


-Tabulation to determine Ri

Weight/unit
length
(kN/m)
1.90
0.68
1.33
7.22
0.630

Moment arm
from point C
(m)

Moment
(kN-m)

Section
No.

1.35
1.00
1.75
2.55
2.87
3.50

60.53
15.93
54.93
340.60
33.41
67.79

W1
W2
W3
W4
W5
Pv

=
=
=
=
=

44.84
15.93
31.39
133.57
11.6562
= 19.37

R = 256.75

MR =

573.20
-Overturning Moment, MO

Ph

MO = Ph (h/3)
= 188.1 kN-m

h/3

> 2, safe against overturning

FSoverturning =

-Soil Pressure

x=

MR - MO
R

e = B/2 - x

= 1.500

qmax
qmin

m
<

= 0.25
B/6 = 0.45

<

150

m
m

= R/B(1 6e/B)

qmax = 147.96 kN/m2


qmin = 42.22 kN/m2

kN/m2

SAFE

-Design of Wall (consider 1


Coeff. of Active Pressure, kh =
Moment, MU =
deff =
reqd =
min =
As =
using
A1bar =
spacing =

0.217
61.48
725
0.0003
0.0034
2452
20
314.2
0.128

kN-m
mm
z
mm2
mm bar
mm2
m

3.80

-Design of Heel
kN
kN
kN
qmax = 147.96 kN/m2
qmin = 42.22 kN/m2
q' = 73.5536 kN/m2

Moment, MU = 114.7 kN-m


deff = 625 mm
reqd = 0.0008
min = 0.0034
As = 2114 mm2
using 20 mm bar
A1bar = 314.2 mm2
spacing = 0.149 m

RWR3
Concrete Strength, f'c =
Steel Yield Strength, fy =
Allow. Soil Bearing Capacity, qa =
Soil Unit Weight, s =
Concrete Unit Weight, c =
Angle of Internal Friction, =
Inclination of ground surface, =
sin =
cos =
Backfill Pressure Hor. Coeff., kh =
Pa =
Pv = Pa sin =
Ph = Pa cos =

21
414
150
18.00
23.6
40
10
0.175
0.985
0.450
108.0
18.84
106.3

MPa
MPa
kN/m2
kN/m3
kN/m3

0.50

W5

W1

W4

3.80
4.50
W2
W3
kN/m
kN/m
kN/m

0.70
C

0.80

0.80

actor of Safety Against Overturning (consider 1-m strip)


-Tabulation to determine Righting Moment, MR
Weight/unit
length
(kN/m)

Area
(m2)
3.80
0.30
1.90
3.80
1
/2 x 1.90
1

/2 x

x
x
x
x
x

0.50
4.50
0.70
1.90
0.663

=
=
=
=
=

1.90
0.68
1.33
7.22
0.630

23.60
23.60
23.60
18.00

x
x
x
x
18.00 x

1.90
0.68
1.33
7.22
0.630

Moment arm
from point C
(m)

Moment
(kN-m)

1.35
1.00
1.75
2.55
2.87
3.50

60.53
15.93
54.93
331.40
32.51
65.95

=
=
=
=
=

44.84
15.93
31.39
129.96
11.3412
= 18.84

R = 252.30

MR =

561.26

-Overturning Moment, MO

Ph
h/3

FSoverturning =

MR
MO

3.07

> 2, safe against overturning

MO = Ph (h/3)
= 183.0 kN-m

1.90

-Soil Pressure
B
CL

R
x

x=

MR - MO
R

e = B/2 - x

= 1.499
qmax

qmin

qmax
qmin

m
<

= 0.25
B/6 = 0.45

<

150

m
m

= R/B(1 6e/B)

qmax = 145.55 kN/m2


qmin = 41.34 kN/m2

kN/m2

-Design of Wall (consider 1-m strip)


