Micrologic 5.0P and 6.0P Electronic Trip Units


ENGLISH

v PLogic-2002-AA and Later

Instruction Bulletin
48049-137-05
Rev. 01, 07/2012
Retain for future use.

Micrologic 5.0P and 6.0P Electronic Trip Units

ENGLISH

Hazard Categories and Special


Symbols

48049-137-05
Rev. 01, 07/2012

Read these instructions carefully and look at the equipment to become


familiar with the device before trying to install, operate, service or maintain
it. The following special messages may appear throughout this bulletin or on
the equipment to warn of potential hazards or to call attention to information
that clarifies or simplifies a procedure.
The addition of either symbol to a Danger or Warning safety label
indicates that an electrical hazard exists which will result in personal injury if
the instructions are not followed.

ANSI

This is the safety alert symbol. It is used to alert you to potential personal
injury hazards. Obey all safety messages that follow this symbol to avoid
possible injury or death.

DANGER
IEC

DANGER indicates a hazardous situation which, if not avoided, will result


in death or serious injury.

WARNING
WARNING indicates a hazardous situation which, if not avoided, can
result in death or serious injury.

CAUTION
CAUTION indicates a hazardous situation which, if not avoided, can
result in minor or moderate injury.

NOTICE
NOTICE is used to address practices not related to physical injury. The
safety alert symbol is not used with this signal word.

NOTE: Provides additional information to clarify or simplify a procedure.

Please Note

Electrical equipment should be installed, operated, serviced, and


maintained only by qualified personnel. No responsibility is assumed by
Schneider Electric for any consequences arising out of the use of this
material.

FCC Notice

This equipment has been tested and found to comply with the limits for a
Class A digital device, pursuant to part 15 of the FCC Rules. These limits
are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This
equipment generates, uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the instruction manual, may cause
harmful interference to radio communications. Operation of this equipment
in a residential area is likely to cause harmful interference in which case the
user will be required to correct the interference at his own expense. This
Class A digital apparatus complies with Canadian ICES-003.

2-EN

20002012 Schneider Electric All Rights Reserved

SECTION 1:

Micrologic 5.0P and 6.0P Electronic Trip Units


Table of Contents

GENERAL INFORMATION

...................................................................................................................... 7
Introduction ................................................................................................. 7
Communications ......................................................................................... 7
Power and Control Settings ........................................................................ 7
Switch Settings ........................................................................................... 7
Micrologic 5.0P Trip Unit ....................................................................... 8
Micrologic 6.0P Trip Unit ....................................................................... 9
LSIG Protection ......................................................................................... 10
Long-Time Protection .......................................................................... 10
Short-Time Protection ......................................................................... 12
Instantaneous Protection ..................................................................... 13
Ground-Fault Protection for Equipment ............................................... 13
Micrologic Trip Unit Configuration ............................................................. 14
Control Power ...................................................................................... 14
External Power Supply ........................................................................ 15
Micrologic Setup ....................................................................................... 15
Advanced Protection ................................................................................. 16
Neutral Protection ................................................................................ 16
Alarms ................................................................................................. 17
Minimum (Under) and Maximum (Over) Demand Current and Voltage
Protection ............................................................................................ 18
Current or Voltage Unbalance Protection ............................................ 18
Reverse Power Protection (rPmax) ..................................................... 19
Minimum (Under) and Maximum (Over) Frequency Protection ........... 19
Load Shedding .................................................................................... 20
Phase Rotation Protection ................................................................... 20
M2C and M6C Programmable Contact Kits .............................................. 20
Zone-selective Interlocking ....................................................................... 21
Metering .................................................................................................... 21
Trip Unit Testing ........................................................................................ 21
Operation Counter .................................................................................... 21
Indicator Lights .......................................................................................... 22
Overload Indicator Light ...................................................................... 22
Trip Indicator Lights ............................................................................. 22
Test/Reset Button ..................................................................................... 22
Graphic Display Screen ............................................................................ 23
Contact Wear Indicator ............................................................................. 23

SECTION 2:

GRAPHIC DISPLAY NAVIGATION ................................................................................................................... 24


Graphic ..................................................................................................... 24
Bar Graph display and Menus .................................................................. 25
Metering Menu .................................................................................... 25
Maintenance Menu .............................................................................. 27
Protection Menu .................................................................................. 29

SECTION 3:

TRIP UNIT CONFIGURATION

.................................................................................................................... 31
Trip Unit Parameters Adjustment .............................................................. 31
M2C/M6C Programmable Contacts .................................................... 31
Micrologic Trip Unit Setup ................................................................... 34
Metering Setup .................................................................................... 38
Communication Module Setup ............................................................ 42
Switch Settings Adjustment ...................................................................... 43
Examples .................................................................................................. 45
Micrologic 5.0P Trip Unit ..................................................................... 45
Micrologic 6.0P Trip Unit ..................................................................... 45
Zone-Selective Interlocking (ZSI) .............................................................. 46
Trip Unit Operation Verification ................................................................. 47

20002012 Schneider Electric All Rights Reserved

3-EN

ENGLISH

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Table of Contents

48049-137-05
Rev. 01, 07/2012

ENGLISH

Trip Unit Resetting .................................................................................... 47


Equipment Ground-Fault Trip Functions Testing ...................................... 48
Trip Unit Status Check .............................................................................. 49
SECTION 4:

OPERATION

.................................................................................................................... 50
Metered Values ......................................................................................... 50
Current Levels ..................................................................................... 50
Voltage Levels ..................................................................................... 51
Power Levels ....................................................................................... 52
Energy Levels ...................................................................................... 53
Frequency ............................................................................................ 54
Trip Unit History ........................................................................................ 54
Trip History .......................................................................................... 54
Alarm History ....................................................................................... 55
Operation Counter ............................................................................... 55
Contact Wear ....................................................................................... 55
Protection Setup ........................................................................................ 56
Amperage Protection ........................................................................... 56
Voltage Protection ............................................................................... 59
Other Protection .................................................................................. 60
Current Load Shedding ....................................................................... 61
Power Load Shedding ......................................................................... 61

SECTION 5:

TRIP UNIT REPLACEMENT

.................................................................................................................... 62
Required Tools .......................................................................................... 62
Preparation ................................................................................................ 62
Record Switch Settings ....................................................................... 62
Circuit Breaker Disconnection ............................................................. 62
Circuit Breaker Accessory Cover Removal ......................................... 62
Rating Plug Removal ........................................................................... 63
Trip Unit Removal ................................................................................ 63
Trip Unit Replacement .............................................................................. 63
Battery Installation ............................................................................... 63
Trip Unit Installation ............................................................................. 64
Circuit Breaker Accessory Cover Replacement ........................................ 65
Trip Unit Installation Check ....................................................................... 66
Secondary Injection Testing ................................................................ 66
Primary Injection Testing ..................................................................... 66
Check Accessory Operation ................................................................ 66
Trip Unit Setup .......................................................................................... 66
Circuit Breaker Reconnection ................................................................... 66

SECTION 6:

ADJUSTABLE RATING PLUG REPLACEMENT .............................................................................................. 67


Remove Rating Plug ................................................................................. 67
Install New Rating Plug ............................................................................. 67

SECTION 7:

BATTERY REPLACEMENT

.................................................................................................................... 68
Circuit Breaker Disconnection ................................................................... 68
Accessory Cover Removal ........................................................................ 68
Withstand Module Shifting ........................................................................ 68
Battery Replacement ................................................................................. 68
Withstand Module Replacement ............................................................... 69
Accessory Cover Replacement ................................................................. 69
Circuit Breaker Reconnection ................................................................... 69

APPENDIX A: GRAPHIC DISPLAY FLOWCHARTS ................................................................................................................ 70


Metering Menu Flowchart .......................................................................... 70
4-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Table of Contents

APPENDIX B: DEFAULT SETTINGS AND TOLERANCES ...................................................................................................... 73


Default Settings ......................................................................................... 73
Metering Range and Accuracy .................................................................. 76
APPENDIX C: NETWORK/COM ACCESS

.................................................................................................................... 77
Remotely Readable Values ...................................................................... 77
List of Registers ........................................................................................ 80

APPENDIX D: TRIP UNIT VOLTAGE SUPPLY ARCHITECTURE ........................................................................................... 89


Minimum Voltage Protection ..................................................................... 89
Voltage Unbalance Protection .................................................................. 89
Loss of Multiple Phases ............................................................................ 90
APPENDIX E: TRIP UNIT SETTINGS

.................................................................................................................... 91

Index:

.................................................................................................................... 94

20002012 Schneider Electric All Rights Reserved

5-EN

ENGLISH

Maintenance Menu Flowchart ................................................................... 71


Protection Menu Flowchart ....................................................................... 72

Micrologic 5.0P and 6.0P Electronic Trip Units


Table of Contents

48049-137-05
Rev. 01, 07/2012

ENGLISH
6-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

Micrologic trip units provide adjustable tripping


functions on electronic trip circuit breakers. The
product name (A) specifies the level of
protection provided by the trip unit.
Micrologic 5.0P
Type of protection
2Basic IEC protection (LSO)
3Basic UL protection (LI)
5Selective protection (LSI)
6Selective protection plus ground fault
protection for equipment (LSIG)

Figure 1:

Micrologic Trip Unit


I

06134748

Introduction

A
B

AProduct Name
BTrip Indicators
CBattery Housing
DAdjustable Switches
ESwitch Cover
FSealing Tab
GAdjustable Rating Plug
HReset Button for Battery Status Check
and Trip Indicators
IExternal Terminal Block Connection

H
0P

5.
logic
Micro

C
F

G
alarm

time
long

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

Trip unit series


0Indicates the first version
Type of measurement
NoneProvides protection only
AProvides protection plus ammeter measurements
PProvides protection plus power measurements
HProvides protection plus harmonic metering

ENGLISH

Section 1General Information

tr

(s) 4

2
1
.5

8 12
16
20
24
Ir
at 6

Micrologic trip units are field replaceable to allow


for upgrading of the trip unit in the field. For
complete information on available circuit breaker
models, frame sizes, interrupting ratings, sensor
plugs, rating plugs and trip units, see the product
catalog.

Communications

Micrologic trip units can communicate with other devices using Modbus
through the Circuit Breaker Communication Module (BCM). For information
on the communication feature, see the product catalog and Modbus
Communications System, Data Bulletin 0613IB1201.

Power and Control Settings

Using the graphic display screen and keypad on the trip unit, trip unit
options can be set or system measurements checked. See Section 2
Graphic Display Navigation for more information. System measurements
can also be checked using the System Manager Software (SMS), Version
3.2 or later, or other network system management software.

Switch Settings

On the face of the trip unit are adjustable switches to allow changing of the
LSI or LSIG trip characteristics of the trip unit. Trip units are shipped with the
long-time pickup switch set at 1.0 and all other trip unit switches set at their
lowest settings. All advanced protection settings are turned off.
Fine switch adjustments can be made with the navigation keys. See
page 44.

20002012 Schneider Electric All Rights Reserved

7-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

48049-137-05
Rev. 01, 07/2012

The Micrologic 5.0P trip unit provides selective (LSI) protection and power
measurement.

A. Graphic display screen

Figure 2:

5.0P Trip Unit

B. Protection menu button*


D. Metering menu button*
E. Down button
F. Up button

Micrologic 5.0 P

N 1 2 3

H. Long-time pickup (Ir) switch

100

Long-time delay (tr) switch

t
50

K. Short-time delay (tsd) switch

B
D

N. Long-time pickup overload indicator light

P. Self-protection and advanced-protection


indicator light
Q. Short-time or instantaneous trip indicator
light
R. Long-time trip indicator light

tr

M. Test plug receptacle


O. Reset button for battery status check and trip
indicator LED

Ir

06134751

J. Short-time pickup (Isd) switch


L. Instantaneous pickup (Ii) switch

4260A

G. Enter button
I.

R Q

C. Maintenance menu button*


06134749

ENGLISH

Micrologic 5.0P Trip Unit

Isd
tsd

Ii

F
H

G
I
J

Ir
.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

Ir

Isd

Ii

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
8
2
1.5
10
x Ir
setting

K
L

long time

tsd
(s)

Ii

.4 .4 .3

.3
.2
.1
on

.2
.1
0
2
I t off

4
3

6 8 10
12
15
off
2
x In

delay

*Button includes an LED indicating the active menu.

8-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

The Micrologic 6.0P trip unit provides selective and ground-fault protection
for equipment (d 1200 A) (LSIG) and power measurement.

A. Graphic display screen

Figure 3:

6.0P Trip Unit

B. Protection menu button*

V U T S
06134750

C. Maintenance menu button*


E. Down button
F. Up button

4260A
100

Long-time delay (tr) switch

J. Short-time pickup (Isd) switch


B

S. Self-protection and advanced-protection


indicator light
T. Ground-fault trip indicator light

Isd

Ii

t
06134752

N. Ground-fault protection delay (tg) switch

R. Reset button for battery status check and trip


indicator LED

Ir

M. Ground-fault protection pickup (Ig) switch

Q. Long-time pickup overload indicator light

Ii
0

50

K. Short-time delay (tsd) switch

P. Ground-fault push-to-trip button

Isd
tsd

N 1 2 3

H. Long-time pickup (Ir) switch

O. Test plug receptacle

Ir
tr

G. Enter button

L. Instantaneous pickup (Ii) switch

Micrologic 6.0 P

06134751

D. Metering menu button*

I.

ENGLISH

Micrologic 6.0P Trip Unit

I2t on

F
H

G
I
J

.7
.6
.5
.4

.8

x In

L
N

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

tg

D
C
B
A

I2t off

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Ig

Ig

@ 6 Ir

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

on

I t

off

delay

. 4 .4 . 3
.2
.3
.1
.2
.1 2 0

(s)

on

I t

4
3

6 8 10
12
15
off
2
x In
test

tg
F
G
H
J

Ii

(s)

setting

long time

Ir

off

Ig

P
O

ground fault

U. Short-time or instantaneous trip indicator


light
V. Long-time trip indicator light

*Button includes an LED indicating the active menu.

20002012 Schneider Electric All Rights Reserved

9-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

48049-137-05
Rev. 01, 07/2012

LSIG Protection

Long-time protection protects equipment


against overloads.

NOTE: Micrologic trip units are powered from the circuit to always
provide fault protection. All other functions (display, metering,
communications, etc.) require external power. See page 15 for more
information.

Figure 4:

Long-Time Protection Switches

Micrologic 5.0P Trip Unit

Long-time pickup (Ir) (A) sets the


maximum current level based on sensor
plug rating (In) which the circuit breaker
will carry continuously. If current exceeds
this value, circuit breaker will trip after the
preset time delay. The long-time pickup
(Ir) is adjustable from 0.41.0 times the
circuit breaker sensor plug rating (In) (D).

Micrologic 6.0P Trip Unit

06134754

Long-time protection is standard on all trip


units.

06134753

ENGLISH

Long-Time Protection

long time

Ir
.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

setting

Ir
.7
.6
.5
.4

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd
(s)

Ii

.4 .4 .3

.3
.2
.1
on

.2
.1

4
3

0
2
I t off

C
alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

6 8 10
12
15
off
2
x In

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

D
C
B
A

on

I t

off

4
3

6 8 10
12
15
off
2
x In

delay

tg
F
G
H
J

Ii

(s)

setting

delay

Ig

Long-time delay (tr) (B) sets the length of


time that the circuit breaker will carry an
overcurrent below the short-time or
instantaneous pickup current level before
tripping. Two options are available:

long time

(s)

test

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

ground fault

In 2000 A

In 2000 A

Standard I2t long-time delay curve.


See Table 1 for I2t long-time delay
settings.
Idmtl (inverse definite minimum time
lag) long-time delay curves vary in
slope to enhance selectivity.

Table 1:

Micrologic Trip Unit I2t Long-Time Delay Values

Option Description

Curve

Setting1

Long-Time Delay in Seconds2

DT

Constant

tr at 1.5 x Ir

12.5

25

50

100

200

300

400

500

600

tr at 6 x Ir

0.5

12

16

20

24

0.69

1.38

2.7

5.5

8.3

11

13.8

16.6

SIT

Definite time
Standard inverse time

0.5

VIT

Very inverse time

It

tr at 7.2 x Ir

EIT

Extremely inverse time

I2t

HVF

High-voltage fuse compatible I4t

The overload indicator light (C) indicates


that the long-time pickup threshold Ir has
been exceeded.

For Masterpact NT and NW circuit


breakers, sensor value (In) can be
changed by replacing sensor plug (D)
located below the trip unit. For further
information, see the instructions packed
with the sensor plug replacement kit.

Neutral protection is not available when


Idmtl protection is selected.

10-EN

0.34

Ir = In x long-time pickup. In = sensor rating. Trip threshold between 1.05 and 1.20 Ir.
2
Time-delay accuracy +0/-20%.
3
When tsd is set to 0.4 off, then tr = 0.5 instead of 0.34.

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

The Idmtl selections do not utilize the


same thermal imaging feature as the I2t
long-time protection function. Both the
basic long-time protection and Idmtl EIT
are I2t curves, but the different thermal
imaging features result in different system
performances. For welding applications it
is recommended the basic I2t long-time
protection be used to ensure expected
system performance.
Both long-time pickup and long-time delay
are located on the field-replaceable
adjustable rating plug. To change settings
to more precisely match the application,
various rating plugs are available. For
instructions on replacing the rating plug,
see Section 6Adjustable Rating Plug
Replacement.

Table 2:

Option Setting1
tr at 1.5 x Ir

NOTE: If checking trip times, wait a minimum


of 15 minutes after circuit breaker trips before
resetting to allow the thermal imaging to reset
completely to zero or use a test kit to inhibit
the thermal imaging.

20002012 Schneider Electric All Rights Reserved

Long-Time Delay in Seconds


0.52

Tolerance
12

16

20

24

+0/-20%

tr at 6 x Ir

0.52

12

16

20

24

+0/-20%

tr at 7.2 x Ir

0.52

12

16

16.6

16.6

+0/-20%

tr at 10 x Ir

0.52

12

16

16.6

16.6

+0/-20%

tr at 1.5 x Ir

1.9

3.8

7.6

15.2

30.4

45.5

60.7

75.8

91

+0/-30%

tr at 6 x Ir

0.7

12

16

20

24

+0/-20%

tr at 7.2 x Ir

0.7

0.88

1.77

3.54

7.08

10.6

14.16 17.7

21.2

+0/-20%

0.8

1.43

2.86

5.73

8.59

11.46 14.33 17.19 +0/-20%

DT

SIT
2

tr at 10 x Ir

0.7

tr at 1.5 x Ir

1.9

7.2

14.4

28.8

57.7

86.5

115.4 144.2 173.1 +0/-30%

tr at 6 x Ir

0.7

12

16

20

tr at 7.2 x Ir

0.7

0.81

1.63

3.26

6.52

9.8

13.1

16.34 19.61 +0/-20%

tr at 10 x Ir

0.72

0.75

1.14

2.28

4.57

6.86

9.13

11.42 13.70 +0/-20%

tr at 1.5 x Ir

12.5

25

50

100

200

300

400

500

24

+0/-20%

VIT

Long-time protection uses true RMS


measurement.

Thermal imaging provides continuous


temperature rise status of the wiring, both
before and after the device trips. This allows
the circuit breaker to respond to a series of
overload conditions which could cause
conductor overheating, but would go
undetected if the long-time circuit was
cleared every time the load dropped below
the pickup setting or after every tripping
event.

Micrologic Trip Unit Idmtl Long-Time Delay Values

600

+0/-30%

tr at 6 x Ir

0.7

12

16

20

24

+0/-20%

tr at 7.2 x Ir

0.72

0.69

1.38

2.7

5.5

8.3

11

13.8

16.6

+0/-20%

tr at 10 x Ir

0.72

0.73

0.73

1.41

2.82

4.24

5.45

7.06

8.48

+0/-20%

tr at 1.5 x Ir

164.5 329

658

1316 2632 3950 5265 6581 7900 +0/-30%

EIT

tr at 6 x Ir

0.7

12

16

20

24

tr at 7.2 x Ir

0.72

0.73

1.13

1.42

3.85

5.78

7.71

9.64

11.57 +0/-20%

tr at 10 x Ir

0.72

0.72

0.73

0.73

1.02

1.53

2.04

2.56

3.07

HVF

+0/-20%

+0/-20%

Ir = In x long-time pickup. In = sensor rating. Trip threshold between 1.05 and 1.20 Ir.
Tolerance = +0/-60%
3
Tolerance = +0/-40%
2

11-EN

ENGLISH

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

Short-Time Protection

48049-137-05
Rev. 01, 07/2012

Figure 5:

Short-Time Protection Switches

long time

Ir
.7
.6
.5
.4

Short-time protection is standard on 5.0P


and 6.0P trip units.
The short-time pickup (Isd) (A) sets current
level (below instantaneous trip level) at
which circuit breaker will trip after the preset
time delay.

With I2t off selected, fixed time delay is


provided.
2t

I2t

With I on selected, inverse time


protection is provided up to 10 x Ir.
Above 10 x Ir, fixed time delay is
provided.

Intermittent currents in the short-time tripping


range which do not last sufficiently long to
trigger a trip are accumulated and shorten
the trip delay appropriately.

Short-time protection can be zone-selective


interlocked (ZSI) with upstream or
downstream circuit breakers. Setting tsd to
the 0 setting turns off zone-selective
interlocking.

Short-time protection uses true RMS


measurement.

Short-time pickup and delay can be adjusted


to provide selectivity with upstream or
downstream circuit breakers.

.8

x In

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

setting

long time

Ir
.7
.6
.5
.4

@ 6 Ir

instantaneous

short time

tsd
(s)

.3
.2
.1
on

.2
.1
2

I t

0
off

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

Ii

.4 . 4 .3

6 8 10
4
12
3
15
off
2
x In

delay

D
C
B
A

tsd
(s)

Ii

. 4 .4 .3

.3
.2
.1
on

setting

Ig

The short-time delay (tsd) (B) sets the length


of time that the circuit breaker will carry an
overcurrent above the short-time pickup
current level before tripping.
The I2t on/I2t off option provides improved
selectivity with downstream protective
devices:

06134754

06134753

ENGLISH

Micrologic 6.0P Trip Unit

Micrologic 5.0P Trip Unit

Short-time protection protects equipment


against short circuits.

.2
.1
2

I t

0
off

4
3

6 8 10
12
15
off
2
x In

delay

test

tg

.4 . 4 . 3
.2
.3
.1
.2
.1 2 0

(s)

F
G
H
J

on

I t

off

ground fault

In 2000 A

Table 3:

In 2000 A

Micrologic Trip Unit Short-Time Delay Values

Setting

Short-Time Delay

I2t off (ms at 10 Ir) (seconds)

0.1

0.2

0.3

0.4

I t on (ms at 10 Ir) (seconds)

0.1

0.2

0.3

0.4

tsd (min. trip) (milliseconds)

20

80

140

230

350

tsd (max. trip) (milliseconds)

80

140

200

320

500

NOTE: Use I2t off with ZSI for proper


coordination. Using I2t on with ZSI is not
recommended as the delay in the upstream
device receiving a restraint signal could result in
the trip unit tripping in a time shorter than the
published trip curve.

12-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Figure 6:

Instantaneous Protection Switches

Micrologic 6.0P Trip Unit


06134754

06134753

Micrologic 5.0P Trip Unit

Instantaneous protection protects equipment


against short circuits with no intentional time
delay.

long time

Ir
.7
.6
.5
.4

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

Instantaneous protection (Ii) (A) is standard


on all trip units.
Instantaneous protection is based on the
circuit breaker sensor rating (In).

long time

Ir
.7
.6
.5
.4

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd
(s)

0
off

on

setting

6 8 10
4
12
3
15
off
2
x In

.2
.1

.3
.2
.1

I t

Instantaneous protection uses peak current


measurement.

When instantaneous protection switch is set


to off, the instantaneous protection is
disabled.

x In

@ 6 Ir

instantaneous

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

delay

tsd
(s)

Ig
D
C
B
A

Ii

.4 .4 .3

.3
.2
.1
on

setting

Circuit breaker open command is issued as


soon as threshold current is exceeded.

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

short time

Ii

. 4 .4 .3

ENGLISH

Instantaneous Protection

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

.2
.1
2

I t

4
3

0
off

delay

tg
(s)

F
G
H

test

.4 .4 .3

.3
.2
.1

6 8 10
12
15
off
2
x In

on

I t

.2
.1
0
off

ground fault

In 2000 A

In 2000 A

Table 4:

Micrologic Instantaneous Values

Setting

Interruption Current

Ii (= In x..)

10

12

15

off

Ii = instantaneous
In = sensor rating
Pickup accuracy 10%

Ground-Fault Protection for Equipment

Figure 7:

Ground-Fault Protection Switches

Micrologic 6.0P Trip Unit

06134754

Equipment ground-fault protection protects


conductors against overheating and faults from
ground-fault currents (d1200 A).

long time

Ir
.7
.6
.5
.4

Neutral protection and equipment groundfault protection are independent and can
operate concurrently.

NOTE: Use I2t off with ZSI for proper


coordination. Using I2t on with ZSI is not
recommended as the delay in the upstream
device receiving a restraint signal could result in
the trip unit tripping in a time shorter than the
published trip curve.

20002012 Schneider Electric All Rights Reserved

@ 6 Ir

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

Ground-fault pickup (Ig) (A) sets ground


current level where circuit breaker will trip
after the preset time delay.

Equipment ground-fault protection can be


zone-selective interlocked (ZSI) with
upstream or downstream circuit breakers.
Setting the ground-fault delay (tg) to the 0
setting turns off zone-selective interlocking.

x In

instantaneous

short time

Equipment ground-fault protection is


standard on 6.0P trip units.

Ground-fault delay (tg) (B) sets the length of


time that the circuit breaker will carry a
ground-fault current above the ground-fault
pickup current level before tripping.

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

on

setting

Ig
D
C
B
A

A
B

I t

off

delay

tg
F
G
H
J

Ii

(s)

(s)

4
3

6 8 10
12
15
off
2
x In
test

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

ground fault

In 2000 A

Table 5:

Micrologic Trip Unit Ground-Fault Pickup Values

Ig (= In x....)

In d 400 A

0.3

0.3

0.4

0.5

0.6

0.7

0.8

0.9

400 A < In d 1200 A

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

In > 1200 A

500 A 640 A 720 A 800 A 880 A 960 A 1040 A 1120 A 1200 A

In = sensor rating.
Ig = ground-fault pickup.

Table 6:

Micrologic Trip Unit Ground-Fault Delay Values

Setting

Ground-Fault Delay

I2t off (ms at In) (seconds)

0.1

0.2

0.3

0.4

I2t on (ms at In) (seconds)

0.1

0.2

0.3

0.4

tsd (min. trip) (milliseconds)

20

80

140

230

350

tsd (max. trip) (milliseconds)

80

140

200

320

500

13-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

48049-137-05
Rev. 01, 07/2012

Micrologic Trip Unit Configuration


ENGLISH

Control Power

The P trip unit is designed to be used with an external 24 Vdc power supply.
The large LCD display used by the P trip unit requires too much current to
be powered by current flow through the circuit breaker.
The P trip unit has a circuit voltage power supply which will power the trip
unit when there is approximately 150 Vac or more between two phases. The
standard configuration for the voltage probes inside the circuit breaker is at
the bottom connections. If the circuit breaker is open in a top fed application,
there is no voltage at the bottom of the circuit breaker and the trip unit will
not be powered.
The following will be powered and functional even if the trip unit is not
externally powered:

Fault protection for LSIG functions. The P trip unit is fully circuit powered
for fault protection.

LED trip indication (powered by an onboard battery). The batterys only


function is to provide LED indication if all other power is off.

Ground-fault push-to-trip button works for testing ground fault when the
trip unit is powered by the circuit voltage power supply. The ground-fault
push-to-trip is also functional if a Hand-Held Test Kit or Full-Function
Test Kit is powering the trip unit.

The following will be powered and functional with external power:

14-EN

All of the above functions which are functional without external power.

All metering, monitoring, and history logs are functional.

Modbus communications are functional, using a separate 24 Vdc power


supply for the circuit breaker communications module. This separate 24
Vdc power supply is required to maintain the isolation between the trip
unit and communications.

The ground-fault push-to-trip is also functional if a Hand-Held Test Kit or


Full-Function Test Kit is powering the trip unit.

LCD display and backlight are functional. Backlight intensity is not


controlled or adjustable, and may be different from one trip unit to
another.
Communications from the trip unit to M2C and M6C programmable
contact modules are powered by a 24 Vdc power supply at F1 and F2.
The M6C also required an external 24 Vdc power supply.

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

The trip unit can be powered by:

CAUTION
HAZARD OF SHOCK, ARC FLASH OR
EQUIPMENT DAMAGE
Trip unit and communication module must use
separate power supplies.
Failure to follow this instruction can result
in personal injury or equipment damage.

24 Vdc external power supply (recommended).


Over 150 V on the bottom circuit breaker terminals on two phases.
Over 150 V on the top circuit breaker terminals with external voltage
option.

Table 7:

Power Supply Specifications

Function

Specification

Power for Trip Unit Alone

24 Vdc, 50 mA

Minimum Input-to-Output Isolation

2400 V

Output (Including Max. 1% Ripple)

5%

Dielectric Withstand (Input/Output)

3 kV rms

Connections

Connections UC3
F1 (-)
F2 (+)

24 Vdc

Power supply is used for:


Graphic screen display when the circuit breaker is open and top fed.
Option of linking an alarm to a relay output.
To maintain date and time when the circuit breaker is open.

Micrologic Setup
NOTE: If trip unit is connected to a
communication network which provides date
and time synchronization, date/time cannot be
set from trip unit.
See page 34 for step-by-step instructions to set
up the Micrologic trip unit.
See Section 3 on page 31 for other trip unit
configurations instructions.

20002012 Schneider Electric All Rights Reserved

Use the Maintenance Menu by pressing the wrench key.


Figure 8:
06133330

Micrologic Setup

Micrologic Setup

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Micrologic
setup
Language

Selects display language

Date/time

Sets date and time

Breaker
selection

Enters information about the circuit breaker


in which the trip unit is installed

Power
sign

Selects power sign direction for


metering menus

VT ratio

Selects the voltage ratio; if no external voltage


transformer is present, select 690:690

System
frequency

Selects the system frequency

15-EN

ENGLISH

External Power Supply

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

48049-137-05
Rev. 01, 07/2012

Advanced Protection

NOTICE

Neutral protection protects neutral conductors


against overheating.

HAZARD OF EQUIPMENT DAMAGE

For a three-pole circuit breaker, neutral


protection is possible if a neutral current
transformer is used.

If a four-pole circuit breaker neutral pole switch is set to 4P3D setting, the
current in the neutral must not exceed the rated current of the circuit
breaker.

Adjust the neutral using the trip unit


keypad.

For a three-pole circuit breaker with oversize neutral protection (1.6N),


select the appropriate oversize neutral current transformer.

Possible settings are OFF, N/2, N, or


1.6N.

Failure to follow this instruction can result in equipment damage.

Factory setting is OFF.


Oversize neutral protection (1.6N)
requires use of the appropriate oversize
neutral current transformer.

For a four-pole circuit breaker, set system


type using the circuit breaker neutral selector
dial (see Figure 9).
Make fine adjustments using the trip unit
keypad, with the circuit breaker dial
setting providing the upper limit for
adjustment.

Figure 9:

Four-Pole Circuit Breaker Neutral Selector Dial


Neutral Protection Settings for
Four-Pole Circuit Breaker

06134824

ENGLISH

Neutral Protection

4D
4P

Factory setting is 4P4D.

Neutral protection conductor type has four


possible settings:
OffNeutral protection is turned off.
N/2Neutral conductor capacity is onehalf that of the line conductors.
NNeutral conductor capacity is the
same as that of the line conductors.
1.6NNeutral conductor capacity is 1.6
times that of the line conductors. (Threepole circuit breaker only.)

Table 8:

Setting

Circuit Breaker
Selector Dial

Available
Keypad Setting

4P 3D

Off, N/2, N

3P N/2

N/2

4P 4D

N/2, N

Micrologic Trip Unit Conductor Type

Long-Time
Pickup

Short-Time
Pickup

Instantaneous

Ground-Fault
Pickup

Trip Unit Neutral Trip Unit Neutral Trip Unit Neutral Trip Unit Neutral
OFF

Ir

None

Isd

None

Ii

None

Ig

None

N/2

Ir

1/2 Ir

Isd

1/2 Isd

Ii

Ii

Ig

Ig

Ir

Ir

Isd

Isd

Ii

Ii

Ig

Ig

1.6N

Ir

1.6 x Ir

Isd

1.6 x Isd* Ii

Ii

Ig

Ig

*In order to limit the range, limited to 10 x In

16-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

Alarms

Table 9:

Alarms can be enabled or disabled for protection


or load shedding.

Alarm

Menu

Symbol

Alarm

Trip

Long-time pickup

Current protection

Ir

Short-time pickup

Current protection

Isd

Instantaneous pickup

Current protection

Ii

When an alarm occurs, an entry is made in


the alarm log.

For a trip unit to activate an alarm, both the


pickup level and time delay must be
exceeded. Therefore for LSIG protection and
advanced protection programmed to trip the
circuit breaker, the trip unit will not activate
the alarm until the circuit breaker trips. (For
example, if a relay is programmed for the
long-time pickup Ir, the trip unit will not signal
an alarm when the long-time overload
indicator lights. The trip unit will only activate
the alarm once the long-time overload
exceeds the time delay and trips the circuit
breaker.)

Link alarms to a visual or audible signal by


programming the optional M2C or M6C
module contacts, when an external 24 V
power supply is used on the trip unit.
View alarms by:
History logs menu
The network system management
software

Ground-fault current

Current protection

Ground-fault alarm

Current protection

Al

Current unbalance

Current protection

Iunbal

Phase A maximum demand current

Current protection

Ia max

Phase B maximum demand current

Current protection

Ib max

Phase C maximum demand current

Current protection

Ic max

Neutral maximum demand current

Current protection

In max

Minimum voltage (undervoltage)

Voltage protection

Vmin

Maximum voltage (overvoltage)

Voltage protection

Vmax

Voltage unbalance

Voltage protection

Vunbal

Reverse power

Other protection

rPmax

Fmin

Minimum frequency (underfrequency) Other protection


Maximum frequency (overfrequency)

Other protection

Fmax

Phase rotation

Other protection

) rotation

Current load shedding

Load shedding I

Ished

Power load shedding

Load shedding P

Pshed

M2C/M6C contact characteristics:


Minimum load of 100 mA/24 V
Breaking capacity at a 0.7 power factor

240 Vac

5A

380 Vac

3A

24 Vdc

1.8 A

48 Vdc

1.5 A

125 Vdc

0.4 A

250 Vdc

0.15 A

When several alarms are activated, screen


response/refresh time will be slower.

See Appendix B for default and range values.

20002012 Schneider Electric All Rights Reserved

17-EN

ENGLISH

Trip Unit Alarms

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

Figure 10:

Minimum/Maximum Protection Curves

Pickup time delay (B) is set to start timing


once the pickup value has been passed.

Dropout value (C) is set to deactivate the


alarm and/or contact.

Dropout time delay (D) is set to start timing


once the dropout value has been passed.

Minimum (under) voltage protection (Vmin) is


activated when any line-line voltage is below
the minimum voltage setting.

Maximum (over) voltage protection (Vmax) is


activated when any line-line voltage is above
the maximum voltage setting.

Vmin has a dropout value t pickup value.

Ground-fault alarm on the 5.0P and 6.0P trip


unit is based on true rms value of the ground
current.

Ground-fault trip on the 6.0P trip unit is


based on true rms value of the ground
current.

Do not set undervoltage protection below


80%*

Minimum Protection

Pickup value (A) is set to activate an alarm


or trip.

I/VLL

VLL

Vmax has a dropout value d pickup value.


If current or voltage protection trips the
circuit breaker, the circuit breaker cannot be
reset until the current or voltage problem
which caused the trip is corrected.

Current or Voltage Unbalance


Protection
This protection applies to unbalanced values for
the three-phase currents and voltages.

Unbalance values are based on the true


RMS values of the three-phase currents.

Do not set Vunbal above 20%*.

06134770

Maximum Protection

Provides pickup and dropout values for alarm,


contacts or tripping for current and voltage
values. (There is no minimum for current.)

Figure 11:
06134769

ENGLISH

Minimum (Under) and Maximum (Over)


Demand Current and Voltage Protection

48049-137-05
Rev. 01, 07/2012

Current or Voltage Unbalance Protection

max

Iavg
or
Vavg
0

I1

I2

I +I +I
Iavg = a b c
3

V + Vb + Vc
Vavg = a
3

Iunbal = |'max|
Iavg

Vunbal = |'max|
Vavg

I3

Do not use voltage unbalance protection to


determine the loss of multiple phases*.

For an explanation of system protection behavior, see Appendix D

18-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Figure 12:

Reverse power protection applies a trip


curve based on the total actual power value
(A) over all three phases.

A time delay (B) starts timing if the total


actual power of the three phases is not
flowing in the defined direction and if it
exceeds a reverse power threshold.

The power direction is defined during trip unit


setup.

Minimum (Under) and Maximum (Over)


Frequency Protection

06134771

Reverse power protection protects alternators


against absorption of the total actual power over
all three phases in the event that a drive motor
fails.

Reverse Power Protection

ENGLISH

Reverse Power Protection (rPmax)

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

A
B

Figure 13:

Minimum/Maximum Frequency Curves

06133266

Minimum Protection

Provides pickup and dropout values for


frequency.

Pickup time delay (B) is set to start timing


once the pickup value has been passed.

Dropout value (C) is set to deactivate the


alarm and/or contact.

Dropout time delay (D) is set to start timing


once the dropout value has been passed.

Fmin has a dropout value t pickup value.

Pickup value (A) is set to activate an alarm


or trip.

Maximum Protection

C
D

Fmin

Fmax

Fmax has a dropout value d pickup value.


When system frequency is set to 400 Hz, the
frequency protection is disabled.

20002012 Schneider Electric All Rights Reserved

19-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

Load Shedding
t

Long-time
Protection
Curve

C
A
D

Load shedding is defined by a threshold and


time delay:

AActivation threshold
0

BActivation time delay

CDropout threshold
DDropout time delay

Current load shedding is connected to the I2t


or Idmtl long-time delay values.

Current load shedding cannot be activated if


Long-time OFF rating plug is installed.

Phase Rotation Protection

M2C and M6C Programmable


Contact Kits
One or more alarms can be activated using an
optional M2C or M6C programmable contact kit.
The M2C contact kit provides two form A
contacts with common neutral. The M6C contact
kit provides six form C contacts. Each contact
can be programmed through the trip unit for one
alarm condition.

Protects the circuit when two of the three phases are reversed.

If one of the phases is down, this protection is inactive.

Do not use phase rotation protection to determine the loss of multiple


phases in delta connected systems.

Options are ABC or ACB.


When system frequency is set to 400 Hz, phase rotation protection is
disabled.

Figure 15:

M2C: 24 Vdc power


supplied by trip unit

20-EN

M6C: external 24 Vdc power supply required

Characteristics for M2C/M6C


V
Programmable Contacts

S1 S2

A 24 Vdc, 5 W auxiliary power supply is required


for operation of trip unit/M2C or M6C contact kit
combination.

Minimum Load

471

NOTE: Trip unit and communication modules


(BCM and CCM) must use separate power
supplies. The M2C and M6C contact kits can
share the trip unit auxiliary power supply.

M2C/M6C Wiring Diagrams

06133934

Power load shedding depends on the flow


direction set during trip unit setup.

484

474

ENGLISH

Load shedding does not trip the circuit breaker,


but may be used to activate an alarm linked to
an M2C or M6C contact (controlling non-priority
network loads).

Figure 14:
06134771

Load Shedding

48049-137-05
Rev. 01, 07/2012

24 Vdc

100 mA

240 Vac

5A

380 Vac

3A

Breaking Capacity at a

24 Vdc

1.8 A

Power Factor (p.f.) of 0.7

48 Vdc

1.5 A

125 Vdc

0.4 A

250 Vdc

0.15 A

20002012 Schneider Electric All Rights Reserved

Zone-selective Interlocking
Short-time and ground-fault protection can be
interlocked to provide zone-selective
interlocking.
Control wiring links several trip units in the
distribution network and in the event of a fault, a
trip unit will obey the set delay time only if
receiving a signal from a downstream trip unit.

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

NOTE: Use I2t off with ZSI for proper coordination. Using I2t on with ZSI is
not recommended as the delay in the upstream device receiving a restraint
signal could result in the trip unit tripping in a time shorter than the published
trip curve.
NOTE: Setting short-time delay (tsd) or ground-fault delay (tg) to the 0
setting will eliminate selectivity for that circuit breaker.

If the trip unit does not receive a signal, tripping


will be instantaneous (with no intentional delay).
The fault is cleared instantaneously by the
nearest upstream circuit breaker.

Thermal stresses (I2t) in the network are


minimized without any effect on the correct
time delay coordination of the installation.

Figure 16 shows circuit breakers 1 and 2 zoneselective interlocked.

A fault at A is seen by circuit breakers 1 and


2. Circuit breaker 2 trips instantaneously and
also informs circuit breaker 1 to obey set
delay times. Thus, circuit breaker 2 trips and
clears the fault. Circuit breaker 1 does not
trip.

A fault at B is seen by circuit breaker 1.


Circuit breaker 1 trips instantaneously since
it did not receive a signal from the
downstream circuit breaker 2. Circuit breaker
1 trips and clears the fault. Circuit breaker 2
does not trip.

Figure 16:

Zone-selective Interlocking

06133376

Metering

The Micrologic P trip unit provides continuous metering of system values.


Metered values can be checked using the graphic display screen or network
system management software.

Trip Unit Testing

Trip unit LSIG functions can be tested using primary injection testing or
secondary injection testing. Test trip unit using the full-function test kit or
hand-held test kit. (See Trip Unit Installation Check on page 66 for more
information.)

