Product Specification

37217C

Genset Control for Auto


Start and Transfer Switch
↓ easYgen-350
Operation (Model "320/350")

DESCRIPTION • AMF/loss of mains


auto start/stop
↑ easYgen-320 I/O's
• 1 or 3 phase generator and mains true rms • Complete engine and
voltage, measuring inputs: rated 480 Vac generator protection in
(max. 600 Vac) one unit
• Maximum 2 configurable discrete inputs
APPLICATIONS • Maximum 2 programmable relays • True RMS sensing of
• D+ input (charge alternator input/output) voltage
The easYTMgen-320 offers automatic engine starting,
Protection (ANSI #) • Counters for operating
stopping, metering, and generator protection (the
easYTMgen-350 adds AMF and transfer switching). The Generator / Engine: Battery voltage, over- hours, service
easYTMgen-300 series is designed for single unit iso- speed (12), over-/undervoltage (59/27), over- hours, and starts
lated operation applications. /underfrequency (81O/U), charge alternator
failure • Freely configurable
The multi purpose 6 digit 7 segment LED offers the ability discrete inputs
to display measured values and alarm messages. The
Features
CAN bus operation adds the ability to display J1939 • Start/stop sequence for Diesel engines • Freely programmable
messages from an engine ECU. • Pre-glow control relay outputs
• Operating hours, service hours, and start
counters • PC and/or front panel
• Configurable trip levels/delays/alarm classes configurable
• 6digit 7segment LED for
o display of measuring values (V, f, speed) • Password protected
O/C
o display of counters (see above) front panel configuration
o display of alarms
Load Load
o display of ECU messages
• Event logger
O/C O/C
• PC and/or front panel configurable (selection • Customized display
of parameters for front panel configuration)
using paper-strips
• Password protected front panel configuration
G G • 15 entry event logger • 6.5 to 32.0 Vdc power
• Customized display using paper-strips supply
320 & 350 Differentiation
breaker applications
• Front panel-mounting
• Model "320": GCB (generator circuit breaker)
The isolated J1939 CAN bus permits long distance net- operation only • Display of J1939 data
works for selected ECU manufacturers. Our sales de- • Model "350": GCB and MCB (mains circuit
partment can provide information regarding the selected breaker) operation • Visualization of J1939
ECU manufacturers. • Generator voltage measurement DM1 / DM2 SPN-FMI er-
o 1phase-2wire ror messages
o Option "X": 3phase-4wire, 3phase-3wire,
1phase-3wire, and 1phase-2wire • D+ charge alternator
• Mains voltage measurement input/output
o Model "350": 3phase-4wire
o Model "350X": 3phase-4wire, 3phase-3wire, • CE marked
1phase-3wire, and 1phase-2wire • Shock and vibration
• Option "X": Visualization of J1939 messages
• Option "X": MPU input (magnetic/switching)
test approved
• UL/cUL listed
SPECIFICATIONS
Power supply.................................................. 12/24 Vdc (6.5 to 32.0 Vdc) Discrete inputs...............................................................................isolated
Intrinsic consumption ................................................................max. 10 W Input range....................................................... 12/24 Vdc (6.5 to 32.0 Vdc)
Degree of pollution ................................................................................... 2 Input resistance....................................................................approx. 6.7 kΩ
Ambient temperature (operation) ..................... -20 to 70 °C / -4 to 158 °F Relay outputs .................................................................................isolated
Ambient temperature (storage) ........................ -20 to 85 °C / -4 to 185 °F Contact material............................................................................... AgCdO
Ambient humidity.................................................... 95 %, non-condensing Load (GP) ..................................................................... 2.00 Aac@250 Vac
Voltage ..............................................................................................( /Δ) 2.00 Adc@24 Vdc / 0.36 Adc@125 Vdc / 0.18 Adc@250 Vdc
480 Vac Rated (Vrated)........................................277/480 Vac Pilot duty (PD)..............................................................................................
Maximum value (Vmax)........................................346/600 Vac 1.00 Adc@24 Vdc / 0.22 Adc@125 Vdc / 0.10 Adc@250 Vdc
Rated voltage phase-ground...............................................300 Vac Housing Flush-mount...................Type Woodward
Rated surge voltage..................................................4.0 kV Dimensions .......................................................................158×158×40 mm
Linear measuring range ................ ............................................. 1.3 x Vrated Front cutout...........................................................138[+1.0]×138[+1.0] mm
Measuring frequency.......................40 (mains) or 15 (generator) to 85 Hz Connection.................................................... screw/plug terminals 2.5 mm²
Accuracy ........................................................................................ Class 1 Tightening torque ..............................................................................0.5 Nm
Input resistance..............................................................................2.0 MΩ Housing........................................................................... insulating surface
Max. power consumption per path ...............................................< 0.15 W Protection system ....................................................with correct installation
Speed input..................................................................capacitive isolated Front ...................................IP54 pending
Input impedance.......................................................... min. approx. 17 kΩ Weight.................................................................................... approx. 450 g
Input voltage.............................................................................875 mV eff. Disturbance test (CE) ......... tested according to applicable EN guidelines
D+ input/output ........................................................................................ Sinusoidal Vibration .........................................................4G, 5 to 100 Hz
Max. exciter current.....................12 Vdc (terminal 4)......................0.11 A Endurance Vibration........................................................4G, 30 Hz, 1.5 h
24 Vdc (terminal 3)......................0.11 A Random Vibration.........................................1.04Grms, 10 to 500 Hz, 2 h
Shock ...............................................................................40G peak, 11 ms
Listings ........................................................................................... UL/cUL