Coeff. of Active Pressure, kh =
Moment, MU =
deff =
P

reqd =
min =
As =
using
A1bar =
spacing =

0.283
78.01
725
0.0004
0.0034
2452
20
314.2
0.128

kN-m
mm

mm2
mm bar
mm2
m

-Design of Heel
W3 = 31.39 kN
W4 = 129.96 kN
W5 = 11.341 kN

qmin

q'
R2
R1
R1 =
R2 =

29.33
78.55

kN
kN

qmax = 145.55 kN/m2


qmin = 41.34 kN/m2
q' = 72.2173 kN/m2

Moment, MU = 111.5 kN-m


deff = 625 mm
reqd = 0.0008
min = 0.0034
As = 2114 mm2
using 20 mm bar
A1bar = 314.2 mm2
spacing = 0.149 m

RW ID : RWL1
0.663

Concrete Strength, f'c =


Steel Yield Strength, fy =
Allow. Soil Bearing Capacity, qa =
Soil Unit Weight, s =
Concrete Unit Weight, c =

Pv
Pa

Angle of Internal Friction, =


Inclination of ground surface, =
sin =
cos =
Backfill Pressure Hor. Coeff., kh =

Ph

Pa =
Pv = Pa sin =
Ph = Pa cos =

21
414
150
18.50
23.6
40
10
0.175
0.985
0.450
111.0
19.37
109.3

MPa
MPa
kN/m2
kN/m3
kN/m3
4.50

kN/m
kN/m
kN/m

Factor of Safety Against Overturning (consider 1-m strip)


-Tabulation to determine Righting Moment, MR
Section
No.
W1
W2
W3
W4
W5
Pv

Weight/unit
length
(kN/m)

Area
(m2)
3.80
0.30
1.90
3.80
1
/2 x 1.90
1

/2 x

x
x
x
x
x

0.50
4.50
0.70
1.90
0.663

=
=
=
=
=

1.90
0.68
1.33
7.22
0.630

23.60
23.60
23.60
18.50

x
x
x
x
18.50 x

1.90
0.68
1.33
7.22
0.630

=
=
=
=
=

44.84
15.93
31.39
133.57
11.6562
= 19.37

R = 256.75
-Overturning Moment, MO

Ph
h/3

FSoverturning =

MR
MO

3.05

> 2, safe against overturning

-Soil Pressure
B
CL

R
x

x=

MR - MO
R

= 1.500
qmax

qmin

qmax
qmin

= R/B(1 6e/B)

qmax = 147.96
qmin = 42.22

SAFE

-Design of Wall (consider 1-m strip)


Coeff. of Active Pressure, kh =
Moment, MU =
P
z
3.80
spacing =

-Design of Heel
W3 = 31.39 kN
W4 = 133.57 kN
W5 = 11.656 kN

mm bar

qmin

q'
R2
R1
R1 =
R2 =

29.76
80.22

kN
kN

qmax = 147.96
qmin = 42.22
q' = 73.5536

0.50

W5

RW ID : RWL2
0.663

W1

W4

Concrete Strength, f'c =


Steel Yield Strength, fy =
Allow. Soil Bearing Capacity, qa =
Pa

Soil Unit Weight, s =


Concrete Unit Weight, c =

Ph

Angle of Internal Friction, =


Inclination of ground surface, =

Pv

3.80
W2
W3

Backfill Pressure Hor. Coeff., kh =


0.70
C

0.80

0.80

Pv = Pa sin =
Ph = Pa cos =

1.90

Factor of Safety Against Overturning (consi


-Tabulation to determine Righting Moment, MR
Moment arm
from point C
(m)

Moment
(kN-m)

Section
No.

1.35
1.00
1.75
2.55
2.87
3.50

60.53
15.93
54.93
340.60
33.41
67.79

W1
W2
W3
W4
W5
Pv

inst overturning

MR =

Area
(m2)
3.80
0.30
1.90
3.80
1
/2 x 1.90
/2 x

x
x
x
x
x

573.20
-Overturning Moment, MO

MO = Ph (h/3)
= 188.1 kN-m

FSoverturning =

MR
MO

-Soil Pressure
B
R
e = B/2 - x
m
<

= 0.25
B/6 = 0.45

m
m
qmax

R/B(1 6e/B)

kN/m2
kN/m2

<

150

kN/m2

SAFE

-Design of Wall (consider 1-m strip)