Operation Counter

The circuit breaker communication module is required to display the total


number of times the circuit breaker has opened since initial installation and
since the last reset and the day/time of last reset

20002012 Schneider Electric All Rights Reserved

21-EN

ENGLISH

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

48049-137-05
Rev. 01, 07/2012

Indicator Lights
Figure 17:

Overload Indicator Light


Micrologic 6.0P Trip Unit
06134754

The overload indicator light (A) lights when the Ir


long-time pickup level has been exceeded.

06134753

Micrologic 5.0P Trip Unit


long time

Ir
.7
.6
.5
.4

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

long time

Ir
.7
.6
.5
.4

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

Ii

(s)

on

setting

I t

4
3

off

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

6 8 10
12
15
off
2
x In

delay

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

D
C
B
A

on

I t

off

delay

tg
F
G
H
J

Ii

(s)

setting

Ig

(s)

4
3

6 8 10
12
15
off
2
x In
test

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

ground fault

Trip Indicator Lights

NOTICE

A trip indicator light on the trip unit will light when


the circuit breaker trips. If the trip unit has
auxiliary power connected, the trip unit will
display information about the trip.

HAZARD OF EQUIPMENT DAMAGE


If the circuit breaker remains closed and the Ap light remains lit after the
reset, open the circuit breaker and contact the sales office.

The trip indicator light will remain lit until it is


reset by pressing the reset button (A). Cause of
trip should be corrected before resetting.

Isd/Ii trip indicator light (C) lights when shorttime pickup (Isd) or instantaneous pickup (Ii)
signals the circuit breaker to trip.

Figure 18:

Trip Indicator Lights

B C
06134251

Ir trip indicator light (B) lights when long-time


pickup (Ir) signals the circuit breaker to trip.

Failure to follow this instruction can result in equipment damage

E A

Micrologic 6.0 P

Ig trip indicator light (D) lights when ground-fault


pickup (Ig) signals the circuit breaker to trip.
Ap self-protection/advanced-protection indicator
light (E) lights when the advanced protection
features cause a trip to occur, the trip unit
overheats, the instantaneous override value is
exceeded or a trip unit power supply failure
occurs.

NOTE: In cases where a number of causes may result in tripping, the LED
signalling the last cause is the only one to remain on.

Test/Reset Button

Figure 19:

The test/reset button (A) must be pressed after a


trip to reset the fault information on the graphic
display and clear the trip indicator light.

22-EN

06134251

ENGLISH

Overload Indicator Light

Reset Button

Micrologic 6.0 P

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Trip unit must be powered for graphic display


screen to operate. The trip unit is powered if:

circuit breaker is on and has more than


150 V of load voltage on two phases (circuit
breaker is closed or bottom fed).
the full-function or hand-held test kit is
connected and on.

the 24 Vdc external power supply is


connected.

an external voltage tap is installed and


voltage of more than 150 V is present on two
phases.

Contact Wear Indicator

20002012 Schneider Electric All Rights Reserved

Graphic Display Screen

ENGLISH

The graphic display screen (A) shows the trip


unit settings and information. Navigation buttons
(B) are used to display and modify items on the
screen. Default display shows current levels.

Figure 20:
06134749

Graphic Display Screen

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 1General Information

Micrologic 5.0 P

4260A

N 1 2 3
100

50

The trip unit keeps track of the circuit breaker contact wear when a
Masterpact circuit breaker type is selected. The amount of wear on the
circuit breaker contacts can be transferred when a trip unit is replaced.
(External trip unit power supply is required.)

23-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 2Graphic Display Navigation

48049-137-05
Rev. 01, 07/2012

Section 2Graphic Display Navigation


ENGLISH

Graphic

Figure 21:

Graphic Display

Display

4260A

Graphic display (A) functions if the trip unit is


connected to a 24 Vdc external power supply or
there is 150 V on at least two phases. Current
alone (from primary injection test set or electrical
system) will power the LSIG protection
functions, but will not power the display.

N 1 2 3

Navigation buttons (B):

100

50

Metering Menu ButtonProvides access


to metering menus
Maintenance Menu ButtonProvides
access to maintenance menus
Protection Menu ButtonProvides
access to protection menus
Down ButtonMoves cursor downward
or decreases setting value
Up ButtonMoves cursor upward or
increases setting value
Enter ButtonSelects an option from a
list or enters the set values

24-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

4260A
N 1 2 3

A. Bar Graph DisplayProvides real-time bar


graph display of line currents and
measurement of line current and neutral
current (if applicable) (default display)

100

B. Metering MenuProvides access to


metered values of current, voltage, power,
energy and frequency

B
06134267

06134792

A
The Micrologic P trip unit has a default bar graph
display of currents and three different menus
which can be accessed using navigation
buttons:

50

(A)

V
P
E

(V)
(kWh)

(Hz)

(kW)

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

C. Maintenance MenuAllows user to change


the trip unit configuration and provides
access to history logs
D. Protection MenuAllows precision
adjustments to basic and advanced
protection
When the switch cover is closed, the trip unit will
return to the bar graph (default) display after 3.5
minutes of no input. (If the switch cover is open,
the display stays at the window selected.) To
access another menu, press the button that
corresponds to the desired menu. The menu
appears on the display and the green LED
below the menu button lights up.

Use the metering button to access the metered


values of:

Figure 23:

Metering Menu
06134267

Metering Menu

(A)

Moves cursor down

(V)

Moves cursor up

(kW)

Selects boxed item

D. Energy

V
P
E

(kWh)

Returns to previous screen

E. Frequency

(Hz)

A. Current
B. Voltage
C. Power

20002012 Schneider Electric All Rights Reserved

Returns to bar graph display

25-EN

ENGLISH

Menus

06133331

Figure 22:

06133330

Bar Graph display and Menus

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 2Graphic Display Navigation

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 2Graphic Display Navigation

Current

48049-137-05
Rev. 01, 07/2012

ENGLISH

06134267

Figure 24:

26-EN

(A)

V
P
E

(V)

(A)

Instant.
Ia, Ib, Ic, In

Displays current for A, B, C and


Neutral (depending on network type)

(kWh)

Max

Displays and resets maximum current values

(Hz)

Demand

(kW)

Ia, Ib, Ic, In

Displays current demand for A, B, C and


Neutral (depending on network type)

Max

Displays and resets maximum demand values

Voltage Levels

(A)

V
P
E

(kWh)

(Hz)

(V)

Instant.

(V)
(kW)

Figure 26:
06134267

Power

Figure 25:
06134267

Voltage

Current Levels

Displays phase-to-phase instantaneous


voltage (Vab, Vbc, Vca) and phase-to-neutral
instantaneous voltages (Van, Vbn, Vcn)
(3 phases, 4-wire with neutral CT)

Average 3) Displays average of phase-to-phase voltages


Unbal 3)

Displays phase-to-phase voltage unbalance

Phase
Rotation

Displays phase sequence

Power Levels

(A)

V
P
E

(V)

(Hz)

(kW)
Instant.

(kW)

P, Q, S

Displays total active power (P)


Displays total reactive power (Q)
Displays total apparent power (S)

(kWh)

Power
factor

Displays power factor

Demand
P, Q, S

Displays active demand power (P)


Displays reactive demand power (Q)
Displays apparent demand power (S)

Max

Displays and resets maximum demand values

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

V
P
E

(kWh)

(Hz)

(kW)

(A)

V
P
E

(V)
(kWh)

(Hz)

Figure 29:

B. To set up the M2C/M6C contacts


C. To set up the Micrologic trip unit
D. To set up the metering parameters
E. To set up the communication module

Figure 30:
06133330

E total

Displays total active power (E. P.)


Displays total reactive power (E. Q.)
Displays total apparent power (E. S.)

E in

Displays total active power (E. P.) in.


Displays total reactive power (E. Q.) in

E out

Displays total active power (E. P.) out.


Displays total reactive power (E. Q.) out

Reset
energy

Resets all energy values to zero.

Displays frequency (F)

(kW)

A. To access the history log

20002012 Schneider Electric All Rights Reserved

(kWh)

Frequency

Use the maintenance button to access the


maintenance menu.

History Logs

(V)

Maintenance Menu
06133330

Maintenance Menu

(A)

Figure 28:
06134267

Frequency

Energy Levels

ENGLISH

Figure 27:
06134267

Energy

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 2Graphic Display Navigation

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Moves cursor down

Moves cursor up

Selects boxed item

Returns to previous screen

Returns to bar graph display

History Logs
History
logs
Trip
history

Displays log of last ten faults recorded

Alarm
history

Displays log of last ten alarms activated

Operation
counter

Displays number of operations (opening or trips)

Contact
wear

Displays circuit breaker contact wear status

27-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 2Graphic Display Navigation

Available only if M2C/M6C contacts are


installed.
One alarm per contact.
Can select those set up as alarm or trip
under protection menu.

M2C/M6C Contacts Setup


Contacts
M2C / M6C

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Alarm
Type
S#

Reset

NOTE: If trip unit is connected to a


communication network which provides date
and time synchronization, date/time cannot be
set from trip unit.

Metering Setup

Figure 32:
06133330

Micrologic Setup

28-EN

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Sets mode for S# contact


# equals 1 or 2 for M2C contact
# equals 1 to 6 for M6C contact
Resets contacts after an alarm

Micrologic Setup

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Figure 33:

Assigns a protective alarm to S# contact


# equals 1 or 2 for M2C contact
# equals 1 to 6 for M6C contact

Setup
S#

06133330

ENGLISH

Figure 31:
06133330

M2C/M6C Programmable Contacts

48049-137-05
Rev. 01, 07/2012

Micrologic
setup
Language

Selects display language

Date/time

Sets date and time

Breaker
selection

Enters information about the circuit breaker


in which the trip unit is installed

Power
sign

Selects power sign direction for


metering menus

VT ratio

Selects the voltage ratio; if no external voltage


transformer is present, select 690:690

System
frequency

Selects the system frequency

Metering Setup
Metering
setup
System
type

Selects system type

Current
demand

Sets current demand

Power
demand

Sets power demand

Sign
convention

Selects sign convention

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Com.
setup

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Figure 35:

Use the protection button to access the menus.


A. To display and adjust current protection
B. To display and adjust voltage protection
C. To display and adjust other protection
D. To set current load shedding
E. To set power load shedding

Figure 36:
06133331

Amperage Protection

Com.
parameter

Sets up the communication module

Remote
access

Determines access to trip unit settings via the


communication module

Remote
control

Determines if circuit breaker can be turned on


and/or off via the communication module

Protection Menu
06133331

Protection Menu

Communication Module Setup

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

Moves cursor down

Moves cursor up

Selects boxed item

Returns to previous screen

Returns to bar graph display

Amperage Protection

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

Amperage
protection
Displays and fine-adjusts I2t long-time,

(A) short-time and instantaneous protection

I dmtl

(A) short-time and instantaneous protection

(A) protection (Micrologic 6.0P only)

Displays and fine-adjusts Idmtl long-time,


Displays and fine-adjusts equipment ground-fault

I neutral (A)
I

20002012 Schneider Electric All Rights Reserved

ENGLISH

Figure 34:
06133330

Communication Setup

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 2Graphic Display Navigation

Sets neutral (Off, N, N/2, 1.6N)

Alarm Sets equipment ground-fault alarm values

Iunbal (%)

Sets allowable current unbalance

Iamax (A)

Sets maximum demand current in A-phase

Ibmax (A)

Sets maximum demand current in B-phase

Icmax (A)

Sets maximum demand current in C-phase

Inmax (A)

Sets maximum demand neutral current

29-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 2Graphic Display Navigation

Voltage Protection

48049-137-05
Rev. 01, 07/2012

ENGLISH

06133331

Figure 37:

30-EN

Vmin

(V) Sets minimum (under) voltage protection

Vmax (V)

Sets maximum (over) voltage protection

Vunbal (%)

Sets unbalanced voltage protection

Other
protection

rPmax (W)

Sets reverse power protection

F min (Hz)

Sets minimum (under) frequency protection

Fmax (Hz)

Sets maximum (over) frequency protection

Phase
rotation

Sets phase reversal protection

Current Load Shedding

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

Figure 40:
06133331

Power Load Shedding

Voltage
protection

Other Protection

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

Figure 39:
06133331

Current Load Shedding

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

Figure 38:
06133331

Other Protection

Voltage Protection

Load
shedding

Sets current load shedding values (alarm only)

Power Load Shedding

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

Load
shedding

Sets power load shedding values (alarm only)

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

Maintenance Menu
06133330

NOTE: The protection menu settings cannot be


adjusted unless the switch cover is open. When
settings have been adjusted, press one of the
menus buttons to save the new values.

Figure 41:

06134825

Trip Unit Parameters Adjustment

ENGLISH

Section 3Trip Unit Configuration

5.0
ogic

Microl

1. Open switch cover (A).


2. Press maintenance button (B) to bring up
maintenance menu (C).

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Down

20002012 Schneider Electric All Rights Reserved

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

06133334

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

M2C/M6C Contact Kits Setup


06133330

If M2C or M6C contact kit is installed, use


Contacts M2C/M6C menu to set alarm type
and operational mode. The M2C kit has S1 and
S2 contacts. The M6C kit has S1, S2, S3, S4,
S5 and S6 contacts.

Figure 42:
06133330

M2C/M6C Programmable Contacts

Contacts
M2C / M6C
Alarm
type
Setup
Reset

Enter

31-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

IiInstantaneous pickup

Set M2C/M6C Contact Alarm Type

Contacts
M2C / M6C

06133336

06133334

IrLong-time pickup

Figure 43:

Alarm
type

IsdShort-time pickup

Alarm
type

S1

S1

S1

Ii

Isd

S2

Setup

I Ground-fault current
Reset

AI Ground-fault alarm
IunbalCurrent unbalanced

Up/
Down

Enter

Enter

Enter

IamaxPhase A demand overcurrent

Enter

IcmaxPhase C demand overcurrent

Exit

VminVoltage is below set minimum

06133335

InmaxNeutral demand overcurrent

06133336

IbmaxPhase B demand overcurrent

Alarm
type

S2

S1
S2

Not
selected

Down

Down

Enter

Enter

Enter

Do you want
to save new
settings?

VmaxVoltage is above set maximum


VunbalVoltage unbalanced
rPmaxReversed power

No

FminFrequency is below set minimum

Yes

FmaxFrequency is above set maximum


)rotPhase rotation

S2
IsdIsd

Up/
Down
Enter

IshedCurrent shedding
Exit

Not SelectedNo alarms selected

06133336

PshedPower shedding
06133335

ENGLISH

1. Enter M2C/M6C contacts alarm type into trip


unit memory. Available alarms are:

48049-137-05
Rev. 01, 07/2012

Do you want
to save new
settings?

Alarm
type
S1
S2

No
Yes
Down

Exit

Enter

32-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Contacts
M2C / M6C
Alarm
type

Nonlatching contactDrops out after


fault is removed.

Setup
M2C/M6C

S1

S1

Mode

Mode

S1

Locked 1

time delay

ENGLISH

Set M2C/M6C Contact Alarm Mode


06133337

Latching contactStays latched until


reset

Figure 44:
06133334

2. Set up M2C/M6C contact alarm mode.


Contact modes available are:

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

S2

Setup

Delay

Time DelayDelay placed on contacts

Reset

1s

For troubleshooting purposes only the


following modes are available:

Up/
Down

Enter

Enter

Enter

Locked 0Contacts are locked open

Enter

Each alarm occurrence will activate the


relay and will signal and continue to
signal an alarm until the trip unit
test/reset button is pressed.

S1

S1

Mode

Mode

time delay

time delay

Delay

Do you want
to save new
settings?

Delay

Setup
M2C/M6C
S1
S2

No
5s

1s

This latching behavior occurs regardless


of whether latching or nonlatching
contact mode was used during alarm
setup.

06133335

For short-time, instantaneous and ground


fault (SIG) alarms only:

06133337

Locked 1Contacts are locked closed

Yes
Up/
Down

Down
Enter

3. Reset displays states of relays and allows


them to be reset.

Enter

Down

Down

Enter

Enter

Exit

NOTE: Select reset option under the


M2C/M6C menu to reset all alarms. The
test/reset button on the trip unit will reset the
trip unit so that it will stop activating the
alarm, but does not reset the M2C/M6C
contact.

S2

S2

S2

S2

Mode

Mode

Mode

Mode

Locked 1

time delay

time delay

time delay

Delay

Delay

360s

360s

Up/
Down

Enter

Delay
1s

Up/
Down

Down
Enter

Enter

Enter

Do you want
to save new
settings?

Setup
M2C/M6C
S1
S2

No

06133334

06133335

06133337

Exit

Contacts
M2C / M6C
Alarm
type
Setup

Time delay mode only

Reset

Yes
Down

Exit

Exit

Enter

20002012 Schneider Electric All Rights Reserved

33-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

1. Set display language.

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup
Enter

Figure 46:

Set Language

Language
Date / time
Breaker
selection

06133338

06133330

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Micrologic Trip Unit Setup

Down

06133339

ENGLISH

Use Micrologic setup menu to set display


language, date and time, circuit breaker
information, power sign, VT ratio and system
frequency.

Figure 45:
06133330

Micrologic Trip Unit Setup

48049-137-05
Rev. 01, 07/2012

Language
Date / time
Breaker
selection
Power
sign
VT ratio
System
frequency

Language
Deutsch
English US
English UK

Power
sign

Espaol

VT ratio

Franais
Up/
Down

Enter
Enter

34-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Language

Date

Date

Date

Date / time

02 / 25 / 2001

01
02 / 25 / 2001

01 / 28 / 2001

Time

Time

Time

06:12:35pm

06:12:35pm

06:12:35pm

Breaker
selection
Power
sign
VT ratio
Enter

After using the test kit to do secondary


injection testing, thermal imaging inhibit, ZSI
testing or ground-fault inhibit, the time will
need to be reset if the trip unit is not
connected to a communication network
providing date and time synchronization.

Date

Enter

Enter

Date

Up/
Down

Up/
Down

Enter

NOTE: In US English the date format is


month/day/year. In all other languages the
date format is day/month/year.

NOTE: If time is not synchronized by a


supervisor using the network system
management software, reset time semiannually, or more often if needed.

Set Date and Time

ENGLISH

NOTE: If trip unit is connected to a


communication network which provides date
and time synchronization, date/time cannot
be set from trip unit. If trip unit is not
connected to a communication network
which provides data and time
synchronization, date and time will need to
be re-entered every time trip unit power is
lost.)

Figure 47:
06133339

2. Set trip unit date and time.

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

Date

Date

2001
02 / 28 / 2001

02 / 28 / 2001

02 / 28 / 2001

02 / 28 / 2001

Time

Time

Time

Time

06:12:35pm

06:12:35pm

06:12:35pm
06

11
07:12:35pm

Up/
Down
Enter

Enter

Date

Date

02 / 28 / 2001

02 / 28 / 2001

Time

Time

25
07:11:35pm

07:11:25pm

Up/
Down

Up/
Down

Up/
Down

Down
Enter

Enter

Exit

Enter

20002012 Schneider Electric All Rights Reserved

35-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

StandardANSI, UL, IEC or IEC/GB


Circuit Breaker FamilyMasterpact (ANSI,
UL, IEC or IEC/GB), Powerpact (UL or IEC)
or Compact NS (IEC)
Circuit Breaker TypeFound on the circuit
breaker faceplate

Figure 48:
06133339

Set Circuit Breaker Information

Breaker
selection

Language
Date / time
Breaker
selection
Power
sign
VT ratio

Breaker
selection

Standard
ANSI
Circuit breaker
Masterpact
Type
NW32H2
0000

Breaker
selection
Standard
ANSI
Circuit breaker
Masterpact
Type
NW32H2
0000

Standard
UL
Circuit breaker
Masterpact
Type
NW32H2
0000

HLogic2002AA

HLogic2002AA
Up/
Down

HLogic2002AA

Enter

Enter

Circuit Breaker Contact Wear CodeOnly


modified when replacing an existing trip unit
with contact wear information
NOTE: The contact wear meter is active only
when circuit breaker type is Masterpact.
To maintain contact wear indicator
information when replacing an existing trip
unit:
a. Read code on trip unit to be replaced.
(The code is a hexadecimal number.)
b. Remove old trip unit and install new trip
unit in circuit breaker.
c. Enter code from old trip unit in new trip
unit.

Breaker
selection

Breaker
selection

Breaker
selection

Standard
UL
Circuit breaker
Masterpact
Type
NW32H2
0000

Standard
UL
Circuit breaker
Masterpact
Type
NW32H2
0000

Standard
UL
Circuit breaker
Masterpact
Type
NW40H2
0000

HLogic2002AA
Up/
Down

HLogic2002AA

HLogic2002AA
Up/
Down

Down

Down
Enter

Enter

Enter

Enter

Enter

Breaker
selection

Breaker
selection

Breaker
selection

Breaker
selection

Standard
UL
Circuit breaker
Masterpact
Type
NW40H2
0000

Standard
UL
Circuit breaker
Masterpact
Type
NW40H2
0000

Standard
UL
Circuit breaker
Masterpact
Type
NW40H2
1000

Standard
UL
Circuit breaker
Masterpact
Type
NW40H2
10
200

HLogic2002AA

HLogic2002AA

HLogic2002AA

HLogic2002AA

Up/
Down

Down
Enter

Up/
Down

Down
Enter

Enter

Enter
Repeat for each digit
to be set.

Breaker
selection
Standard
UL
Circuit breaker
Masterpact
Type
NW40H2
1234

06133335

ENGLISH

3. Enter circuit breaker information into trip unit


memory.The following information must be
entered to properly identify the circuit
breaker over the communication network:

48049-137-05
Rev. 01, 07/2012

Do you want
to save new
settings?

Modify contact wear code only


if replacing circuit breaker.

No
Yes

HLogic2002AA
Exit

Down
Enter

36-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Language

Power
sign

Power
sign

P-

P+

Date / time

Do you want
to save new
settings?

P+: Power absorbed from upstream to


downstream (top fed)

Breaker
selection

P-: Power absorbed from downstream to


upstream (bottom fed)

Power
sign

No

Default value is P+

VT ratio

Yes

Enter

Up/
Down

Enter

ENGLISH

Set Power Sign


06133335

Choose the signing convention to be used


for power metering, energy metering and
load shedding:

Figure 49:
06133339

4. Select power sign.

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

Down
Enter

Enter
Exit

If supply voltage for the trip unit exceeds


690V, an external voltage transformer is
required.

Figure 50:
06133339

5. Enter VT ratio of external voltage


transformer into trip unit memory. If no
external voltage transformer is present, set
both primary value and secondary value to
690V.

Set VT Ratio

VT ratio

Language
Date / time
Breaker
selection

Primary

690V

VT ratio

VT ratio
Primary

Primary

690V

660V

Secondary

Secondary

Secondary

690V

690V

690V

Power
sign
VT ratio

Up/
Down

Enter

Enter

VT ratio
Primary

660V
Secondary

690V

Enter

06133335

Enter

Down

Do you want
to save new
settings?
No
Yes

Up/
Down
Enter

Down
Enter

Exit

20002012 Schneider Electric All Rights Reserved

37-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

Set System Frequency

Date / time
Breaker
selection

Reactive power absolute value will be


correct, but sign will be wrong.

Power
sign

PF absolute value will be correct, but


sign will be wrong.

VT ratio

Frequency value may not be accurate.

System
frequency

Frequency protection is disabled.

System
frequency

System
frequency

50-60Hz

50-60Hz

06133335

06133340

NOTE: When system frequency is set to


400 Hz:

Figure 51:

Do you want
to save new
settings?
No
Yes

Up/
Down

Enter

Enter

Phase rotation protection is disabled.


Enter

Down
Enter

Exit

Use Metering setup menu to set parameters


for metering system current and power.

Figure 52:
History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup
Down

38-EN

Metering Setup
06133330

Metering Setup

06133330

ENGLISH

6. Enter system frequency into trip unit


memory.

48049-137-05
Rev. 01, 07/2012

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

System
type
Current
demand
Power
demand
Sign
convention

Enter

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

Network Type
3-phase, 3-wire, 3 CT
(Uses 2 wattmeters)

Neutral

Phase Current

No

Ia, Ib and Ic
measured

3-phase, 4-wire, 4 CT*


Yes
(Uses 3 wattmeters)

Ia, Ib, Ic and In


measured

3-phase, 4-wire, 3 CT
(Uses 3 wattmeters)

Ia, Ib and Ic
measured

No

*Do not use 3-phase, 4-wire, 4 CT type unless neutral


is effectively connected to the trip device (neutral
voltage connection is external to the 3-pole circuit
breaker). (See neutral CT instruction bulletin.)

System
type
Current
demand
Power
demand
Sign
convention

System
type

System
type

3) 4w
3 CT

3) 3w
3 CT

ENGLISH

Three measurement options are available:

Set System Type


06133335

Figure 53:
06133311

1. Select system type.

Do you want
to save new
settings?
No
Yes
Up/
Down

Enter

Enter

Enter

Down
Enter

Exit

NOTE: In the case of a four-pole circuit breaker,


the ability to set the neutral is limited by the
setting of the neutral type switch on the circuit
breaker.
In measurement is not available for
3-phase, 4-wire, 3 CT network types and
Van, Vbn and Vcn simple voltage
measurements are not available for
3-phase, 3-wire, 3 CT network types.
If these measurements are desired, and if
the connected system is a wye (4-wire)
system, select 3-phase, 4-wire, 4 CT and
connect to neutral (Vn) voltage terminal on
the neutral CT.

The calculation method can be block interval


or thermal calculation.
The window type is factory set as a sliding
window.
The time interval can be set from five to 60
minutes in one minute increments.

Figure 54:
06133311

2. Set current calculation method and interval.

Set Current Demand

System
type
Current
demand
Power
demand
Sign
convention

Current
demand

Current
demand

Calculation
method
block
interval
Window type
sliding
Interval

Enter

Calculation
method
thermal

Calculation
method
thermal

Window type
sliding

Window type
sliding
Interval

Interval

15 min

15 min

15 min
Up/
Down

Enter

Current
demand

Calculation
method
thermal

Calculation
method
thermal

Window type
block
Interval
25 min

Window type
block
Interval

Up/
Down
Enter

20002012 Schneider Electric All Rights Reserved

Down
Down
Enter

06133335

Enter

Current
demand

Current
demand

Do you want
to save new
settings?
No
Yes

25 min
Exit

Down
Enter

39-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

NOTE: The sync to comms method is


available only with the communication
option. This function determines demand
power based on a signal from the
communication module.

Set Power Demand

System
type
Current
demand
Power
demand
Sign
convention

The default window type is sliding.


The time interval can be set from five to 60
minutes in one minute increments.

Enter

Power
demand

Power
demand

Calculation
method
block
interval
Window type
sliding
Interval

Calculation
method
thermal

Calculation
method
thermal

Window type
sliding
Interval

Window type
sliding
Interval

15 min

15 min

15 min

Up/
Down

Enter
Enter

Power
demand

Power
demand

Calculation
method
thermal

Calculation
method
thermal

Window type
block
Interval
25 min

Window type
block
Interval

Up/
Down
Enter

40-EN

Power
demand

Down
Down
Enter

06133335

ENGLISH

The calculation method can be block


interval, thermal calculation or sync. to
comms.

Figure 55:
06133311

3. Set power calculation method and interval.

48049-137-05
Rev. 01, 07/2012

Do you want
to save new
settings?
No
Yes

25 min
Exit

Down
Enter

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

IEEE
IEC
IEEE alt

Set Sign Convention

System
type
Current
demand
Power
demand
Sign
convention

Sign
convention

Sign
convention

IEEE

IEC

ENGLISH

Figure 56:

06133335

Choose the signing convention to be used


for reactive power (VARS) and reactive
energy (VARhrs) and power factor
measurements:

06133311

4. Select sign convention.

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

Do you want
to save new
settings?
No
Yes
Up/
Down

Enter

Enter

Enter

Down
Enter

Exit
IEEE Sign Convention
Reactive
Power

Quadrant 1
Quadrant 2
Watts Negative (-) Watts Positive (+)
VARs Positive (+)
VARs Positive (+)
PF Lagging (-)
PF Leading (+)
Reverse Power Flow Normal Power Flow

Active
Power

Quadrant 4
Quadrant 3
Watts Negative (-) Watts Positive (+)
VARs Negative (-) VARs Negative (-)
PF Leading (+)
PF Lagging (-)

IEC Sign Convention


Reactive
Power

Quadrant 1
Quadrant 2
Watts Negative (-) Watts Positive (+)
VARs Positive (+)
VARs Positive (+)
PF Lagging (+)
PF Leading (-)
Reverse Power Flow Normal Power Flow

Active
Power

Quadrant 3
Quadrant 4
Watts Negative (-) Watts Positive (+)
VARs Negative (-) VARs Negative (-)
PF Lagging (-)
PF Leading (+)

IEEE Alt Sign Convention


Reactive
Power

Quadrant 1
Quadrant 2
Watts Negative (-) Watts Positive (+)
VARs Negative (-) VARs Negative (-)
PF Lagging (-)
PF Leading (+)
Reverse Power Flow Normal Power Flow

Active
Power

Quadrant 4
Quadrant 3
Watts Negative (-) Watts Positive (+)
VARs Positive (+)
VARs Positive (+)
PF Leading (+)
PF Lagging (-)

20002012 Schneider Electric All Rights Reserved

41-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

NOTE: Com. setup parameters can only be


entered if a circuit breaker communication
module (BCM) is installed.

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Address = 47

Figure 58:
06133459

1. Set communication parameters. Default


values are:
Baud-rate = 19.2k
Parity = even

06133459

06133330

Communication Module Setup


Com.
parameters
Remote
access
Remote
control

Enter

Down

Set Modbus Com Values

Modbus
Com

Com.
parameters
Remote
access
Remote
control

Modbus
Com

Address

Baud-rate

Baud-rate

19.2k

19.2k

Baud-rate

19.2k

Parity

Parity

Even

Even

Even
Up/
Down

Enter

Enter

Modbus
Com

Address

Address

Parity

Down
Enter

Modbus
Com

Modbus
Com

Address

Address

Baud-rate

19.2k

19.2k

Parity

Enter

No

Parity

Even
Up/
Down

Baud-rate

19.2k

Parity

Even

Do you want
to save new
settings?

Address

Baud-rate

Modbus
Com

Yes

Even
Up/
Down

Down
Enter

06133335

Enter

Enter

Down
Enter

Exit

2. Remote access.
Remote access is factory set and does not
require adjustment.
NOTE: Remote access setting can be
changed to allow protection settings to be
changed via the communication network.
Contact the local sales office about the
availability of software to utilize this feature.

Figure 59:
06133459

ENGLISH

Use Com. setup menu to set communication


module setup.

Figure 57:
06133330

Communication Module Setup

48049-137-05
Rev. 01, 07/2012

Com.
parameters
Remote
access
Remote
control

Check Remote Access

Remote
access
Access
Permit

No
Access
code

0000
Enter

42-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

NOTE: For remote operation of the circuit


breaker, the BCM must be set to enable
opening and/or closing and circuit breaker
must have communicating shunt coils with
wire harness installed.

Remote
Control

Remote
Control

Manual

ENGLISH

Auto: The circuit breaker can be opened or


closed via the network system management
software.

Com.
parameters
Remote
access
Remote
control

Set Remote Control


06133335

Manual: The circuit breaker cannot be


opened or closed via the network system
management software.

Figure 60:
06133459

3. Set remote control.

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

Do you want
to save new
settings?

Auto

No
Yes
Enter

Up/
Down

Enter
Enter

Down
Enter

Exit

Switch Settings Adjustment

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Using the switches to set trip unit values will override settings made
using the keypad.
Changing the switch setting for overload, short-time or instantaneous,
or changing the neutral protection selector on a four-pole circuit
breaker, will delete all fine adjustments previously made using the
keypad for overload, short-time and instantaneous protection.
Changing the switch setting for ground-fault will delete all fine
adjustments made with the keypad for ground-fault protection.
If cover pin located on back of the protective cover is missing, contact
sales office for a replacement cover.
Failure to follow this instruction can result in equipment damage.

20002012 Schneider Electric All Rights Reserved

43-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

5.0 P

5.0 P

06134826

Micro

logic

5.0 P

D
F

4. Make fine adjustments using navigation keys


(F) or network system management
software. All fine adjustments are stored in
non-volatile memory.

C
B
Idmtl Trip Curve

Idmtl (A)

Long-time pickup = 1 A

Trip

1000 A

Ir

1000 A

1.0 s

tr

1.0 s
EIT

2000 A
0.2 s

Long-time delay = 0.5 sec.

2000 A
0.2 s

Isd
tsd
Ii

4000 A

Short-time pickup = 10 A

Ground-fault Trip Curve

Idmtl (A)

Trip

Fine switch settings are in the following


increments:

06134767

E
06134766

I2t Trip Curve


06134765

NOTE: Fine adjustments can only be made


for values less than those set with the
switches. Using switches to set values after
making fine adjustments using the keypad
will override the keypad adjustments.

logic

Micro

06134755

ogic

Microl

Adjust Switch Settings

3. Adjust the appropriate switches (C) to


desired values. Display screen (D)
automatically shows appropriate setting
curve (E). The set value is displayed as a
boxed value in amperes or seconds.

4000 A

I (A)
Trip

Ir
tr

1200A

Ig

0.5s

tg

Idmtl
Isd
tsd
Ii

Short-time delay = 0.1 sec.


Instantaneous pickup = 10 A
Example

Ground-fault pickup = 1 A

06134768

Ground-fault delay = 0.1 sec.


log
Micro

06134826

ENGLISH

2. Confirm that cover pin (B) is on back of the


protective cover. This pin is necessary to
lock trip unit settings when they are set to
trip.

Figure 61:

06134825

1. Open switch cover (A).

48049-137-05
Rev. 01, 07/2012

44-EN

ic 5.0

I(A)

I(A)

I(A)

Trip

Trip

Trip

1000 A

1000 A

995 A

1.0 s

1.0 s

1.0 s

2000 A
0.2 s

2000 A
0.2 s

2000 A
0.2 s

4000 A

4000 A

4000 A

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

5.0 P

Micro

logic

6. Check settings using keypad (B) and graphic


display or the network system management
software.

ENGLISH

logic

Check Switch Settings

06134756

NOTE: When the cover is closed, the


navigation keys can no longer be used to
make adjustments to the trip unit settings if
they are set to trip.

Figure 62:

06134828

5. Replace switch cover. Use wire seal


MICROTUSEAL (A), not supplied, to provide
tamper evidence if necessary.

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

5.0 P

Micro

Examples
Figure 63:

1. Set switches:
BLong-time delay (tr)
CShort-time pickup (Isd)
DShort-time delay (tsd)

A
B

.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
@ 6 Ir

tsd
(s)

.3
.2
.1

on

I t

setting

.2
.1
0
off

6 8 10
4
12
3
15
off
2
x In

tr

delay

CShort-time pickup (Isd)


DShort-time delay (tsd)
EInstantaneous pickup (Ii)
FGround-fault pickup (Ig)
GGround-fault delay (tg)

Isd C
tsd

E
0

Ir

Ii

A
B
C
D
F
G

Set Pickup Levels


t

long time

Ir
.7
.6
.5
.4

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

tsd
(s)

on

setting

D
C
B
A

.2
.1
2

I t

0
off

delay

tg
F
G
H
J

(s)

Ii

.4 .4 .3

.3
.2
.1

A
tr

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Ig

Ir

06134751

06134754

Figure 64:

6 8 10
4
12
3
15
off
2
x In
test

Isd C
tsd

Ii

.4 .4 .3

.3
.2
.1
on

.2
.1
0
I t off

Ir

Isd

D
E

Ii

ground fault

In 2000 A

t
I2t on
Ig

2. Fine-tune adjust using keypad and graphic


display screen or the network system
management software.

F
tg

20002012 Schneider Electric All Rights Reserved

Isd

D
E

In 2000 A

1. Set switches:
BLong-time delay (tr)

Ii

2. Fine-tune adjust using keypad and graphic


display screen or the network system
management software.

ALong-time pickup (Ir)

Ii

.4 .4 .3

EInstantaneous pickup (Ii)

Micrologic 6.0P Trip Unit

Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

C
D

long time

Ir

06134758

ALong-time pickup (Ir)

Set Pickup Levels


06134751

06134753

Micrologic 5.0P Trip Unit

Ig

I2t off

45-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

Micrologic #.0x Trip Units

15

Federal Pioneer USRC and USRCM Trip Units

Merlin Gerin STR58 Trip Units

Downstream Device
(sends output to RIM)

Square D GC-200 Ground-Fault Relay for


Equipment Protection

Upstream Device
(receives input from RIM)

Square D GC-100 Ground-Fault Relay


for Equipment Protection

ENGLISH

The number of devices which can be interlocked


are shown in Table 10.

ZSI Combinations

Square D Micrologic Series B Trip Units

Table 10:

Micrologic #.0x Trip Units

Zone-Selective Interlocking (ZSI)

48049-137-05
Rev. 01, 07/2012

15

15

Square D Micrologic Series B Trip Units R

26

15

Square D GC-100 Ground-Fault Relay


for Equipment Protection

Square D GC-200 Ground-Fault Relay


for Equipment Protection

15

15

15

Merlin Gerin STR58 Trip Units

15

15

15

Merlin Gerin STR53 Trip Units

15

15

15

Federal Pioneer USRC and USRCM Trip


R
Units

15

15

Square D Add-On Ground Fault Module


R
for Equipment Protection

RRIM module is required to restrain any devices.


Numerical ReferencesMaximum number of upstream circuit breakers which can be restrained
without requiring a RIM Module.

Circuit breaker terminals are shipped with


terminals Z3, Z4 and Z5 jumpered to selfrestrain the short-time and ground-fault
functions. Remove the jumpers when activating
zone-selective interlocking.

Figure 65:

Jumpered Terminals

UC1
Z5
M1
Z3

Z4

Z1

Z2

Auxiliary Connections

46-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

NOTE: Use I2t off with ZSI for proper


coordination. Using I2t on with ZSI is not
recommended as the delay in the upstream
device receiving a restraint signal could result in
the trip unit tripping in a time shorter than the
published trip curve.

ZSI Wiring Example


UC1
Z5
M1

Figure 67:

06134825

Use a test kit connected to the trip unit test plug


receptacle (A) to verify trip unit is functioning as
desired. See instructions shipped with test kit to
perform verification tests.

Z3

Z4

Z1

Z2

UC1
Z5
M1

Auxiliary
Connections 1

Secondary
Connector
Position
Z1
Z2
Z3
Z4
Z5

Trip Unit Operation Verification

ENGLISH

Figure 66:

5.0
ogic

Z2

UC1
Z5
M1

Description
ZSI out signal
ZSI out
ZSI in signal
ZSI in short time
ZSI in ground fault

Z3

Z4

Z1

Z2

Auxiliary
Connections 3

Verify Trip Unit Operation

ogic

Microl

Microl

5.0 P

Figure 68:
06134781

When the circuit breaker trips, the fault indicator


will remain lit until the trip unit is reset.

Z4

Z1

Auxiliary
Connections 2

NOTE: To verify operation of the circuit breaker


and trip unit, use primary injection testing. (See
Trip Unit Installation Check on page 66 for
more information.)

Trip Unit Resetting

Z3

06134086

Wire circuit breakers for zone-selective


interlocking.

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

Micrologic 6.0P

Reset Trip Unit


A

Do not return circuit breaker to service until


cause of trip is determined. For more
information, refer to the circuit breaker
installation instructions shipped with the circuit
breaker.
Press the reset/test button (A) to reset the trip
unit after trip.

20002012 Schneider Electric All Rights Reserved

47-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

48049-137-05
Rev. 01, 07/2012

Paragraph 230-95 (c) of the National Electrical


Code requires that all equipment ground-fault
protection systems be tested when first installed.
With the trip unit powered and the circuit breaker
closed, test the equipment ground-fault
(Micrologic 6.0P trip unit) trip function.
The trip unit is powered if:

circuit breaker is on and has more than


150 V of load voltage on two phases (circuit
breaker is closed or bottom fed).

the Full-Function or Hand-Held Test Kit is


connected and on.

the 24 Vdc external power supply is


connected.

an external voltage tap is installed and


voltage of more than 150 V is present on two
phases.

For instructions on how to close circuit breaker,


refer to the circuit breaker installation
instructions shipped with the circuit breaker.

Figure 69:

06134784

ENGLISH

Equipment Ground-Fault Trip


Functions Testing

logic

Test Equipment Ground-Fault Trip Function

5.0 P

Micro

To test trip function, press the ground-fault test


button (A). Circuit breaker should trip.
If circuit breaker does not trip, contact the local
field office.

48-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 3Trip Unit Configuration

ENGLISH

Trip Unit Status Check


Check trip unit battery and trip indicators.
1. Make sure trip unit is powered. The trip unit
is powered if:
circuit breaker is on and has more than
150 V of load voltage on two phases
(circuit breaker is closed or bottom fed).
the Full-Function or Hand-Held Test Kit is
connected and on.

2. Press test/reset button (A).


All trip indicators (B) will light up

Check Trip Unit Status

Micrologic 6.0P

06133380

the external voltage tap is installed and


voltage of more than 150 V is present on
two phases.

Figure 70:

06134782

the 24 Vdc external power supply is


connected.

Battery Fully Charged


Battery Half Charged

Battery status will be displayed


The battery bar graph reading is valid
after the reset button has been released

Replace Battery

3. If the battery bar graph shows the battery


needs to be changed, use Square D battery
catalog number S33593:
lithium battery
1.2AA, 3.6 V, 800 ma/h
For instructions on replacing battery, see
Section 7Battery Replacement.

20002012 Schneider Electric All Rights Reserved

49-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

48049-137-05
Rev. 01, 07/2012

Section 4Operation

Metering Menu
06134267

Figure 71:

Use the metering menus to monitor circuit


breaker current (I), voltage (V), power (P),
energy (E) and frequency (F).
NOTE: System measurements can also be
checked remotely using System Manager
Software (SMS) (version 3.3 or later) or other
network system management software.

Current Levels
IaInstantaneous A phase current
IbInstantaneous B phase current
IcInstantaneous C phase current
InInstantaneous neutral current
I Instantaneous ground current
IamaxMaximum instantaneous A phase
current
IbmaxMaximum instantaneous B phase
current
IcmaxMaximum instantaneous C phase
current

Figure 72:
06134267

ENGLISH

Metered Values

(A)

V
P
E

(V)
(kWh)

(Hz)

(kW)

Check Current Levels

(A)

V
P
E

(V)
(kWh)

(Hz)

Iinst.