DIMENSIONS

158 136

136 40

158

PART NUMBERS
Model Part Number (P/N) Description
Model "320" P/N 8440-1798 EASYGEN-320-50B
Model "320/X" P/N 8440-1800 EASYGEN-320-50B/X
Model "350" P/N 8440-1799 EASYGEN-350-50B
Model "350/X" P/N 8440-1801 EASYGEN-350-50B/X
WIRING DIAGRAMS
Battery Battery

1 1
2 2
The socket for the PC configuration The socket for the PC configuration
is situated on the back of the item. is situated on the back of the item.
This is where the DPC This is where the DPC
has to be plugged in. has to be plugged in.

not connected 7 not connected 7


not connected 6 not connected 6
not connected 5 not connected 5
N L3 L2 L1 N L3 L2 L1

Common 15 Common 15
DI1 Oil pressure 16 DI1 Oil pressure 16
DI2 Coolant temperature 17 DI2 Coolant temperature 17
DI3 Remote start 18 DI3 Remote start 18
DI4 free programmable 19 DI4 free programmable 19
DI5 Reply GCB / free progr. 20 DI5 Reply GCB / free progr. 20

8 GCB 8 GCB
GCB close (relay 2) GCB close (relay 2)
9 9

Generator voltage L3 29
not connected 30
Generator voltage L2 31
not connected 32

easygen 320 X (genset control)


(genset control)

Generator voltage L1 33 Generator voltage L1 33


not connected 34 N L3 L2 L1 not connected 34 N L3 L2 L1

Generator voltage N 35 Generator voltage N 35


not connected 36

not connected 10
G not connected 10
G
B+ B+
Common 11 Auxiliary Common 11 Auxiliary
Free programmable (relay 4) 12 alternator Free programmable (relay 4) 12 D+ alternator
D+
Fuel relay (relay 5) 13 Fuel relay (relay 5) 13
Crank (relay 6) 14 Crank (relay 6) 14
easygen 320

Engine Engine

D+, 24 Vdc (charge alternator) 3 D+, 24 Vdc (charge alternator) 3


D+, 12 Vdc (charge alternator) 4 D+, 12 Vdc (charge alternator) 4

MPU + 37
MPU - 38
CAN-L 39
ECU
CAN-H 40
Subject to technical mocifications. 2004-09-21 | easYgen-300 Wiring Diagram eYg300ww-0439-ap.skf Subject to technical mocifications. 2004-09-21 | easYgen-300 Wiring Diagram eYg300ww-0439-ap.skf