Active Pressure, kh =
Moment, MU =
deff =
reqd =
min =
As =
using
A1bar =
spacing =

0.238
67.43
725
0.0003
0.0034
2452
20
314.2
0.128

kN-m
mm
z
mm2
mm bar
mm2
m

3.80

-Design of Heel

kN/m2
kN/m2
kN/m2

Moment, MU = 114.7 kN-m


deff = 625 mm
reqd = 0.0008
min = 0.0034
As = 2114 mm2
using 20 mm bar
A1bar = 314.2 mm2
spacing = 0.149 m

q'

R1 =
R2 =

0.50

oncrete Strength, f'c =


eel Yield Strength, fy =
Bearing Capacity, qa =

Soil Unit Weight, s =


crete Unit Weight, c =

of Internal Friction, =
of ground surface, =
sin =
cos =
essure Hor. Coeff., kh =
Pa =
Pv = Pa sin =
Ph = Pa cos =

21
414
150
18.50
23.6
40
10
0.175
0.985
0.450
111.0
19.37
109.3

MPa
MPa
kN/m2
kN/m3
kN/m3

0.663

W1

Ph
W2
W3

kN/m
kN/m
kN/m

0.70
C

Weight/unit
length
(kN/m)
1.90
0.68
1.33
7.22
0.630

0.80

0.80

23.60
23.60
23.60
18.50

x
x
x
x
18.50 x

1.90
0.68
1.33
7.22
0.630

Moment arm
from point C
(m)

Moment
(kN-m)

1.35
1.00
1.75
2.55
2.87
3.50

60.53
15.93
54.93
340.60
33.41
67.79

=
=
=
=
=

44.84
15.93
31.39
133.57
11.6562
= 19.37

R = 256.75

Ph
h/3

MR
MO

3.05

Pv
Pa

4.50

Area
(m2)
=
=
=
=
=

W4

3.80

Against Overturning (consider 1-m strip)


termine Righting Moment, MR

0.50
4.50
0.70
1.90
0.663

W5

> 2, safe against overturning

MR =

573.20

MO = Ph (h/3)
= 188.1 kN-m

1.90

B
CL

x=

MR - MO
R

e = B/2 - x

= 1.500
qmin

qmax
qmin

m
<

= 0.25
B/6 = 0.45

<

150

m
m

= R/B(1 6e/B)

qmax = 147.96 kN/m2


qmin = 42.22 kN/m2

kN/m2

consider 1-m strip)


Coeff. of Active Pressure, kh =
Moment, MU =
deff =
P

reqd =
min =
As =
using
A1bar =
spacing =

W3 = 31.39 kN
W4 = 133.57 kN
W5 = 11.656 kN

qmin
R2
R1
29.76
80.22

kN
kN

qmax = 147.96 kN/m2


qmin = 42.22 kN/m2
q' = 73.5536 kN/m2

0.238
67.43
725
0.0003
0.0034
2452
20
314.2
0.128

kN-m
mm

mm2
mm bar
mm2
m

Moment, MU = 114.7 kN-m


deff = 625 mm
reqd = 0.0008
min = 0.0034
As = 2114 mm2
using 20 mm bar
A1bar = 314.2 mm2
spacing = 0.149 m

SAFE

DESIGN OF RETAINING WALL


INPUT DATA:
Concrete Strength,
Steel Yield Strength,
Retaining Wall height,
Dia. of main bar,
Thickness,
Effective thickness,
LATERAL LOADS:
Soil:

Surcharge:

Water:

f'c
fy
h
d1
t
deff

=
=
=
=
=
=

Ps = kh
FPsu

=
=

Psc
Wu
Pw
FPwu

41.4
414
3.00
16
300
272.00

MPa
MPa
m
mm
mm
mm

9.84 ft.