I (A)
Instant

Ia, Ib, Ic, In

Demand

Max

(kW)

Enter

Enter

Enter

Iinst.

Imax

Ia, Ib, Ic, In


Max

InmaxMaximum instantaneous neutral current


I maxMaximum instantaneous ground
current

Ia =
Ib =
Ic =
In =
I =

301 A
309 A
309 A
307 A
17 A

Ib Demand B phase current

Down

Enter
(To reset)

Ic Demand C phase current

Enter

Exit

Demand

IamaxMaximum demand A phase current

Ia, Ib, Ic, In

IbmaxMaximum demand B phase current

Max

Ic maxMaximum demand C phase current


InmaxMaximum demand neutral current
Maximum measurements can also be reset to
zero.

0A
0A
0A

In =
I =

0A
0A

Exit

I (A)

Ia, Ib, Ic, In

Instant

Max

Demand

Exit

Down
Enter

Demand

Demand
Ia, Ib, Ic, In

15 min
Ia =
Ib =
Ic =

356 A
148 A
159 A

In =

84 A

Max

Imax

Demand
15 min
Ia = 357 A
Ib = 148 A
Ic = 185 A
1A
In =
Reset (- / +)

Enter

50-EN

Ia =
Ib =
Ic =

Reset (- / +)

Ia Demand A phase current

In Demand neutral current

Iinst.

Iinst.

Exit

Down

Enter
(To reset)

Enter

Exit

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

VcaInstantaneous voltage between C and A


phases
VanInstantaneous voltage between A phase
and neutral

VcnInstantaneous voltage between C phase


and neutral

(A)

V
P
E

(kWh)

(Hz)

(V)
(kW)

Enter
06133858

VbnInstantaneous voltage between B phase


and neutral

V Inst.

V (V)
Instant

Vab = 430 V
Vbc = 401 V
Vca = 431 V

Average 3
Unbal 3

Van = 245 V
Vbn = 242 V
Vcn = 242 V

Phase
rotation
Enter

Instant

V avg.
3)

Average 3

421 V

V (V)

ENGLISH

VbcInstantaneous voltage between B and C


phases

Check Voltage Levels


06133858

VabInstantaneous voltage between A and B


phases

Figure 73:
06134267

Voltage Levels

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

Exit

Unbal 3
Phase
rotation

Down

Exit

06133858

Enter

V (V)
Instant
Average 3

V unbal
3)
-4 %

Unbal 3
Phase
rotation

Down

Exit

V (V)

Phase Rotation

Instant
Average 3

') A, B, C

06133858

06133858

Enter

V (V)
Instant
Average 3

Unbal 3

Unbal 3

Phase
rotation

Phase
rotation

Down

Exit

Exit

Enter

20002012 Schneider Electric All Rights Reserved

51-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

ENGLISH

PInstantaneous active power


QInstantaneous reactive power
SInstantaneous apparent power
Power FactorInstantaneous power factor
PDemand active power
QDemand reactive power

Figure 74:
06134267

Power Levels

48049-137-05
Rev. 01, 07/2012

(A)

V
P
E

(V)
(kWh)

(Hz)

PmaxMaximum demand active power

SmaxMaximum demand apparent power


Maximum measurements can also be reset to
zero.

Instant

Demand

Power
Factor

(kW)
0

(kvar)
0

(kVA)
0

Enter

Enter

Power
factor

Power
Factor

-0.16

Exit

Lag
(Ind.)

NOTE: To ensure reliable power and power


factor measurements, Power sign, page 37,
and Sign convention, page 41, must be set.
Down

Exit

Enter

Exit

P (kW)

P, Q, S

Demand

Max

Enter

(kW)
26
(kvar)
Q
86
S
(kVA)
92
Reset (- / +)
P

(kW)
26

(kvar)
83

(kVA)
87

Exit

Enter

Pmax
Demand

Demand

Demand

Instant

Down

52-EN

P inst.

P, Q, S

P, Q, S

P Inst.

P inst.

P (kW)

(kW)

Enter

SDemand apparent power

QmaxMaximum demand reactive power

Check Power Levels

Demand
P, Q, S
Max

Down
Enter

Demand
P, Q, S
Max

Enter
(To reset)

Exit

Exit

Exit

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Total reactive energy (Q)


Total apparent energy (S)
Active energy in (E.P.)
Reactive energy in (E.Q.)
Active energy out (E.P.)

(A)

V
P
E

(V)
(kWh)

(Hz)

(kW)

Enter

Reactive energy out (E.Q.)


Energy measurements can also be reset to
zero.
NOTE: To ensure reliable energy
measurements, Power sign, page 37, and
Sign convention, page 41, must be set.

Check Energy Levels

E (kW)
E total

E. P

(kWh)
0

E. Q (kvarh)
0

E out
Reset
Energy

Enter

E. S

(kVAh)
0

Exit

E in
E. P

E in
E out

E total

E in

E (kW)
E total

ENGLISH

Total active energy (P)

Figure 75:
06134267

Energy Levels

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

(kWh)
0

E. Q (kvarh)
0

Reset
Energy

Exit

Down
Enter

E (kW)
E total
E in
E out

E out
E. P

(kWh)
0

E. Q (kvarh)
0

Reset
Energy

Down

Exit

Enter

E (kW)
E total
E in

Reset
Energy
Are you
sure?

E out
Reset
Energy

20002012 Schneider Electric All Rights Reserved

E total
To reset
energy
press
enter

Yes
Down
(To reset)

Enter

Enter

Enter

(kWh)
0

E. Q (kvarh)
0
E. S

No

Down

E. P

(kVAh)
0

Exit

53-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

ENGLISH

06134267

Figure 76:

Check Frequency

(A)

V
P
E

(V)
(kWh)

(Hz)

(kW)

F (Hz)

60.0

Enter

Figure 77:

History Log Menu


06133330

Trip Unit History

Exit

Use the maintenance menu to review the trip


unit history stored in the history logs.

06133467

Frequency

48049-137-05
Rev. 01, 07/2012

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Trip
history
Alarm
history
Operation
counter
Contact
wear

Enter

The trip unit stores information about the LSIG


fault causing the last ten trips. For each fault the
following are stored:

Current values of Ir, Isd, Ii, and Ig

Date

Pickup setpoint for voltage and other


protection

Figure 78:
06133467

Trip History

Check Trip History

Trip
history
Alarm
history
Operation
counter
Contact
wear

Trip
history
Ii
05 / 20 / 00
Ii
04 / 28 / 00
Vmin
04 / 28 / 00

Time (hour, minute and second)


Enter

Trip
05 / 20 / 00
10:23:42 am
Ii 7200 A
Ia =
Ib =
Ic =
In =

7800 A
7800 A
7800 A
7800 A

Enter

Enter

NOTE: Trips from use of a test kit are not


recorded in the trip history log.

Ii
05 / 20 / 00
Ii
04 / 28 / 00
Vmin
04 / 28 / 00
Down
Enter

Trip
04 / 28 / 00
Ii 7200A
Ia =
Ib =
Ic =
In =

7500 A
7500 A
7500 A
7500 A

Enter

54-EN

Trip
history

Trip
history
Ii
05 / 20 / 00

Trip
04 / 28 / 00
12:03:33 am
V min 100V

Ii
04 / 28 / 00
Vmin
04 / 28 / 00
Down

Exit

Enter

Exit

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Indication and value of the alarm setting


Date
Time (hour, minute and second)

Al
05 / 20 / 00

Trip
05 / 20 / 00
Al

996A

Alarm
history
Al
05 / 20 / 00

Al
02 / 28 / 00

Al
02 / 28 / 00

Al
02 / 26 / 00

Al
02 / 26 / 00

Enter

Enter

Enter

ENGLISH

Alarm
history

06133983

Trip
history
Alarm
history
Operation
counter
Contact
wear

Check Alarm History


06133983

The trip unit records measurement at each of


the last ten alarms activated. For each alarm the
following are stored:

Figure 79:
06133467

Alarm History

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

Down

Trip
02 / 28 / 00
Al

996A

06133983

Enter

Alarm
history
Al
05 / 20 / 00

Trip
02 / 26 / 00
Al

996A

Al
02 / 28 / 00
Al
02 / 26 / 00
Enter

This displays the maximum number of


operations (trip or circuit breaker openings)
since the circuit breaker was installed. The
number is obtained from the circuit breaker
communication module (BCM).

Figure 80:
06133467

Operation Counter

Trip
history
Alarm
history
Operation
counter
Contact
wear

Enter

This displays the amount of contact wear on the


contact with the greatest wear. When this
number reaches 100, it is recommended that a
visual inspection of the contacts be done. This
function works only on Masterpact NT and
NW circuit breakers.

Figure 81:
06133467

Contact Wear

Trip
history
Alarm
history
Operation
counter
Contact
wear

Enter

Down

Exit

Enter

Exit

Check Operation Counter


Number of
Operations
Total
19
Operations
since last
reset
Exit

Check Contact Wear

Contact
wear
63

Exit
Exit

20002012 Schneider Electric All Rights Reserved

55-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

Figure 82:

Protection Menu
Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

Refer to Appendix B for default settings and


setting ranges.

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P
Enter

The Change I (A) setting with Idmtl(A) screen


will only appear if long-time, short-time and/or
instantaneous adjustments have been
previously made under the I(A) menu screen. If
the user responds Yes, the I(A) settings will be
lost when the menu goes to the Idmtl(A)
adjustment screen. If no adjustments have been
made under the Idmtl(A) menu screen, the
menu goes directly to the I(A) adjustment
screen.
NOTE: Neutral protection is disabled if Idmtl
protection is selected.

(A)

Idmtl

(A)

(A)

I(A)
Change Idmtl
(A) settings with
I(A)?

Ineutral (A)
I

No
Yes

Alarm

I unbal

(%)

Down

Ia max

(A)

Enter

Ib max

(A)

Ic max

(A)

In max

(A)

06133471

Check Amperage Protection

Idmtl (A)
Trip
1000 A
1.0 s
2000 A
0.2 s
4000 A

Exit

Enter

(A)

Idmtl

(A)

(A)

Ineutral (A)
I

Alarm

Idmtl(A)
Change I(A)
settings with
Idmtl(A)?

No
Yes

Down

Down

Enter

Enter

06133472

The Change Idmtl (A) setting with I(A) screen


will only appear if long-time, short-time and/or
instantaneous adjustments have been
previously made under the Idmtl (A) menu
screen. If the user responds Yes, the Idmtl (A)
settings will be lost when the menu goes to the
I(A) adjustment screen. If no adjustments have
been made under the Idmtl (A) menu screen,
the menu goes directly to the I(A) adjustment
screen.

Figure 83:
06133331

Amperage Protection

06133474

Use the protection menus to check protection


setup for amperage protection, voltage
protection, other protection, current load
shedding and power load shedding.

06133474

ENGLISH

06133331

Protection Setup

48049-137-05
Rev. 01, 07/2012

I dmtl (A)
Trip
1000 A
1.0 s
EIT
2000 A
0.2 s
4000 A

Exit

Continued on next page

56-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

(A)

Idmtl

(A)

(A)

(A)
Trip
1200 A

Ineutral (A)
I

0.5s

Alarm

Circuit
Breaker

Neutral CT
Protection Choices
Type

All

none

06133474

Enter

NOTE: Selection of the CT type determines the


Ineutral protection in the Protection menu.

disabled

Four-pole

internal

Exit

(A)

Idmtl

(A)

(A)

Ineutral (A)

OFF: no neutral protection

N/2: half neutral protection


N: full neutral protection

Alarm

Ineutral (A)
Neutral CT
External
Protection
OFF
Exit

Down

OFF: no neutral protection

ENGLISH

Check Amperage Protection (continued)


06133473

Figure 83:
06133474

Amperage Protection (continued)

Enter

Three-pole

external

N: full neutral protection


1.6N: oversized neutral
protection

06133474

N/2: half neutral protection

(A)

Idmtl

(A)

(A)

Alarm
Alarm

Ineutral (A)
I

Alarm

Pick up
996A
1.0s
Drop out
996A
1.0s
Exit

Down
Enter

Idmtl

(A)

(A)

I unbal (%)
Off
Pick up

Ineutral (A)
I

Alarm

I unbal
Down

(%)

60%
40.0s
Drop out
60%
1.0s
Exit

Enter
Continued on next page

20002012 Schneider Electric All Rights Reserved

57-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

Amperage Protection (continued)

48049-137-05
Rev. 01, 07/2012

Figure 83:

ENGLISH

Check Amperage Protection (continued)

(A)

Ia max (A)
Off

Ineutral (A)
I

Alarm

I unbal (%)
Ia max

(A)

Pick up
240A
1500s
Drop out
240A
15s
Exit

Down
Enter

Ineutral (A)

Ib max (A)
Off

Alarm

I unbal (%)
Ia max

(A)

Ib max

(A)

Pick up
240A
1500s
Drop out
240A
15s
Exit

Down
Enter

Alarm

I unbal

(%)

Ia max

(A)

Ib max

(A)

Ic max

(A)

Ic max (A)
Off
Pick up
240A
1500s
Drop out
240A
15s
Exit

Down
Enter

NOTE: To set In max, the neutral CT must be


set to external or internal under Micrologic setup
under the maintenance menu
.

I unbal (%)
Ia max

Off

(A)

Ib max (A)
Ic max

(A)

In max (A)

58-EN

In max (A)
Pick up
240A
1500s
Drop out
240A
15s

Down

Exit

Enter

Exit

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

Voltage Protection

Setting undervoltage protection (Vmin) below


80% or voltage unbalance (Vunbal) above 20%
can cause the trip unit to not perform as
expected.
Failure to follow this instruction can result in
equipment damage

Unbalance values are based on the true RMS


values of the three-phase currents.

Vmin

(V)

Vmax

(V)

(V)

Vmax

(V)

Vmin (V)
Off

Vunbal (%)

Pick up
100V
5.00s
Drop out
100V
0.20s
Exit

Vmax (V)
Off

Vunbal (%)

Undervoltage alarm drops out upon the loss of


the second phase.

Vmin

Enter

Enter

06133476

Voltage protection pickup settings are phase-tophase values.

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

ENGLISH

HAZARD OF EQUIPMENT DAMAGE

Check Voltage Protection


06133476

NOTICE

06133331

Figure 84:

NOTE: Do not set undervoltage protection


below 80%. Do not set Vunbal above 20%*.

Pick up
725V
5.00s
Drop out
725V
0.20s
Exit

Down

06133476

Enter

Vmin

(V)

Vmax

(V)

Off

Vunbal (%)

Vunbal (%)
Pick up
30%
40.0s
Drop out
30%
10.0s

Down

Exit

Enter

Exit

For an explanation of system protection behavior, refer to Appendix D

20002012 Schneider Electric All Rights Reserved

59-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

ENGLISH

06133331

Figure 85:

Check Other Protection

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

06133484

Enter

rPmax (W)
F min (Hz)
F max (Hz)
Phase
rotation

Down

06133484

Other Protection

48049-137-05
Rev. 01, 07/2012

rPmax (W)
F min (Hz)
F max (Hz)
Phase
rotation

rPmax (W)
Off
Pick up
500kW
5.00s
Drop out
500kW
1.0s
Exit

Enter

Fmin (Hz)
Off
Pick up
45.0Hz
5.00s
Drop out
45.0Hz
1.00s
Exit

06133484

Enter

rPmax (W)
F min (Hz)
F max (Hz)
Phase
rotation

Down

Fmax (Hz)
Off
Pick up
65.0Hz
5.00s
Drop out
65.0Hz
1.00s
Exit

06133484

Enter

rPmax (W)

Phase
rotation

F min (Hz)

Off

F max (Hz)

'): A, B, C

Phase
rotation

60-EN

Down

Exit

Enter

Exit

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Check Current Load Shedding

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P
Enter

Power load shedding can be configured for


alarm only. It cannot be used to trip the circuit
breaker.

20002012 Schneider Electric All Rights Reserved

Figure 87:
06133331

Power Load Shedding

Load
shedding
Off

ENGLISH

Current load shedding can be configured for


alarm only. It cannot be used to trip the circuit
breaker.

Figure 86:
06133331

Current Load Shedding

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 4Operation

Pick up
100% Ir
80% tr
Drop out
100% Ir
10s
Exit

Check Power Load Shedding


Load
shedding

Amperage
protection
Voltage
protection
Other
protection
Load
shedding I
Load
shedding P

Pick up
10.00MW
3600s
Drop out
10.00MW
10s

Enter

Exit

Off

61-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 5Trip Unit Replacement

48049-137-05
Rev. 01, 07/2012

Section 5Trip Unit Replacement


ENGLISH

Trip unit replacement must be done by qualified


persons, as defined by the National Electric
Code, who are familiar with the installation and
maintenance of power circuit breakers.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Failure to follow these instructions for installation, trip test and primary
injection testing may result in the failure of some or all protective function.

Before replacing trip unit, confirm that the circuit


breaker is in good working condition. If the
condition of the circuit breaker is unknown, do
not proceed. For assistance in evaluating the
condition of the circuit breaker, call Technical
Support.

Apply appropriate personal protective equipment (PPE) and follow safe


electrical work practices. See NFPA 70E or CSA Z462.
Replacement/upgrading of a trip unit in the field must be done by
qualified persons, as defined by the National Electric Code, who are
familiar with the installation and maintenance of power circuit breakers.

Read this entire section before starting the


replacement procedure.

Before replacing/upgrading trip unit, confirm that the circuit breaker is in


good working condition. If the condition of the circuit breaker is unknown,
do not proceed. For assistance in evaluating the condition of the circuit
breaker, call Technical Support.

NOTE: If trip unit being replaced is a Micrologic


2.0, 3.0 or 5.0 trip unit, order connector block
S33101 and circuit breaker or cradle wiring
harness if necessary.

If the circuit breaker fails to function properly in any manner upon


completion of the trip unit installation, immediately remove the circuit
breaker from service and call Field Services.
Turn off all power supplying this equipment before working on or inside
equipment. Follow instructions shipped with circuit breaker to disconnect
and reconnect circuit breaker.
Replace all devices, doors and covers before returning equipment to
service.
Failure to follow this instruction will result in death or serious injury.

Required Tools

Torque-controlled screwdriver, set at 7 in-lbs (0.8 Nm) 10%


(Lindstrom torque driver MAL500-2 or equivalent)

Micrologic Full-Function Test Kit (part number S33595)

Preparation
Record Switch Settings

Record all trip unit switch and advanced protection settings for later use.

Circuit Breaker Disconnection

Disconnect circuit breaker as directed in the circuit breaker instruction


bulletin shipped with the circuit breaker. The circuit breaker must be
completely isolated. (For a drawout circuit breaker, place circuit breaker in
the disconnected position. For a fixed-mounted circuit breaker, all voltage
sources, including auxiliary power, must be disconnected.)

Circuit Breaker Accessory Cover


Removal

Remove circuit breaker accessory cover as directed in the Install


Accessories section of the circuit breaker instruction bulletin shipped with
the circuit breaker.

62-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

5.0
Micro

logic

ic 5.0

06134831

logic

5.0

ENGLISH

1. Open switch cover (A).

Micro

Remove Adjustable Rating Plug

06134830

A small Phillips screwdriver is needed to remove


the adjustable rating plug.

Figure 88:

06134783

Rating Plug Removal

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 5Trip Unit Replacement

log
Micro

2. Unscrew adjustable rating plug mounting


screw (B).
B

3. Remove adjustable rating plug (C). Save for


installation in replacement trip unit.

C
alarm
long

Figure 89:

1. Remove connector block (A) from top of trip


unit, if present.

A
06134078

2. Loosen two trip unit screws (B).


3. Slide out trip unit (C).

Microlo

tr
(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

Remove Existing Trip Unit

06134079

Trip Unit Removal

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

Microlo

gic 5.0

gic 5.0

Trip Unit Replacement

Press test/reset button (A). All four indicator


lights (B) should light. If they do not light, check
polarity of battery and retest. If indicator lights
still do not light up when test/reset button is
pressed, stop installation and contact the local
sales office for factory authorized service

20002012 Schneider Electric All Rights Reserved

Install Battery

A
06133375

Install battery holder with battery (A) in trip unit,


observing the correct polarity as indicated on the
battery compartment.

Figure 90:

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

If a new trip unit is being installed, install the trip


unit battery.

NOTE: Battery holder with battery is located under the side flap in the
cardboard box the trip unit is shipped in.

Figure 91:

Trip Indicator Lights

B
06133245

Battery Installation

Micrologic 6.0 A

63-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 5Trip Unit Replacement

48049-137-05
Rev. 01, 07/2012

Trip Unit Installation

Figure 92:

Install Trip Unit

Masterpact NW Circuit Breaker

06135452

2. Inspect trip unit mounting base on the circuit


breaker. Clear any debris from area and
check that all accessory wiring is properly
routed for the trip unit being installed. If there
is any damage or contamination, stop
installation and contact the local sales office
for factory authorized service.

06135453

ENGLISH

1. Inspect trip unit connector pins and surfaces.


If there is any damage, misaligned pins, or
contamination, stop installation and contact
the local sales office for factory authorized
service.

3. For Masterpact NW circuit breaker only:


Manually depress trip unit interlock (A) and
hold it in place during steps 46 below.

logic

5.0

Micro

4. Align guide rail (B) on bottom of trip unit with


guide rail slot (C) on trip unit mounting base
in circuit breaker and gently slide the trip unit
in until it stops.
NOTE: The Masterpact NT and NW trip unit
mounting bases are shock mounted and
therefore can flex slightly.

C
B
A

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Check installation of trip unit to assure proper connections and seating.
Failure to follow this instruction can result in equipment damage or
improper circuit breaker tripping.

64-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Secure Trip Unit

ENGLISH

Figure 93:

A
06134080

5. Align the trip unit so top mounting screw (A)


aligns with the top threaded insert and start
the screw by turning the screw two full
rotations.

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 5Trip Unit Replacement

6. Use a torque-controlled screwdriver to drive


the bottom screw (B) to 7 in-lbs (0.8 Nm)
10%. The back of the trip unit must be flush
with the trip unit mounting base.

gic 5.0
Microlo

Must be seated

7 lb-in
[0.8 Nm]

7. Use a torque-controlled screwdriver to drive


the top screw to 7 in-lbs (0.8 Nm) 10%.
Mounting tab must be flush with the
mounting standoff and sensor plug.

NOTE: The face of the closed switch cover must


be flush with adjoining mounting base surfaces.
If these surfaces are not flush, stop installation
and contact the local sales office for factory
authorized service.

Must be flush
06134081

C
Microlo

gic 5.0

NOTE: If you are upgrading from a Micrologic


2.0, 3.0 or 5.0 trip unit, the connector block must
be ordered separately (Part Number S33101).
See instructions shipped with the connector
block for installation into circuit breaker.
8. Install connector block (C) into top of trip unit.
9. Install adjustable rating plug into the trip unit.

Figure 94:

Install Adjustable Rating Plug

c. Gently push adjustable rating plug (B)


into new trip unit.

log
Micro

ic 5.0

06134833

b. Inspect mounting area for debris and


contamination.

06134832

a. Open switch cover (A) on new trip unit.


P

Micro

5.0
logic

d. Tighten adjustable rating plug mounting


screw (C). The plug will be drawn into
position flush with front face as screw is
tightened.
alarm
long

11. Close switch cover (A).

Circuit Breaker Accessory Cover


Replacement

20002012 Schneider Electric All Rights Reserved

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

10. Set trip unit switches and advanced


protection settings to values recorded above
or per coordination study results.
A

tr
(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

Replace circuit breaker accessory cover as directed in the Install


Accessories section of the circuit breaker instruction bulletin shipped with
the circuit breaker.

65-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 5Trip Unit Replacement

48049-137-05
Rev. 01, 07/2012

Trip Unit Installation Check


ENGLISH

Secondary Injection Testing

Field installation of a trip unit requires secondary injection testing with a FullFunction Test Kit. This will ensure that the newly-installed trip unit is
functioning properly. The test will require opening and closing the circuit
breaker. Follow the procedures outlined in the instruction bulletins shipped
with the circuit breaker and the Full-Function Test Kit.
1. Make sure the circuit breaker is isolated from all upstream and
downstream devices.
2. Perform secondary injection testing as outlined in the instruction bulletin
shipped with the test kit. Verify that all applicable trip unit functions are
operating properly.
3. Repeat step 2 with the circuit breaker in the open position.
NOTE: The test kit states that the circuit breaker should be closed when
performing the test. Do not close the circuit breaker for this step.
4. If any test fails, do not put the circuit breaker into service and contact the
local sales office for factory authorization service.

Primary Injection Testing

Primary injection testing is recommended to ensure that all trip system


connections have been correctly made. Perform primary injection testing
per the instructions in the Field Testing and Maintenance Guide, bulletin
0600IB1201.

Check Accessory Operation

1. Installed accessories Validate the proper operation of all installed


accessories. See the corresponding accessory instruction bulletins for
operational testing procedures.
2. Programmable contact module If circuit breaker has an M2C or M6C
programmable contact module installed, validate its proper operation.
See the corresponding accessory instruction bulletins for operational
testing procedures.
3. Zone selective interlocking If the circuit breaker is part of a ZSI system,
follow the zone selective interlocking test procedures as outlined in the
Full Function Test Kit instruction bulletin.
4. Communications If communication modules exist, validate circuit
breaker has re-established communications with the supervisor.

Trip Unit Setup

1. If an auxiliary power supply is being used for the Micrologic trip unit,
reconnect the auxiliary power supply.
2. Reset the trip unit switches and advanced protection settings to original
values, as recorded at the beginning of this section.

Circuit Breaker Reconnection

66-EN

Reconnect circuit breaker as directed in the circuit breaker instruction


bulletin shipped with the circuit breaker.

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 6Adjustable Rating Plug Replacement

ENGLISH

Section 6Adjustable Rating Plug Replacement

NOTE: To select correct replacement rating


plug, see the product catalog.

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

NOTE: Adjustable rating plug must be removed


when doing hi-pot testing. Adjustable rating plug
must be installed for voltage measurement. If
adjustable rating plug is removed, the circuit
breaker will default to a long-time pickup rating
of 0.4 x sensor size (In) and a long-time delay of
whatever setting was selected before the rating
plug was removed.

Apply appropriate personal protective equipment (PPE) and follow safe


electrical work practices. See NFPA 70E or CSA Z462.
This equipment must be installed and serviced only by qualified electrical
personnel.
Turn off all power supplying this equipment before working on or inside
equipment. Follow instructions shipped with circuit breaker to disconnect
and reconnect circuit breaker.
Replace all devices, doors and covers before returning equipment to
service.
Failure to follow this instruction will result in death or serious injury.

logic

5.0
Micro

logic

logic
Micro

06134831

Micro

Remove Adjustable Rating Plug

06134830

1. Disconnect circuit breaker as directed in the


circuit breaker instruction bulletin shipped
with the circuit breaker.

Figure 95:

06134783

Remove Rating Plug

5.0

5.0 P

2. Open switch cover (A).


3. Record switch settings in Appendix E (switch
settings and those set with graphic screen, if
applicable).

4. Unscrew plug mounting screw (B).


alarm
long

5. Remove adjustable rating plug (C).

2. Gently push in new rating plug (A).

Figure 96:

logic
Micro

tr

(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

Install New Adjustable Rating Plug

5.0 P

06134833

1. Inspect mounting area for debris and


contamination.

06134832

Install New Rating Plug

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

3. Tighten adjustable rating plug mounting


screw (B).

Micro

logic

5.0

B
A

4. Set trip unit settings to values recorded in


Appendix E or per coordination study results.

7 lb-in
[0.8 Nm]

5. Close switch cover (C).


alarm
long

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr
(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

20002012 Schneider Electric All Rights Reserved

67-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 7Battery Replacement

48049-137-05
Rev. 01, 07/2012

Section 7Battery Replacement

DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH

Disconnect circuit breaker as directed in the


circuit breaker instruction bulletin shipped with
the circuit breaker.

Apply appropriate personal protective equipment (PPE) and follow safe


electrical work practices. See NFPA 70E or CSA Z462.
This equipment must be installed and serviced only by qualified electrical
personnel.

Accessory Cover Removal

Turn off all power supplying this equipment before working on or inside
equipment. Follow instructions shipped with circuit breaker to disconnect
and reconnect circuit breaker.

Remove circuit breaker accessory cover as


directed in the Install Accessories section of the
circuit breaker instruction bulletin shipped with
the circuit breaker.

Replace all devices, doors and covers before returning equipment to


service.

Withstand Module Shifting

Figure 97:

NOTE: R-frame and NS1600bNS3200 circuit


breakers only.

06134083

Failure to follow this instruction will result in death or serious injury.

Loosen screws (A) securing withstand module


(B). Swing module to side to access trip unit
battery cover. Do not remove withstand module
connector.

Shift Withstand Module

06133372

1. Insert small screwdriver blade into battery


housing cover notch and rotate to slide
battery housing cover (A) out of trip unit.

Remove Battery Cover

06134857

Figure 98:

LITHIUM
LITHIUM BATTERY
BATTERY
3.6V
3.6V -- SL
SL -- 550/S
550/S
SONNENSCHEIN
SONNENSCHEIN

Battery Replacement

06133375

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

Replace Battery

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

4. Replace battery housing cover (C).

Figure 99:

06133374

3. Insert new battery (B). Make sure that the


polarity is correct.

06133373

2. Remove battery (A).

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

ENGLISH

Circuit Breaker Disconnection

68-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Replace withstand module (A). Tighten screws


(B) securing withstand module.

ENGLISH

NOTE: R-frame and NS1600bNS3200 circuit


breakers only.

Figure 100: Replace Withstand Module

06124084

Withstand Module Replacement

Micrologic 5.0P and 6.0P Electronic Trip Units


Section 7Battery Replacement

B
5 lb-in
[0.6 Nm]

Accessory Cover Replacement

Replace circuit breaker accessory cover as directed in the Install


Accessories section of the circuit breaker instruction bulletin shipped with
the circuit breaker.

Circuit Breaker Reconnection

Reconnect circuit breaker as directed in the circuit breaker instruction


bulletin shipped with the circuit breaker.

20002012 Schneider Electric All Rights Reserved

69-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix AGraphic Display Flowcharts

48049-137-05
Rev. 01, 07/2012

Appendix AGraphic Display Flowcharts


ENGLISH

Metering Menu Flowchart

(A)

(V)

(kW)

(kWh)

(Hz)

(A)

(V)
Instant.

Instant.
Ia, Ib, Ic, In
Ia
Ib
Ic
In

=
=
=
=
I =

356 A
147 A
158 A
0A
212 A

Max
Ia
Ib
Ic
In
I

Vab = 429 V
Vbc = 430 V
Vca = 399 V

359 A
153 A
188 A
0A
214 A

Reset (- / +)
Demand

Instant.
P, Q, S

E. Q (kvarh)
513

(kVAR)
83

E. S

(kVAh)
545

(kVA)
86

E. P

(kWh)
155

-0.29

E in

E. Q (kvarh)
514

Demand
E out
P, Q, S
E. P

'): A,C,B

(kw)
25

(kVAR)
77

(kVA)
83

(kWh)
0

E. Q (kvarh)
0
Reset
energy
Are you sure?

Max
P

(kw)
26

(kVAR)
81

(kVA)
86

Max
15 min
Ia = 357 A
Ib = 148 A
Ic = 155 A
In =
0A

(kWh)
155

(kw)
27

Ia, Ib, Ic, In


15 min
351 A
Ia =
Ib =
145 A
156 A
Ic =
In =
84 A

E. P

Power
factor

(Hz)
60.0

Unbal 3)

Phase
rotation

(kWh)
E total

Average 3)

-4%

(kW)

Van = 246 V
Vbn = 241 V
Vcn = 242 V

419 V
=
=
=
=
=

No
Yes

Reset (- / +)

Reset (- / +)

70-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix AGraphic Display Flowcharts

ENGLISH

06134793

Maintenance Menu Flowchart


History
Logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Contacts
M2C / M6C

History logs
Trip history

Alarm Type

Ii

S1
date
Ii 7200 A
Ia =
Ib =
Ic =
In =

0A
0A
0A
0A

Choose type
S2
Choose type
Repeat for all contacts

Vmin
Setup
Date
12:03:33 am
V min 100 V

Choose mode
S2

Choose mode
date
I 7200 A
Ia = 0 A
Ib = 0 A
Ic =
0A
In = 0 A

Vmin

Language
Deutsch
English US
English UK
Espanol
Francais
Date / time
Date
01 / 02 / 2000
Time
06:12:35pm

Metering
setup
System type
choose type
Current demand
Calculation
method
Window type
Interval
Power demand

S1

Repeat for all history


Alarm history

Micrologic
setup

Repeat for all contacts

Breaker
selection
Standard

Window type

Circuit breaker

Interval

Type
Circuit breaker
Number

Reset
S1
S2
Reset (- / +)

Date
12:03:33 am
V min 100 V
Repeat for all history
Operation
counter
Contact wear

Calculation
method

Com.
setup
Com. parameters
Address
Baud rate
Parity
Remote access
Access permit
Access code
Remote control

Sign
convention
Choose sign
convention

Power sign
Choose current
flow direction
VT ratio
Primary
Secondary
System
frequency
Choose frequency

20002012 Schneider Electric All Rights Reserved

71-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix AGraphic Display Flowcharts

48049-137-05
Rev. 01, 07/2012

Protection Menu Flowchart


ENGLISH

Amperage
protection
Voltage
protection
Other
protection

Amperage
protection

Load
shedding

Load
shedding

P
P

Mode
(trip/alarm/off)

Pickup

Pickup

Pickup

Pickup

Dropout

Dropout

Dropout

Dropout

Idmtl

(A)

Mode
(trip/alarm/off)

(A)

Alarm

Load
shedding

Mode
(on/off)

(V)

(A)

Mode
(on/off)

Vmin

Ineutral (A)

Load
shedding

Other
protection

Voltage
protection

Vmax

(V)

rPmax (W)

Fmin

(Hz)

Iunbal

(%)

Mode
(trip/alarm/off)

Mode
(trip/alarm/off)

Iamax

(A)

Pickup

Pickup

Ibmax

(A)

Dropout

Dropout

Icmax

(A)

Vunbal (%)

Fmax (Hz)

Inmax

(A)

Mode
(trip/alarm/off)

Mode
(trip/alarm/off)

Pickup

Pickup

Dropout

Dropout
Phase
rotation
Mode
(alarm/off)
Phase order

72-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix BDefault Settings and Tolerances

Default Settings

Table 12:

Table 11:

ENGLISH

Appendix BDefault Settings and Tolerances

Default SettingsSwitches

Description

Symbol

Long-time pickup

Ir

Default Value
Maximum

Long-time delay

tr

Minimum

Short-time pickup

Isd

Minimum

Short-time delay

tsd

Minimum

Ground-fault pickup

Ig

Minimum

Ground-fault delay

tg

Minimum

Instantaneous

Ii

Minimum

Default SettingsMaintenance

Submenu
M2C/M6C contacts

Description

Line Item

Default Value

Setting Range

Alarm type

S#

Not selected

Not selected, Isd, Ir, Iunbal (SeeTable 9)

Setup

S#

Latching

Latching contact, time delay, non-latching contact,


Locked 0, Locked 1

English US

Deutsch, English US, English UK, Espanol, Francais

Standard

NA

Not def, ANSI, IEC, UL, IEC/GB

Circuit breaker

NA

Language
Date/Time

Breaker selection
Micrologic setup

Type

NA

Circuit breaker number

0000

Power sign
VT ratio

P+, P-

Primary

690

000690

Secondary

690

000690

System frequency

50-60 Hz

50-60 Hz, 400 Hz

System type

3) 4 w 4 CT

3) 4w 4CT, 3) 4w 3CT, 3) 3w 3CT

Current demand
Metering setup

0000FFFF

P+

Power demand

Interval

15 min.

560 min

Window type

Sliding

Sliding, block

Interval

Sign convention

15 min.

560 min

IEEE

IEEE, IEEE alt, IEC

Com parameter
Com setup

Remote access

No

Yes, no

Remote control

Auto

Auto, manual

20002012 Schneider Electric All Rights Reserved

73-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix BDefault Settings and Tolerances

Table 13:

ENGLISH

Submenu

48049-137-05
Rev. 01, 07/2012

Default SettingsProtection
Description

Symbol

Line Item

Default Value

Setting Range

Tolerance

Long-time pickup

Ir

Maximum

10%

Long-time delay

tr

Minimum

-20%, +0%
10%

Short-time pickup

Isd

Minimum

Short-time delay

tsd

Minimum

Instantaneous

Ii

Ground-fault alarm (5.0P trip unit)

Minimum

Ground-fault (6.0P trip unit)

Neutral current

Ineutral

Ground-fault alarm

Current unbalance

alarm

Iunbal

Amperage
protection

Max. phase A demand current

Max. phase B demand current

Max. phase C demand current

Max. neutral demand current

10%

No protection

Iamax

Ibmax

Icmax

Inmax

Mode

Trip

Trip

Pickup

Switch setting

In d 400 A: 30%100% In
400 < In d 1200 A: 20%100% In
1200 A < In: 500 A1200 A

10%

Pickup delay

Switch setting

140 sec.

-20%, +0%

Off

Off, N/2, N, 1.6N

Mode

Off

Alarm, off

Pickup

1200 A

20 x In1200 A

Pickup delay

10.0 sec.

1.010.0 sec.

-20%, +0%

Dropout

1200 A

20 Apickup

15%
-20%, +0%

Dropout delay

1.0 sec.

1.010.0 sec.

Mode

Off

Alarm, trip, off

15%

Pickup %

60%

560%

Pickup delay

40 sec.

140 sec.

-10%, +0%
-20%, +0%

Dropout %

Iunbal pickup %

5%pickup %

-10%, +0%
-20%, +0%

Dropout delay

10 sec.

10360 sec.

Mode

Off

Alarm, trip, off

Pickup

In

0.2 x In In

Pickup delay

1500 sec.

151500 sec.

-20%, +0%

Dropout

Iamax pickup

0.2 x Inpickup

6.6%
-20%, +0%

6.6%

Dropout delay

15 sec.

153000 sec.

Mode

Off

Alarm, trip, off

Pickup

In

0.2 x InIn

Pickup delay

1500 sec.

151500 sec.

-20%, +0%

Dropout

Ibmax Pickup

0.2 x Inpickup

6.6%
-20%, +0%

6.6%

Dropout delay

15 sec.

153000 sec.

Mode

Off

Alarm, trip, off

Pickup

In

0.2 x InIn

Pickup delay

1500 sec.

151500 sec.

-20%, +0%

Dropout

Icmax pickup

0.2 x Inpickup

6.6%
-20%, +0%

6.6%

Dropout delay

15 sec.

153000 sec.

Mode

Off

Alarm, trip, off

Pickup

In

0.2 x InIn

Pickup delay

1500 sec.

151500 sec.

-20%, +0%

Dropout

Inmax pickup

0.2 x Inpickup

6.6%

Dropout delay

15 sec.

153000 sec.

6.6%

-20%, +0%
Continued on next page

74-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Submenu

Default SettingsProtection (continued)


Description

Minimum (under) voltage

Voltage
protection

Maximum (over) voltage

Voltage unbalance

Reverse power

Other protection

Minimum (under) frequency

Maximum (over) frequency

Phase rotation

Load shedding I

Phase rotation

Load shedding I

Load shedding P Load shedding P

Symbol

Vmin

Vmax

Vunbal

rP

Fmin

Fmax

Line Item

Default Value

Setting Range

Mode

Off

Alarm, trip, off

Tolerance

Pickup

100 V

100 VVmax pickup

-5%, +0%

Pickup delay

5 sec.

1.25 sec.

-0%, +20%

Dropout

Vmin pickup

Vmin pickup1200 A

-5%, +0%

Dropout delay

1.2 sec.

1.236 sec.

-0%, +20%

Mode

Off

Alarm, trip, off

Pickup

725 V

Vmin1200 A

Pickup delay

5 sec.

1.25 sec.

-0%, +20%

Dropout

Vmax pickup

100Vmax pickup

-0%, +5%
-0%, +20%

-0%, +5%

Dropout delay

1.2 sec.

1.236 sec.

Mode

Off

Alarm, trip, off

Pickup

20%

220%*

-10%, +0%

Pickup delay

40 sec.

140 sec.

-20%, +0%

Dropout

Vunbal pickup

2%Vunbal pickup

-10%, +0%

Dropout delay

10 sec.

10360 sec.

-20%, +0%

Mode

Off

Alarm, trip, off

Pickup

500 kW

5500kW

Pickup delay

20 sec.

0.220 sec.

-0%, +20%

Dropout

rP pickup

5kWrP pickup

2.5%

Dropout delay

1 sec.

1360 sec.

-0%, +20%

Mode

Off

Alarm, trip, off

Pickup

45 Hz

45 HzFmax pickup

Pickup delay

5 sec.

0.25 sec.

-0%, +20%

Dropout

Fmin pickup

Fmin Pickup440 Hz

0.5 Hz
-0%, +20%

2.5%

0.5 Hz

Dropout delay

1 sec.

136 sec.

Mode

Off

Alarm, trip, off

Pickup

65 Hz

Fmin Pickup440 Hz

Pickup delay

5 sec.

0.25 sec.

-0%, +20%

Dropout

Fmax pickup

45 HzFmax pickup

0.5 Hz

Dropout delay

1 sec.

136 sec.

-0%, +20%

Sequence

Phase A, phase C,
phase B direction

Phase A, phase B, phase C direction


or phase A, phase C, phase B
direction

Mode

Off

Off, alarm

Mode

Off

Off, on

Pickup %

100% Ir

50% Ir100% Ir

6%

Pickup delay %

80% tr

2080% tr

-20%, +0%

Dropout %

Load shedding I
pickup

30%Load shedding I pickup %

6%

Dropout delay

10 sec.

10600 sec.

-20%, +0%

Mode

Off

Off, On

0.5 Hz

Pickup

10,000 kW

20010,000 kW

2.5%

Pickup delay

3600 sec.

103600 sec.