Battery Battery

1 1
2 2
The socket for the PC configuration The socket for the PC configuration
is situated on the back of the item. is situated on the back of the item.
This is where the DPC This is where the DPC
has to be plugged in. N L3 L2 L1 has to be plugged in. N L3 L2 L1
Mains voltage L3 21 Mains voltage L3 21
not connected 22 not connected 22
Mains voltage L2 23 Mains voltage L2 23
not connected 24 not connected 24
Mains voltage L1 25 Mains voltage L1 25
not connected 26 not connected 26
Mains voltage N 27 Mains voltage N 27
not connected 28 not connected 28

7 7
MCB open (relay 1) 6 MCB MCB open (relay 1) 6 MCB
5 5
N L3 L2 L1 N L3 L2 L1

Common 15 Common 15
DI1 Oil pressure 16 DI1 Oil pressure 16
DI2 Coolant temperature 17 DI2 Coolant temperature 17
DI3 Remote start 18 DI3 Remote start 18
DI4 Reply MCB / free progr. 19 DI4 Reply MCB / free progr. 19
DI5 Reply GCB / free progr. 20 DI5 Reply GCB / free progr. 20

8 GCB 8 GCB
GCB close (relay 2) GCB close (relay 2)
9 9

not connected 29 Generator voltage L3 29


not connected 30 not connected 30
not connected 31 Generator voltage L2 31
not connected 32 not connected 32
(genset control)

easygen 350 X (genset control)

Generator voltage L1 33 Generator voltage L1 33


not connected 34 N L3 L2 L1 not connected 34 N L3 L2 L1
Generator voltage N 35 Generator voltage N 35
not connected 36

Free programmable (relay 3) 10


G Free programmable (relay 3) 10
G
B+ B+
Common 11 Auxiliary Common 11 Auxiliary
Free programmable (relay 4) 12 D+ alternator Free programmable (relay 4) 12 D+ alternator
Fuel relay (relay 5) 13 Fuel relay (relay 5) 13
Crank (relay 6) 14 Crank (relay 6) 14
easygen 350

Engine Engine

D+, 24 Vdc (charge alternator) 3 D+, 24 Vdc (charge alternator) 3


D+, 12 Vdc (charge alternator) 4 D+, 12 Vdc (charge alternator) 4

MPU + 37
MPU - 38
CAN-L 39
ECU
CAN-H 40
Subject to technical mocifications. 2004-09-21 | easYgen-300 Wiring Diagram eYg300ww-0439-ap.skf Subject to technical mocifications. 2004-09-21 | easYgen-300 Wiring Diagram eYg300ww-0439-ap.skf
FEATURES OVERVIEW
International
Woodward
PO Box 1519 easYTMgen-300
Fort Collins CO, USA 320 320/X 350 350/X
80522-1519
1000 East Drake Road
Fort Collins CO 80525
Ph: +1 (970) 482-5811
Fax: +1 (970) 498-3058

Europe
Woodward Governor Company Measuring
Leonhard-Reglerbau GmbH Generator voltage rated 277/480 Vac
Handwerkstrasse 29 1p-2w configurable#1 1p-2w configurable#1
70565 Stuttgart, Germany
- true rms max. 346/600 Vac
Ph: +49 (0) 711 789 54-0 Mains voltage rated 277/480 Vac
3p-4w configurable#1
Fax: +49 (0) 711 789 54-100 - true rms max. 346/600 Vac
Control
Distributors & Service
Woodward has an international Push-buttons to operate the unit 9 9 9 9
network of distributors and Isolated single-unit operation 9 9 9 9
service facilities. For your near- AMF (auto mains failure operation) 9 9
est representative, call the Fort Stand-by operation 9 9 9 9
Collins plant or see the World- Open transition (break-before-make) 9 9
wide Directory on our website. ATS (automatic transfer switching) 9 9
Corporate Headquarters Accessories
Rockford IL, USA 6digit 7segment LED (display of values and alarms) 9 9 9 9
Ph: +1 (815) 877-7441 Global multi-lingual use with customized paper-strip 9 9 9 9
Start/stop logic for Diesel engines 9 9 9 9
www.woodward.com/power
Operating hours/service hours/start counter 9 9 9 9
15 entry event logger 9 9 9 9
Configuration via front panel (password protected) 9 9 9 9
Configuration via PC #2 9 9 9 9
Protection
Engine: over-/underspeed 9 9
For more information contact:

Generator: voltage/frequency 9 9 9 9
J1939 DM1 red / amber lamp 9 9
I/Os
MPU input (magnetic/switching; Pickup) 9 9
D+ (charge alternator input/output) 9 9 9 9
Discrete alarm inputs (fixed) 2 2 2 2
Discrete remote start input (fixed) 1 1 1 1
Discrete alarm inputs (configurable) #3 2 2 2 2
Relay outputs (fixed) 3 3 4 4
Relay outputs (configurable) 1 1 2 2
CAN bus communication #4 9 9
Listings/Approvals
CE marked 9 9 9 9
Subject to technical UL/cUL listed 9 9 9 9
modifications. Shock and vibration test approvals 9 9 9 9
This document is distributed for Part Numbers P/N
informational purposes only. It is not
8440-1798 8440-1800 8440-1799 8440-1801
to be construed as creating or
becoming part of any Woodward #1 Configurable: 1p-2w, 1p-3w, 3p-3w, 3p-4w #2 Cable incl. software necessary (DPC = Part Number P/N 5417-557)
Governor Company contractual or #3 Only available if breaker replies are not used #4 fixed CAN J1939 (selected ECU manufacturers; request information)
warranty obligation unless expressly
stated in a written sales contract.
Example for customizable paper strips:
Alarm Messages:
X = Only available in X-Versions 350 = Only available in EasyGen 350/350X 0/1 = Off/On 10A Generator overfrequency
We appreciate your comments 01 Horn reset time [s] 52 Gen. under freq. [%] 72 Display level 11A Generator underfrequency
about the content of our publica- 10 Rated frequency [Hz] 53 Gen. under freq. [s] 80 Mains settling time [s] (350) 12A Generator overvoltage
11 Gen. rated volt [V] 54 Gen . over volt [%] 81 Mains over volt. [%] (350) 13A Generator undervoltage
tions. Please send comments 12 Mains rated volt [V](350) 55 Gen. over volt [s] 82 Mains under volt [%] (350) 14A Mains rotation field 350
including the document number 20 Fuel relay [0/1] 56 Gen. under volt [%] 83 Mains volt. hysteresis [%] (350) 20A Engine overspeed (X)
below to 21 Preglow time [s] 57 Gen. under volt [s] 84 Mains over frequency [%] (350) 21A Engine underspeed (X)
stgt-doc@woodward.com 30 Pickup [0/1] (X) 58 Eng. ovrspd. monit. [0/1] (X) 85 Mains under frequency [%] (350) 30A Start failure
31 Nom. speed [rpm](X) 59 Eng. over speed [rpm](X) 86 Mains freq. hysteresis [%] (350) 31A Unintended stop
32 No. pickup teeth (X) 60 Batt. under volt [V] 90 J1939 Device type (X) 40A Maintenance hours
© Woodward Governor 40 Cool down time [s] 61 Charge fail monit. [0/1] 91 J1939 Request send address (X) 50A Battery undervoltage
50 Gen. over freq. [%] 62 Charge fail level [V] 92 J1939 Receive device No. (X) 51A Charge failure
Company 51 Gen. over freq. [s] 71 Reset maint hours [0/1] 93 J1939 Monitoring [0/1] (X) 60A Discrete input 1
61A Discrete input 2
62A Discrete input 4
All Rights Reserved 63A Discrete input 5
64A J1939 Error (X)
37217C - 06/3/S