0.000 ksf
0.00 kN

=
@

0.00 kPa
1.00 m

=
=

0 ksf
0.000 ksf

0 kPa

=
=

0.614 ksf
61.88 kN

=
@

29.467 kPa
1.00 m

3.00

1.00 m
SURCHARGE
MOMENTS:
-Mu =
reqd =
min =
As =

+Mu
reqd
min
As

=
=
=
=

WATER + SOIL

34.38 kN-m
0.0013
0.0034
919.81
PROVIDE

16 -mm @

218.6 m. O.C.

18.33 kN-m
0.0007
0.0034
919.81
PROVIDE

16 -mm @

218.6 m. O.C.

FPu =

61.9

kN

DESIGN OF RETAINING WALL


INPUT DATA:
Concrete Strength,
Steel Yield Strength,
Retaining Wall height,
Dia. of main bar,
Thickness, t =
Effective thickness,

f'c
fy
h
d1
L/25
Use t
deff

=
=
=
=
=
=
=

28
414
1.70
16
68
200
117

MPa
MPa
m
mm
mm
mm
mm

5.58

ft.

P1

1.70

P2

h/2

h/3

Ca sh1

MOMENTS:
-Mu =
reqd =
min =
As =

Assume surcharge

=
=

h1

surcharge
s

0.599

Ca

1 - sin
1 + sin

0.33

P1 = Cash1
P2 = CawH2/2

=
=

59.10
0.0131
0.0034
1529.61

200
9.58

Ca wH

9.14
7.95

psf
kPa

kN
kN

kN-m

PROVIDE 16 - mm @
+Mu
reqd
min
As

=
=
=
=

31.60
0.0066
0.0034
768.81

0.13144654 m. O.C.

kN-m

PROVIDE 16 - mm @

0.2615

m. O.C.

Subject
Date
Designer
Mark

:
:
:
:

Design of Retaining Wall


20-Aug-02
Boyce
RW-1

Minimum

t = L/25 =
d=

54
154

say

200

mm

mm

H = 1.35

CasH =
8.10
DESIGN CRITERIA :
f'c =
fy =
surcharge
=
s =
=
w =

28
276
0.1

mPa
mPa
kPa

18.00
30

kN/m3
degrees
kN/m3

Ca =

0.1
1-sin
1+sin

0.333

h1 =
=

surcharges
0.006

Considering 1-m strip of wall :


-Mu =

3.49

kN-m

Check for Shear :


Vu =
Vn =

7.72
115.44

Vertical Reinforcements :
dia bar =
12
As1 =
113.10

kN
kN

mm
mm2

Safe

kPa

-Mu
Rn

As
s

=
=

3.49
0.16

=
=
=

0.00059
385.00
293.76

Horizontal Reinforcements :
dia bar =
12
As1 =
113.10
As =
s =

200
565.49

kN-m
min
mm
mm

0.0025

say

300

mm

say

300

mm

mm
mm2
mm2
mm2

h1

Cash1 =
0.03

wH =
kPa

0.135

kPa

PROPOSED EDITHA MANSION


DESIGN OF RETAINING WALL
INPUT DATA:
Concrete Strength,
Steel Yield Strength,
Retaining Wall height,
Dia. of main bar,
Thickness,
Effective thickness,
LATERAL LOADS:
Soil:

Surcharge:

Water:

f'c
fy
h
d1
t
deff

=
=
=
=
=
=

Ps = kh
FPsu

=
=

Psc
Wu
Pw
FPwu

28
414
2.70
16
250
222.00

MPa
MPa
m
mm
mm
mm

8.856 ft.

0.292 ksf
32.19 kN

=
@

14.02 kPa
0.90 m

=
=

0.165 ksf
0.281 ksf

13.461 kPa

=
=

0.553 ksf
50.12 kN

=
@

26.52 kPa
0.90 m

2.70

0.90 m
SURCHARGE
MOMENTS:
-Mu =
reqd =
min =
As =

+Mu
reqd
min
As

=
=
=
=

WATER + SOIL

53.42 kN-m
0.0030
0.0034
750.72
PROVIDE 16 -mm @

267.8 m. O.C.

28.85 kN-m
0.0016
0.0034
750.72
PROVIDE 16 -mm @

267.8 m. O.C.

FPu =

82.31

kN