-20%, +0%

Dropout

Load shedding P
pickup

100 kWLoad shedding P pickup %

2.5%

Dropout delay

10 sec.

103600 sec.

-20%, +0%

Do not adjust above 20%

20002012 Schneider Electric All Rights Reserved

75-EN

ENGLISH

Table 13:

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix BDefault Settings and Tolerances

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix BDefault Settings and Tolerances

48049-137-05
Rev. 01, 07/2012

Metering Range and Accuracy


ENGLISH

Table 14:
Item

Instantaneous
Current

Demand Current

Voltage

Instantaneous
Power
Power Factor

Demand Power

Energy Total

Energy In

Energy Out
Frequency

76-EN

Metering Range and Accuracy


Description

Symbol

Range

Tolerance

Instantaneous current in A phase

Ia

032 kA

1.5%

Instantaneous current in B phase

Ib

032 kA

1.5%

Instantaneous current in C phase

Ic

032 kA

1.5%

Instantaneous current in neutral

In

032 kA

1.5%

Instantaneous current in ground

032 kA

1.5%

Max. instantaneous current in A phase

Iamax

032 kA

1.5%

Max. instantaneous current in B phase

Ibmax

032 kA

1.5%

Max. instantaneous current in C phase

Icmax

032 kA

1.5%

Max. instantaneous current in neutral

Inmax

032 kA

1.5%

Max. instantaneous current in ground

032 kA

1.5%

Demand current in A phase

Ia

032 kA

1.5%

Demand current in B phase

Ib

032 kA

1.5%

Demand current in C phase

Ic

032 kA

1.5%

Demand current in neutral

In

032 kA

1.5%

Max. demand current in A phase

Iamax

032 kA

1.5%

max

Max. demand current in B phase

Ibmax

032 kA

1.5%

Max. demand current in C phase

Icmax

032 kA

1.5%

Max. demand current in neutral

Inmax

032 kA

1.5%

Phase-to-phase instantaneous voltage between A and B phase

Vab

01200 V

0.5%

Phase-to-phase instantaneous voltage between B and C phase

Vbc

01200 V

0.5%

Phase-to-phase instantaneous voltage between C and A phase

Vca

01200 V

0.5%

Phase-to-phase instantaneous voltage between A and neutral phase

Van

01200 V

0.5%

Phase-to-phase instantaneous voltage between B and neutral phase

Vbn

01200 V

0.5%

Phase-to-phase instantaneous voltage between C and neutral phase

Vcn

01200 V

0.5%

Average phase-to-phase voltage

V avg 3)

01200 V

0.5%

Voltage unbalance

V unbal 3)

0100 V

0.5%

Instantaneous active power

032 MW

2%

Instantaneous reactive power

032 Mvar

2%

Instantaneous apparent power

032 MVA

2%
0.01%

Power factor

PF

-11

Active demand power

032 MW

2%

Reactive demand power

032 Mvar

2%

Apparent demand power

032 MVA

2%

Max. active demand power since last reset

Pmax

032 MW

2%

Max. reactive demand power since last reset

Qmax

032 Mvar

2%

Max. apparent demand power since last reset

Smax

032 MVA

2%

Total active power

E. P

-10101010 Kwh

2%

Total reactive power

E. Q

-10101010 Kvarh

2%

Total apparent power

E. S

-10101010 KVAh

2%

Total active power in

E. P

-1010 1010 Kwh

2%

Total reactive power in

E. Q

-10101010 Kvarh

2%

Total active power out

E. P

-10101010 Kwh

2%

Total reactive power out

E. Q

-10101010 Kvarh

2%

System frequency

45440 Hz

0.1 Hz

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

Remotely Readable Values

Table 15:
Item

The communication option can be used to


remotely access the Micrologic trip unit, using
System Manager Software (SMS) (version 3.3
or later) or other network system management
software. See the product catalog for more
information on the SMS software.

Current

Demand
Currents

ENGLISH

Appendix CNetwork/Com Access

Remotely Readable Values


Description

Symbol

Instantaneous current in A phase

Ia

Instantaneous current in B phase

Ib

Instantaneous current in C phase

Ic

Instantaneous current in neutral

In

Instantaneous current in ground

Average current in A phase

Iaavg

Average current in B phase

Ibavg

Average current in C phase

Icavg

Average current in neutral

Inavg

Average current in ground

Maximum instantaneous current in A phase

Iamax

Maximum instantaneous current in B phase

Ibmax

avg

Maximum instantaneous current in C phase

Icmax

Maximum instantaneous current in neutral

Inmax

Maximum instantaneous current in ground

Instantaneous current unbalance in A phase

Iaunbal

max

Instantaneous current unbalance in B phase

Ibunbal

Instantaneous current unbalance in C phase

Icunbal

Instantaneous current unbalance in neutral

Inunbal

Maximum instantaneous current unbalance

Iunbal max

Demand current in A phase

Ia

Demand current in B phase

Ib

Demand current in C phase

Ic

Demand current in neutral

In

Max. demand current since last reset in A phase

Iamax

Max. demand current since last reset in B phase

Ibmax

Max. demand current since last reset in C phase

Icmax

Max. demand current since last reset in neutral

Inmax

Time stamping of demand current max.

Voltage

Active Power

Instantaneous voltage between A and B phase

V inst Vab

Instantaneous voltage between B and C phase

V inst Vbc

Instantaneous voltage between C and A phase

V inst Vca

Instantaneous voltage between A and neutral phase

V inst Van

Instantaneous voltage between B and neutral phase

V inst Vbn

Instantaneous voltage between C and neutral phase

V inst Vcn

Average phase-to-phase voltage

V avg Vpp

Average phase-to-neutral voltage

V avg Vpn

Voltage unbalance between Vab and mean

V unbal Vab

Voltage unbalance between Vbc and mean

V unbal Vbc

Voltage unbalance between Vca and mean

V unbal Vca

Voltage unbalance between Van and mean

V unbal Van

Voltage unbalance between Vbn and mean

V unbal Vbn

Voltage unbalance between Vcn and mean

V unbal Vcn

Max. phase-to-phase voltage unbalance

V max unbal Vpp

Max. phase-to-neutral voltage unbalance

V max unbal Vpn

Instantaneous active power per phase

P
Continued on next page

20002012 Schneider Electric All Rights Reserved

77-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

48049-137-05
Rev. 01, 07/2012

Table 15:

ENGLISH

Item

Demand
Power

Remotely Readable Values (continued)


Description

Symbol

Active demand power

Reactive demand power

Apparent demand power

Max. active demand power since last reset

Pmax

Max. reactive demand power since last reset

Qmax

Max. apparent demand power since last reset

Smax

Predicted active demand power at end of window


Predicted reactive demand power at end of window
Predicted apparent demand power at end of window
Time stamping of demand power max.
Total active energy
Energy

Active energy in
Active energy out

Fault values
Frequency

Fault type
Interrupted current values
System frequency

Interval between last update of real-time values and the current


Update dates table
Update date of demand currents, demand power and energy
Trip history
History

Alarm history
Event history
Contact wear

Counters

Operation counter since last reset


Date/time of last operation counter reset
Operation counter total (lifetime)
Setting of date and time
Password
Trip unit ID code
Trip unit ID name
Measurement calculation algorithm
Sign convention
Total-energy measurement mode

Setup

Scale factors
Demand-current calculation window interval
Power quality indication
Demand-power calculation mode
Demand-power calculation window interval
Battery-charge indication
Programmable contact assignments
Programmable contact setup
Continued on next page

78-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

Item

Remotely Readable Values (continued)


Description

Symbol

Circuit breaker rated current


Type of neutral protection
Long-time protection settings
Short-time protection settings
Instantaneous protection settings
Protection

Ground-fault protection settings


Current-unbalance protection settings
I

alarm settings

Maximum-current protection settings


Voltage protection settings
Other protective functions settings

20002012 Schneider Electric All Rights Reserved

79-EN

ENGLISH

Table 15:

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

List of Registers

48049-137-05
Rev. 01, 07/2012

To access available registers, the following address scheme applies

ENGLISH

Module Module Name

The quantities are listed in alphabetical order


according to the SMS topic name.
NOTE: A system scan rate of 500 ms or greater
is recommended to minimize communications
timeout issues.
Table 16:

Equation

Address Range

BCM

Circuit Breaker Communication Module

147

CCM

Cradle Communication Module

5197

PM

Protection Module (Internal to trip unit)

BCM + 100

101147

MM

Meter Module (Internal to trip unit)

BCM + 200

201247

BCM + 50

List of Registers1

SMS Topic Name User Description

Number of
Registers

Register

Module

810D_LDPU

Breaker LDPU in Progress

8862

PM

Scaling N/A

810DBrkrStatus

Breaker Status

661

BCM

Bit 0; ON = closed; OFF = open

810DBrkrTripStat

Breaker Trip Unit Status

661

BCM

Bit 2; ON = tripped; OFF = not tripped

BCM_SN

BCM Serial Number

516

BCM

ASCII text

BkrPos

Breaker Position

661

CCM

Bit 8 = disconnected
Bit 9 = connected
Bit 10 = test position

CFVAB

Crest Factor Voltage A-B

1119

MM

CFVAN

Crest Factor Voltage A-N

1122

MM

No Units Hundredths

CFVBC

Crest Factor Voltage B-C

1120

MM

No Units Hundredths

CFVBN

Crest Factor Voltage B-N

1123

MM

No Units Hundredths

CFVCA

Crest Factor Voltage C-A

1121

MM

No Units Hundredths

CFVCN

Crest Factor Voltage C-N

1124

MM

No Units Hundredths

DT_3Regs

Device Clock Date/Time

679

BCM

DTLastTrip

D/T of Last Trip

693

BCM

DTPkIAD

D/T Peak Demand Current A

3005

MM

DTPkIBD

D/T Peak Demand Current B

3008

MM

DTPkICD

D/T Peak Demand Current C

3011

MM

DTPkIND

D/T Peak Demand Current N

3014

MM

DTPkKFDA

D/T K-Factor Dmd Peak A

3041

MM

No Units

DTPkKFDB

D/T K-Factor Dmd Peak B

3044

MM

No Units

DTPkKFDC

D/T K-Factor Dmd Peak C

3047

MM

No Units

DTPkKFDN

D/T K-Factor Dmd Peak N

3050

MM

No Units

DTPkkVAD

D/T Peak Demand Apparent Power

3023

MM

DTPkkVARD

D/T Peak Demand Reactive Power

3020

MM

DTPkkWD

D/T Peak Demand Active Power

3017

MM

DTResetEnergy

D/T Last Reset Accum. Energies

3038

MM

DTResetMinMax

D/T Last Reset Min/Max

3032

MM

DTResetPkID

D/T Last Reset Peak Dmd Currents

3026

MM

DTResetPkkWD

D/T Last Reset Peak Dmd Power

3029

MM

2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format
2
3-register date/time format

EnableCloseBkr

Remote Closing Enabled

669

BCM

Bit 2; ON = enabled, OFF = not enabled

EnableOpenBkr

Remote Opening Enabled

669

BCM

Bit 1; ON = enabled; OFF = not enabled

Units

Scale

No Units Hundredths

Continued on next page


1
For register entries that are not listed and scale factor information, refer to bulletin 0613IB1201, Modbus Communications System. Contact your local sales representative.
2

3-register date/time format:register 1: month (byte 1) = 112; day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year);
hour (byte 2) = 023; register 3: minutes (byte 1) = 059; seconds (byte 2) = 059
Note: Bits 14 and 15 of the month/day register must be masked.
3Power factor format: 1 to 999 for lagging power factors, 1000 for unity power factor 1.000, and 1 to 999 for leading power factors.
4
Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999).
Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.

80-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

List of Registers1

SMS Topic Name User Description

Number of
Registers

Register

Module

EnableRemCtrl

Remote Control Enabled

669

BCM

Units

ENGLISH

Table 16:

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

Scale
Bit 3; ON = auto (enabled);
OFF = manual (not enabled)

fkVAA

Fundamental Apparent Power A

1084

MM

kVA

Scale E

fkVAB

Fundamental Apparent Power B

1085

MM

kVA

Scale E

fkVAC

Fundamental Apparent Power C

1086

MM

kVA

Scale E

fkVATtl

Fundamental Apparent Power Total

1087

MM

kVA

Scale E

fVAngA

Fundamental Voltage Ang A-B/A-N

1133

MM

Deg

Tenths

fVAngB

Fundamental Voltage Ang B-C/B-N

1134

MM

Deg

Tenths

fVAngC

Fundamental Voltage Ang C-A/C-N

1135

MM

Deg

Tenths

GFAlarmStatus

GF Alarm Status

8860

PM

Bit 0; ON = active; OFF = inactive

GFPreAlarmStatus

GF Alarm Pre-Alarm Status

8864

PM

Bit 0; ON = active; OFF = inactive

Hz

Frequency

1054

MM

Hz

Scale F

IA

Current A

1016

MM

Scale A - Phase Current

IA_PCT

Current A % Load

8837

PM

Unity

IAD

Demand Current A

2200

MM

Scale A

IAppA

Current Apparent A

1023

MM

Scale A

IAppB

Current Apparent B

1024

MM

Scale A

IAppC

Current Apparent C

1025

MM

Scale A

IAppN

Current Apparent N

1026

MM

Scale B

IAvg

Current Avg

1027

MM

Scale A - Phase Current

IB

Current B

1017

MM

Scale A - Phase Current

IB_PCT

Current B % Load

8838

PM

Unity

IBD

Demand Current B

2201

MM

Scale A

IC

Current C

1018

MM

Scale A - Phase Current

IC_PCT

Current C % Load

8839

PM

Unity

ICD

Demand Current C

2202

MM

Scale A

IDatPkKFD_A

Current Demand at Peak K-Factor Demand A

2270

MM

Scale A

IDatPkKFD_B

Current Demand at Peak K-Factor Demand B

2271

MM

Scale A

IDatPkKFD_C

Current Demand at Peak K-Factor Demand C

2272

MM

Scale A

IDatPkKFD_N

Current Demand at Peak K-Factor Demand N

2273

MM

Scale B

IG

Current G

1021

MM

Scale C

IG_PCT

Current G % Load

8841

PM

Unity

IG_PCT_VIGI

Current G (VIGI) % Load

8842

PM

Hundredths

IG_VIGI

Current G (VIGI)

8826

PM

Thousandths

IMax

Current Max Present

1020

MM

Scale A - Phase Current

IN

Current N

1019

MM

Scale B - Neutral Current

IN_PCT

Current N % Load

8840

PM

Unity

IND

Demand Current N

2203

MM

Scale B

IUnbalA

Current Unbalance A

1028

MM

IUnbalAlrm

Current Unbalance Alarm Status

8859

PM

Tenths
Bit 0; ON = active; OFF = inactive
Continued on next page

1
For register entries that are not listed and scale factor information, refer to bulletin 0613IB1201, Modbus Communications System. Contact your local sales representative.
2

3-register date/time format:register 1: month (byte 1) = 112; day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year);
hour (byte 2) = 023; register 3: minutes (byte 1) = 059; seconds (byte 2) = 059
Note: Bits 14 and 15 of the month/day register must be masked.
3Power factor format: 1 to 999 for lagging power factors, 1000 for unity power factor 1.000, and 1 to 999 for leading power factors.
4Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999).
Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.

20002012 Schneider Electric All Rights Reserved

81-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

Table 16:

48049-137-05
Rev. 01, 07/2012

List of Registers1

ENGLISH

SMS Topic Name User Description

Number of
Registers

Register

Module

Units

Scale

IUnbalB

1029

MM

Tenths

Current Unbalance B

IUnbalC

Current Unbalance C

1030

MM

IUnbalPreAlrm

Current Unbalance Pre-Alarm Status

8863

PM

Tenths
Bit 0; ON = active, OFF = inactive

IUnbalW

Current Unbalance Worst

1032

MM

KFDatPkID_A

K-Factor Demand at Peak Demand Current A

2254

MM

No Units Tenths

Tenths

KFDatPkID_B

K-Factor Demand at Peak Demand Current B

2255

MM

No Units Tenths

KFDatPkID_C

K-Factor Demand at Peak Demand Current C

2256

MM

No Units Tenths

KFDatPkID_N

K-Factor Demand at Peak Demand Current N

2257

MM

No Units Tenths

KFDN

K-Factor Demand N

2215

MM

No Units Tenths

KFN

K-Factor N

1118

MM

No Units Tenths

kVAA

Apparent Power A

1042

MM

kVA

Scale E

kVAB

Apparent Power B

1043

MM

kVA

Scale E

kVAC

Apparent Power C

1044

MM

kVA

Scale E

kVAD

Demand Apparent Power

2236

MM

kVA

Scale D

kVAD_PkkVARD

KVA Dmd Coincident w/Peak KVAR Dmd

2235

MM

kVA

Scale D

kVAD_PkkWD

KVA Dmd Coincident w/Peak KW Dmd

2229

MM

kVA

Scale D

kVAHr

Apparent Energy

2024

MM

kVAH

Unity

kVARA

Reactive Power A

1038

MM

kVAR

Scale E

kVARB

Reactive Power B

1039

MM

kVAR

Scale E

kVARC

Reactive Power C

1040

MM

kVAR

Scale E

kVARD

Demand Reactive Power

2230

MM

kVAR

Scale D

kVARD_PkkVAD

KVAR Dmd Coincident w/Peak KVA Dmd

2241

MM

kVAR

Scale D

kVARD_PkkWD

KVAR Dmd Coincident w/Peak KW Dmd

2228

MM

kVAR

Scale D

kVARHr

Reactive Energy

2004

MM

kVARH

Unity

kVARHr_I

Reactive Energy Into the Load

2016

MM

kVARH

Unity

kVARHr_O

Reactive Energy Out of the Load

2020

MM

kVARH

Unity

kVARTtl

Reactive Power Total

1041

MM

kVAR

Scale E

kVATtl

Apparent Power Total

1045

MM

kVA

Scale E

kWA

Active Power A

1034

MM

kW

Scale E

kWB

Active Power B

1035

MM

kW

Scale E

kWC

Active Power C

1036

MM

kW

Scale E

kWD

Demand Active Power

2224

MM

kW

Scale D

kWD_PkkVAD

KW Dmd Coincident w/Peak KVA Dmd

2240

MM

kW

Scale D

kWD_PkkVARD

KW Dmd Coincident w/Peak KVAR Dmd

2234

MM

kW

Scale D

kWHr

Real Energy

2000

MM

kWH

Unity

kWHr_I

Real Energy Into the Load

2008

MM

kWH

Unity

kWHr_O

Real Energy Out of the Load

2012

MM

kWH

Unity

kWTtl

Active Power Total

1037

MM

kW

Scale E

LDPUValue

Long Delay Pickup Value

8756

PM

Unity

LSCurrAlrm

Load Shed Current Alarm Status

8859

PM

Bit 13; ON = active; OFF = inactive


Continued on next page

1For register entries that are not listed and scale factor information, refer to bulletin 0613IB1201, Modbus Communications System. Contact your local sales representative.
23-register date/time format:register 1: month (byte 1) = 112; day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year);

hour (byte 2) = 023; register 3: minutes (byte 1) = 059; seconds (byte 2) = 059
Note: Bits 14 and 15 of the month/day register must be masked.

3Power factor format: 1 to 999 for lagging power factors, 1000 for unity power factor 1.000, and 1 to 999 for leading power factors.
4Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999).

Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.

82-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

List of Registers1

SMS Topic Name User Description

Number of
Registers

Register

Module

LSCurrPreAlrm

Load Shed Current Pre-Alarm Status

8863

PM

LSPwrAlrm

Load Shed Power Alarm Status

8859

PM

Bit 14; ON = active; OFF = inactive

LSPwrPreAlrm

Load Shed Power Pre-Alarm Status

8863

PM

Bit 14; ON = active; OFF = inactive

M2C_M6CR1Status

Relay Module R1 Status

8857

PM

Bit 0; ON = on; OFF = off

M2C_M6CR2Status

Relay Module R2 Status

8857

PM

Bit 1; ON = on; OFF = off

M2C_M6CR3Status

Relay Module R3 Status

8857

PM

Bit 2; ON = on; OFF = off

M2C_M6CR4Status

Relay Module R4 Status

8857

PM

Bit 3; ON = on; OFF = off

M2C_M6CR5Status

Relay Module R5 Status

8857

PM

Bit 4; ON = on; OFF = off

M2C_M6CR6Status

Relay Module R6 Status

8857

PM

Bit 5; ON = on; OFF = off

MaxCFVAB

Maximum Crest Factor Voltage A-B

1719

MM

No Units Hundredths

MaxCFVAN

Maximum Crest Factor Voltage A-N

1722

MM

No Units Hundredths

MaxCFVBC

Maximum Crest Factor Voltage B-C

1720

MM

No Units Hundredths

MaxCFVBN

Maximum Crest Factor Voltage B-N

1723

MM

No Units Hundredths

MaxCFVCA

Maximum Crest Factor Voltage C-A

1721

MM

No Units Hundredths

MaxCFVCN

Maximum Crest Factor Voltage C-N

1724

MM

No Units Hundredths

Units

Scale
Bit 13; ON = active; OFF = inactive

MaxfkVAA

Maximum Fundamental Apparent Power A

1684

MM

kVA

Scale E

MaxfkVAB

Maximum Fundamental Apparent Power B

1685

MM

kVA

Scale E

MaxfkVAC

Maximum Fundamental Apparent Power C

1686

MM

kVA

Scale E

MaxfkVATtl

Maximum Fundamental Apparent Power Total 1

1687

MM

kVA

Scale E

MaxfVMagAB

Maximum Fundamental Voltage Mag A-B

1656

MM

Scale D

MaxfVMagAN

Maximum Fundamental Voltage Mag A-N

1659

MM

Scale D

MaxfVMagBC

Maximum Fundamental Voltage Mag B-C

1657

MM

Scale D

MaxfVMagBN

Maximum Fundamental Voltage Mag B-N

1660

MM

Scale D

MaxfVMagCA

Maximum Fundamental Voltage Mag C-A

1658

MM

Scale D

MaxfVMagCN

Maximum Fundamental Voltage Mag C-N

1661

MM

Scale D

MaxHz

Max Frequency

1654

MM

Hz

Scale F

MaxIA

Max Current A

1616

MM

Scale A - Phase Current

MaxIAppA

Maximum Current Apparent A

1623

MM

Scale A

MaxIAppB

Maximum Current Apparent B

1624

MM

Scale A

MaxIAppC

Maximum Current Apparent C

1625

MM

Scale A

MaxIAppN

Maximum Current Apparent N

1626

MM

Scale B

MaxIAvg

Max Current Avg

1627

MM

Scale A - Phase Current

MaxIB

Max Current B

1617

MM

Scale A - Phase Current

MaxIC

Max Current C

1618

MM

Scale A - Phase Current

MaxIG

Max Current G

1621

MM

Scale C

MaxIG_VIGI

Max Current G (VIGI)

8832

PM

Thousandths

MaxIN

Max Current N

1619

MM

Scale B - Neutral Current

MaxIUnbalA

Max Current Unbalance A

1628

MM

Tenths

MaxIUnbalB

Max Current Unbalance B

1629

MM

Tenths

MaxIUnbalC

Max Current Unbalance C

1630

MM

Tenths
Continued on next page

1For register entries that are not listed and scale factor information, refer to bulletin 0613IB1201, Modbus Communications System. Contact your local sales representative.
23-register date/time format:register 1: month (byte 1) = 112; day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year);

hour (byte 2) = 023; register 3: minutes (byte 1) = 059; seconds (byte 2) = 059
Note: Bits 14 and 15 of the month/day register must be masked.

3Power factor format: 1 to 999 for lagging power factors, 1000 for unity power factor 1.000, and 1 to 999 for leading power factors.
4Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999).

Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.

20002012 Schneider Electric All Rights Reserved

83-EN

ENGLISH

Table 16:

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

Table 16:

48049-137-05
Rev. 01, 07/2012

List of Registers1

ENGLISH

SMS Topic Name User Description

Number of
Registers

Register

Module

Units

Scale

MaxIUnbalW

1632

MM

Tenths

Max Current Unbalance Worst

MaxKFN

Maximum K-Factor N

1718

MM

No Units Tenths

MaxkVAA

Max Apparent Power A

1642

MM

kVA

MaxkVAB

Max Apparent Power B

1643

MM

kVA

Scale E

MaxkVAC

Max Apparent Power C

1644

MM

kVA

Scale E
Scale E

Scale E

MaxkVARA

Max Reactive Power A

1638

MM

kVAR

MaxkVARB

Max Reactive Power B

1639

MM

kVAR

Scale E

MaxkVARC

Max Reactive Power C

1640

MM

kVAR

Scale E

MaxkVARTtl

Max Reactive Power Total

1641

MM

kVAR

Scale E

MaxkVATtl

Max Apparent Power Total

1645

MM

kVA

Scale E

MaxkWA

Max Active Power A

1634

MM

kW

Scale E

MaxkWB

Max Active Power B

1635

MM

kW

Scale E

MaxkWC

Max Active Power C

1636

MM

kW

Scale E

kW

MaxkWTtl

Max Active Power Total

1637

MM

MaxPFA

Max Power Factor A

1646

MM

PF format

Scale E

MaxPFB

Max Power Factor B

1647

MM

PF format

MaxPFC

Max Power Factor C

1648

MM

PF format

MaxPFTtl

Max Power Factor Total

1649

MM

3
PF format

MaxVAB

Max Voltage A-B

1600

MM

Scale D - Voltage

MaxVAN

Max Voltage A-N

1603

MM

Scale D - Voltage

MaxVBC

Max Voltage B-C

1601

MM

Scale D - Voltage
Scale D - Voltage

3
3
3

MaxVBN

Max Voltage B-N

1604

MM

MaxVCA

Max Voltage C-A

1602

MM

Scale D - Voltage

MaxVCN

Max Voltage C-N

1605

MM

Scale D - Voltage

MaxVLLAvg

Max Voltage L-L Avg

1606

MM

Scale D - Voltage

MaxVLNAvg

Max Voltage L-N Avg

1607

MM

Scale D - Voltage

MaxVUnbalAB

Max Voltage Unbalance A-B

1608

MM

Tenths

MaxVUnbalAN

Max Voltage Unbalance A-N

1611

MM

Tenths

MaxVUnbalBC

Max Voltage Unbalance B-C

1609

MM

Tenths

MaxVUnbalBN

Max Voltage Unbalance B-N

1612

MM

Tenths

MaxVUnbalCA

Max Voltage Unbalance C-A

1610

MM

Tenths

MaxVUnbalCN

Max Voltage Unbalance C-N

1613

MM

Tenths

MaxVUnbalLLW

Max Voltage Unbalance L-L Worst

1614

MM

Tenths
Tenths

MaxVUnbalLNW

Max Voltage Unbalance L-N Worst

1615

MM

MinCFVAB

Minimum Crest Factor Voltage A-B

1419

MM

No Units Hundredths

MinCFVAN

Minimum Crest Factor Voltage A-N

1422

MM

No Units Hundredths

MinCFVBC

Minimum Crest Factor Voltage B-C

1420

MM

No Units Hundredths

MinCFVBN

Minimum Crest Factor Voltage B-N

1423

MM

No Units Hundredths

MinCFVCA

Minimum Crest Factor Voltage C-A

1421

MM

No Units Hundredths

MinCFVCN

Minimum Crest Factor Voltage C-N

1424

MM

No Units Hundredths
Continued on next page

1For register entries that are not listed and scale factor information, refer to bulletin 0613IB1201, Modbus Communications System. Contact your local sales representative.
23-register date/time format:register 1: month (byte 1) = 112; day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year);

hour (byte 2) = 023; register 3: minutes (byte 1) = 059; seconds (byte 2) = 059
Note: Bits 14 and 15 of the month/day register must be masked.

3Power factor format: 1 to 999 for lagging power factors, 1000 for unity power factor 1.000, and 1 to 999 for leading power factors.
4Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999).

Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.

84-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

List of Registers1

SMS Topic Name User Description

Number of
Registers

Register

Module

Units

Scale

MinfkVAA

Minimum Fundamental Apparent Power A

1384

MM

kVA

Scale E

MinfkVAB

Minimum Fundamental Apparent Power B

1385

MM

kVA

Scale E

MinfkVAC

Minimum Fundamental Apparent Power C

1386

MM

kVA

Scale E

MinfkVATtl

Minimum Fundamental Apparent Power Total

1387

MM

kVA

Scale E

MinfVMagAB

Minimum Fundamental Voltage Mag A-B

1356

MM

Scale D

MinfVMagAN

Minimum Fundamental Voltage Mag A-N

1359

MM

Scale D

MinfVMagBC

Minimum Fundamental Voltage Mag B-C

1357

MM

Scale D

ENGLISH

Table 16:

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

MinfVMagBN

Minimum Fundamental Voltage Mag B-N

1360

MM

Scale D

MinfVMagCA

Minimum Fundamental Voltage Mag C-A

1358

MM

Scale D

MinfVMagCN

Minimum Fundamental Voltage Mag C-N

1361

MM

Scale D

MinHz

Min Frequency

1354

MM

Hz

Scale F

MinIA

Min Current A

1316

MM

Scale A - Phase Current

MinIAppA

Minimum Current Apparent A

1323

MM

Scale A

MinIAppB

Minimum Current Apparent B

1324

MM

Scale A

MinIAppC

Minimum Current Apparent C

1325

MM

Scale A

MinIAppN

Minimum Current Apparent N

1326

MM

Scale B

MinIAvg

Min Current Avg

1327

MM

Scale A - Phase Current

MinIB

Min Current B

1317

MM

Scale A - Phase Current

MinIC

Min Current C

1318

MM

Scale A - Phase Current

MinIN

Min Current N

1319

MM

Scale B - Neutral Current

MinIUnbalA

Min Current Unbalance A

1328

MM

Tenths

MinIUnbalB

Min Current Unbalance B

1329

MM

Tenths

MinIUnbalC

Min Current Unbalance C

1330

MM

Tenths

MinIUnbalW

Min Current Unbalance Worst

1332

MM

Tenths

MinKFN

Minimum K-Factor N

1418

MM

No Units Tenths

MinkVAA

Min Apparent Power A

1342

MM

kVA

MinkVAB

Min Apparent Power B

1343

MM

kVA

Scale E

MinkVAC

Min Apparent Power C

1344

MM

kVA

Scale E

MinkVARA

Min Reactive Power A

1338

MM

kVAR

Scale E

MinkVARB

Min Reactive Power B

1339

MM

kVAR

Scale E

MinkVARC

Min Reactive Power C

1340

MM

kVAR

Scale E

MinkVARTtl

Min Reactive Power Total

1341

MM

kVAR

Scale E

MinkVATtl

Min Apparent Power Total

1345

MM

kVA

Scale E

MinkWA

Min Active Power A

1334

MM

kW

Scale E

MinkWB

Min Active Power B

1335

MM

kW

Scale E

MinkWC

Min Active Power C

1336

MM

kW

Scale E

MinkWTtl

Min Active Power Total

1337

MM

kW

Scale E

MinPFA

Min Power Factor A

1346

MM

MinPFB

Min Power Factor B

1347

MM

MinPFC

Min Power Factor C

1348

MM

Scale E

3
PF format
3
PF format
3
PF format
Continued on next page

1For register entries that are not listed and scale factor information, refer to bulletin 0613IB1201, Modbus Communications System. Contact your local sales representative.
23-register date/time format:register 1: month (byte 1) = 112; day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year);

hour (byte 2) = 023; register 3: minutes (byte 1) = 059; seconds (byte 2) = 059
Note: Bits 14 and 15 of the month/day register must be masked.

3Power factor format: 1 to 999 for lagging power factors, 1000 for unity power factor 1.000, and 1 to 999 for leading power factors.
4Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999).

Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.

20002012 Schneider Electric All Rights Reserved

85-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

Table 16:

48049-137-05
Rev. 01, 07/2012

List of Registers1

ENGLISH

SMS Topic Name User Description

Number of
Registers

Register

Module

MinPFTtl

Min Power Factor Total

1349

MM

MinVAB

Min Voltage A-B

1300

MM

MinVAN

Min Voltage A-N

1303

MM

Scale D - Voltage

MinVBC

Min Voltage B-C

1301

MM

Scale D - Voltage

MinVBN

Min Voltage B-N

1304

MM

Scale D - Voltage
Scale D - Voltage

Units

Scale
PF format

Scale D - Voltage

MinVCA

Min Voltage C-A

1302

MM

MinVCN

Min Voltage C-N

1305

MM

Scale D - Voltage

MinVLLAvg

Min Voltage L-L Avg

1306

MM

Scale D - Voltage

MinVLNAvg

Min Voltage L-N Avg

1307

MM

Scale D - Voltage

MinVUnbalAB

Min Voltage Unbalance A-B

1308

MM

Tenths

MinVUnbalAN

Min Voltage Unbalance A-N

1311

MM

Tenths

MinVUnbalBC

Min Voltage Unbalance B-C

1309

MM

Tenths

MinVUnbalBN

Min Voltage Unbalance B-N

1312

MM

Tenths

MinVUnbalCA

Min Voltage Unbalance C-A

1310

MM

Tenths

MinVUnbalCN

Min Voltage Unbalance C-N

1313

MM

Tenths

MinVUnbalLLW

Min Voltage Unbalance L-L Worst

1314

MM

Tenths

MinVUnbalLNW

Min Voltage Unbalance L-N Worst

1315

MM

Tenths

NominalCurrent

Breaker Nominal Current

8750

PM

OverFreqAlrm

Over Frequency Alarm Status

8859

PM

Bit 11; ON = active, OFF = inactive

Unity

OverFreqPreAlrm

Over Frequency Pre-Alarm Status

8863

PM

Bit 11; ON = active, OFF = inactive

OverIAAlrm

Over IA Demand Alarm Status

8859

PM

Bit 1; ON = active, OFF = inactive


Bit 1; ON = active, OFF = inactive

OverIAPreAlrm

Over IA Demand Pre-Alarm Status

8863

PM

OverIBAlrm

Over IB Demand Alarm Status

8859

PM

Bit 2; ON = active, OFF = inactive

OverIBPreAlrm

Over IB Demand Pre-Alarm Status

8863

PM

Bit 2; ON = active, OFF = inactive

OverICAlrm

Over IC Demand Alarm Status

8859

PM

Bit 3; ON = active, OFF = inactive


Bit 3; ON = active, OFF = inactive

OverICPreAlrm

Over IC Demand Pre-Alarm Status

8863

PM

OverINAlrm

Over IN Demand Alarm Status

8859

PM

Bit 4; ON = active, OFF = inactive

OverINPreAlrm

Over IN Demand Pre-Alarm Status

8863

PM

Bit 4; ON = active, OFF = inactive

OverVoltAlrm

Over Voltage Alarm Status

8859

PM

Bit 6; ON = active, OFF = inactive


Bit 6; ON = active, OFF = inactive

OverVoltPreAlrm

Over Voltage Pre-Alarm Status

8863

PM

PF_PkkVAD

PF Coincident w/Peak KVA Demand

2239

MM

Thousandths

PF_PkkVARD

PF Coincident w/Peak KVAR Demand

2233

MM

Thousandths

PF_PkkWD

PF Coincident w/Peak KW Demand

2227

MM

Thousandths
3
PF format
3
PF format
3
PF format
3
PF format

PFA

Power Factor A

1046

MM

PFB

Power Factor B

1047

MM

PFC

Power Factor C

1048

MM

PFTtl

Power Factor Total

1049

MM

PhaRotAlrm

Phase Rotation Alarm Status

8859

PM

PkIAD

Peak Demand Current A

2204

MM

Scale A

PkIBD

Peak Demand Current B

2205

MM

Scale A

Bit 12; ON = active, OFF = inactive

Continued on next page


1For register entries that are not listed and scale factor information, refer to bulletin 0613IB1201, Modbus Communications System. Contact your local sales representative.
23-register date/time format:register 1: month (byte 1) = 112; day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year);

hour (byte 2) = 023; register 3: minutes (byte 1) = 059; seconds (byte 2) = 059
Note: Bits 14 and 15 of the month/day register must be masked.

3Power factor format: 1 to 999 for lagging power factors, 1000 for unity power factor 1.000, and 1 to 999 for leading power factors.
4Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999).

Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.

86-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

List of Registers1

SMS Topic Name User Description

Number of
Registers

Register

Module

Units

Scale

PkICD

Peak Demand Current C

2206

MM

Scale A

PkIND

Peak Demand Current N

2207

MM

Scale A

PkKFDA

Peak K-Factor Demand A

2216

MM

No Units Tenths

PkKFDB

Peak K-Factor Demand B

2217

MM

No Units Tenths

PkKFDC

Peak K-Factor Demand C

2218

MM

No Units Tenths

PkKFDN

Peak K-Factor Demand N

2219

MM

No Units Tenths

PkkVAD

Peak Demand Apparent Power

2237

MM

kVA

Scale A

PkkVARD

Peak Demand Reactive Power

2231

MM

kVAR

Scale A

PkkWD

Peak Demand Active Power

2225

MM

kW

Scale A

PredIAD

Predicted Demand Current A

2208

MM

Scale A

PredIBD

Predicted Demand Current B

2209

MM

Scale A

ENGLISH

Table 16:

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

PredICD

Predicted Demand Current C

2210

MM

Scale A

PredIND

Predicted Demand Current N

2211

MM

Scale A

PredKFDA

Predicted K-Factor Demand A

2220

MM

No Units Tenths

PredKFDB

Predicted K-Factor Demand B

2221

MM

No Units Tenths

PredKFDC

Predicted K-Factor Demand C

2222

MM

No Units Tenths

PredKFDN

Predicted K-Factor Demand N

2223

MM

No Units Tenths

PredkVAD

Predicted KVA Demand

2238

MM

kVA

Scale A

PredkVARD

Predicted KVAR Demand

2232

MM

kVAR

Scale A

PredkWD

Predicted KW Demand

2226

MM

kW

Scale A

R1OpsCounter

Relay 1 Operations Counter

9081

PM

Unity

R2OpsCounter

Relay 2 Operations Counter

9082

PM

Unity

R3OpsCounter

Relay 3 Operations Counter

9083

PM

Unity

R4OpsCounter

Relay 4 Operations Counter

9084

PM

Unity

R5OpsCounter

Relay 5 Operations Counter

9085

PM

Unity

R6OpsCounter

Relay 6 Operations Counter

9086

PM

Unity

ReadyToClose

Breaker Ready to Close

661

BCM

Bit 5; ON = yes, OFF = no

RevPwrAlrm

Reverse Power Alarm Status

8859

PM

Bit 9; ON = active; OFF = inactive

RevPwrPreAlrm

Reverse Power Pre-Alarm Status

8863

PM

Bit 9; ON = active; OFF = inactive

TimeToTrip

Time Remaining to LT Trip

8865

PM

TU_BATT_PCT

Trip Unit % Battery

8843

PM

TU_SN

Trip Unit Serial Number

8700

PM

ASCII text

TUCommStatus

Trip Unit Internal Comms Status

552

BCM

Bit 11; ON = not responding; OFF = OK

UnderFreqAlrm

Under Frequency Alarm Status

8859

PM

Bit 10; ON = active; OFF = inactive

UnderFreqPreAlrm

Under Frequency Pre-Alarm Status

8863

PM

Bit 10; ON = active; OFF = inactive

UnderVoltAlrm

Under Voltage Alarm Status

8859

PM

Bit 5; ON = active; OFF = inactive

UnderVoltPreAlrm

Under Voltage Pre-Alarm Status

8863

PM

Bit 5; ON = active; OFF = inactive

Tenths
%

Unity

VAB

Voltage A-B

1000

MM

Scale D - Voltage

VAN

Voltage A-N

1003

MM

Scale D - Voltage

VBC

Voltage B-C

1001

MM

Scale D - Voltage
Continued on next page

1For register entries that are not listed and scale factor information, refer to bulletin 0613IB1201, Modbus Communications System. Contact your local sales representative.
23-register date/time format:register 1: month (byte 1) = 112; day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year);

hour (byte 2) = 023; register 3: minutes (byte 1) = 059; seconds (byte 2) = 059
Note: Bits 14 and 15 of the month/day register must be masked.

3Power factor format: 1 to 999 for lagging power factors, 1000 for unity power factor 1.000, and 1 to 999 for leading power factors.
4Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999).

Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.

20002012 Schneider Electric All Rights Reserved

87-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix CNetwork/Com Access

Table 16:

48049-137-05
Rev. 01, 07/2012

List of Registers1

ENGLISH

SMS Topic Name User Description

Number of
Registers

Register

Module

Units

Scale

VBN

Voltage B-N

1004

MM

Scale D - Voltage
Scale D - Voltage

VCA

Voltage C-A

1002

MM

VCN

Voltage C-N

1005

MM

VigiAlarm

Vigi Alarm Status

8860

PM

Bit 1; ON = active; OFF = inactive

VigiPreAlrm

Vigi Pre-Alarm Status

8864

PM

Bit 1; ON = active; OFF = inactive

Scale D - Voltage

VLLAvg

Voltage L-L Avg

1006

MM

Scale D - Voltage

VLNAvg

Voltage L-N Avg

1007

MM

Scale D - Voltage

VUnbalAB

Voltage Unbalance A-B

1008

MM

VUnbalAlrm

Voltage Unbalance Alarm Status

8859

PM

Tenths
Bit 7; ON = active, OFF = inactive

VUnbalAN

Voltage Unbalance A-N

1011

MM

Tenths

VUnbalBC

Voltage Unbalance B-C

1009

MM

Tenths

VUnbalBN

Voltage Unbalance B-N

1012

MM

Tenths

VUnbalCA

Voltage Unbalance C-A

1010

MM

Tenths

VUnbalCN

Voltage Unbalance C-N

1013

MM

Tenths

VUnbalLLW

Voltage Unbalance L-L Worst

1014

MM

Tenths

VUnbalLNW

Voltage Unbalance L-N Worst

1015

MM

VUnbalPreAlrm

Voltage Unbalance Pre-Alarm Status

8863

PM

Tenths
Bit 7; ON = active, OFF = inactive

1
For register entries that are not listed and scale factor information, refer to bulletin 0613IB1201, Modbus Communications System. Contact your local sales representative.
2

3-register date/time format:register 1: month (byte 1) = 112; day (byte 2) = 131; register 2: year (byte 1) = 0199 (add to 1900 to determine the actual year);
hour (byte 2) = 023; register 3: minutes (byte 1) = 059; seconds (byte 2) = 059
Note: Bits 14 and 15 of the month/day register must be masked.
3Power factor format: 1 to 999 for lagging power factors, 1000 for unity power factor 1.000, and 1 to 999 for leading power factors.
4
Modulo 10,000 format: 1 to 4 sequential registers. Each register is Modulo 10,000 (range = 9,999 to +9,999).
Result is [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. Range is zero to 9,999,999,999,999,999.

88-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix DTrip Unit Voltage Supply Architecture

The trip unit has an integral internal three-phase


voltage power supply which appears as a threephase delta configured load to the system
(Figure 101). This power supply is a three-phase
load by itself and will inject voltage on an open
phase (Figure 102). The impact of a three-phase
delta configured load on the voltage-based
protection functions is as follows:

The minimum (under) voltage protection


function is based on phase-to-phase voltage
measurement.

NOTICE
HAZARD OF EQUIPMENT DAMAGE
Setting undervoltage protection (Vmin) below 80% or voltage unbalance
(Vunbal) above 20% can cause the trip unit to not perform as expected.
Failure to follow this instruction can result in equipment damage.

Figure 101: Integral Internal Three-phase Power Supply


06134076

Minimum Voltage Protection

VA
Integrated
3-phase
Power Supply

VB
VC

Metering
Chain
VN

Figure 102: Open Phase on Three-phase Power Supply


06134077

For circuit configuration 1 (Figure 103), 2 (Figure


104) or 3 (Figure 105), if a fuse opens the trip
unit will inject voltage on the open phase.
Therefore the trip unit will meter the voltage
being injected on the open phase accurately.
The phase-to-phase voltage (VLL) measurement
will be higher than when the open phase is at
zero volts. The trip unit will also accurately meter
the phase-to-neutral voltage (VLN) injected on
the open phase and display a value greater than
zero.
For circuit configuration 4 (Figure 106), the trip
unit has a return path through the transformer
and the injected voltage on the open phase will
be zero. In this configuration the trip unit will
accurately meter zero volts on VLN.

Voltage Unbalance Protection


The voltage unbalance protection function is
based on phase-to-phase voltage
measurement.

Fuse
Fuse
Fuse

VA
Integrated
3-phase
Power Supply

VB
VC

Metering
Chain
VN

Figure 103: Circuit Configuration 1


06134062

To ensure the Micrologic trip system will perform


as expected regardless of system configuration
the user should limit the undervoltage pickup
range to 80%100% of the nominal phase-tophase system voltage.

ENGLISH

Appendix DTrip Unit Voltage Supply Architecture

Open
Fuse
Fuse

Motor

Fuse
Contactor

For circuit configuration 1 (Figure 103), 2 (Figure


104) or 3 (Figure 105), if a fuse opens the trip
unit will inject voltage on the open phase.
Therefore the trip unit will meter the voltage
being injected on the open phase accurately.

20002012 Schneider Electric All Rights Reserved

89-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix DTrip Unit Voltage Supply Architecture

Figure 104: Circuit Configuration 2


06134064

Open

Motor

For circuit configuration 4 (Figure 106), the trip


unit has a return path through the transformer
and the injected voltage on the open phase will
be zero. In this configuration the trip unit will
accurately meter zero volts on VLN.

Contactor
Fuse
Fuse
Fuse

To ensure the Micrologic trip system will perform


as expected regardless of system configuration
the user should limit the voltage unbalance
protection settings to 020%.

Do not use either minimum voltage protection or


voltage unbalance protection to determine the
loss of multiple phases.

Figure 105: Circuit Configuration 3


06134165

Loss of Multiple Phases

Load

The internal voltage power supply requires


voltage of two phases to operate. (The
voltage power supply has an operating
range from 100 V to 690 V.)

Fuse

Fuse

Fuse

In circuit configurations 1 (Figure 103), 2


(Figure 104) and 3 (Figure 105), when
multiple phases are lost the trip unit will
measure the system voltage of the
remaining phase on all three phases. For
example, if two phases are lost on a 480 V
three-phase delta system, the trip unit will
meter 480 VLL on all three phases.

Additional System
Metering Devices
and Protection
Relays

Figure 106: Circuit Configuration 4


Open
06134063

ENGLISH

The phase-to-phase voltage (VLL) measurement


will be higher than when the open phase is at
zero volts. The trip unit will also accurately meter
the phase-to-neutral voltage (VLN) injected on
the open phase and display a value greater than
zero.

48049-137-05
Rev. 01, 07/2012

Fuse
Motor
Fuse

Contactor

Fuse

90-EN

20002012 Schneider Electric All Rights Reserved

48049-137-05
Rev. 01, 07/2012

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix ETrip Unit Settings

Enter setting values in settings tables.

Table 17:

SettingsSwitches

Description

Symbol

Long-time pickup

Ir

Long-time delay

tr

Short-time pickup

Isd

Short-time delay

tsd

Ground-fault pickup

Ig

Ground-fault delay

tg

Table 18:

ENGLISH

Appendix ETrip Unit Settings

Settings

SettingsMaintenance Menu

Submenu

Description

M2C/M6C contacts

Alarm type

S#

Setup

S#

Micrologic setup

Line Item

Trip Unit Setting

Language
Date/Time
Breaker selection

Standard
Circuit breaker
Type
Circuit breaker number

Neutral CT
VT ratio

Primary
Secondary

System frequency
Metering setup

System type
Current demand

Interval

Power demand

Window type
Interval

Power sign
Sign convention
Com setup

Com parameter
Remote access
Remote control

20002012 Schneider Electric All Rights Reserved

91-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix ETrip Unit Settings

Table 19:

48049-137-05
Rev. 01, 07/2012

SettingsProtection Menu

ENGLISH

Submenu

Description

Symbol

Long-time pickup

Ir

Long-time delay

tr

Short-time pickup

Isd

Short-time delay

tsd

Instantaneous

Ii

Idmtl Long-time pickup

Idmtl Ir

Idmtl Long-time delay

Idmtl tr

Line Item

Trip Unit Setting

Idmtl Mode
Idmtl Short-time pickup

Idmtl Isd

Idmtl Short-time delay

Idmtl tsd

Idmtl Instantaneous

Idmtl Ii

Ground-fault (6.0P trip unit)

Neutral current

Ineutral

Mode
Pickup
Pickup delay

Mode
Pickup
Ground-fault alarm

alarm

Pickup delay
Dropout
Dropout delay
Mode
Pickup %

Amperage protection

Current unbalance

Iunbal

Pickup delay
Dropout %
Dropout delay
Mode
Pickup

Max. phase A demand current

Iamax

Pickup delay
Dropout
Dropout delay
Mode
Pickup

Max. phase B demand current

Ibmax

Pickup delay
Dropout
Dropout delay
Mode
Pickup

Max. phase C demand current

Icmax

Pickup delay
Dropout
Dropout delay
Mode
Pickup

Max. neutral demand current

Inmax

Pickup delay
Dropout
Dropout delay
Continued on next page

92-EN

20002012 Schneider Electric All Rights Reserved

Micrologic 5.0P and 6.0P Electronic Trip Units


Appendix ETrip Unit Settings

Table 19:

SettingsProtection Menu (continued)

Submenu

Description

Symbol

Line Item

Trip Unit Setting

ENGLISH

48049-137-05
Rev. 01, 07/2012

Pickup
Minimum (under) voltage

Vmin

Pickup delay
Dropout
Dropout delay
Pickup

Voltage protection

Maximum (over) voltage

Vmax

Pickup delay
Dropout
Dropout delay
Pickup

Voltage unbalance

Vunbal

Pickup delay
Dropout
Dropout delay
Pickup

Reverse power

rP

Pickup delay
Dropout
Dropout delay
Pickup

Maximum (over) frequency

Fmax

Other protection

Pickup delay
Dropout
Dropout delay
Pickup

Minimum (under) frequency

Fmin

Pickup delay
Dropout
Dropout delay

Phase rotation

Mode
Sequence
Mode
Pickup %

Load shedding I

Load shedding I

Pickup delay %
Dropout %
Dropout delay
Mode
Pickup

Load shedding P

Load shedding P

Pickup delay
Dropout
Dropout delay

20002012 Schneider Electric All Rights Reserved

93-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Index

Index
A
Adjustable rating plug See See Rating plug
Adjustable switch settings 31, 4445
Adjustable switches. See Switches
Advanced protection
checking values 50
description 14
Advanced-protection indicator light 22
Alarm contacts. See M2C/M6C
programmable contacts
Alarms
description 17
history 55
Amperage protection 29
checking 56

B
Battery
check status 49
replacement 68
Buttons
down 24
enter 24
ground-fault test 48
maintenance menu 24
metering menu 24
navigation 24
protection menu 24
test/reset 22
up 24

C
Circuit breaker information 36
Communication module 7, 42
Communication setup menu 29
Contact wear indicator
checking 55
code setting 36
meter 36
Current demand 39
Current levels
checking 50
display 23
menu 26
Current load shedding
alarm 17
checking 61
description 20
menu 30
Current shedding. See Current load
shedding
Current unbalance
alarm 32
protection 18

D
Date setting 35
Default settings

maintenance 73
protection 74
switches 73
Delay
ground-fault 13
long-time 10
short-time 12
Down button 24

E
Energy levels
checking 53
menu 27
Enter button 24
Equipment ground-fault protection. See
Ground-fault protection
External power supply 15

F
Flowchart
maintenance menu 71
metering menu 70
protection menu 72
Frequency
alarm 32
checking 54
entering 38
menu 27

G
Graphic display
flowchart 70
menus 25
navigation 24
screen 23
Ground-fault protection
alarm 32
delay switch 13
description 13
pickup switch 13
test function 48

H
History logs
checking 54
description 2728

I
I2t off 12
I2t on 12
Idmtl. See Long-time protection
Ig. See Ground-fault protection pickup switch
Ii. See Instantaneous protection
In. See Sensor sizes
Indicator lights
advanced-protection 22
ground-fault 22
overload 22

20002012 Schneider Electric All Rights Reserved

self-protection 22
trip 22
Instantaneous protection
description 13
pickup switch 13
Ir. See Long-time protection pickup switch
Isd. See Short-time protection pickup switch

L
Language setting 34
Load shedding. See Current load shedding,
voltage load shedding
Long-time protection
alarm 32
delay switch 10
description 10
I2t delay 10
Idmtl delay
pickup switch 10
Loss of multiple phases 90
LSI. See Trip unit, 5.0P
LSIG See Trip unit, 6.0P

M
M2C/M6C programmable contacts
menu description 28
menu setting 31
M2C/M6Cprogrammable contacts
kit description 20
Maintenance menu
default settings 73
description 27
flowchart 71
setting 31
Maintenance menu button 24
Maximum current alarm 32
Maximum demand current protection 18
Maximum frequency protection 19
Maximum voltage protection 18
Menus
alarm history 55
amperage protection 29, 56
communication setup 29
contact wear 55
current levels 26, 50
current load shedding 30
energy levels 27, 53
frequency 54
history logs 2728
M2C/M6C programmable contacts 28
maintenance 27
metering 25
metering setup 28
Micrologic setup 15, 28, 15, 16
operation counter 55
other protection 30, 60
power levels 26, 52
power load shedding 30, 61
protection 29

94-EN

ENGLISH

48049-137-05
Rev. 01, 04/2012

trip history 54
voltage levels 26, 51
voltage protection 30, 59
Metering
accuracy 76
range 76
Metering menu
button 24
checking 50
description 25
flowchart 70
Metering setup menu
description 28
setting 38
Micrologic setup menu
description 15, 28, 15, 16
setting 34
Micrologic trip unit. See Trip unit
Minimum demand current protection 18
Minimum frequency protection 19
Minimum voltage protection 18
Modbus com values 42

N
Navigation buttons 24
Neutral protection 16

O
Operation 50
Operation counter
description 23
menu 55
Other protection
checking 60
description 14
Other protection menu 30
Overcurrent. See Maximum current
protection
Overfrequency. See Maximum frequency
protection
Overheating trip indicator light 22
Overvoltage. See Maximum voltage
protection

P
Phase reversal
alarm 32
checking 60
Phase rotation protection 20
Pickup
ground-fault 13
instantaneous 13
long-time 10
short-time 12
Pickup levels, setting 43, 46
Plug, rating. See Rating plug
Power demand 40
Power flow
power sign direction setup 37
reactive power sign convention setup 41
Power levels
checking 52
menu 26
Power load shedding

Micrologic 5.0P and 6.0P Electronic Trip Units


Index
alarm 32
checking 61
menu 30
Primary injection testing 21
Product name 7
Protection
advanced 14
alarms 17
amperage 56
current load shedding 30
current unbalance 18
default settings 74
ground-fault 13
instantaneous 13
load shedding 20
long-time 10
maximum demand current 18
maximum frequency 19
maximum voltage 18
minimum demand current 18
minimum frequency 19
minimum voltage 18
neutral 16
other 60
phase rotation 20
power load shedding 30
reverse power 19
short-time 12
voltage 59
voltage unbalance 18
Protection designation 7
Protection menu
button 24
checking 56
default settings 74
description 29
flowchart 72

R
Rating plug
description 7, 11
replacement 67
Remote access 42
Remote control 43
Remotely readable measurements 77
Replacement
battery 68
rating plug 67
trip unit 62
Reset button 47
Reset trip unit 47
Reverse power protection
alarm 32
description 19
RPmax. See Reverse power protection

S
Secondary injection testing 21
Self-protection indicator light 22
Sensor plug 7
Short-time protection
alarm 32
delay switch 12
description 12

20002012 Schneider Electric All Rights Reserved

pickup switch 12
Sign convention 41
Status
battery 49
trip unit 49
Switch cover
illustration 7
opening slot 43
Switches
adjusting 43
description 7
ground-fault delay 13
ground-fault pickup 13
instantaneous pickup 13
long-time delay 10
long-time pickup 10
short-time delay 12
short-time pickup 12
System type 39

English
ENGLISH

48049-137-05
Rev. 01, 04/2012

T
Test 22
Test plug 47
Test/reset button 22
Testing
ground-fault trip function 48
primary injection 21
secondary injection 21
test kits 47
trip unit 21
Thermal imaging 11
Time setting 35
Tr. See Long-time protection delay switch
Trip history 54
Trip indicator lights 22
Trip indicators
check status 49
Ig 22
Isd/Ii 22
lights 22
Trip unit
5.0P 8
6.0P 9
history 54
replacement 62
reset 47
settings
circuit breaker family 36
circuit breaker type 36
contact wear code 36
date 35
frequency 38
ground-fault protection 13
instantaneous protection 13
language 34
long-time protection 10
recording tables 91
short-time protection 12
standards 36
time 35
VT ratio 37
setup 34
status check 49
testing 21

95-EN

Micrologic 5.0P and 6.0P Electronic Trip Units


Index

48049-137-05
Rev. 01, 04/2012

ENGLISH

verify operation 47
voltage supply architecture 89
Trip unit settings
long-time protection 10
Tripping functions 7
Tsd. See Short-time protection delay switch

U
Undercurrent. See Minimum current
protection
Underfrequency. See Minimum frequency
protection
Undervoltage. See Minimum voltage
protection
Up button 24

V
Verify trip unit operation 47
Voltage levels
checking 51
menu 26
Voltage protection
alarm 32
checking 59
Voltage protection menu 30
Voltage supply architecture 89
Voltage transformer ratio 37
Voltage unbalance
alarm 32
protection 18
voltage architecture 90

Z
Zone-selective interlocking
description 21
installation 46
jumpers 46
wiring 47
ZSI. See Zone-selective interlocking

96-EN

20002012 Schneider Electric All Rights Reserved

ENGLISH

Micrologic 5.0P and 6.0P Electronic Trip Units


Instruction Bulletin

ENGLISH
Electrical equipment should be installed, operated, serviced, and maintained only by qualified
personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of
the use of this material.

Schneider Electric

Square D, Schneider Electric, Micrologic, and Masterpact are trademarks or registered


trademarks of Schneider Electric. Other trademarks used herein are the property of their
respective owners.

3700 Sixth St. SW


Cedar Rapids, IA 52404 USA
1-888-778-2733
www.schneider-electric.us

48049-137-05 Rev. 01, 07/2012


Replaces 48049-137-05 07/2008
20002012 Schneider Electric All Rights Reserved

Unidades de disparo electrnico Micrologic


5.0P y 6.0P
v PLogic-2002-AA

48049-137-05
Rev. 01, 07/2012
Conservar para uso futuro.

ESPAOL

Boletn de instrucciones

Unidades de disparo electrnico Micrologic 5.0P y 6.0P

Categoras de peligros y smbolos


especiales

48049-137-05
Rev. 01, 07/2012

Asegrese de leer detenidamente estas instrucciones y realice una


inspeccin visual del equipo para familiarizarse con l antes de instalarlo,
hacerlo funcionar o prestarle servicio de mantenimiento. Los siguientes
mensajes especiales pueden aparecer en este boletn o en el equipo para
advertirle sobre peligros potenciales o llamar su atencin sobre cierta
informacin que clarifica o simplifica un procedimiento.
La adicin de cualquiera de los dos smbolos a una etiqueta de seguridad
de Peligro o Advertencia indica que existe un peligro elctrico que
causar lesiones si no se siguen las instrucciones.

ANSI

ESPAOL

Este es el smbolo de alerta de seguridad. Se usa para avisar sobre


peligros potenciales de lesiones. Respete todos los mensajes de seguridad
con este smbolo para evitar posibles lesiones o la muerte.

PELIGRO
IEC

PELIGRO indica una situacin peligrosa que, si no se evita, causar la


muerte o lesiones serias.

ADVERTENCIA
ADVERTENCIA indica una situacin peligrosa que, si no se evita, puede
causar la muerte o lesiones serias.

PRECAUCIN
PRECAUCIN indica una situacin peligrosa que, si no se evita, puede
causar lesiones menores o moderadas.

AVISO
AVISO se usa para hacer notar prcticas no relacionadas con lesiones
fsicas. El smbolo de alerta de seguridad no se usa con esta palabra de
indicacin.
NOTA: Proporciona informacin adicional para clarificar o simplificar un
procedimiento.

Observe que

Solamente el personal especializado deber instalar, hacer funcionar y


prestar servicios de mantenimiento al equipo elctrico. Schneider Electric
no asume responsabilidad alguna por las consecuencias emergentes de la
utilizacin de este material.

Aviso FCC

El equipo ha sido probado y cumple con los lmites establecidos para los
dispositivos digitales Clase A , segn la seccin 15 de las normas de la FCC
(Comisin federal de comunicaciones de los EUA). Estos lmites han sido
establecidos para proporcionar la proteccin adecuada contra interferencias
que puedan daar el equipo cuando ste se utiliza en un entorno comercial.
Este equipo genera, utiliza y puede radiar energa de radiofrecuencia y, si no
se instala y utiliza siguiendo las indicaciones del manual de instrucciones,
puede provocar interferencias que afecten a las radiocomunicaciones. Si se
utiliza en una zona residencial, las interferencias podran causar daos. En tal
caso, el usuario es el responsable de corregir dichas interferencias por su
propia cuenta y riesgo.

2-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

INFORMACIN GENERAL

...................................................................................................................... 7
Introduccin ................................................................................................ 7
Comunicaciones ......................................................................................... 7
Ajustes de potencia y de control ................................................................. 7
Ajustes de los selectores ............................................................................ 7
Unidad de disparo Micrologic 5.0P ........................................................ 8
Unidad de disparo Micrologic 6.0P ........................................................ 9
Proteccin LSIG ........................................................................................ 10
Proteccin de tiempo largo .................................................................. 10
Proteccin de tiempo corto .................................................................. 12
Proteccin instantnea ........................................................................ 13
Proteccin contra fallas a tierra del equipo .................................................13
Configuracin de la unidad de disparo Micrologic .................................... 14
Alimentacin de control ....................................................................... 14
Fuente de alimentacin externa .......................................................... 15
Configuracin Micrologic ........................................................................... 15
Proteccin avanzada ................................................................................ 16
Alarmas ............................................................................................... 17
Valores de proteccin de demanda de corriente y tensin mnima (baja)
y mxima (sobre) ................................................................................ 18
Proteccin de desequilibrio de corriente o tensin .............................. 19
Proteccin de potencia inversa (rPmx) ............................................. 19
Protecciones de frecuencia mxima (sobre) y mnima (baja) ............. 19
Desconexin de carga (Desconex. reconex.) ..................................... 20
Proteccin de rotacin de fases .......................................................... 20
Accesorios de contactos programables M2C y M6C ................................ 21
Enclavamiento selectivo de zona .............................................................. 21
Medicin .................................................................................................... 22
Prueba de la unidad de disparo ................................................................ 22
Contador de maniobras ............................................................................ 22
Luces indicadoras ..................................................................................... 22
Luz indicadora de sobrecarga ............................................................. 22
Luces indicadoras de disparo .............................................................. 23
Botn de prueba/restablecimiento ............................................................ 23
Pantalla de visualizacin de grficos ........................................................ 24
Indicador de desgaste de los contactos .................................................... 24

SECCIN 2:

NAVEGACIN POR LA VISUALIZACIN DE GRFICOS............................................................................... 25


Visualizacin de grficos .......................................................................... 25
Visualizacin de grficos de barras y mens ............................................ 26
Men de medicin ............................................................................... 26
Men de servicio de mantenimiento .................................................... 28
Men de proteccin ............................................................................. 30

SECCIN 3:

CONFIGURACIN DE LA UNIDAD DE DISPARO ............................................................................................ 32


Ajuste de los parmetros de la unidad de disparo .................................... 32
Contactos programables M2C/M6C .................................................... 32
Configuracin de la unidad de disparo Micrologic ............................... 35
Configuracin de las mediciones ........................................................ 39
Configuracin del mdulo de comunicacin ........................................ 43
Ajuste de los selectores de configuracin ................................................. 44
Ejemplos ................................................................................................... 46
Unidad de disparo Micrologic 5.0P ...................................................... 46
Unidad de disparo Micrologic 6.0P ...................................................... 46
Enclavamiento selectivo de zona (ZSI) ..................................................... 47
Verificacin del funcionamiento de la unidad de disparo .......................... 48
Restablecimiento de la unidad de disparo ................................................ 48

20002012 Schneider Electric Reservados todos los derechos

3-ES

ESPAOL

SECCIN 1:

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Contenido

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Contenido

48049-137-05
Rev. 01, 07/2012

Prueba de la funcin de disparo por falla a tierra del equipo .................... 49


Verificacin del estado de la unidad de disparo ........................................ 50
SECCIN 4:

FUNCIONAMIENTO

.................................................................................................................... 51

ESPAOL

Valores de medicin .................................................................................. 51


Niveles de corriente ............................................................................. 51
Niveles de tensin ............................................................................... 52
Niveles de potencia ............................................................................. 53
Niveles de energa ............................................................................... 54
Frecuencia ........................................................................................... 55
Historial de la unidad de disparo ............................................................... 55
Historial de disparo .............................................................................. 55
Historial de alarmas ............................................................................. 56
Contador de maniobras ....................................................................... 56
Desgaste de contactos ........................................................................ 56
Configuracin de proteccin ..................................................................... 57
Proteccin de corriente ........................................................................ 57
Proteccin de tensin .......................................................................... 60
Otro tipo de proteccin ........................................................................ 61
Desconexin de carga de la corriente ................................................. 62
Desconexin de carga de la alimentacin ........................................... 62
SECCIN 5:

SUSTITUCIN DE LA UNIDAD DE DISPARO................................................................................................... 63


Herramientas necesarias .......................................................................... 63
Preparacin ............................................................................................... 63
Anotacin de los ajustes de los selectores .......................................... 63
Desconexin del interruptor ................................................................. 63
Extraccin de la cubierta de accesorios del interruptor ....................... 64
Desmontaje del calibrador ................................................................... 64
Desmontaje de la unidad de disparo ................................................... 64
Sustitucin de la unidad de disparo .................................................................. 64
Instalacin de la batera ...................................................................... 64
Instalacin de la unidad de disparo ..................................................... 65
Colocacin de la cubierta de accesorios del interruptor ........................... 67
Verificacin de la instalacin de la unidad de disparo .............................. 67
Pruebas de inyeccin secundaria ........................................................ 67
Pruebas de inyeccin primaria ............................................................ 67
Verificacin del funcionamiento de los accesorios .............................. 67
Configuracin de la unidad de disparo ...................................................... 68
Re-energizacin del interruptor ................................................................. 68

SECCIN 6:

SUSTITUCIN DEL CALIBRADOR AJUSTABLE............................................................................................. 69


Desmontaje del calibrador ........................................................................ 69
Instalacin del nuevo calibrador ................................................................ 69

SECCIN 7:

SUSTITUCIN DE LA PILA

.................................................................................................................... 70
Desconexin del interruptor ...................................................................... 70
Desmontaje de la cubierta de accesorios ................................................. 70
Desplazamiento del mdulo de aguante ................................................... 70
Sustitucin de la pila ................................................................................. 70
Colocacin del mdulo de aguante ........................................................... 71
Colocacin de la cubierta de accesorios ................................................... 71
Re-energizacin del interruptor ................................................................. 71

APNDICE A: DIAGRAMAS DE FLUJO DE VISUALIZACIN DE GRFICOS........................................................................... 72


Diagrama de flujo del men de mediciones .............................................. 72
4-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Contenido

Diagrama de flujo del men de servicio de mantenimiento ...................... 73


Diagrama de flujo del men de protecciones ............................................ 74
APNDICE B: AJUSTES DE FBRICA Y TOLERANCIAS....................................................................................................... 75
Ajustes de fbrica ..................................................................................... 75
Gama de medicin y precisin .................................................................. 78
APNDICE C: ACCESO A LA RED/COM

.................................................................................................................... 79

APNDICE D: ARQUITECTURA DE LA TENSIN DE ALIMENTACIN DE LA UNIDAD DE DISPARO............................... 91


Proteccin de tensin mnima ................................................................... 91
Proteccin de desequilibrio de tensin ..................................................... 92
Prdida de fases mltiples ........................................................................ 92
APNDICE E: AJUSTES DE LA UNIDAD DE DISPARO .......................................................................................................... 93
ndice:

.................................................................................................................... 96
................................................................................................................... 96

20002012 Schneider Electric Reservados todos los derechos

5-ES

ESPAOL

Valores de lectura remota ......................................................................... 79


Lista de registros ....................................................................................... 82

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Contenido

48049-137-05
Rev. 01, 07/2012

ESPAOL
6-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Seccin 1Informacin general

Tipo de proteccin
2Proteccin bsica IEC (LSO)
3Proteccin bsica UL (LI)
5Proteccin selectiva (LSI)
6Proteccin selectiva y proteccin contra
fallas a tierra del equipo (LSIG)

A
B

ANombre del producto


BIndicadores de disparo
CCompartimiento para pilas
DSelectores ajustables
ECubierta de los selectores
FLengeta de cierre hermtico
GCalibradores ajustables
HBotn de restablecimiento de la
verificacin del estado de las pilas e
indicadores de disparo
IConexin del bloque de terminales externo

H
0P

5.
logic
Micro

C
F

G
alarm

time
long

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

Serie de la unidad de disparo


0Indica la primera versin
Tipo de medicin
NingunaProporciona solamente proteccin
AProporciona proteccin y mediciones
del amprmetro
PProporciona proteccin y mediciones de potencia
HProporciona proteccin y mediciones
de armnicos

Unidad de disparo Micrologic

tr

(s) 4

2
1
.5

8 12
16
20
24
Ir
at 6

Las unidades de disparo Micrologic se pueden


actualizar en campo a una versin ms reciente.
Consulte el catlogo de productos para obtener
informacin ms detallada acerca de los
modelos de interruptores, tamaos de marcos,
valores nominales de interrupcin, enchufes
sensores, calibradores y unidades de disparo
disponibles.

Comunicaciones

Las unidades de disparo Micrologic se pueden comunicar con otros


dispositivos a travs de Modbus mediante el mdulo de comunicacin del
interruptor (MCI). Para obtener informacin sobre el mdulo de
comunicacin, consulte el catlogo del producto y el boletn de datos del
producto no. 0613IB1201, sistema de comunicacin Modbus.

Ajustes de potencia y de control

Ajuste las opciones de la unidad de disparo o verifique las mediciones del


sistema con la pantalla de visualizacin de grficos y la terminal de
programacin y ajustes. Consulte la seccin 2 Navegacin por la
visualizacin de grficos para obtener ms informacin. Tambin es posible
verificar las mediciones del sistema con el software System Manager
Software (SMS), versin 3.2 o posterior, o cualquier otro software de
gestin de sistemas de red.

Ajustes de los selectores

Las funciones de disparo de LSI o LSIG se pueden ajustar en los selectores


ubicados en la parte frontal de la unidad de disparo. Las unidades de
disparo vienen de fbrica con el selector de activacin de tiempo largo
ajustado en 1,0 y los otros selectores ajustados en su valor ms bajo. Los
ajustes de proteccin avanzada vienen desactivados.

20002012 Schneider Electric Reservados todos los derechos

7-ES

ESPAOL

Las unidades de disparo Micrologic


proporcionan funciones de disparo ajustables a
los interruptores de disparo electrnico. El
nombre del producto (A) especifica el tipo de
proteccin provisto por la unidad de disparo.
Micrologic 5.0P

Figura 1:

06134748

Introduccin

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

48049-137-05
Rev. 01, 07/2012

Es posible realizar ajustes finos a los selectores a travs de las teclas de


navegacin, consulte la pgina 45.

Unidad de disparo Micrologic 5.0P

La unidad de disparo Micrologic 5.0P proporciona proteccin selectiva (LSI)


y mediciones de potencia.

A. Pantalla de visualizacin de grficos

Figura 2:

Unidad de disparo 5.0P

B. Botn del men de proteccin*


06134749

D. Botn del men de medicin*


E. Botn flecha abajo

Micrologic 5.0 P

4260A

G. Botn de introduccin de valores

N 1 2 3

H. Selector de activacin de tiempo largo (Ir)

100

Selector de retardo de tiempo largo (tr)

J. Selector de activacin de tiempo corto (Isd)

50

K. Selector de retardo de tiempo corto (tsd)


L. Selector de activacin instantnea (Ii)

O. Botn de restablecimiento de la verificacin


del estado de las pilas y el LED indicador de
disparo
P. Luz indicadora de autoproteccin y
proteccin avanzada
Q. Luz indicadora de disparo de tiempo corto o
instantneo

Ir
tr

C
D

M. Receptculo para el enchufe de prueba


N. Luz indicadora de sobrecarga de activacin
de tiempo largo

06134751

ESPAOL

F. Botn flecha arriba

I.

R Q

C. Botn del men de proteccin*

Isd
tsd

Ii

F
H

G
I
J

long time

Ir
.7
.6
.5
.4

.8

x In

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

Ir

Isd

Ii

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
8
2
1.5
10
x Ir
setting

K
L

alarm

tr

tsd
(s)

Ii

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

4
3

6 8 10
12
15
off
2
x In

delay

R. Luz indicadora de disparo de tiempo largo

*Este botn incluye un LED que indica el men activo.

8-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Unidad de disparo Micrologic 6.0P

La unidad de disparo Micrologic 6.0P proporciona proteccin selectiva y de


falla a tierra del equipo (LSIG) ( 1200 A) as como mediciones de potencia.

A. Pantalla de visualizacin de grficos

Figura 3:

Unidad de disparo 6.0P

B. Botn del men de proteccin*

V U T S
06134750

E. Botn flecha abajo

4260A
Isd
tsd

N 1 2 3

G. Botn de introduccin de valores


H. Selector de activacin de tiempo largo (Ir)
I.

Ir
tr

F. Botn flecha arriba

Micrologic 6.0 P

100

Selector de retardo de tiempo largo (tr)

Ii
0

Ir

Isd

Ii

50

J. Selector de activacin de tiempo corto (Isd)


L. Selector de activacin instantnea (Ii)
M. Selector de activacin de proteccin contra
fallas a tierra (Ig)
N. Selector de retardo de proteccin contra
fallas a tierra (tg)

D
E

I2t on

F
H

G
I

O. Receptculo para el enchufe de prueba

P. Botn de disparo por falla a tierra


Q. Luz indicadora de sobrecarga de activacin
de tiempo largo

C
06134752

K. Selector de retardo de tiempo corto (tsd)

R. Botn de restablecimiento de la verificacin


del estado de las pilas y el LED indicador de
disparo

.7
.6
.5
.4

.8

x In

L
N

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

tg

D
C
B
A

I2t off

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Ig

Ig

@ 6 Ir

tsd

. 4 . 4 .3
.2
.3
.1
.2
.1 2 0

on

I t

off

delay

4
3

6 8 10
12
15
off
2
x In
test

tg
F
G
H
J

Ii

(s)

setting

long time

Ir

. 4 .4 . 3
.2
.3
.1
.2
.1 2 0

Ig

(s)

on

I t

off

ground fault

S. Luz indicadora de autoproteccin y


proteccin avanzada
T. Luz indicadora de disparo por falla a tierra
U. Luz indicadora de disparo de tiempo corto o
instantneo
V. Luz indicadora de disparo de tiempo largo

*Este botn incluye un LED que indica el men activo.

20002012 Schneider Electric Reservados todos los derechos

9-ES

ESPAOL

D. Botn del men de medicin*

06134751

C. Botn del men de servicio de


mantenimiento*

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

48049-137-05
Rev. 01, 07/2012

Proteccin LSIG

La proteccin de tiempo largo protege al


equipo contra sobrecargas.

ESPAOL

La proteccin de tiempo largo es una


funcin estndar en todas las unidades de
disparo.

Figura 4:

Selectores de proteccin de tiempo largo

Unidad de disparo Micrologic 5.0P

La activacin de tiempo largo (Ir) (A)


establece el nivel mximo de la corriente
(en base a los valores nominales del
enchufe sensor [In]) que llevar el
interruptor continuamente. Si la corriente
excede este valor, se disparar el
interruptor una vez que alcanza el valor
del retardo de tiempo prefijado. La
activacin de tiempo largo (Ir) se puede
ajustar de 0,4 a 1,0 veces el valor nominal
del enchufe sensor (In) del interruptor (D).

A
06134753

NOTA: Las unidades de disparo Micrologic son alimentadas desde el circuito


para proporcionar proteccin contra fallas en todo momento. Todas las dems
funciones (mdulos de visualizacin, medicin, comunicacin, etc.) requieren
una fuente de alimentacin externa. Consulte la pgina 15 para obtener ms
informacin.

Unidad de disparo Micrologic 6.0P

06134754

Proteccin de tiempo largo

long time

Ir
.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
@ 6 Ir

setting

Ir
.7
.6
.5
.4

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd
(s)

.3
.2
.1
on

.2
.1
2

I t

0
off

alarm

x In

@ 6 Ir

instantaneous

short time

6 8 10
4
12
3
15
off
2
x In

tsd

.4 .4 . 3
.2
.3
.1
.2
.1 2 0

D
C
B
A

D
In 2000 A

on

I t

4
3

off

6 8 10
12
15
off
2
x In

delay

tg
F
G
H
J

Ii

(s)

setting

delay

Ig

El retardo de tiempo largo (tr) (B)


establece el perodo durante el cual el
interruptor llevar una sobrecorriente por
debajo del nivel de la corriente de
activacin instantnea o de tiempo corto
antes de dispararse. Se encuentran
disponibles dos opciones:

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

Ii

.4 . 4 .3

long time

(s)

test

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

ground fault

In 2000 A

Curva de retardo de tiempo largo I2t


estndar. Consulte la tabla 1 para
obtener los ajustes de retardo de
tiempo largo de I2t.
Las curvas de retardo de tiempo largo
Idmtl (retardo mnimo de tiempo
inverso independiente) varan en su
pendiente para mejorar la selectividad.

Valores de retardo de tiempo largo de I2t de la


unidad de disparo Micrologic

Opcin Descripcin

Curva

Ajuste1

Retardo de tiempo largo en segundos2

DT

Constante

tr a 1,5 x Ir

12,5

25

50

100

200

300

400

500

600

tr a 6 x Ir

0,5

12

16

20

24

2,7

5,5

8,3

11

13,8

16,6

SIT

Tabla 1:

Tiempo independiente
Tiempo inverso estndar

0,5

VIT

Gran tiempo inverso

EIT

Tiempo extremadamente
inverso

HVF

Compatible con fusibles de alta 4


I t
tensin

It
I2t

tr a 7,2 x Ir

0,34

0,69 1,38

Ir = In x activacin de tiempo largo. In = valor nominal del sensor.


Umbral de disparo entre 1,05 y 1,20 Ir.
2
Precisin del retardo +0/-20%.
3
Cuando tsd se ajusta en 0,4 off, tr = 0,5 en lugar de 0,34.

La luz indicadora de sobrecarga (C) se


ilumina cuando se ha excedido el valor de
umbral de activacin de tiempo largo Ir.

10-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Es posible cambiar el valor del sensor In


en los interruptores de potencia
MasterpactNT y NW sustituyendo el
enchufe sensor (D) ubicado debajo de la
unidad de disparo. Lea las instrucciones
incluidas con el accesorio de sustitucin
del enchufe sensor para obtener
informacin adicional.

La proteccin del neutro no est


disponible al seleccionar la proteccin
Idmtl.

Las selecciones de Idmtl no utilizan la


misma opcin de imagen trmica que la
funcin de proteccin de tiempo largo I2t.
La proteccin bsica de tiempo largo y
tiempo extremadamente inverso de Idmtl
son curvas I2t, cuyas opciones diferentes
de imagen trmica resultan en
rendimientos diferentes del sistema. Para
las aplicaciones de soldadura se
recomienda la utilizacin de proteccin
bsica de tiempo largo I2t para obtener el
rendimiento esperado del sistema.

Las funciones de activacin de tiempo


largo y retardo de tiempo largo estn
situadas en el calibrador ajustable de
sustitucin en campo. Para modificar los
ajustes en valores ms apropiados para la
aplicacin, se encuentran disponibles
varios tipos de calibradores. Consulte la
seccin 6 Sustitucin del calibrador
ajustable para obtener informacin sobre
cmo sustituirlo.

Tabla 2:

Opcin Ajuste1

Retardo de tiempo largo en segundos

Tolerancia

tr a 1,5 x Ir 0,52

12

16

20

24

+0/-20%

tr a 6 x Ir

0,52

12

16

20

24

+0/-20%

tr a 7,2 x Ir 0,52

12

16

16,6

16,6

+0/-20%

tr a 10 x Ir

12

16

16,6

16,6

+0/-20%

DT
0,52

tr a 1,5 x Ir 1,9

3,8

7,6

15,2

30,4

45,5

60,7

75,8

91

+0/-30%

tr a 6 x Ir

12

16

20

24

+0/-20%

0,88 1,77

3,54

7,08

10,6

14,16 17,7

21,2

+0/-20%

0,8

2,86

5,73

8,59

11,46 14,33 17,19 +0/-20%

0,7

SIT
tr a 7,2 x Ir 0,7
tr a 10 x Ir

0,72

1,43

tr a 1,5 x Ir 1,9

7,2

14,4

28,8

57,7

86,5

115,4 144,2 173,1 +0/-30%

tr a 6 x Ir

12

16

20

0,81 1,63

3,26

6,52

9,8

13,1

16,34 19,61 +0/-20%

0,75 1,14

2,28

4,57

6,86

9,13

11,42 13,70 +0/-20%

0,7

24

+0/-20%

VIT
tr a 7,2 x Ir 0,7
tr a 10 x Ir

0,72

tr a 1,5 x Ir 12,5
tr a 6 x Ir
EIT

0,73

tr a 7,2 x Ir 0,72
tr a 10 x Ir

La proteccin de tiempo largo utiliza


medicin de rcm verdadera.

Imgenes trmicas proporcionan informacin


sobre el estado continuo de elevacin de la
temperatura del cableado, antes y despus
de dispararse el dispositivo. Esto permite al
interruptor responder a una serie de
condiciones de sobrecarga que podran
provocar el sobrecalentamiento del
conductor, las cuales podran pasar
desapercibidas si se restablece el circuito de
tiempo largo cada vez que la carga desciende
por debajo del ajuste de activacin o despus
de cada disparo.

Valores de retardo de tiempo largo de Idmtl de la unidad de


disparo Micrologic

0,72

25

50

100

200

300

400

500

600

+0/-30%

12

16

20

24

+0/-20%

0,69 1,38

2,7

5,5

8,3

11

13,8

16,6

+0/-20%

0,73

0,73

1,41

2,82

4,24

5,45

7,06

8,48

+0/-20%

tr a 1,5 x Ir 164,5 329

658

1316 2632 3950 5265

6581

7900

+0/-30%

tr a 6 x Ir

0,73

12

16

20

24

+0/-20%

tr a 7,2 x Ir

0,72

0,73

1,13

1,42

3,85

5,78

7,71

9,64

11,57 +0/-20%

tr a 10 x Ir

0,72

0,72

0,73

0,73

1,02

1,53

2,04

2,56

3,07

HVF

+0/-20%

1Ir

= In x activacin de tiempo largo. In = valor nominal del sensor. Umbral de disparo entre 1,05 y
1,20 Ir.
2
Tolerancia = +0/-60%
3
Tolerancia = +0/-40%

NOTA: Cuando verifique los tiempos de


disparo, espere por lo menos 15 minutos
despus de haberse disparado el interruptor y
antes de restablecerse para permitir que se
restablezca completamente en cero la
imagen trmica o utilice un equipo de pruebas
para inhibirla.

20002012 Schneider Electric Reservados todos los derechos

11-ES

ESPAOL

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Proteccin de tiempo corto

48049-137-05
Rev. 01, 07/2012

Figura 5:

Selectores de proteccin de tiempo corto


Unidad de disparo Micrologic 6.0P

ESPAOL

06134753

La proteccin de tiempo corto es una funcin


estndar en las unidades de disparo 5.0P y
6.0P.
La activacin de tiempo corto (Isd) (A) ajusta
el nivel de la corriente (inferior al nivel de
disparo instantneo) en el que el interruptor
se disparar despus de alcanzar el valor de
retardo de tiempo preajustado.
El retardo de tiempo corto (tsd) (B) ajusta el
perodo durante el cual el interruptor llevar
una sobrecorriente por encima del nivel de la
corriente de activacin de tiempo corto antes
de dispararse.
La opcin I2t on/I2t off proporciona un criterio
selectivo mejorado mediante los dispositivos
de proteccin de corriente descendente:
Cuando se selecciona I2t off, se
proporciona un retardo con tiempo fijo.
Cuando se selecciona I2t on, se
proporciona una proteccin I2t de tiempo
inverso hasta un mximo de 10 veces Ir.
Para valores mayores que 10 veces el
valor de Ir, se proporciona un retardo de
tiempo fijo.

Las corrientes intermitentes, en la gama de


disparo de tiempo corto con una duracin
insuficiente para activar un disparo,
acumulan y acortan el retardo del disparo
adecuadamente.

Es posible seleccionar un enclavamiento


selectivo de zona (ZSI) en la proteccin de
tiempo corto con los interruptores de
corriente ascendente o descendente. Al
ajustar en 0 tsd, se desactiva el
enclavamiento selectivo de zona.

La proteccin de tiempo corto utiliza valores


de medicin rcm verdaderos.

La activacin y el retardo de tiempo corto


pueden ser ajustados para proporcionar un
criterio selectivo con los interruptores de
corriente ascendente y descendente.

long time

Ir
.7
.6
.5
.4

.8

x In

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
setting

long time

Ir
.7
.6
.5
.4

@ 6 Ir

instantaneous

short time

06134754

Unidad de disparo Micrologic 5.0P

Esta funcin protege al equipo contra


cortocircuitos.

tsd
(s)

.3
.2
.1
on

.2
.1
0
off

I t

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

Ii

.4 . 4 .3

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

6 8 10
4
12
3
15
off
2
x In

delay

(s)

D
C
B
A

Ii

. 4 .4 .3

.3
.2
.1
on

setting

Ig

tsd

.2
.1
2

I t

0
off

4
3

6 8 10
12
15
off
2
x In

delay

test

tg
F
G
H
J

.4 . 4 . 3
.2
.3
.1
.2
.1 2 0

(s)

on

I t

off

ground fault

In 2000 A

Tabla 3:

In 2000 A

Valores de retardo de tiempo corto de la unidad


de disparo Micrologic

Ajuste

Retardo de tiempo corto

I t off (ms a 10 Ir) (segundos)


2

0,1

0,2

0,3

0,4

I t on (ms a 10 Ir) (segundos)

0,1

0,2

0,3

0,4

tsd (disparo mn.) (milisegundos)

20

80

140

230

350

tsd (disparo mx.) (milisegundos)

80

140

200

320

500

NOTA: Utilice I2t off con ZSI para obtener una


coordinacin correcta. No se recomienda utilizar
I2t on con ZSI ya que, debido al retardo en el
dispositivo de corriente ascendente que recibe
la seal de restriccin, es posible que se dispare
la unidad en un perodo ms corto que el
indicado en la curva de disparo publicada.

12-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Figura 6:

Selectores de proteccin instantnea

Unidad de disparo Micrologic 5.0P

Unidad de disparo Micrologic 6.0P


06134754

06134753

La proteccin instantnea protege al equipo


contra cortocircuitos sin retardo de tiempo
intencional.

long time

Ir
.7
.6
.5
.4

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

.7
.6
.5
.4

@ 6 Ir

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd

Ii

.4 .4 .3
.2
.3
.1
.2
.1 2 0

(s)

on

setting

I t

4
3

off

La proteccin instantnea utiliza los valores


de medicin de la corriente pico.
Cuando se ajusta en off el selector de
proteccin instantnea, sta queda
inhabilitada.

Proteccin contra fallas a tierra del equipo

x In

@ 6 Ir

6 8 10
12
15
off
2
x In

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

instantaneous

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

Ig
D
C
B
A

Ii

(s)

on

setting

delay

La proteccin instantnea se basa en los


valores nominales del sensor (In) del
interruptor.
Se emite un comando de apertura del
interruptor tan pronto se excede la corriente
de umbral.

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

short time

instantaneous

short time

La proteccin instantnea (Ii) (A) es una


funcin estndar en todas las unidades de
disparo.

long time

Ir

I t

off

delay

tg
F
G
H
J

(s)

4
3

6 8 10
12
15
off
2
x In

test

.4 .4 .3

.3
.2
.1
on

.2
.1
0
I t off
2

ground fault

In 2000 A

ESPAOL

Proteccin instantnea

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

In 2000 A

Tabla 4:

Valores de proteccin instantnea de la unidad de


disparo Micrologic

Ajuste

Corriente de irrupcin

Ii (= In x..)

10

12

15

off

Ii = proteccin instantnea. In = valor nominal del sensor. Precisin de activacin 10%

Figura 7:

Selectores de proteccin contra fallas a tierra

Unidad de disparo Micrologic 6.0P

06134754

La proteccin contra fallas a tierra del equipo


protege a los conductores contra
sobrecalentamiento y fallas de las corrientes de
falla a tierra ( 1 200 A).

long time

Ir
.7
.6
.5
.4

Las protecciones neutra y contra fallas a


tierra del equipo son independientes y
pueden funcionar simultneamente.

NOTA: Utilice I2t off con ZSI para obtener una


coordinacin correcta. No se recomienda utilizar
I2t on con ZSI ya que, debido al retardo en el
dispositivo de corriente ascendente que recibela
seal de restriccin, es posible que se dispare la
unidad en un perodo ms corto que el indicado
en la curva de disparo publicada.

@ 6 Ir

instantaneous

tsd
(s)

Ig
D
C
B
A

A
B

Ii

.4 .4 .3

.3
.2
.1
on

setting

La activacin de falla a tierra (Ig) (A) ajusta el


nivel de la corriente de falla a tierra cuando se
dispara el interruptor despus de transcurrido
un retardo de tiempo predefinido.

Es posible utilizar un enclavamiento selectivo


de zona (ZSI) en la proteccin contra fallas a
tierra del equipo con los interruptores de
corriente ascendente o descendente. Al
ajustar en 0 el retardo de falla a tierra (tg), se
desactiva el enclavamiento selectivo de zona.

x In

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

La proteccin contra fallas a tierra del equipo


es una funcin estndar en las unidades de
disparo 6.0P.

El retardo de falla a tierra (tg) (B) ajusta el


perodo durante el cual el interruptor llevar
una corriente de falla a tierra por encima del
nivel de activacin de la corriente de falla a
tierra antes de dispararse.

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

.2
.1
2

I t

4
3

0
off

delay

6 8 10
12
15
off
2
x In
test

tg
F
G
H
J

.4 .4 .3
.2
.3
.1
.2
.1 2 0

(s)

on

I t

off

ground fault

In 2000 A

Tabla 5:

Valores de activacin de falla a tierra de la unidad de


disparo Micrologic

Ig (= In x....)

In  400 A

0.3

0.3

0.4

0.5

0.6

0.7

0.8

0.9

400 A < In  1 200 A

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

In > 1 200 A

500 A 640 A 720 A 800 A 880 A 960 A 1 040 A 1 120 A 1 200 A

In = valor nominal del sensor. Ig = activacin de falla a tierra.

Tabla 6:

Valores de retardo de falla a tierra de la unidad de disparo


Micrologic

Ajuste

Retardo de falla a tierra

0,1

0,2

0,3

0,4

I t on (ms en In) (segundos)

0,1

0,2

0,3

0,4

tsd (disparo mn.) (milisegundos)

20

80

140

230

350

tsd (disparo mx.) (milisegundos)

80

140

200

320

500

I t off (ms en In) (segundos)

20002012 Schneider Electric Reservados todos los derechos

13-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

48049-137-05
Rev. 01, 07/2012

Configuracin de la unidad de
disparo Micrologic
Alimentacin de control

La unidad de disparo P ha sido diseada para usarse con una fuente de


alimentacin externa de 24 V --- (cd). La pantalla de cristal lquido grande
que usa la unidad de disparo P necesita demasiada corriente para ser
energizada por el flujo de corriente que pasa por el interruptor automtico.

ESPAOL

La unidad de disparo P tiene una fuente de alimentacin de tensin del


circuito que energizar la unidad de disparo cuando hay aproximadamente
150 V~ (c.a.) o ms entre las dos fases. La configuracin estndar para las
sondas de tensin dentro del interruptor automtico se encuentra en las
conexiones en la parte inferior. Si el interruptor automtico est abierto en
una aplicacin de alimentacin por la parte superior, no habr tensin en la
parte inferior del interruptor y la unidad de disparo no estar energizada.
Las siguientes funciones estarn energizadas y disponibles aun cuando la
unidad de disparo no sea alimentada con una fuente externa:

Proteccin contra fallas para las funciones LSIG. La unidad de disparo


P est completamente energizada por el circuito para protegerla contra
fallas.

LED indicador de disparo (energizado por una batera integrada). La


funcin exclusiva de la batera es proporcionar una indicacin por LED
cuando todas la dems fuentes de alimentacin estn desconectadas.

El botn de disparo por falla a tierra funciona para pruebas de falla a


tierra cuando la unidad de disparo es energizada por la fuente de
alimentacin de tensin del circuito. El botn de disparo por falla a tierra
tambin funciona cuando un equipo de pruebas de plenas funciones o
porttil est energizando la unidad de disparo.

Las siguientes funciones estarn energizadas y disponibles con


alimentacin externa:

14-ES

Todas las funciones anteriores que estn disponibles sin alimentacin


externa.

La pantalla de cristal lquido y la contraluz funcionan correctamente. La


intensidad de la contraluz no se puede controlar ni ajustar, y puede ser
diferente en cada unidad de disparo.

Todas las funciones de medicin, supervisin y registros cronolgicos


de historial estn disponibles.

Las comunicaciones entre la unidad de disparo y los mdulos de


contactos programables M2C y M6C son energizadas por una fuente de
alimentacin de 24 V --- (cd) en F1 y F2. El mdulo M6C tambin
necesita una fuente de alimentacin externa de 24 V --- (cd).

Los mdulos de comunicaciones Modbus funcionan empleando una


fuente de alimentacin independiente de 24 V --- (cd) para el mdulo de
comunicaciones del interruptor automtico. Esta fuente de alimentacin
independiente de 24 V --- (cd) es necesaria para mantener el
aislamiento entre la unidad de disparo y el mdulo de comunicaciones.

El botn de disparo por falla a tierra tambin funciona cuando un equipo


de pruebas de plenas funciones o porttil est energizando la unidad de
disparo.

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Fuente de alimentacin externa


La unidad de disparo se puede energizar con:

PELIGRO DE DESCARGA ELCTRICA,


DESTELLO POR ARQUEO O DAO AL
EQUIPO
La unidad de disparo y el mdulo de
comunicaciones debern utilizar fuentes de
alimentacin independientes.
El incumplimiento de esta instruccin
puede causar lesiones personales o dao al
equipo.

una fuente de alimentacin externa de 24 V --- (cd), recomendada.

ms de 150 V en las terminales superiores del interruptor automtico


con opcin de tensin externa.

ms de 150 V en las terminales inferiores del interruptor automtico, en


dos fases.

Tabla 7:

Especificaciones de la fuente de alimentacin

Funcin

Especificacin

ESPAOL

PRECAUCIN

Alimentacin nicamente para la unidad de disparo 24 V --- (c.d.), 50 mA


Aislamiento mnimo de entrada a salida

2 400 V

Salida (incluyendo una ondulacin mx. del 1%)

5%

Rigidez dielctrica (entrada/salida)

3 kV rcm

Conexiones

Conexiones UC3
F1 (-)
24 V--- (c.d.)
F2 (+)

La fuente de alimentacin se utiliza para:


visualizar grficos en pantalla cuando el interruptor automtico est abierto
y es alimentado por la parte superior.
conectar una alarma a una salida de relevador.
conservar la fecha y hora mientras el interruptor automtico est abierto.

Configuracin de Micrologic
NOTA: Si la unidad de disparo est conectada a
una red de comunicacin que proporciona la
sincronizacin de fecha y hora, no es posible
configurar la fecha y hora desde la unidad de
disparo.
Consulte la pgina 35 para obtener las
instrucciones paso a paso para configurar la
unidad de disparo Micrologic.

Utilice el men de servicio de mantenimiento presionando la llave para


tuercas.
Figura 8:
06133330

Configuracin Micrologic

History
logs
Contacts
M2C / M6C
Micrologic
setup
Metering
setup
Com.
setup

Consulte la Seccin 3 en la pgina 32 para


obtener otras instrucciones de configuracin de
la unidad de disparo.

20002012 Schneider Electric Reservados todos los derechos

Configuracin Micrologic
Configurar
Micrologic
Idioma

Selecciona el idioma de las pantallas

Fecha/hora

Configura la fecha y hora

Seleccin
interruptor

Permite ingresar la informacin acerca del


interruptor en el que est instalada la
unidad de disparo

Signo
potencia

Selecciona la direccin del signo de potencia


para los mens de medicin

Transfo de
tensin

Selecciona la razn de tensin, si no est


presente un transformador de tensin
externo, seleccione 690:690

Frecuencia
de red

Selecciona la frecuencia del sistema

15-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

48049-137-05
Rev. 01, 07/2012

Proteccin avanzada
Proteccin neutra

AVISO

La proteccin neutra protege a los conductores


del neutro contra el sobrecalentamiento.

PELIGRO DE DAO AL EQUIPO.

ESPAOL

Es posible obtener una proteccin neutra


con un dispositivo de tres polos si se utiliza
un transformador de corriente al neutro.

Si se ajusta en 4P3D el selector de polo neutro de un interruptor de cuatro


polos, la corriente del neutro no deber exceder la corriente nominal del
interruptor.

Ajuste el neutro con la terminal de


programacin y ajustes de la unidad de
disparo.

Seleccione un transformador de corriente al neutro de tamao adecuado


para un interruptor de tres polos con proteccin neutra mayor (1,6N).
El incumplimiento de esta instruccin puede causar dao al equipo.

Ajustes posibles: OFF, N/2, N o 1.6N.


Ajuste de fbrica: OFF.
La proteccin neutra mayor (1,6N)
requiere un transformador de corriente al
neutro de mayor tamao.
Seleccione el tipo de sistema en el selector
de neutro de un interruptor de cuatro polos
(vea la figura 9).
Realice ajustes precisos a travs de la
terminal de programacin y ajustes de la
unidad de disparo; sin embargo,
seleccione el lmite superior de ajuste
con el selector del interruptor.

Figura 9:

Selector de neutro de un interruptor de cuatro polos


Ajustes de proteccin neutra para
un interruptor de cuatro polos

06134824

4D
4P

Selector del
interuptor

Ajustes
disponibles a
travs de la
terminal de
programacin y
ajustes

4P 3D

Off, N/2, N

3P N/2

N/2

4P 4D

N/2, N

Ajuste de fbrica: 4P4D.

La proteccin neutra para conductores tiene


cuatro ajustes posibles:
OffDesactivacin de la proteccin
neutra.

Tabla 8:

Activacin de
tiempo largo
Ajuste

1.6NLa capacidad del conductor


neutro es 1,6 veces la de los
conductores de lnea (interruptores de
tres polos solamente).

16-ES

Activacin de
tiempo corto

Instantnea

Activacin de
falla a tierra

Unidad
Unidad
Unidad
Unidad
de
Neutra de
Neutra de
Neutra de
disparo
disparo
disparo
disparo

Neutra

OFF

Ir

Ninguna Isd

Ninguna Ii

Ninguna Ig

Ninguna

N/2

Ir

1/2 Ir

1/2 Isd

Ii

Ii

Ig

Ig

Ir

Ir

Isd

Isd

Ii

Ii

Ig

Ig

1.6N

Ir

1,6 x Ir

Isd

1,6 x Isd* Ii

Ii

Ig

Ig

N/2La capacidad del conductor neutro


es la mitad de la de los conductores de
lnea.
NLa capacidad del conductor neutro
es la misma que la de los conductores de
lnea.

Tipo de proteccin para la unidad de disparo Micrologic

Isd

*Limitado en 10 x In, segn el lmite de la gama.

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Alarmas

Tabla 9:

Es posible activar o desactivar las alarmas con la


funcin de proteccin o desconexin de carga.

Alarma

Men

Smbolo

Alarma Disparo

Activacin de tiempo largo

Proteccin corriente

Ir

Activacin de tiempo corto

Proteccin corriente

Isd

Activacin instantnea

Proteccin corriente

Ii

Cuando se activa o desactiva una alarma,


sta se registra en el archivo cronolgico de
alarmas.
Para que una unidad de disparo active una
alarma, el nivel de activacin y el retardo de
tiempo debern ser excedidos. Sin embargo,
para que las protecciones LSIG y avanzada
programadas disparen el interruptor, la
unidad de disparo no activar la alarma hasta
que se dispare el interruptor. Por ejemplo, si
la activacin de tiempo largo Ir de un rel
est programada, la unidad de disparo no
indicar una alarma cuando se encienda el
indicador de sobrecarga. La unidad de
disparo activar la alarma slo cuando la
sobrecarga de tiempo largo exceda el retardo
de tiempo y dispare el interruptor).
Conecte las alarmas a una seal visual o
audible programando los contactos M2C o
M6C del mdulo opcional cuando se utiliza
una fuente de alimentacin externa de 24
V --- (cd) en la unidad de disparo.
Visualice las alarmas en el:
men de registros cronolgicos histricos

Corriente de falla a tierra

Proteccin corriente

Alarma de falla a tierra

Proteccin corriente

Al

Desequilibrio de corriente

Proteccin corriente

Ideseq.

Demanda de corriente mxima, fase 1 Proteccin corriente

I1 mx

Demanda de corriente mxima, fase 2 Proteccin corriente

I2 mx

Demanda de corriente mxima, fase 3 Proteccin corriente

I3 mx

Demanda de corriente mxima neutra Proteccin corriente

In mx

Tensin mnima (baja tensin)

Proteccin de tensin Umn

Tensin mxima (sobretensin)

Proteccin de tensin Umx

Desequilibrio de tensin

Proteccin de tensin Udeseq.

Potencia inversa

Otras proteccion.

rPmx

Frecuencia mnima (baja frecuencia)

Otras proteccion.

Fmn

Frecuencia mxima (sobrefrecuencia) Otras proteccion.

Fmx

Rotacin de fases

Otras proteccion.

rot 

Desconexin de carga de corriente

Desconex. reconex. I

Desconex.
reconex. I

Desconexin de carga de
alimentacin

Desconex.
reconex. P

Desconex.
X
reconex. P

ESPAOL

Alarmas de la unidad de disparo

software de gestin del sistema de la red

Caractersticas de los contactos M2C/M6C:


carga mnima de 100 mA/24 V --- (cd)
capacidad de interrupcin con un factor
de potencia de 0,7
240 V~

5A

380 V~

3A

24 V --- (cd)

1,8 A

48 V --- (cd)

1,5 A

125 V --- (cd) 0,4 A


250 V --- (cd) 0,15 A

Cuando se activan varias alarmas, el tiempo


de respuesta/regeneracin de la pantalla
ser ms lento.

Consulte el apndice B para obtener la gama de


valores y los valores por omisin.

20002012 Schneider Electric Reservados todos los derechos

17-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Proporciona los valores de activacin y


desactivacin de alarma, contactos o disparo
para los valores de corriente y tensin. (no
existe un mnimo para la corriente).

ESPAOL

El valor de activacin (A) se ajusta para


activar una alarma o disparo.

El retardo de tiempo de activacin (B) se


ajusta para empezar a contar el tiempo
transcurrido una vez que ha pasado el valor
de activacin.

El valor de desactivacin (C) se ajusta para


desactivar la alarma y/o el contacto.

El retardo de tiempo de desactivacin (D) se


ajusta para empezar a contar el tiempo
transcurrido una vez que ha pasado el valor
de desactivacin.

La proteccin de tensin (baja) mnima


(Umn) se activa cuando una tensin de lnea
a lnea es inferior al ajuste de tensin mn.

La proteccin de tensin mxima (sobre)


(Umx) se activa cuando una tensin de lnea
a lnea es superior al ajuste de tensin mx.

Umn tiene un valor de desactivacin  valor


de activacin.

Umx tiene un valor de desactivacin  valor


de activacin.

Si la proteccin de corriente o tensin


dispara el interruptor, no es posible
restablecerlo sino hasta que se corrija el
problema de corriente o tensin que caus
el disparo.

El valor de la alarma de falla a tierra en las


unidades de disparo 5.0P y 6.0P se basa en
valores de rcm verdaderos de la corriente de
tierra.

El valor de disparo de falla a tierra en la


unidad de disparo 6.0P se basa en un valor
de rcm verdadero de la corriente de tierra.

No ajuste la proteccin de baja tensin por


debajo del 80%*.

Figura 10:

Curvas de proteccin mnima y mxima

Proteccin mxima
06134770

Valores de proteccin de demanda de


corriente y tensin mnima (baja) y
mxima (sobre)

48049-137-05
Rev. 01, 07/2012

Proteccin mnima

C
D

A
B

I/VLL

VLL

Consulte el apndice D para obtener una explicacin del comportamiento de la proteccin del sistema.

18-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Los valores de desequilibrio se basan en los


valores de rcm verdaderos de las corrientes
de tres fases.

No ajuste el valor de Udeseq. en un valor


superior al 20%* .

No utilice la proteccin de desequilibrio de


tensin para determinar la prdida de
mltiples fases*.

Proteccin de desequilibrio de corriente o tensin

max

Iavg
or
Vavg
0

I1

I2

I +I +I
Imedia = 1 2 3
3

U + U2 + U3
Umedia = 1
3

Ideseq. = |'mx|
Imedia

Udeseq. = |'mx|
Umedia

I3

ESPAOL

Esta proteccin se aplica a los valores de


desequilibrio de tensiones y corrientes de tres
fases.

Figura 11:
06134769

Proteccin de desequilibrio de corriente


o tensin

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Consulte el apndice D para obtener una explicacin del comportamiento de la proteccin del sistema.

Proteccin de potencia inversa (rPmx)

Figura 12:

La proteccin de potencia inversa aplica una


curva de disparo en base al valor total de la
potencia real (A) de las tres fases.

El retardo de tiempo (B) comienza a contar


el tiempo transcurrido si el valor total de la
potencia real de las tres fases no circula en
la direccin definida y si ste excede un
umbral de potencia inversa.

La direccin de la potencia se define durante


la configuracin de la unidad de disparo.

Protecciones de frecuencia mxima


(sobre) y mnima (baja)

06134771

Este tipo de proteccin protege a alternadores


contra la absorcin total de la potencia real de
las tres fases ante la posible falla de un motor
accionador.

Proteccin de potencia inversa

A
B

Figura 13:

Curvas de frecuencia mnima y mxima

06133266

Proteccin mnima

Proporciona valores de activacin y


desactivacin a la frecuencia.

El retardo de tiempo de activacin (B) se


ajusta para empezar a contar el tiempo
transcurrido una vez que ha pasado el valor
de activacin.

El valor de desactivacin (C) se ajusta para


desactivar la alarma y/o el contacto.

El retardo de tiempo de desactivacin (D) se


ajusta para empezar a contar el tiempo
transcurrido una vez que ha pasado el valor
de desactivacin.

Fmn tiene un valor de desactivacin  valor


de activacin.

El valor de activacin (A) se ajusta para


activar una alarma o disparo.

Proteccin mxima

C
D

20002012 Schneider Electric Reservados todos los derechos

Fmin

Fmax

19-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Fmx tiene un valor de desactivacin  valor


de activacin.

Cuando la frecuencia del sistema se ajusta


en 400 Hz, la proteccin de frecuencia se
desactiva.

Desconexin de carga (Desconex.


reconex.)

ESPAOL

La desconexin de carga no dispara el


interruptor pero se puede utilizar para activar
una alarma conectada a un contacto M2C o
M6C (que controla las cargas de red no
prioritarias).

Figura 14:
06134771

48049-137-05
Rev. 01, 07/2012

Desconexin de carga (Desconex. reconex.)


t

Curva de
proteccin
de tiempo
largo

C
A
D

La desconexin de carga se define con un


umbral y un retardo de tiempo.

AUmbral de activacin
BRetardo de tiempo de activacin
CUmbral de desactivacin
DRetardo de tiempo de desactivacin

La desconexin de carga de la alimentacin


depende de la direccin del flujo definida
durante la configuracin de la unidad de
disparo.

La desconexin de carga de la corriente est


conectada a los valores de retardo de
tiempo largo I2t o Idmtl.

La desconexin de carga de corriente no


puede ser activada si se ajusta el calibrador
de tiempo largo en OFF.

Proteccin de rotacin de fases

20-ES

Protege el circuito cuando se invierten dos de las tres fases.

Si existe una falla en una de las fases, esta psroteccin estar inactiva.

No utilice la proteccin de rotacin de fases para determinar la prdida


de mltiples fases en los sistemas conectados en delta.

Las opciones son 123 132.


Cuando la frecuencia del sistema se ajusta en 400 Hz, la proteccin de
rotacin de fases se desactiva.

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Es posible interbloquear la proteccin de tiempo


corto y contra fallas a tierra para proporcionar
un enclavamiento selectivo de zona.
El cableado de control conecta varias unidades
de disparo en la red de distribucin y, en caso
de una falla, una unidad de disparo obedecer
el tiempo de retardo ajustado slo si recibe una
seal de una unidad de disparo de corriente
descendente.

471

NOTA: La unidad de disparo y los mdulos de


comunicacin (MCI y MCC) debern utilizar
fuentes de alimentacin independientes. Los
accesorios de contactos M2C y M6C pueden
compartir la fuente de alimentacin auxiliar de la
unidad de disparo.

M6C: fuente de alim. externa de 24 V

(cd) necesaria

06133934

(cd)

Caractersticas de los
contactos programables
M2C/M6C

Carga mnima

24 V

(cd)

100 mA

240 V~

5A

380 V~

3A

Capacidad de ruptura con un factor 24 V


de potencia (f.p.) de 0,7
48 V

(cd)

1,8 A

(cd)

1,5 A

125 V

(cd) 0,4 A

250 V

(cd) 0,15A

NOTA: Utilice I2t off con ZSI para obtener una coordinacin correcta. No se
recomienda utilizar I2t on con ZSI ya que, debido al retardo en el dispositivo
de corriente ascendente que recibe la seal de restriccin, es posible que
se dispare la unidad en un perodo ms corto que el indicado en la curva de
disparo publicada.
NOTA: Cuando se ajusta en 0 el retardo de tiempo corto (tsd) o retardo de
falla a tierra (tg), se borrar (de la memoria) el criterio selectivo del
interruptor.

Si la unidad de disparo no recibe una seal, el


disparo ser instantneo (sin retardo
intencional).

La falla es restablecida instantneamente


por el interruptor de corriente ascendente
ms cercano.

Los esfuerzos trmicos (I2t) en la red se ven


reducidos sin afectar la correcta
coordinacin del retardo de tiempo de la
instalacin.

20002012 Schneider Electric Reservados todos los derechos

21-ES

ESPAOL

S1 S2

La unidad de disparo necesita una fuente de


alimentacin auxiliar de 24 V
(cd), 5 W para
hacer funcionar cualquier combinacin de
accesorio de contactos M2C o M6C.

Enclavamiento selectivo de zona

Diagramas de cableado de los contactos M2C/M6C

M2C: alim. de 24 V
suministrada por la
unidad de disparo
484

Es posible activar una o dos alarmas con el


accesorio de contactos programables M2C o
M6C opcional. El accesorio de contactos M2C
proporciona dos contactos forma A con neutro
en comn. El accesorio de contactos M6C
proporciona seis contactos forma C. Es posible
programar cada contacto para una condicin de
alarma a travs de la unidad de disparo.

Figura 15:

474

Accesorios de contactos
programables M2C y M6C

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Los interruptores 1 y 2 muestran la


deteccin de una falla en A. El interruptor 2
se dispara instantneamente y ordena al
interruptor 1 que respete los tiempos de
retardo establecidos. Por consiguiente, el
interruptor 2 se dispara y restablece la falla.
El interruptor 1 no se dispara.

El interruptor 1 muestra la deteccin de una


falla en B. El interruptor 1 se dispara
instantneamente puesto que no recibi una
seal del interruptor de corriente
descendente 2. El interruptor 1 se dispara y
restablece la falla. El interruptor 2 no se
dispara.

Enclavamiento selectivo de zona

Medicin

La unidad de disparo Micrologic P proporciona medicin continua de los


valores de la red. Los valores medidos pueden verificarse a travs de la
pantalla de visualizacin de grficos o el software de gestin del sistema de
la red.

Prueba de la unidad de disparo

Las funciones LSIG de la unidad de disparo se prueban con inyeccin


primaria o secundaria. Realice pruebas a la unidad de disparo utilizando el
equipo de pruebas de plenas funciones o el equipo de pruebas porttil.
(Consulte la seccin Verificacin de la instalacin de la unidad de disparo
en la pgina 67 para obtener ms informacin.)

Contador de maniobras

Se necesita un mdulo de comunicacin del interruptor para visualizar la


cantidad total de instancias en que se ha abierto el interruptor desde su
instalacin inicial y desde el ltimo restablecimiento as como la fecha/hora
de este ltimo restablecimiento.

Luces indicadoras
Luz indicadora de sobrecarga

Figura 17:

Luz indicadora de sobrecarga

Unidad de disparo Micrologic 5.0P


long time

Ir
.7
.6
.5
.4

.8

x In

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

@ 6 Ir

setting

long time

Ir
.7
.6
.5
.4

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

Unidad de disparo Micrologic 6.0P


06134754

La luz indicadora de sobrecarga (A) se ilumina


cuando se ha excedido el nivel de activacin de
tiempo largo (Ir).

06134753

ESPAOL

Figura 16:

06133376

La figura 16 muestra los interruptores 1 y 2 con


enclavamiento selectivo de zona.

48049-137-05
Rev. 01, 07/2012

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

Ii

(s)

on

I t

off

4
3

6 8 10
12
15
off
2
x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

delay

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

on

setting

Ig
D
C
B
A

I t

off

delay

tg
F
G
H
J

Ii

(s)

(s)

4
3

6 8 10
12
15
off
2
x In
test

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

ground fault

22-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

Luces indicadoras de disparo

AVISO

Una luz indicadora se iluminar cuando se


dispare el interruptor. Si la unidad de disparo
tiene una fuente de alimentacin auxiliar
conectada, la unidad mostrar informacin
acerca del disparo.

El incumplimiento de esta instruccin puede causar dao al equipo.


Figura 18:

Luces indicadoras de disparo

B C

E A

ESPAOL

La luz indicadora de disparo Ir (B) se ilumina


cuando la activacin de tiempo largo (Ir)
provoca el disparo del interruptor.

Si despus de un restablecimiento el interruptor permanece cerrado y la


luz Ap permanece iluminada, abra el interruptor y pngase en contacto
con la oficina de ventas.

06134251

La luz indicadora permanecer iluminada hasta


que se restablece al oprimir el botn de
restablecimiento (A). La causa del disparo
deber corregirse antes de restablecer la luz
indicadora.

PELIGRO DE DAO AL EQUIPO

Micrologic 6.0 P

La luz indicadora de disparo Isd/Ii (C) se ilumina


cuando la activacin de tiempo corto (lsd) o
activacin instantnea (Ii) provoca el disparo del
interruptor.

La luz indicadora de autoproteccin/proteccin


avanzada Ap (E) se ilumina cuando las
funciones de proteccin avanzada ocasionan un
disparo, la unidad de disparo se sobrecalienta,
se rebasa el nivel mximo de proteccin
instantnea o se produce una falla en la fuente
de alimentacin de la unidad de disparo.

Botn de
prueba/restablecimiento

NOTA: Si las causas de disparo son varias, el LED de sealizacin de la


ltima causa ser el nico que permanecer conectado.

Figura 19:
06134251

La luz indicadora de disparo Ig (D) se ilumina


cuando la activacin de falla a tierra (Ig) provoca
el disparo del interruptor.

Botn de restablecimiento

Micrologic 6.0 P

El botn de prueba/restablecimiento (A) deber


oprimirse despus de un disparo para
restablecer la informacin de la falla en la
pantalla de grficos y apagar la luz indicadora
de disparo.

20002012 Schneider Electric Reservados todos los derechos

23-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 1Informacin general

La pantalla de visualizacin de grficos (A)


muestra los ajustes e informacin acerca de la
unidad de disparo. Los botones de navegacin
(B) se utilizan para mostrar y modificar
elementos en la pantalla. La visualizacin por
omisin muestra los niveles de corriente.

Figura 20:
06134749

Pantalla de visualizacin de
grficos

48049-137-05
Rev. 01, 07/2012

Pantalla de visualizacin de grficos

Micrologic 5.0 P

4260A

N 1 2 3
100

50

ESPAOL

La unidad de disparo deber estar energizada


para que funcione la pantalla de visualizacin
de grficos. La unidad de disparo est
energizada:

si el interruptor est conectado y tiene ms


de 150 V de tensin de carga en dos fases
(el interruptor est cerrado o recibe
alimentacin por la parte inferior).

si el equipo de pruebas de plenas funciones


o porttil est conectado y energizado.

si la fuente de alimentacin externa de 24


V --- (cd) est conectada.

si la derivacin de tensin externa est


instalada y hay ms de 150 V en dos fases.

Indicador de desgaste de los


contactos

24-ES

La unidad de disparo lleva un registro del desgaste de los contactos de un


interruptor cuando se selecciona un interruptor de potencia Masterpact. Es
posible transferir este registro de desgaste de los contactos del interruptor
cuando se sustituye una unidad de disparo (se necesita una fuente de
alimentacin externa para la unidad de disparo).

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 2Navegacin por la visualizacin de grficos

Seccin 2Navegacin por la visualizacin de grficos

Figura 21:

El visualizador de grficos (A) funciona


solamente si la unidad de disparo est
conectada a una fuente de alimentacin externa
de 24 V --- (cd) o si hay 150 V en por lo menos
dos fases. La corriente (de un equipo de
pruebas de inyeccin primaria o sistema
elctrico) nicamente energizar las funciones
de proteccin LSIG pero no energizar el
visualizador.

Visualizacin de grficos

4260A
N 1 2 3

100

ESPAOL

Visualizacin de grficos

50

Botones de navegacin (B):


Botn del men de medicin: proporciona
acceso a los mens de medicin
Botn del men de servicio de
mantenimiento: proporciona acceso a los
mens de servicio de mantenimiento
Botn del men de proteccin:
proporciona acceso a los mens de
proteccin
Botn flecha abajo: desplaza el cursor
hacia abajo o disminuye el valor de los
ajustes
Botn flecha arriba: desplaza el cursor
hacia arriba o aumenta el valor de los
ajustes
Botn de introduccin de valores:
selecciona una opcin de una lista o
ingresa los valores de los ajustes

20002012 Schneider Electric Reservados todos los derechos

25-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 2Navegacin por la visualizacin de grficos

4260A

(A)
(V)

50

U
P
E

(kWh)

(Hz)

N 1 2 3
100

06133330

Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

(kW)

06133331

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

B. Men de medicin: proporciona acceso a los


valores de medicin de corriente, tensin,
potencia, energa y frecuencia
C. Men de servicio de mantenimiento: permite
al usuario cambiar la configuracin de la
unidad de disparo y proporciona acceso a
los archivos cronolgicos de historial
D. Men de proteccin: permite realizar ajustes
precisos a las protecciones bsica y
avanzada
Una vez que se cierra la cubierta de los
selectores, la unidad de disparo regresar a la
visualizacin (por omisin) de grficos de barras
despus de transcurridos 3 1/2 minutos sin
ingresar un valor. (si la cubierta de los
selectores est abierta, la visualizacin
permanecer en la ventana seleccionada.) Si
desea visualizar otro men, presione el botn
correspondiente. Aparecer el men en la
visualizacin y se encender el LED verde
debajo del botn del men.

Men de medicin
Utilice el botn de medicin para acceder a los
valores de medicin de:
A. Corriente
B. Tensin
C. Potencia
D. Energa
E. Frecuencia

26-ES

Figura 23:

Men de medicin
06134267

ESPAOL

A. Visualizacin de grficos de barras:


proporciona una visualizacin de grficos de
barras en tiempo real de las corrientes de
lnea y mediciones de las corrientes de lnea
y neutra, si es aplicable, (visualizacin por
omisin)

Mens

06134267

La unidad de disparo Micrologic P incluye una


visualizacin por omisin de grficos de barras
de corrientes y tres mens diferentes los cuales
se pueden acceder a travs de los botones de
navegacin:

Figura 22:

06134792

Visualizacin de grficos de
barras y mens

48049-137-05
Rev. 01, 07/2012

(A)

Desplaza el cursor hacia abajo

U
P
E

(V)

Desplaza el cursor hacia arriba

(kW)

Selecciona el elemento en
cuestin

(kWh)

(Hz)

Regresa a la pantalla anterior


Regresa a la visualizacin
de grficos de barras

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

(A)

U
P
E

(V)
(kWh)

(Hz)

instant.
I1, I2, I3, In

Visualiza las corrientes 1, 2, 3 y


neutro (segn el tipo de red)

Mx

Visualiza y restablece los valores


mximos de la corriente

media
I1, I2, I3, In

Visualiza la demanda de corriente para


1, 2, 3 y neutro (segn el tipo de red)

Mx

Visualiza y restablece los valores


mximos de la demanda

Niveles de tensin

(kWh)

(Hz)

(V)

(U)

(A)

U
P
E

eficaz

(V)

Visualiza las tensiones instantneas de


fase a fase (U12, U23, U31) y de fase a neutro
tensiones instantneas (U1n, U2n, U3n)
(3 fases, 4 hilos con TC al neutro)

(kW)
media 3)

Visualiza la media de las tensiones de


fase a fase

deseq. 3)

Visualiza el desequilibrio de tensin de


fase a fase

Rotacin
de fases

Visualiza la secuencia de las fases

Niveles de potencia

(A)

U
P
E

(V)
(kWh)

(Hz)

20002012 Schneider Electric Reservados todos los derechos

(A)

(kW)

Figura 26:
06134267

Potencia

Figura 25:
06134267

Tensin

Niveles de corriente

(kW)

(kW)
instant.
P, Q, S

Visualiza la potencia activa total (P)


Visualiza la potencia reactiva total (Q)
Visualiza la potencia aparente total (S)

Factor de
potencia

Visualiza el factor de potencia

media
P, Q, S

Visualiza la demanda de potencia activa (P)


Visualiza la demanda de potencia reactiva (Q)
Visualiza la demanda de potencia aparente (S)

Mx

Visualiza y restablece los valores mximos


de la demanda

27-ES

ESPAOL

Figura 24:
06134267

Corriente

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 2Navegacin por la visualizacin de grficos

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 2Navegacin por la visualizacin de grficos

Figura 27:
06134267

Energa

ESPAOL

Niveles de energa

(A)

U
P
E

(kWh)

(Hz)

(V)
(kW)

(kWh)
E total

Visualiza la potencia activa total (E.P.)


Visualiza la potencia reactiva total (E.Q.)
Visualiza la potencia aparente total (E.S.)

E+
Consumida

Visualiza la potencia activa total (E.P.) consumida


Visualiza la potencia reactiva total (E.Q.)
consumida

EGenerada

Visualiza la potencia activa total (E.P.) generada


Visualiza la potencia reactiva total (E.Q.)
generada

Reset
energas

Restablece en cero todos los valores de energa

Frecuencia

(A)

U
P
E

(V)
(kWh)

(Hz)

Visualiza la frecuencia (F)

(kW)

Figura 29:

Men de servicio de mantenimiento


06133330

Men de servicio de mantenimiento

Figura 28:
06134267

Frecuencia

48049-137-05
Rev. 01, 07/2012

Utilice el botn de servicio de mantenimiento


para acceder a los mens correspondientes.

Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

A. Para acceder al archivo cronolgico de


historial
B. Para configurar los contactos M2C/M6C
C. Para configurar la unidad de disparo
Micrologic
D. Para configurar los parmetros de medicin

Desplaza el cursor hacia abajo

Desplaza el cursor hacia arriba

Selecciona el elemento
en cuestin

Regresa a la pantalla anterior

Regresa a la visualizacin
de grficos de barras

E. Para configurar el mdulo de comunicacin

Figura 30:
06133330

Archivos cronolgicos de historial

Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

28-ES

Archivos cronolgicos de historial


Histricos
Histrico
defectos

Visualiza el registro cronolgico de las


ltimas diez fallas registradas

Histrico
alarmas

Visualiza el registro cronolgico de las


ltimas diez alarmas activadas

Contador de
maniobras

Visualiza la cantidad de operaciones


(aperturas o disparos)

Estado de
contactos

Visualiza el estado de desgaste de


los contactos del interruptor automtico

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Disponible solamente si estn instalados los


contactos M2C/M6C.

Una alarma por contacto.

Contactos programables M2C/M6C


Contactos
M2C / M6C

Histricos

Tipo de
alarma

Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

Solamente se pueden seleccionar aqullos


configurados como alarma o disparo en
el men de proteccin.

S#

Configurar
S#

Reset

NOTA: Si la unidad de disparo est conectada a


una red de comunicacin que proporciona la
sincronizacin de fecha y hora, no es posible
configurar la fecha y hora desde la unidad de
disparo.

Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

Figura 34:
06133330

Configuracin de comunicaciones

Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

20002012 Schneider Electric Reservados todos los derechos

Restablece los contactos despus de


haberse activado una alarma

Configurar
Micrologic

Histricos

Figura 33:

Configura el modo para el contacto S#


# es igual a 1 2 para el contacto M2C
# es igual a partir de 1 a 6 para el
contacto M6C

Configuracin de Micrologic

Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

06133330

Configuracin de mediciones

Figura 32:
06133330

Configuracin de Micrologic

Asigna una alarma de proteccin al


contacto S#
# es igual a 1 2 para el contacto M2C
# es igual a partir de 1 a 6 para el
contacto M6C

Idioma

Seleccin del idioma de visualizacin

Fecha/hora

Configura la fecha y hora

Seleccin
interruptor

Ingresa informacin sobre el interruptor


automtico en el que se instal la unidad
de disparo

Signo
potencia

Selecciona la direccin del signo de potencia


para mens de medicin

Transfo
de tensin

Selecciona la razn de tensin. Si no est


presente un transformador de tensin externo,
seleccione 690:690

Frecuencia
de red

Selecciona la frecuencia del sistema

Configuracin de mediciones
Configurar
medidas
Tipo de
red

Selecciona tipo de sistema de la red

Clculo
I media

Ajusta la demanda de corriente

Clculo
P media

Ajusta la demanda de potencia

Convencin
de signos

Selecciona la convencin de signos

Configuracin del mdulo de comunicaciones


Configurar
Com.
Parmetros
com.

Configura el mdulo de comunicacin

Regulacin
a distancia

Determina el acceso a los ajustes de la unidad


de disparo a travs del mdulo de comunicacin

Mando a
distancia

Determina si es posible conectar o desconectar


el interruptor automtico a travs del
mdulo de comunicacin

29-ES

ESPAOL

Figura 31:
06133330

Contactos programables M2C/M6C

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 2Navegacin por la visualizacin de grficos

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 2Navegacin por la visualizacin de grficos

Figura 35:

Men de proteccin
06133331

Men de proteccin

48049-137-05
Rev. 01, 07/2012

Utilice el botn de proteccin para acceder a los


mens.
A. Para visualizar y ajustar la proteccin de la
corriente
B. Para visualizar y ajustar la proteccin de la
tensin
C. Para visualizar y ajustar otro tipo de
proteccin

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

Desplaza el cursor hacia abajo

Desplaza el cursor hacia arriba

Selecciona el elemento
en cuestin

Regresa a la pantalla anterior

Regresa a la visualizacin
de grficos de barras

E. Para configurar la desconexin de carga de


la alimentacin
Figura 36:
06133331

Proteccin de corriente

Proteccin de corriente

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

Proteccin
corriente
Visualiza y proporciona un ajuste preciso a la

(A) proteccin I2t de tiempo largo, tiemp corto

I dmtl

Visualiza y proporciona un ajuste preciso a la


(A) proteccin Idmtl de tiempo largo, tiemp corto
e instantnea

(A) a la proteccin de falla a tierra

e instantnea

Visualiza y proporciona un ajuste preciso


(slo a Micrologic 6.0P)

I neutro (A)
I

Proteccin de tensin

Figura 37:
06133331

ESPAOL

D. Para configurar la desconexin de carga de


la corriente

30-ES

Ajusta el neutro (Off, N, N/2, 1.6N)

Alarm Ajusta los valores de alarma de falla a tierra

Ideseq. (%)

Ajusta los valores permitidos de desequilibrio


de corriente

I1mx (A)

Ajusta el valor mximo de demanda de corriente


en la fase 1

I2mx (A)

Ajusta el valor mximo de demanda de corriente


en la fase 2

I3mx (A)

Ajusta el valor mximo de demanda de corriente


en la fase 3

Inmx (A)

Ajusta el valor mximo de demanda de corriente


neutra

Proteccin de la tensin

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

Proteccin
de tensin

Umn

(V) Ajusta la proteccin mnima de (baja) tensin

Umx (V)

Ajusta la proteccin mxima de (sobre) tensin

Udeseq. (%)

Ajusta la proteccin de desequilibrio de


la tensin

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

rPmx (W)

Ajusta la proteccin de la potencia inversa

F mn (Hz)

Ajusta la proteccin mnima de (baja) frecuencia

Fmx (Hz)

Ajusta la proteccin mxima de


(sobre) frecuencia

Rotacin
de fases

Ajusta la proteccin de inversin de fases

Desconex.
Reconex.

Ajusta los valores de desconexin de carga


de la corriente (alarma solamente)

Desconexin de carga de la alimentacin

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

20002012 Schneider Electric Reservados todos los derechos

Otras
proteccion.

Desconexin de carga de la corriente

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

Figura 40:
06133331

Desconexin de carga de la alimentacin

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

Figura 39:
06133331

Desconexin de carga de la corriente

Otro tipo de proteccin

ESPAOL

Figura 38:
06133331

Otro tipo de proteccin

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 2Navegacin por la visualizacin de grficos

Ajusta los valores de desconexin de carga


Desconex.
Reconex. P de la alimentacin (alarma solamente)

31-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

48049-137-05
Rev. 01, 07/2012

Seccin 3Configuracin de la unidad de disparo

06133330

Men de servicio de mantenimiento

5.0
ogic

Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.
Abajo

32-ES

Configuracin de los accesorios de contactos


programables M2C/M6C
Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

06133334

Figura 42:

06133330

Si est instalado el accesorio de contactos M2C


o M6C, utilice el men Contactos M2C/M6C
para configurar el tipo de alarma y modo de
funcionamiento. El accesorio M2C tiene
contactos S1 y S2. El accesorio M6C tiene
contactos S1, S2, S3, S4, S5 y S6.

Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

2. Presione el botn de servicio de


mantenimiento (B) para mostrar el men de
servicio de mantenimiento (C).

Contactos programables M2C/M6C

Histricos

Microl

1. Abra la cubierta de los selectores (A).

06133330

ESPAOL

NOTA: La cubierta de los selectores deber


estar abierta para poder ajustar la unidad de
disparo a travs del men de proteccin. Una
vez que se han configurado los ajustes,
presione uno de los botones de men para
guardar los nuevos valores.

Figura 41:

06134825

Ajuste de los parmetros de la


unidad de disparo

Contactos
M2C / M6C
Tipo de
alarma
Configurar
Reset

Intro

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

IiActivacin instantnea

Configuracin del tipo de alarma para los contactos


M2C/M6C

Contactos
M2C / M6C

06133336

IrActivacin de tiempo largo

Figura 43:
06133334

1. Ingrese el tipo de alarma para los contactos


M2C/M6C en la memoria de la unidad de
disparo. Las alarmas disponibles son:

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Tipo de
alarma

IsdActivacin de tiempo corto

Tipo
de alarma
S1

S1

S1

Ii

Isd

S2

Configurar

I Corriente de falla a tierra


Reset

AI Alarma de falla a tierra

Intro

Intro

I1mxSobrecorriente en la fase 1

Arriba/
Abajo

Intro
Intro

I3mxSobrecorriente en la fase 3

Salir
06133335

UmnTensin por debajo del ajuste


mnimo

06133336

I2mxSobrecorriente en la fase 2

InmxSobrecorriente en el neutro

Desea
guardar los
cambios?

UmxTensin por arriba del ajuste


mximo

Tipo
de alarma
S1
S2

S2
No
utilizado

ESPAOL

Ideseq.Desequilibrio de corriente

S2
IsdIsd

No

Udeseq.Desequilibrio de tensin
Si

rPmxPotencia inversa
FmnFrecuencia por debajo del ajuste
mnimo

Abajo

Abajo

Intro

Intro

FmxFrecuencia por arriba del ajuste


mximo

Desconex. reconex. PDesconexin de


carga de la alimentacin

06133336

Desconex. reconex. IDesconexin de


carga de la corriente

Intro
Salir

06133335

rot. )Rotacin de fases

Arriba/
Abajo

Intro

Desea
guardar los
cambios?

Tipo
de alarma
S1
S2

No

No seleccionadoNo se seleccion ninguna


alarma

Si
Abajo

Salir

Intro

20002012 Schneider Electric Reservados todos los derechos

33-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Configuracin del modo de alarma para los contactos


M2C/M6C

Contactos
M2C / M6C

06133337

Con enganchePermanece
enganchado hasta que se restablece

Figura 44:
06133334

2. Configuracin del modo de alarma para los


contactos M2C/M6C. Los modos de los
contactos disponibles son:

48049-137-05
Rev. 01, 07/2012

Tipo de
alarma

Sin engancheSe desactiva despus de


solucionar la falla

Configurar
M2C/M6C

S1

S1

Contacto

Contacto

S1

Forzado a 1

Transitorio

S2

Configurar

Tiempo

Retardo de tiempoRetardo asignado a


los contactos

Reset

Arriba/
Abajo

Intro

Intro

Intro

Forzado a 0Se bloquean los contactos


en posicin abierta

Para las alarmas de tiempo corto,


instantnea y de falla a tierra (SIG)
solamente:

S1

S1

Contacto

Contacto

Transitorio

Transitorio

Tiempo

Desea
guardar los
cambios?

Tiempo

Configurar
M2C/M6C
S1
S2

No

5s

1s

Cada instancia de alarma activar el rel


y emitir una seal de alarma que
continuar hasta que se presione el
botn de prueba/restablecimiento de la
unidad de disparo.

06133335

Forzado a 1Se bloquean los contactos


en posicin cerrada

06133337

Intro

Si
Arriba/
Abajo

Abajo
Intro

Este comportamiento con enganche


sucede independientemente si se usa o
no el modo de contacto con enganche
o sin enganche durante la
configuracin de la alarma.

Intro

Abajo

Abajo

Intro

Intro

Salir

3. El botn de restablecimiento le permite


visualizar el estado de los rels y, a su vez,
restablecerlos.

S2

S2

S2

S2

Contacto

Contacto

Contacto

Contacto

Forzado a 1

Transitorio

Transitorio

Transitorio

Tiempo

Tiempo

NOTA: Seleccione Reset (restablecer) bajo


el men M2C/M6C para restablecer todas
las alarmas. El botn de
prueba/restablecimiento restablecer la
unidad de disparo para desactivar la alarma
pero no restablecer el contacto M2C/M6C.

360s

360s

Arriba/
Abajo

Intro

Tiempo
1s

Arriba/
Abajo

Abajo
Intro

Intro

Intro

Desea
guardar los
cambios?

Configurar
M2C/M6C
S1
S2

No

06133334

06133337

Salir
06133335

ESPAOL

El diagnstico de problemas se puede


realizar slo bajo los siguientes modos:

1s

Contactos
M2C / M6C
Tipo de
alarma
Configurar

Slo modo Transitorio

Reset

Si
Abajo

Salir

Salir

Intro

34-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.
Intro

Abajo

Figura 46:
06133339

1. Ajuste del idioma de visualizacin.

Fecha / hora

Signo
potencia
Transfo
de tensin

Idioma
Fecha / hora
Seleccin
interruptor
Signo
potencia
Transfo
de tensin
Frecuencia
de red

Ajuste de idioma

Idioma

Seleccin
interruptor

Histricos

ESPAOL

Histricos

06133338

Configuracin de la unidad de disparo Micrologic


06133330

Utilice el men Configurar Micrologic para


ajustar idioma, fecha y hora, informacin sobre
el interruptor, tipo de TC al neutro, razn del
transformador de tensin (Transfo de tensin) y
frecuencia de la red.

Figura 45:
06133330

Configuracin de la unidad de
disparo Micrologic

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Idioma
Deutsch
English US
English UK
Espaol
Franais
Arriba/
Abajo

Intro
Intro

20002012 Schneider Electric Reservados todos los derechos

35-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

ESPAOL

NOTA: Si la unidad de disparo est


conectada a una red de comunicacin que
proporciona la sincronizacin de fecha y
hora, no es posible configurar la fecha y
hora desde la unidad de disparo. (Si la
unidad de disparo no est conectada a la
red de comunicacin que proporciona la
sincronizacin de fecha y hora, stas
tendrn que volver a ingresarse cada vez
que haya una prdida de alimentacin.)
NOTA: El formato de fecha en ingls
americano es mes/da/ao. En todos los
dems idiomas el formato de fecha es
da/mes/ao.
Despus de utilizar el equipo de pruebas de
inyeccin secundaria, inhibicin de
imgenes trmicas, pruebas de ZSI o
inhibicin de fallas a tierra, tendr que volver
a ajustar la hora si la unidad de disparo no
est conectada a una red de comunicacin
que proporcione sincronizacin de fecha y
hora.

Figura 47:
06133339

2. Ajuste de fecha y hora de la unidad de


disparo.

48049-137-05
Rev. 01, 07/2012

Configuracin de fecha y hora

Idioma
Fecha / hora
Seleccin
interruptor
Signo
potencia

Fecha

Fecha

25 / 01 / 2001

28
02 / 01 / 2001

02 / 2001
28 / 28

Hora

Hora

Hora

06:12:35

06:12:35

06:12:35

Transfo
de tensin
Arriba/
Abajo

Arriba/
Abajo

Intro

Intro

Intro

Intro

Fecha

Fecha

Fecha

Fecha

2001
28 / 02 / 2001

28 / 02 / 2001

28 / 02 / 2001

28 / 02 / 2001

Hora

Hora

Hora

Hora

18:12:35

06:12:35
19

11
19:12:35

18:12:35pm

Arriba/
Abajo

Fecha

Fecha

28 / 02 / 2001

28 / 02 / 2001

Hora

Hora

25
19:11:35

19:11:25

Arriba/
Abajo

Arriba/
Abajo

Arriba/
Abajo

Abajo
Intro

Intro

NOTA: Si la hora no es sincronizada por un


supervisor con el software de gestin del
sistema de la red, vuelva a ajustarla cada
seis meses o ms frecuentemente, si es
necesario.

Fecha

Intro

Intro

Salir

Intro

36-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Fecha / hora
Seleccin
interruptor

Familia de interruptoresMasterpact (ANSI,


UL, IEC o IEC/GB), Powerpact (UL o IEC) o
Compact NS (IEC)

Signo
potencia

Cdigo de desgaste de los contactos del


interruptorSolamente se modifica cuando
se sustituye una unidad de disparo existente
con informacin sobre el desgaste de los
contactos
NOTA: El medidor de desgaste del contacto
est activo slo cuando el tipo de interruptor
es Masterpact.
Siga estos pasos para conservar la
informacin del indicador de desgaste del
contacto cuando se sustituye una unidad de
disparo existente:
a. Lea el cdigo en la unidad de disparo
que se va a sustituir (el cdigo es un
nmero hexadecimal).
b. Desmonte la unidad de disparo antigua e
instale la nueva unidad en el interruptor.
c. Ingrese el cdigo de la unidad de disparo
antigua en la unidad nueva.

Seleccin
interruptor

Idioma

NormaANSI, UL, IEC o IEC/GB

Tipo de interruptorInformacin ubicada en


la placa frontal del interruptor

Configuracin de la informacin del interruptor

Transfo
de tensin

Norma
ANSI
Interruptor
Masterpact
Tipo
NW32H2
0000

Norma
UL
Interruptor
Masterpact
Tipo
NW32H2
0000

HLogic2002AA

HLogic2002AA
Arriba/
Abajo

HLogic2002AA

Intro

Seleccin
interruptor

Seleccin
interruptor

Norma
UL
Interruptor
Masterpact
Tipo
NW32H2
0000

Norma
UL
Interruptor
Masterpact
Tipo
NW40H2
0000

HLogic2002AA
Arriba/
Abajo

HLogic2002AA

HLogic2002AA
Arriba/
Abajo

Abajo
Intro

Intro

Intro

Seleccin
interruptor

Seleccin
interruptor

Abajo

Seleccin
interruptor

Norma
UL
Interruptor
Masterpact
Tipo
NW32H2
0000

Intro

Seleccin
interruptor

Norma
ANSI
Interruptor
Masterpact
Tipo
NW32H2
0000
Intro

Intro

Seleccin
interruptor

ESPAOL

Figura 48:
06133339

3. Ingrese la informacin del interruptor en la


memoria de la unidad de disparo. Deber
ingresar la siguiente informacin para
identificar correctamente el interruptor en la
red de comunicacin:

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Seleccin
interruptor

Seleccin
interruptor

Norma
UL
Interruptor
Masterpact
Tipo
NW40H2
0000

Norma
UL
Interruptor
Masterpact
Tipo
NW40H2
0000

Norma
UL
Interruptor
Masterpact
Tipo
NW40H2
1000

Norma
UL
Interruptor
Masterpact
Tipo
NW40H2
10
200

HLogic2002AA

HLogic2002AA

HLogic2002AA

HLogic2002AA

Arriba/
Abajo

Abajo
Intro

Intro

Arriba/
Abajo

Abajo
Intro

Intro

Seleccin
interruptor
Norma
UL
Interruptor
Masterpact
Tipo
NW40H2
1234

06133335

Repita este
procedimiento para

Desea
guardar los
cambios?

Modifique el cdigo de desgaste del


contacto slo cuando sustituya el
interruptor.

No
Si

HLogic2002AA
Salir

Abajo
Intro

20002012 Schneider Electric Reservados todos los derechos

37-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Configuracin del signo de la potencia

Signo
potencia

Idioma

Signo
potencia

Fecha / hora

P+

06133335

Elija la convencin de signos a utilizar para


las mediciones de potencia, energa y
desconexin de carga:

Figura 49:
06133339

4. Seleccione el signo de la potencia.

48049-137-05
Rev. 01, 07/2012

Desea
guardar los
cambios?

P+: Potencia absorbida del flujo


ascendente al flujo descendente
(alimentacin superior)

Seleccin
interruptor
Signo
potencia

No

P-: Potencia absorbida del flujo


descendente al flujo ascendente
(alimentacin inferior)

Transfo
de tensin

Si

P-

Arriba/
Abajo

Intro

Abajo
Intro

Intro
Salir

5. Ingrese la razn del transformador de


tensin externo en la memoria de la unidad
de disparo. Si no est presente un
transformador de tensin externo, ajuste los
valores primario y secundario a 690 V~ (ca).
Se necesitar un transformador de tensin
externo cuando la tensin de alimentacin
de la unidad de disparo exceda 690 V~ (ca).

Figura 50:
06133339

Configuracin de la razn del transformador de tensin

Idioma

Transfo
de tensin

Transfo
de tensin

Transfo
de tensin

Fecha / hora

Primario

Primario

Primario

690V

690V

660V

Secundario

Secundario

Secundario

690V

690V

690V

Seleccin
interruptor
Signo
potencia
Transfo
de tensin

Arriba/
Abajo

Intro

Intro

Intro

Transfo
de tensin

Abajo
Intro

06133335

ESPAOL

Intro

El valor por omisin es P+.

Desea
guardar los
cambios?

Primario

660V
Secundario

No

690V

Si
Arriba/
Abajo
Intro

Abajo
Intro

Salir

38-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Configuracin de la frecuencia de la red

Fecha / hora
Seleccin
interruptor
Signo
potencia
Transfo
de tensin
Frecuencia
de red

El valor absoluto del factor de potencia


ser el correcto, pero tendr el signo
incorrecto.

50-60Hz

50-60Hz

Desea
guardar los
cambios?
No
Si

Arriba/
Abajo

Intro

Intro

El valor de la frecuencia puede que no


sea preciso.

Frecuencia
de red

Intro

La proteccin de la frecuencia estar


inhabilitada.

Abajo

ESPAOL

El valor absoluto de la potencia reactiva


ser el correcto, pero tendr el signo
incorrecto.

Frecuencia
de red

06133335

NOTA: Cuando se ajusta la frecuencia en


400 Hz:

Figura 51:
06133340

6. Ingrese la frecuencia de la red en la


memoria de la unidad de disparo.

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Intro

Salir

La proteccin de rotacin de fases estar


inhabilitada.

Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.
Abajo

20002012 Schneider Electric Reservados todos los derechos

Configuracin de mediciones
06133330

Utilice el men Configurar medidas para


ajustar los parmetros de medicin de la
potencia y corriente de la red.

Figura 52:
06133330

Configuracin de las mediciones

Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

Tipo de
red
Clculo
I media
Clculo
P media
Convencin
de signos

Intro

39-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Estn disponibles tres opciones de


medicin:

ESPAOL

Tipo de red

Neutro

Corriente de
fases

3 fases, 3 hilos, 3 TC
(utiliza 2 wattmetros)

No

Mediciones de I1,
I2 e I3

3 fases, 4 hilos, 4 TC*


(utiliza 3 wattmetros)

Mediciones de I1,
I2, I3 e In

3 fases, 4 hilos, 3 TC
(utiliza 3 wattmetros)

No

Mediciones de I1,
I2 e I3

*No utilice el tipo de 3 fases, 4 hilos, 4 TC salvo que el


neutro est bien conectado a la unidad de disparo (la
conexin de tensin neutra debe realizarse en el
exterior del interruptor de 3 polos). (Consulte el boletn
de instrucciones del TC al neutro).

Tipo de red
Clculo
I media
Clculo
P media
Convencin
de signos

Intro

Configuracin del tipo de red

Tipo de
red

Tipo de
red

3) 4hilos
3 TC

3) 3hilos
3 TC

06133335

Figura 53:
06133311

1. Seleccione el tipo de red.

48049-137-05
Rev. 01, 07/2012

Desea
guardar los
cambios?
No
Si

Arriba/
Abajo

Intro
Intro

Abajo
Intro

Salir

NOTA: El ajuste del neutro en los interruptores


de 4 polos est limitado a los ajustes del
selector tipo neutro en el interruptor.
La medicin In no est disponible para los
tipos de red de 3 fases, 4 hilos, 3 TC. Las
mediciones de tensin simple U1n, U2n y
U3n no estn disponibles para los tipos de
red de 3 fases, 3 hilos, 3 TC.
Si desea obtener estas mediciones, y si la
red est conectada en estrella (4 hilos),
seleccione 3 fases, 4 hilos, 4 TC y conecte a
la terminal de tensin del neutro (Vn) en el
TC al neutro.

40-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Configuracin de la demanda de corriente

Clculo
I media

Tipo de red

Mtodo de
clculo
media
aritmtica
Tipo ventana
deslizante
Duracin

Clculo
I media
Clculo
P media
Convencin
de signos

El tipo de ventana viene ajustado de fbrica


como ventana deslizante.
La duracin puede ajustarse entre 5 y 60
minutos en incrementos de 1 minuto.

Clculo
I media

Mtodo de
clculo

Mtodo de
clculo
modelo
trmico
Tipo ventana
deslizante
Duracin

modelo
trmico
Tipo ventana
deslizante
Duracin

15 min
Intro

Clculo
I media

15 min

15 min
Arriba/
Abajo

Intro

Abajo
Abajo

Intro

Clculo
I media

Mtodo de
clculo
modelo
trmico
Tipo ventana
fijo
Duracin
25 min
Arriba/
Abajo

Mtodo de
clculo
modelo
trmico
Tipo ventana
fijo
Duracin

Desea
guardar los
cambios?
No
Si

25 min
Abajo

Salir

Intro

Intro

NOTA: El mtodo sinc. con comunic. est


disponible slo con la opcin de
comunicacin. Esta funcin determina la
demanda de potencia en base a una seal
del mdulo de comunicacin.

Tipo de red

Clculo
P media

Clculo
P media

Clculo
P media

Clculo
I media
Clculo
P media
Convencin
de signos

Mtodo de
clculo
media
aritmtica
Tipo ventana
deslizante
Duracin

Mtodo de
clculo
modelo
trmico
Tipo ventana
deslizante
Duracin

Mtodo de
clculo
modelo
trmico
Tipo ventana
deslizante
Duracin

15 min

15 min

15 min

Arriba/
Abajo

Intro

Intro

El tipo de ventana por omisin es


deslizante.
La duracin puede ajustarse entre 5 y 60
minutos en incrementos de 1 minuto.

Configuracin de la demanda de potencia

Intro

Clculo
P media

Clculo
P media

Mtodo de
clculo
modelo
trmico
Tipo ventana
fijo
Duracin

Mtodo de
clculo
modelo
trmico
Tipo ventana
fijo
Duracin

25 min

25 min

Arriba/
Abajo
Intro

20002012 Schneider Electric Reservados todos los derechos

Salir

Abajo
Abajo
Intro

06133335

El mtodo de clculo puede ser media


aritmtica, modelo trmico o sinc. con
comunic.

Figura 55:
06133311

3. Configure el mtodo de clculo de la


potencia y duracin.

Intro

06133335

Clculo
I media

ESPAOL

El mtodo de clculo puede ser media


aritmtica o modelo trmico.

Figura 54:
06133311

2. Ajuste el mtodo y el intervalo de clculo de


la corriente.

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Desea
guardar los
cambios?
No
Si
Abajo
Intro

41-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

IEEE
IEC
IEEE alt

Figura 56:

Configuracin de la convencin de signos

Tipo de red
Clculo
I media
Clculo
P media
Convencin
de signos

ESPAOL

Intro

Convencin
de signos

Convencin
de signos

IEEE

IEC

06133335

Elija la convencin de signos que habr de


utilizar para las mediciones de potencia
reactiva (VARS), energa reactiva (VARhrs)
y factor de potencia:

06133311

4. Seleccin de la convencin de signos

48049-137-05
Rev. 01, 07/2012

Desea
guardar los
cambios?
No
Si
Arriba/
Abajo

Intro
Intro

Abajo
Intro

Salir
Convencin de signos de IEEE
Potencia
reactiva

Cuadrante 1
Watts positivo (+)
VARs positivo (+)
Retraso de FP (-)

Cuadrante 2
Watts negativo (-)
VARs positivo (+)
Avance de FP (+)
Sentido de potencia
inverso

Sentido de potencia
normal

Potencia
activa

Cuadrante 4
Watts positivo (+)
VARs negativo (-)
Avance de FP (+)

Cuadrante 3
Watts negativo (-)
VARs negativo (-)
Retraso de FP (-)

Convencin de signos de IEC


Potencia
reactiva

Cuadrante 2
Watts negativo (-)
VARs positivo (+)
Avance de FP (-)
Sentido de potencia
inverso

Cuadrante 3
Watts negativo (-)
VARs negativo (-)
Retraso de FP (-)

Cuadrante 1
Watts positivo (+)
VARs positivo (+)
Retraso de FP (+)
Sentido de potencia
normal

Potencia
activa

Cuadrante 4
Watts positivo (+)
VARs negativo (-)
Avance de FP (+)

Convencin de signos de IEEE Alt


Potencia
reactiva

Cuadrante 2
Watts negativo (-)
VARs negativo (-)
Avance de FP (+)
Sentido de potencia
inverso

Cuadrante 3
Watts negativo (-)
VARs positivo (+)
Retraso de FP (-)

42-ES

Cuadrante 1
Watts positivo (+)
VARs negativo (-)
Retraso de FP (-)
Sentido de potencia
normal

Potencia
activa

Cuadrante 4
Watts positivo (+)
VARs positivo (+)
Avance de FP (+)

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Histricos
Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.
Intro

Abajo

Direccin = 47

Figura 58:
06133459

1. Ajuste los parmetros de comunicacin. Los


valores por omisin son:
Baud-rate (Velocidad en baudios) = 19,2k
Paridad = Par

Paramtros
com.
Regulacin
a distancia
Mando
a distancia

Configuracin de los valores de com. de Modbus

Mdulo
Modbus

Paramtros
com.
Regulacin
a distancia
Mando
a distancia

direccin

Mdulo
Modbus

Mdulo
Modbus

direccin

direccin

Baud-rate

Baud-rate

19.2k

19.2k

19.2k

Paridad

Paridad

Paridad

Par

Par

Baud-rate

Par
Arriba/
Abajo

Intro

Intro

Abajo
Intro

Mdulo
Modbus

Mdulo
Modbus

direccin

direccin

Baud-rate

Mdulo
Modbus
direccin

Baud-rate

19.2k

19.2k

19.2k

Paridad

Paridad

Par

Par

Par

No
Si
Arriba/
Abajo

Abajo
Intro

Desea
guardar los
cambios?

Baud-rate

Paridad
Arriba/
Abajo

06133335

Intro

Intro

ESPAOL

NOTA: No es posible ingresar los parmetros


de configuracin de comunicacin si no est
instalado un mdulo de comunicacin del
interruptor (MCI).

Histricos

06133459

Configuracin del mdulo de comunicacin


06133330

Utilice el men Configurar Com. para


configurar el mdulo de comunicacin.

Figura 57:
06133330

Configuracin del mdulo de


comunicacin

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Intro

Abajo
Intro

Salir

El acceso a distancia viene ajustada de


fbrica y no requiere ajustes adicionales.
NOTA: Es posible modificar el ajuste de
acceso a distancia para permitir la
modificacin de los ajustes de proteccin a
travs de la red de comunicacin. Pngase
en contacto con la oficina de ventas local
para obtener informacin acerca de la
disponibilidad del software que se puede
utilizar con esta opcin.

Figura 59:
06133459

2. Acceso remoto.

Paramtros
com.
Regulacin
a distancia
Mando
a distancia

20002012 Schneider Electric Reservados todos los derechos

Configuracin del acceso remoto

Regulacin
a distancia
Autorizacin
de acceso

No
Cdigo
de acceso

0000
Intro

43-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Auto: El interruptor se puede abrir o cerrar a


travs del software de gestin del sistema
de la red.

ESPAOL

NOTA: Para que el interruptor pueda


funcionar a distancia, deber ajustarse el
MCI para que permita su apertura y/o cierre.
Adems, el interruptor deber tener
instaladas bobinas en derivacin de
comunicacin y arns de cables.

Paramtros
com.
Regulacin
a distancia
Mando
a distancia

Configuracin del mando a distancia.

Mando
a distancia
Manual

Mando
a distancia

06133335

Manual: El interruptor no se puede abrir ni


cerrar a travs del software de gestin del
sistema de la red.

Figura 60:
06133459

3. Ajuste el mando a distancia.

48049-137-05
Rev. 01, 07/2012

Desea
guardar los
cambios?

Auto

No
Si
Intro

Arriba/
Abajo

Intro
Intro

Abajo
Intro

Salir

Ajuste de los selectores de


configuracin

AVISO
PELIGRO DE DAO AL EQUIPO
Si se utilizan los selectores para ajustar los valores de la unidad de
disparo se anularn los ajustes realizados a travs de la terminal de
programacin y ajustes.
Si modifica el ajuste de los selectores de proteccin contra
sobrecargas, de tiempo corto o instantnea, o bien de proteccin
neutra, en un interruptor de cuatro polos, se borrarn todos los
ajustes precisos realizados con anterioridad a travs de la terminal de
programacin y ajustes para estas protecciones.
Si se cambia el ajuste del selector de proteccin contra fallas a tierra
se borrarn todos los ajustes precisos realizados a travs de la
terminal de programacin y ajustes para esta proteccin.
Si se ha perdido el pasador de la cubierta ubicado en la parte posterior
de la cubierta protectora, comunquese con la oficina de ventas para
obtener una cubierta de repuesto.
El incumplimiento se estas instrucciones puede causar dao al
equipo.

44-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

5.0 P

5.0 P

06134826

Micro

logic

5.0 P

D
F

ESPAOL

3. Ajuste los selectores apropiados (C) en los


valores deseados. La pantalla de
visualizacin (D) muestra la curva de ajustes
(E) apropiada. El valor ajustado se muestra
en un recuadro en amperes o segundos.

4. Realice ajustes precisos utilizando las teclas


de navegacin (F) o a travs del software de
gestin del sistema de la red. Estos ajustes
precisos se almacenan en la memoria no
voltil.

B
Curva de disparo
Idmtl

Idmtl (A)

Idmtl (A)
Trip

Trip
1000 A

Ir

1000 A

1.0 s

tr

1.0 s
EIT

2000 A
0.2 s

2000 A
0.2 s

Isd
tsd
Ii

4000 A

Los ajustes finos de los selectores se


realizan en los siguientes incrementos:

Curva de disparo por falla


a tierra

06134767

Curva de disparo I2t


06134765

NOTA: Los ajustes precisos se pueden


realizar slo a valores inferiores a los
realizados con los selectores. Si se utilizan
los selectores para ajustar valores despus
de realizar ajustes precisos a travs de la
terminal de programacin y ajustes se
anular el efecto de estos ltimos.

logic

Micro

06134755

ogic

Microl

Ajuste de los selectores de configuracin

06134766

2. Asegrese de que el pasador de la cubierta


(B) se encuentre en la parte posterior de la
cubierta protectora. Este pasador es
indispensable para bloquear los ajustes de
la unidad de disparo cuando se han
configurado para disparar.

Figura 61:

06134825

1. Abra la cubierta de los selectores (A).

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

4000 A

I (A)
Trip

Ir
tr

1200A

Ig

0.5s

tg

Idmtl
Isd
tsd
Ii

Activacin de tiempo largo = 1 A


Ejemplo

Retardo de tiempo largo = 0,5 s

06134768

Activacin de tiempo corto = 10 A


Retardo de tiempo corto = 0,1 s
Activacin instantnea = 10 A
Activacin de falla a tierra = 1 A

06134826

log
Micro

ic 5.0

I(A)

I(A)

I(A)

Trip

Trip

Trip

1000 A

1000 A

995 A

1.0 s

1.0 s

1.0 s

2000 A
0.2 s

2000 A
0.2 s

2000 A
0.2 s

4000 A

4000 A

4000 A

Retardo de falla a tierra = 0,1 s

20002012 Schneider Electric Reservados todos los derechos

45-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

logic

Verificacin de los ajustes de los selectores de


configuracin

5.0 P

logic

06134756

NOTA: Una vez que se cierra la cubierta, ya


no se pueden utilizar las teclas de
navegacin para realizar modificaciones a
los ajustes de la unidad de disparo cuando
estn ajustados en disparo.

Figura 62:

Micro

06134828

5. Vuelva a colocar la cubierta de los


selectores. Utilice un sello de alambre
MICROTUSEAL (A, no provisto), si es
necesario, para proporcionar evidencia de
manipulaciones no autorizadas.

48049-137-05
Rev. 01, 07/2012

5.0 P

Micro

Ejemplos
Figura 63:

1. Ajuste de los selectores:


AActivacin de tiempo largo (Ir)
BRetardo de tiempo largo (tr)
CActivacin de tiempo corto (Isd)
DRetardo de tiempo corto (tsd)

A
B

Ajuste de los niveles de activacin

.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
@ 6 Ir

tsd
(s)

.2
.1

.3
.2
.1

on

I t

setting

0
off

6 8 10
4
12
3
15
off
2
x In

tr

delay

DRetardo de tiempo corto (tsd)


EActivacin instantnea (Ii)
FActivacin de falla a tierra (Ig)
GRetardo de falla a tierra (tg)
2. Realice ajustes precisos a travs de la
terminal de programacin y ajustes y de la
pantalla de visualizacin de grficos o el
software de gestin del sistema de la red.

46-ES

Ir

Isd

D
E

Ii

In 2000 A

A
B
C
D
F
G

Ajuste de los niveles de activacin


t

long time

Ir
.7
.6
.5
.4

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

tsd
(s)

.3
.2
.1

setting

D
C
B
A

.2
.1
0
off

delay

tg
F
G
H
J

I t

(s)

Ii

.4 .4 .3

on

A
tr

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Ig

Ir

06134751

06134754

Figura 64:

6 8 10
4
12
3
15
off
2
x In
test

Isd C
tsd

Ii

.4 .4 .3

.3
.2
.1
on

I t

.2
.1
0
off

Ir

Isd

D
E

Ii

ground fault

In 2000 A

06134758

CActivacin de tiempo corto (Isd)

Isd C
tsd

E
0

1. Ajuste de los selectores:


BRetardo de tiempo largo (tr)

Ii

2. Realice ajustes precisos a travs de la


terminal de programacin y ajustes y de la
pantalla de visualizacin de grficos o el
software de gestin del sistema de la red.

AActivacin de tiempo largo (Ir)

Ii

.4 .4 .3

EActivacin instantnea (Ii)

Unidad de disparo Micrologic 6.0P

Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

C
D

long time

Ir

06134751

Unidad de disparo Micrologic 5.0P

06134753

ESPAOL

6. Verifique los ajustes a travs de la terminal


de programacin y ajustes (B) y la
visualizacin de grficos o el software de
gestin del sistema de la red.

I2t on
Ig

F
tg

Ig

I2t off

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo Micrologic #.0x

15

15

15

Unidades de disparo Micrologic serie B


R
de Square D

26

15

Relevador de falla a tierra GC-100 de


Square D para proteccin del equipo

Relevador de falla a tierra GC-200 de


Square D para proteccin del equipo

15

15

15

Unidades de disparo STR58 de Merlin


Gerin

15

15

15

Unidades de disparo STR58 de Merlin


Gerin

15

15

15

Unidades de disparo USRC y USRCM


de Federal Pioneer

15

15

Mdulo de falla a tierra suplementario


R
de Square D para proteccin del equipo

RSe requiere un mdulo de RIM para restringir cualquier dispositivo.


Referencias numricasCantidad mxima de interruptores de corriente ascedente que pueden
restringirse sin necesitar un mdulo MIR.

Las terminales Z3, Z4 y Z5 del interruptor vienen


de fbrica conectadas en puente para restringir
automticamente las funciones de tiempo corto
y de falla a tierra. Retire los puentes cuando
active el enclavamiento selectivo de zona.

Figura 65:

Terminales en puente

UC1
Z5
M1
Z3

Z4

Z1

Z2

Conexiones auxiliares

20002012 Schneider Electric Reservados todos los derechos

47-ES

ESPAOL

Unidades de disparo USRC y USRCM de Federal Pioneer

Unidades de disparo STR58 de Merlin Gerin

Dispositivo de corriente
descendente (enva datos
de salida al RIM)

Relevador de falla a tierra GC-200 de Square D para


proteccin del equipo

Dispositivo de corriente
ascendente (recibe datos
de entrada del RIM)

Relevador de falla a tierra GC-100 de Square D


para proteccin del equipo

La tabla 10 muestra la cantidad de dispositivos


que pueden ser enclavados.

Combinaciones de ZSI

Unidades de disparo Micrologic serie B de Square D

Tabla 10:

Unidades de disparo Micrologic #.0x

Enclavamiento selectivo de zona


(ZSI)

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Figura 66:

NOTA: Utilice I2t off con ZSI para obtener una


coordinacin correcta. No se recomienda utilizar
I2t on con ZSI, ya que debido al retardo en el
dispositivo de corriente ascendente que recibe
la seal de restriccin, es posible que se dispare
la unidad en un perodo ms corto que el
indicado en la curva de disparo publicada.

Ejemplo de cableado de ZSI


UC1
Z5
M1

ESPAOL

Figura 67:

06134825

Utilice un equipo de pruebas conectado al


receptculo de enchufe de pruebas (A) de la
unidad de disparo para verificar el
funcionamiento de sta. Lea las instrucciones
adjuntas con el equipo de pruebas para realizar
las pruebas de verificacin.

Z4

Z1

Z2

UC1
Z5
M1

Conexiones
auxiliares 1

Posicin del
segundo
conector
Z1
Z2
Z3
Z4
Z5

Verificacin del funcionamiento


de la unidad de disparo

Z3

5.0
ogic

Z3

Z4

Z1

Z2

UC1
Z5
M1

Conexiones
auxiliares 2
Descripcin
Seal de salida de ZSI
Salida de ZSI
Seal de entrada de ZSI
Seal de entrada de corto tiempo de ZSI
Seal de entrada de falla a tierra de ZSI

Z3

Z4

Z1

Z2

Conexiones
auxiliares 3

Verificacin del funcionamiento de la unidad de disparo

ogic

Microl

Microl

5.0 P

06134086

Conecte los interruptores para enclavamiento


selectivo de zona.

48049-137-05
Rev. 01, 07/2012

NOTA: Para verificar el funcionamiento del


interruptor y la unidad de disparo, realice
pruebas de inyeccin primaria (consulte la
seccin Verificacin de la instalacin de la
unidad de disparo en la pgina 67 para obtener
ms informacin).
Figura 68:
06134781

Restablecimiento de la unidad de
disparo

Micrologic 6.0P

Restablecimiento de la unidad de disparo


A

Cuando se dispara el interruptor, el indicador de


falla permanecer iluminado hasta que se
restablezca la unidad de disparo.
No haga funcionar el interruptor sin antes haber
determinado la causa del disparo. Si desea
obtener ms informacin, consulte las
instrucciones de instalacin del interruptor
incluidas con el envo.
Presione el botn de restablecimiento/prueba
(A) para restablecer la unidad despus de un
disparo.

48-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

Prueba de la funcin de disparo


por falla a tierra del equipo
El inciso 230-95(c) del Cdigo nacional elctrico
de EUA (NEC) y la NOM-001 requiere pruebas
de los sistemas de proteccin contra fallas a
tierra cuando se instalan por primera vez.

si el interruptor est conectado y tiene ms


de 150 V ~ (ca) de tensin de carga en dos
fases (el interruptor est cerrado o recibe
alimentacin por la parte inferior).

si el equipo de pruebas de plenas funciones


o porttil est conectado y energizado.

si la fuente de alimentacin externa de


24 V --- (cd) est conectada.

si la derivacin de tensin externa est


instalada y hay ms de 150 V ~ (ca) en dos
fases.

Figura 69:

06134784

La unidad de disparo est energizada:

logic

ESPAOL

Con la unidad de disparo desenergizada y el


interruptor cerrado, pruebe la funcin de disparo
por falla a tierra del equipo (en la unidad de
disparo Micrologic 6.0P).
Prueba de la funcin de disparo por falla a tierra del
equipo

5.0 P

Micro

Para obtener instrucciones sobre el cierre del


interruptor, consulte las instrucciones de
instalacin correspondientes incluidas.
Para probar la funcin de disparo, presione el
botn de pruebas de falla a tierra (A). El
interruptor se disparar.
Si esto no sucede, pngase en contacto con la
oficina local de campo.

20002012 Schneider Electric Reservados todos los derechos

49-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 3Configuracin de la unidad de disparo

48049-137-05
Rev. 01, 07/2012

Verificacin del estado de la


unidad de disparo
Revise los indicadores de pila y disparo de la
unidad de disparo.
1. Asegrese de que la unidad de disparo est
energizada. La unidad de disparo est
energizada:

si la fuente de alimentacin externa de


24 V --- (cd) est conectada.
si la derivacin de tensin externa est
instalada y hay ms de 150 V ~ (ca) en
dos fases.

Verificacin del estado de la unidad de disparo

Micrologic 6.0P

06133380

si el equipo de pruebas de plenas


funciones o porttil est conectado y
energizado.

Figura 70:

06134782

ESPAOL

si el interruptor est conectado y tiene


ms de 150 V ~ (ca) de tensin de carga
en dos fases (el interruptor est cerrado
o recibe alimentacin por la parte
inferior).

Pila completamente
cargada
Pila media cargada

Sustitucin de la pila

2. Oprima el botn de prueba/restablecimiento


(A).
Todos los indicadores de disparo (B) se
iluminarn
Se mostrar el estado de la pila
La lectura de la grfica de barras de la
batera es vlida despus de haber
soltado el botn de restablecimiento.
3. Si el grfico de barras muestra que es
necesario cambiar la batera, emplee el
nmero de catlogo S33593 Square D para
solicitar una batera de repuesto:
batera de litio
1,2 AA; 3,6 V, 800 ma/h
Consulte la seccin 7 Sustitucin de la pila
para obtener instrucciones al respecto.

50-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

Seccin 4Funcionamiento

Men de medicin

Utilice los mens de medicin para supervisar la


corriente (I), tensin (U), potencia (P), energa
(E) y frecuencia (F) del interruptor.
NOTA: Tambin es posible verificar a distancia
las mediciones del sistema con el System
Manager Software (SMS) (versin 3.3 o
posterior) o cualquier otro software de gestin
de sistemas de red.

I1Corriente instantnea en la fase 1


I2Corriente instantnea en la fase 2
I3Corriente instantnea en la fase 3
InCorriente instantnea en el neutro
I Corriente instantnea en tierra
I1mxCorriente instantnea mxima en la
fase 1

Figura 72:
06134267

Niveles de corriente

I3mxCorriente instantnea mxima en la


fase 3

(A)

U
P
E

(V)
(kWh)

(Hz)

(kW)

Verificacin de los niveles de corriente

(A)

U
P
E

(V)
(kWh)

(Hz)

I2mxCorriente instantnea mxima en la


fase 2

I (A)
instant.

I1 , I2 , I 3 , In

media

Mx

Intro

Intro

Intro

Iinst.

Imx

I1 , I2 , I 3 , In
Mx

I mxCorriente instantnea mxima en tierra

I1 =

301 A

I2 =
I3 =
In =
I =

309 A
309 A
307 A
17 A

I2 Demanda de corriente en la fase 2

Abajo

Intro
(Para rest.)

I3 Demanda de corriente en la fase 3

Intro

Salir

I2mxDemanda de corriente mxima en la


fase 2

Iinst.

Iinst.
I1 =
I2 =
I3 =

0A
0A
0A

In =
I =

0A
0A

Salir

I (A)

I1 , I2 , I 3 , In

instant.

Mx

media

Reset (- / +)

I1 Demanda de corriente en la fase 1

I1mxDemanda de corriente mxima en la


fase 1

Iinst.

(kW)

InmxCorriente instantnea mxima en el


neutro

In Demanda de corriente en el neutro

ESPAOL

Figura 71:

06134267

Valores de medicin

Imedia
I1, I2, I3, In
Mx

I3mxDemanda de corriente mxima en la


fase 3
InmxDemanda de corriente mxima en el
neutro
Las mediciones mximas tambin pueden
volverse a poner en cero.

20002012 Schneider Electric Reservados todos los derechos

Salir

Abajo
Intro

Imedia
15 min
I1 =
I2 =
I3 =

356 A
148 A
159 A

In =

84 A

Imedia
I1, I2, I3, In
Mx

Imx

media
15 min
I1 = 357 A
I2 = 148 A
I3 = 185 A
1A
In =
Reset (- / +)

Intro

Salir

Abajo

Intro
(Para rest.)

Intro

Salir

51-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

U23Tensin eficaz entre las fases 2 y 3


U31Tensin eficaz entre las fases 3 y 1
U1nTensin eficaz entre la fase 1 y el neutro
U2nTensin eficaz entre la fase 2 y el neutro
U3nTensin eficaz entre la fase 3 y el neutro

Verificacin de los niveles de tensin

(A)

U
P
E

(kWh)

(Hz)

(V)
(kW)

06133858

ESPAOL

Intro

U (V)
eficaz
media 3

06133858

U12Tensin eficaz entre las fases 1 y 2

Figura 73:
06134267

Niveles de tensin

48049-137-05
Rev. 01, 07/2012

Uef.

U (V)
eficaz

U12 = 430 V
U23 = 401 V
U31 = 431 V

media 3
deseq. 3

U1n = 245 V
U2n = 242 V
U3n = 242 V

Rotacin
de fases
Intro

Salir

Umedia
3)
421 V

deseq. 3
Rotacin
de fases

Abajo

Salir

06133858

Intro

U (V)
eficaz
media 3

Udeseq.
3)
-4 %

deseq. 3
Rotacin
de fases

Abajo

Salir

U (V)

Rotacin de
fases

eficaz
media 3

') 1, 2, 3

06133858

06133858

Intro

U (V)
eficaz
media 3

deseq. 3

deseq. 3

Rotacin
de fases

Rotacin
de fases

Abajo

Salir

Salir

Intro

52-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Verificacin de los niveles de potencia

(A)
(V)

Factor de potenciaFactor de potencia


instantnea

U
P
E

(kWh)

PDemanda de potencia activa

(Hz)

QPotencia reactiva instantnea


SPotencia aparente instantnea

Intro

P inst.

instant.

P, Q, S

media

Factor de
potencia

(kW)
0

(kvar)
0

(kVA)
0

(kW)

QDemanda de potencia reactiva

P inst.

P (kW)

Intro

Intro

Salir

ESPAOL

PPotencia activa instantnea

Figura 74:
06134267

Niveles de potencia

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

SDemanda de potencia aparente

P inst.

PmxDemanda mxima de potencia activa


QmxDemanda mxima de potencia reactiva
SmxDemanda mxima de potencia aparente

P, Q, S
Factor de
potencia

Las mediciones mximas tambin pueden


volverse a poner en cero.

Factor de
potencia
-0.16
Retraso
(Ind.)

NOTA: Para asegurar mediciones fiables de la


potencia y el factor de potencia, deber
configurarse el signo de la potencia, pgina 38,
y la convencin de signos, pgina 42.

Abajo

Salir

Intro

Salir

P (kW)

P
media

Pmedia

instant.

P, Q, S

media

Mx

Abajo

Intro

Intro

Pmx
media
(kW)
26
(kvar)
Q
86
S
(kVA)
92
Reset (- / +)
P

20002012 Schneider Electric Reservados todos los derechos

(kW)
26

(kvar)
83

(kVA)
87
Salir

Pmedia
P, Q, S
Mx

Abajo
Intro

Pmedia
P, Q, S
Mx

Intro
(Para rest.)

Salir

Salir

Salir

53-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

Energa activa total (P)


Energa reactiva total (Q)
Energa aparente total (S)
Energa activa, consumida (E.P.)
Energa reactiva, consumida (E.Q.)
Energa activa, generada (E.P.)

ESPAOL

Energa reactiva, generada (E.Q.)


Las mediciones de energa tambin se pueden
volver a poner en cero.
NOTA: Para asegurar mediciones fiables de la
energa, deber configurarse el signo de la
potencia, pgina 38, y la convencin de signos,
pgina 42.

Figura 75:
06134267

Niveles de energa

48049-137-05
Rev. 01, 07/2012

Verificacin de los niveles de energa

(A)

U
P
E

(V)
(kWh)

(Hz)

(kW)

Intro

E (kW)
E total
E+
Consumida
EGenerada
Reset
energas

E (kW)
E total

E total
E. P

E+
Consumida
EGenerada
Reset
energas
Intro

(kWh)
0

E. Q (kvarh)
0
E. S

(kVAh)
0

Salir

E+
Consumida
E. P

(kWh)
0

E. Q (kvarh)
0

Salir

Abajo
Intro

E (kW)
E total
E+
Consumida
EGenerada
Reset
energas

Abajo

EGenerada
E. P

(kWh)
0

E. Q (kvarh)
0

Salir

Intro

E (kW)
E total
E+
Consumida
EGenerada
Reset
energas

54-ES

Reset
energas
Puesta a
cero de
energas?

E total
Para
aceptar
pulsar
enter

S
Abajo
(Para rest.)

Intro

Intro

Intro

(kWh)
0

E. Q (kvarh)
0
E. S

No

Abajo

E. P

(kVAh)
0

Salir

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Verificacin de la frecuencia

(A)

U
P
E

(V)
(kWh)

(Hz)

F (Hz)

60.0

(kW)

Intro

Utilice el men de servicio de mantenimiento


para repasar el historial de la unidad de disparo
almacenado en los registros cronolgicos de
historial.

ESPAOL

Figura 77:

Men de registros cronolgicos de historial


06133330

Historial de la unidad de disparo

Salir

Histricos

06133467

Figura 76:
06134267

Frecuencia

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

Histrico
defectos
Histrico
alarmas
Contador de
maniobras
Estado de
contactos

Intro

La unidad de disparo almacena informacin


acerca de la falla de LSIG que provoc los
ltimos diez disparos. Se almacena la siguiente
informacin para cada una de las fallas:

Valores de corriente para Ir, Isd, Ii e Ig


Punto de ajuste de activacin para la tensin
y otro tipo de protecciones

Figura 78:
06133467

Historial de disparo

Verificacin del historial de disparo

Histrico
defectos
Histrico
alarmas
Contador de
maniobras
Estado de
contactos

Fecha
Intro

Hora (hora, minutos y segundos)

NOTA: Los disparos provocados por el equipo


de pruebas no se anotan en el registro
cronolgico de historial.

Histrico
defectos
Ii
20 / 05 / 00
Ii
28 / 04 / 00
Umn
28 / 04 / 00
Intro

Defecto
20 / 05 / 00
10:23:42
Ii 7200 A
I1 =
I2 =
I3 =
In =

7800 A
7800 A
7800 A
7800 A

Intro

Histrico
defectos
Ii
20 / 05 / 00
Ii
28 / 04 / 00
Umn
28 / 04 / 00
Abajo
Intro

Defecto
28 / 04 / 00

Histrico
defectos

Ii 7200A

Ii
20 / 05 / 00

I1 =
I2 =
I3 =
In =

7500 A
7500 A
7500 A
7500 A

Intro

20002012 Schneider Electric Reservados todos los derechos

Defecto
28 / 04 / 00
12:03:33
U mn 100V

Ii
28 / 04 / 00
Umn
28 / 04 / 00
Abajo

Salir

Intro

Salir

55-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

Histrico
defectos
Histrico
alarmas
Contador de
maniobras
Estado de
contactos

Indicacin y valor del ajuste de alarma


Fecha
Hora (hora, minutos y segundos)

Histrico
alarmas

Disparo
20 / 05 / 00

Al
20 / 05 / 00

Al

06133983

Verificacin del historial de alarmas


06133983

La unidad de disparo registra las mediciones


correspondientes a cada una de las diez ltimas
alarmas activadas. Se almacena la siguiente
informacin para cada una de ellas:

Figura 79:
06133467

Historial de alarmas

48049-137-05
Rev. 01, 07/2012

996A

Histrico
alarmas
Al
20 / 05 / 00

Al
28 / 02 / 00

Al
28 / 02 / 00

Al
26 / 02 / 00

Al
26 / 02 / 00

ESPAOL

Intro

Intro

Intro

Abajo

06133983

Intro

Disparo
28 / 02 / 00
Al

996A

Histrico
alarmas
Al
20 / 05 / 00

Disparo
26 / 02 / 00
Al

996A

Al
28 / 02 / 00
Al
26 / 02 / 00
Intro

Desgaste de contactos
Aqu se indica el contacto con mayor desgaste.
Cuando el nmero llega a 100, se recomienda
realizar una inspeccin visual de los contactos.
Esta funcin est disponible slo en los
interruptores de potencia Masterpact NT
y NW.

06133467

ste visualiza la cantidad mxima de


maniobras, disparos o aperturas del interruptor,
desde la instalacin del interruptor. Esta
cantidad la proporciona el mdulo de
comunicacin del interruptor (MCI).

Figura 80:

Salir

Intro

Salir

Verificacin del contador de maniobras

Histrico
defectos
Histrico
alarmas
Contador de
maniobras
Estado de
contactos

Cantidad
total de
operaciones

Intro

Salir

Figura 81:
06133467

Contador de maniobras

Abajo

Nmero de
maniobras
total

Verificacin del desgaste de contactos

Histrico
defectos
Histrico
alarmas
Contador de
maniobras
Estado de
contactos

Intro

19

Estado de
contactos
63

Salir
Salir

56-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Men de proteccin
Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

Consulte el apndice B para obtener los valores


de configuracin por omisin as como las
gamas de stos.

NOTA: La proteccin neutra es inhabilitada si se


selecciona la proteccin de Idmtl.

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P
Intro

(A)

Idmtl

(A)

(A)

I(A)
Cambiar la
regulacin
Idmtl (A) por
I(A)?

Ineutro (A)
I

No
S

Alarma

Ideseq. (%)

Abajo

I1 mx

(A)

Intro

I2 mx

(A)

I3 mx

(A)

In mx

(A)

06133471

Verificacin de la proteccin de corriente

Idmtl (A)
Disparo
1000 A
1.0 s
2000 A
0.2 s
4000 A

Salir

Intro

(A)

Idmtl

(A)

(A)

Ineutro (A)
I

Alarma

Idmtl(A)
Cambiar la
regulacin
I(A) por
Idmtl(A)?

No
S

Abajo

Abajo

Intro

Intro

06133472

La pantalla Cambiar la regulacin I(A) por


Idmtl(A) aparecer slo si los ajustes de tiempo
largo, tiempo corto y/o instantnea se han
realizado con anterioridad en la pantalla del
men I(A). Si el usuario proporciona una
respuesta positiva (S), los ajustes de I(A) se
perdern cuando se cambia de men a la
pantalla de ajuste de ldmtl(A). Si no se ha
realizado ningn ajuste en la pantalla de men
Idmtl(A), el men pasa directamente a la
pantalla de ajuste I(A).

06133331

La pantalla Cambiar la regulacin Idmtl (A) por


I(A) aparecer slo si los ajustes de tiempo
largo, tiempo corto y/o instantnea se han
realizado con anterioridad en la pantalla del
men Idmtl (A). Si el usuario proporciona una
respuesta positiva (S), los ajustes de Idmtl(A)
se perdern cuando se cambia de men a la
pantalla de ajuste de I(A). Si no se ha realizado
ningn ajuste en la pantalla de men Idmtl(A), el
men pasa directamente a la pantalla de
ajuste I(A).

Figura 83:

06133474

Proteccin de corriente

06133474

Utilice los mens de proteccin para verificar la


configuracin de proteccin de la corriente,
tensin, otras protecciones, desconexin de
carga de la corriente y desconexin de carga de
la alimentacin.

ESPAOL

Figura 82:
06133331

Configuracin de proteccin

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

I dmtl (A)
Disparo
1000 A
1.0 s
EIT
2000 A
0.2 s
4000 A

Salir

Contina en la siguiente pgina

20002012 Schneider Electric Reservados todos los derechos

57-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

Verificacin de la proteccin de corriente (continuacin)

(A)

Idmtl

(A)

(A)

06133473

Figura 83:
06133474

Proteccin de corriente (continuacin)

48049-137-05
Rev. 01, 07/2012

(A)
Disparo
1200 A

Ineutro (A)
I

06133474

Tipo de TC
Seleccin de proteccin
Interruptor
al neutro
Todos

ninguno

deshabilitada

Cuatro polos interno

Salir

(A)

Idmtl

(A)

(A)

Ineutro (A)

OFF: sin proteccin de neutro

N/2: media proteccin de neutro


N: proteccin total de neutro

Alarma

Ineutro (A)
TC neutro
externo
Proteccin
OFF
Salir

Abajo

OFF: sin proteccin de neutro

Intro

N/2: media proteccin de neutro


Tres polos

externo

N: proteccin total de neutro


1.6N: proteccin de neutro ms
grande

06133474

ESPAOL

Intro

NOTA: La seleccin del tipo de TC determina la


proteccin Ineutro en el Men de proteccin.

0.5s

Alarma

(A)

Idmtl

(A)

(A)

I Alarma
Alarma

Ineutro (A)
I

Alarma

Activacin
996A
1.0s
Desactiv.
996A
1.0s
Salir

Abajo
Intro

Idmtl

(A)

(A)

Ineutro

(A)

I deseq. (%)
Off

Ideseq. (%)

Activacin
60%
40.0s
Desactiv.
60%
1.0s

Abajo

Salir

Alarma

Intro
Contina en la siguiente pgina

58-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Proteccin de corriente (continuacin)

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

Figura 83:

Verificacin de la proteccin de corriente (continuacin)

(A)

I1 mx (A)
Off

Ineutro (A)
Alarma

Ideseq. (%)
I1 mx

(A)

Activacin
240A
1500s
Desactiv.
240A
15s
Salir

Abajo

ESPAOL

Intro

Ineutro (A)

I2 mx (A)
Off

Alarma

Ideseq. (%)
I1 mx

(A)

I2 mx

(A)

Activacin
240A
1500s
Desactiv.
240A
15s
Salir

Abajo
Intro

Alarma

Ideseq. (%)
I1 mx

(A)

I2 mx

(A)

I3 mx

(A)

I3 mx (A)
Off
Activacin
240A
1500s
Desactiv.
240A
15s
Salir

Abajo
Intro

NOTA: Para ajustar Inmx, el TC al neutro


deber configurarse como externo o interno en
la configuracin de Micrologic bajo el men de
servicio de mantenimiento
.

Ideseq. (%)
I1 mx

In mx (A)
Off

(A)

In mx (A)

Activacin
240A
1500s
Desactiv.
240A
15s

Abajo

Salir

Intro

Salir

I2 mx (A)
I3 mx (A)

20002012 Schneider Electric Reservados todos los derechos

59-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

48049-137-05
Rev. 01, 07/2012

Proteccin de tensin

PELIGRO DE DAO AL EQUIPO


Si se ajusta la proteccin de baja tensin
(Umn) por debajo del 80% o el desequilibrio de
tensin (Udeseq.) por encima del 20% es
posible que no funcione correctamente la
unidad de disparo.

06133476

Los ajustes de activacin de la proteccin de


tensin son valores de fase a fase.

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

Los valores de desequilibrio se basan en los


valores de rcm verdaderos de las corrientes de
tres fases.

Umn

(V)

Umx

(V)

La alarma de baja tensin se desactiva al


perderse la segunda fase.

Umx

(V)

Umn (V)
Off

Udeseq. (%)

Activacin
100V
5.00s
Desactiv.
100V
0.20s
Salir

Umx (V)
Activacin
725V
5.00s
Desactiv.
725V
0.20s
Salir

Abajo
Intro

Umn

(V)

Umx

(V)

Udeseq. (%)
Off

Udeseq. (%)

(V)

Off

Udeseq. (%)

NOTA: No ajuste la proteccin de baja tensin


por debajo del 80%. No ajuste el valor de
Udeseq. en un valor superior al 20%*.

Umn

Intro

Intro

06133476

ESPAOL

El incumplimiento de esta instruccin


puede causar dao al equipo.

Verificacin de la proteccin de tensin


06133476

AVISO

06133331

Figura 84:

Activacin
30%
40.0s
Desactiv.
30%
10.0s

Abajo

Salir

Intro

Salir

Consulte el apndice D para obtener una explicacin del comportamiento de la proteccin del sistema.

60-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Verificacin de otro tipo de proteccin

06133484

Intro

rPmx (W)
F mn (Hz)
F mx (Hz)
Rotacin
de fases

Abajo

rPmx (W)
F mn (Hz)
F mx (Hz)
Rotacin
de fases

Intro

rPmx (W)
Off
Activacin
500kW
5.00s
Desactiv.
500kW
1.0s
Salir

ESPAOL

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

06133484

Figura 85:
06133331

Otro tipo de proteccin

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

Fmn (Hz)
Off
Activacin
45.0Hz
5.00s
Desactiv.
45.0Hz
1.00s
Salir

06133484

Intro

rPmx (W)
F mn (Hz)
F mx (Hz)
Rotacin
de fases

Abajo

Fmx (Hz)
Off
Activacin
65.0Hz
5.00s
Desactiv.
65.0Hz
1.00s
Salir

06133484

Intro

rPmx (W)

Rotacin
de fases

F mn (Hz)

Off

F mx (Hz)

'): 1, 2, 3

Rotacin
de fases

20002012 Schneider Electric Reservados todos los derechos

Abajo

Salir

Intro

Salir

61-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 4Funcionamiento

La desconexin de carga de la corriente puede


configurarse solamente para alarmas. No se
puede utilizar para disparar el interruptor.

Figura 86:
06133331

Desconexin de carga de la
corriente

48049-137-05
Rev. 01, 07/2012

Verificacin de la desconexin de carga de la corriente

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P

Desconexin de carga de la
alimentacin
La desconexin de carga de la alimentacin
puede configurarse solamente para alarmas. No
se puede utilizar para disparar el interruptor.

Figura 87:
06133331

ESPAOL

Intro

62-ES

Activacin
100% Ir
80% tr
Desactiv.
100% Ir
10s
Salir

Verificacin de la desconexin de carga de la


alimentacin

Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.
Desconex. I
Reconex.
Desconex.
Reconex. P
Intro

Desconex. I
Reconex.
Off

Desconex.P
Reconex.

Off
Activacin
10.00MW
3600s
Desactiv.
10.00MW
10s
Salir

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 5Sustitucin de la unidad de disparo

Seccin 5Sustitucin de la unidad de disparo

Segn la definicin del Cdigo nacional


elctrico de EUA (NEC), NOM-001-SEDE,
solamente personal especializado, familiarizado
con la instalacin y servicios de mantenimiento
de los interruptores de potencia, deber sustituir
la unidad de disparo.

PELIGRO
El incumplimiento de estas instrucciones durante la instalacin, la
prueba de disparo y las pruebas de inyeccin primaria podr causar
problemas a algunas o todas las funciones de proteccin.

Antes de sustituir la unidad de disparo,


asegrese de que el interruptor est
funcionando correctamente. Si no es posible
determinar la condicin de funcionamiento del
interruptor, detngase aqu. Si desea obtener
asistencia para evaluar la condicin del
interruptor, comunquese con el Centro de
asistencia tcnica.

Utilice equipo de proteccin personal (EPP) apropiado y siga las


prcticas de seguridad elctrica establecidas por su Compaa, consulte
la norma 70E de NFPA o Z462 de CSA y NOM-029-STPS.
Segn la definicin del Cdigo nacional elctrico de EUA (NEC), NOM001-SEDE, solamente personal especializado, familiarizado con la
instalacin y servicios de mantenimiento de los interruptores de
potencia, deber sustituir/actualizar la unidad de disparo en campo.

Cercirese de leer completamente esta


informacin antes de iniciar el procedimiento de
sustitucin.

Antes de sustituir/actualizar la unidad de disparo, asegrese de que el


interruptor est funcionando correctamente. Si no es posible determinar
la condicin de funcionamiento del interruptor, detngase aqu. Si desea
obtener asistencia para evaluar la condicin del interruptor,
comunquese con el Centro de asistencia tcnica.

NOTA: Si la unidad que va a sustituir es una


unidad de disparo Micrologic 2.0, 3.0 o 5.0,
solicite el bloque de conectores S33101 y un
arns para cables para el interruptor o cuna, si
fuese necesario.

Si el interruptor no funciona correctamente al completar la instalacin de


la unidad de disparo, de inmediato ponga el interruptor fuera de servicio
y llame al Centro de servicios en campo.
Desenergice el equipo antes de realizar cualquier trabajo en l. Siga las
instrucciones incluidas con el interruptor para desconectar y volver a
conectarlo.
Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes
de volver a poner en servicio el equipo.
El incumplimiento de estas instrucciones podr causar la muerte o
lesiones serias.

Herramientas necesarias

Desatornillador de par prefijado en 0,8 Nm (7 lbs-pulg) 10%


(desatornillador Lindstrom MAL500-2 o uno equivalente)

Equipo de pruebas de amplias funciones Micrologic (nmero de pieza


S33595)

Preparacin
Anotacin de los ajustes de los
selectores

Anote todos los ajustes de los selectores y de proteccin avanzada de la


unidad de disparo ya que tendr que utilizarlos posteriormente.

Desconexin del interruptor

Desconecte el interruptor tal como se indica en el boletn de instrucciones


correspondiente incluido. El interruptor debe estar completamente aislado.
(En un interruptor removible, coloque el interruptor en la posicin de
desconectado. En un interruptor fijo, todas las fuentes de tensin,
incluyendo la fuente auxiliar, deben ser desconectadas).

20002012 Schneider Electric Reservados todos los derechos

63-ES

ESPAOL

PELIGRO DE DESCARGA ELCTRICA, EXPLOSIN O DESTELLO


POR ARQUEO

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 5Sustitucin de la unidad de disparo

48049-137-05
Rev. 01, 07/2012

Retire la cubierta de accesorios del interruptor como se indica en la seccin


Instalacin de accesorios en el boletn de instrucciones correspondiente
incluido.

Desmontaje del calibrador

Figure 88:
logic

5.0

logic
Micro

06134831

Micro

Desmontaje del calibrador ajustable


5.0
logic
Micro

06134830

Se necesita un desatornillador Phillips pequeo


para desmontar el calibrador ajustable.

06134783

Extraccin de la cubierta de accesorios


del interruptor

5.0 P

1. Abra la cubierta de los selectores (A).


2. Desatornille el tornillo de montaje (B) del
calibrador ajustable.

C
alarm
long

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr
(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

Desmontaje de la unidad de disparo existente


A

Microlo

06134079

1. Retire el bloque de conectores (A) de la


parte superior de la unidad de disparo, si
est instalado.

Figura 89:

06134078

Desmontaje de la unidad de disparo

Microlo

gic 5.0

gic 5.0

2. Afloje los dos tornillos (B) de la unidad de


disparo.
3. Deslice la unidad de disparo (C) hasta que
est totalmente afuera.

Sustitucin de la unidad de disparo


Instalacin de la batera

Figura 90:

Si se est instalando una unidad de disparo


nueva, primero instale la batera en la unidad.
06133375

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

Instale la cubierta con batera (A) en la unidad


de disparo, observe la polaridad correcta
marcada en el compartimiento de la batera.

Instalacin de la batera

NOTA: La cubierta del compartimiento de la batera y la batera vienen


debajo de la tapa de la caja de embalaje de la unidad de disparo.
Presione el botn de prueba/restablecimiento (A).
Las cuatro luces indicadoras (B) debern
iluminarse. Si no se iluminan, verifique la polaridad
de la batera y vuelva a realizar la prueba. Si las
luces indicadoras todava no se iluminan al
presionar el botn de prueba/restablecimiento,
detenga la instalacin y pngase en contacto con
la oficina local de ventas para solicitar servicio
autorizado de fbrica.

64-ES

Figura 91:

Luces indicadoras

B
06133245

ESPAOL

3. Retire el calibrador ajustable (C). Gurdelo


para instalarlo en la unidad de disparo de
repuesto.

Micrologic 6.0 A

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 5Sustitucin de la unidad de disparo

Instalacin de la unidad de disparo


1. Inspeccione visualmente las espigas del
conector y las superficies de la unidad de
disparo. Si encuentra algn dao, por ejemplo,
espigas desalineadas o contaminacin,
detenga la instalacin y pngase en contacto
con la oficina local de ventas y solicite servicio
autorizado de fbrica.
Instalacin de la unidad de disparo

ESPAOL

Figura 92:

Interruptor de potencia Masterpact NW

06135452

06135453

2. Inspeccione la base de montaje de la unidad


de disparo en el interruptor. Retire los
residuos del rea y asegrese de que los
cables de los accesorios se hayan dirigido
correctamente hacia la unidad de disparo
que se est instalando. Si encuentra algn
dao o contaminacin, detenga la
instalacin y pngase en contacto con la
oficina local de ventas y solicite servicio
autorizado de fbrica.

logic

5.0

Micro

3. En los interruptores de potencia Masterpact


NW solamente: Al realizar los pasos 4 a 6,
manualmente presione y sostenga en su
lugar el bloqueo (A) de la unidad de disparo.
4. Alinee el riel gua (B) situado en la parte
inferior de la unidad de disparo con la ranura
(C) del riel gua en la base de montaje de la
unidad de disparo en el interruptor y deslice
suavemente la unidad hacia adentro hasta
llegar al tope.

C
B

NOTA: Las bases de montaje de las unidades


de disparo para los interruptores de potencia
Masterpact NT y NW se han montado sobre
amortiguadores; por consiguiente, es posible
doblarlas ligeramente.

AVISO
PELIGRO DE DAO AL EQUIPO
Compruebe la instalacin de la unidad de disparo y asegrese de que est
correctamente conectada y apoyada en su lugar.
El incumplimiento de esta instruccin puede causar dao al equipo o
el disparo incorrecto del interruptor.

20002012 Schneider Electric Reservados todos los derechos

65-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 5Sustitucin de la unidad de disparo

Figura 93:

Instalacin de la unidad de disparo


A

6. Utilice un desatornillador de par prefijado


para apretar el tornillo inferior (B) a 0,8 Nm
(7 lbs-pulg) 10%. La lengeta de montaje
debe estar a ras con el separador de
montaje y el enchufe sensor.

06134080

5. Alinee la unidad de disparo de manera que el


tornillo de montaje (A) est alineado con el
inserto roscado superior y gire dos vueltas.

48049-137-05
Rev. 01, 07/2012

Debe estar
apoyada

gic 5.0
Microlo

0,8 Nm
[7 lbs-pulg]

NOTA: Cuando est cerrada, la parte frontal de


la cubierta de los selectores deber estar a ras
con las superficies de la base de montaje. En
caso de que las superficies no se encuentren a
ras, detenga la instalacin y pngase en
contacto con la oficina local de ventas y solicite
servicio autorizado de fbrica.

Debe estar a ras

06134081

C
gic 5.0

Microlo

NOTA: Si est actualizando una unidad de


disparo Micrologic 2.0, 3.0 o 5.0, debe solicitar
el bloque de conectores por separado (nmero
de pieza S33101). Consulte las instrucciones
incluidas con el bloque de conectores al
instalarlo en el interruptor.
8. Instale el bloque de conectores (C) en la
parte superior de la unidad de disparo.

a. Abra la cubierta de los selectores (A) de


la unidad nueva.
b. Realice una inspeccin visual del rea de
montaje y retire cualquier material residual
y/o contaminante que llegase a encontrar.

Figura 94:

log
Micro

Instalacin del calibrador ajustable

ic 5.0

06134833

9. Instale el calibrador ajustable en la unidad


de disparo.

06134832

ESPAOL

7. Utilice un desatornillador de par prefijado


para apretar el tornillo superior a 0,8 Nm
(7 lbs-pulg) 10%. La lengeta de montaje
debe estar a ras con el separador de
montaje flexible.

e. Restablezca los ajustes de la unidad de


disparo en los valores originales
anotados anteriormente o segn los
resultados de los.

logic

5.0

c. Suavemente empuje el calibrador


ajustable (B) hasta que encaje en la
nueva unidad de disparo.
d. Apriete el tornillo de montaje (C) del
calibrador ajustable. El calibrador encajar
debidamente en su posicin, hasta
encontrarse a ras con la parte frontal, a
medida que se aprieta el tornillo.

Micro

alarm
long

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr
(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

10. Restablezca los ajustes de los selectores y


de proteccin avanzada de la unidad de
disparo en los valores originales anotados
anteriormente o segn los resultados de los
estudios de coordinacin.
11. Cierre la cubierta de los selectores (A).

66-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Colocacin de la cubierta de
accesorios del interruptor

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 5Sustitucin de la unidad de disparo

Vuelva a colocar la cubierta de accesorios del interruptor como se indica en


la seccin Instalacin de los accesorios del boletn de instrucciones del
interruptor correspondiente incluido.

Pruebas de inyeccin secundaria

Para la instalacin en campo de una unidad de disparo es necesario


realizar pruebas de inyeccin secundaria con un equipo de pruebas de
amplias funciones. Esto garantizar el funcionamiento correcto de la unidad
de disparo recin instalada. Durante la prueba ser necesario abrir y cerrar
el interruptor. Siga los procedimientos detallados en los boletines de
instrucciones incluidos con el interruptor y el equipo de pruebas de amplias
funciones.
1. Asegrese de que el interruptor est aislado de todos los dispositivos de
corriente ascendente y corriente descendente.
2. Realice las pruebas de inyeccin secundaria de acuerdo con las
instrucciones del boletn incluido con el equipo de pruebas de amplias
funciones. Asegrese de que todas las funciones aplicables de la
unidad de disparo funcionen correctamente.
3. Repita el paso 2 con el interruptor en la posicin de abierto.
NOTA: No cierre el interruptor durante este paso aun cuando el equipo
de pruebas indique que deber estar cerrado.
4. Si falla alguna de las pruebas, no ponga el interruptor en servicio y
comunquese con la oficina local de ventas y solicite servicio autorizado
de fbrica.

Pruebas de inyeccin primaria

Se recomienda realizar las pruebas de inyeccin primaria para garantizar


que todas las conexiones del sistema de disparo se han realizado
correctamente. Realice las pruebas de inyeccin primaria segn las
instrucciones en Pruebas de campo y gua de mantenimiento, boletn
nmero 0600IB1201.

Verificacin del funcionamiento de los


accesorios

1. Accesorios instalados Compruebe el funcionamiento apropiado de


todos los accesorios instalados. Consulte los boletines de instrucciones
correspondientes de los accesorios para conocer los procedimientos de
prueba.
2. Mdulo de contactos programables Si el interruptor tiene instalado un
mdulo M2C o M6C, asegrese de que ste est funcionando
correctamente. Consulte los boletines de instrucciones
correspondientes de los accesorios para conocer los procedimientos de
las pruebas de funcionamiento.
3. Enclavamiento selectivo de zona Si el interruptor es parte del sistema
de ZSI, siga los procedimientos de prueba para ZSI como se describe
en el equipo de pruebas de amplias funciones.
4. Comunicaciones Si el interruptor viene con un mdulo de
comunicacin, compruebe que se haya restablecido la comunicacin
con el supervisor.

20002012 Schneider Electric Reservados todos los derechos

67-ES

ESPAOL

Verificacin de la instalacin de la
unidad de disparo

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 5Sustitucin de la unidad de disparo

Configuracin de la unidad de
disparo

48049-137-05
Rev. 01, 07/2012

1. Si se utiliza una fuente de alimentacin auxiliar en la unidad de disparo


Micrologic, vuelva a conectarla.
2. Vuelva a restablecer los ajustes de los selectores y de proteccin
avanzada de la unidad de disparo en los valores originales anotados al
comienzo de esta seccin.

Re-energizacin del interruptor

Vuelva a conectar el interruptor tal como se indica en el boletn de


instrucciones correspondiente incluido.

ESPAOL
68-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 6Sustitucin del calibrador ajustable

Seccin 6Sustitucin del calibrador ajustable

NOTA: Para seleccionar el calibrador de


repuesto correcto, consulte el catlogo de
productos.

PELIGRO

NOTA: Retire el calibrador ajustable durante la


ejecucin de las pruebas de rigidez dielctrica.
El calibrador ajustable debe estar instalado para
realizar las mediciones de tensin. Si falta este
calibrador, el interruptor regresar al valor
nominal por omisin de activacin de tiempo
largo de 0,4 multiplicado por el tamao del
sensor (ln) y a un retardo de tiempo largo del
ajuste anteriormente seleccionado antes de
haber retirado el calibrador.

Utilice equipo de proteccin personal (EPP) apropiado y siga las


prcticas de seguridad elctrica establecidas por su Compaa, consulte
la norma 70E de NFPA o Z462 de CSA y NOM-029-STPS.
Solamente el personal elctrico especializado deber instalar y prestar
servicio de mantenimiento a este equipo.
Desenergice el equipo antes de realizar cualquier trabajo en l. Siga las
instrucciones incluidas con el interruptor para desconectar y volver a
conectarlo.
Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes
de volver a poner en servicio el equipo.
El incumplimiento de estas instrucciones podr causar la muerte o
lesiones serias.

logic

5.0
Micro

logic

logic
Micro

06134831

Micro

Desmontaje del calibrador ajustable

06134830

1. Desconecte el interruptor tal como se indica


en el boletn de instrucciones
correspondiente incluido.

Figura 95:

06134783

Desmontaje del calibrador

5.0

5.0 P

2. Abra la cubierta de los selectores (A).


3. Anote los ajustes de los selectores en el
apndice E (los ajustes de los selectores y
los de la pantalla de grficos, si
correspondiera).

C
alarm
long

4. Desatornille el tornillo de montaje (B) del


calibrador.

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr

(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

5. Retire el calibrador ajustable (C).

logic

Instalacin del nuevo calibrador ajustable

5.0 P

Micro

06134833

1. Realice una inspeccin visual del rea de


montaje y retire cualquier material residual
y/o contaminante que llegase a encontrar.

Figura 96:

06134832

Instalacin del nuevo calibrador

2. Suavemente empuje el calibrador ajustable


(A) hasta que encaje en la nueva unidad de
disparo.

Micro

logic

5.0

B
A

3. Apriete el tornillo de montaje (B) del


calibrador ajustable.
4. Restablezca los ajustes de la unidad de
disparo en los valores originales anotados
en el apndice E o segn los resultados de
los estudios de coordinacin.

alarm
long

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr
(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

5. Cierre la cubierta de los selectores (C).

20002012 Schneider Electric Reservados todos los derechos

69-ES

ESPAOL

PELIGRO DE DESCARGA ELCTRICA, EXPLOSIN O DESTELLO


POR ARQUEO

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 7Sustitucin de la pila

48049-137-05
Rev. 01, 07/2012

Seccin 7Sustitucin de la pila

Desconexin del interruptor

PELIGRO
PELIGRO DE DESCARGA ELCTRICA, EXPLOSIN O DESTELLO
POR ARQUEO

Desconecte el interruptor tal como se indica en


el boletn de instrucciones correspondiente
incluido.

Desmontaje de la cubierta de
accesorios

Solamente el personal elctrico especializado deber instalar y prestar


servicio de mantenimiento a este equipo.
Desenergice el equipo antes de realizar cualquier trabajo en l. Siga las
instrucciones incluidas con el interruptor para desconectar y volver a
conectarlo.

Retire la cubierta de accesorios del interruptor


como se indica en la seccin Instalacin de
accesorios en el boletn de instrucciones
correspondiente incluido.

Vuelva a colocar todos los dispositivos, las puertas y las cubiertas antes
de volver a poner en servicio el equipo.
El incumplimiento de estas instrucciones podr causar la muerte o
lesiones serias.

Desplazamiento del mdulo de


aguante
NOTA: Interruptores automticos NS1600b
NS3200 y con marco R solamente.

Figura 97:

Desplazamiento del mdulo de aguante

06134083

Apriete los tornillos (A) sujetando el mdulo (B).


Gire el mdulo hacia un lado para tener acceso
a la cubierta de la pila de la unidad de disparo.
No retire el conector del mdulo de aguante.

Extraccin de la cubierta de la pila

06134857

1. Inserte la punta de un destornillador


pequeo en la muesca de la cubierta del
compartimiento de la pila y grelo para sacar
la cubierta (A) de la unidad de disparo.

Figura 98:

06133372

Sustitucin de la pila

LITHIUM
LITHIUM BATTERY
BATTERY
3.6V
3.6V -- SL
SL -- 550/S
550/S
SONNENSCHEIN
SONNENSCHEIN

ESPAOL

Utilice equipo de proteccin personal (EPP) apropiado y siga las


prcticas de seguridad elctrica establecidas por su Compaa, consulte
la norma 70E de NFPA o Z462 de CSA y NOM-029-STPS.

70-ES

20002012 Schneider Electric Reservados todos los derechos

06133375

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

Sustitucin de la pila

06133374

4. Vuelva a colocar la cubierta del


compartimiento de la pila (C).

06133373

3. Coloque la nueva pila (B). Asegrese de que


los polos estn en el sentido correcto.

Figura 99:

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

2. Retire la pila (A).

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Seccin 7Sustitucin de la pila

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

48049-137-05
Rev. 01, 07/2012

ESPAOL

NOTA: Interruptores automticos NS1600b


NS3200 y con marco R solamente.

Figura 100: Colocacin del mdulo de aguante

06124084

Colocacin del mdulo de


aguante

Vuelva a colocar el mdulo de aguante (A).


Apriete los tornillos (B) sujetando el mdulo.

B
0,6 Nm
[5 lbs-pulg]

Colocacin de la cubierta de
accesorios

Vuelva a colocar la cubierta de accesorios del interruptor como se indica en


la seccin Instalacin de los accesorios del boletn de instrucciones del
interruptor correspondiente incluido.

Re-energizacin del interruptor

Vuelva a conectar el interruptor tal como se indica en el boletn de


instrucciones correspondiente incluido.

20002012 Schneider Electric Reservados todos los derechos

71-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice ADiagramas de flujo de visualizacin de grficos

48049-137-05
Rev. 01, 07/2012

Apndice ADiagramas de flujo de visualizacin de grficos


Diagrama de flujo del men de
mediciones
I
U

ESPAOL
I

(A)
(V)

(kW)

(kWh)

(Hz)

(A)

(V)
eficaz

instant.
I1, I2, I3, In
I1
I2
I3
In

=
=
=
=
I =

356 A
147 A
158 A
0A
212 A

Mx
I1
I2
I3
In
I

U12 = 429 V
U23 = 430 V
U31 = 399 V

359 A
153 A
188 A
0A
214 A

Reset (- / +)

instant.
P, Q, S

E. Q (kvarh)
513

(kVAR)
83

E. S

(kVA)
86

Mx
15 min
I1 = 357 A
I2 = 148 A
I3 = 155 A
In =
0A

(kVAh)
545

E+
Consumida
(kWh)
155

E. P

-0.29
media

E. Q (kvarh)
514
EGenerada

P, Q, S

E. P

I1, I2, I3, In


15 min
I1 =
351 A
I2 =
145 A
156 A
I3 =
In =
84 A

(kWh)
155

(kw)
27

'): 1,3,2

media

E. P

Factor de
potencia

(Hz)
60.0

deseq. 3)

Rotacin
de fases

(kWh)
E total

media 3)

-4%

(kW)

U1n = 246 V
U2n = 241 V
U3n = 242 V

419 V
=
=
=
=
=

(kw)
25

(kVAR)
77

(kVA)
83

(kWh)
0

E. Q (kvarh)
0
Reset
energas
Puesta a cero
de energas?

Mx
P

(kw)
26

No

(kVAR)
81

Si

(kVA)
86

Reset (- / +)

Reset (- / +)

72-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice ADiagramas de flujo de visualizacin de grficos

06133330

Diagrama de flujo del men de


servicio de mantenimiento

Histricos

Contactos
M2C / M6C

Histricos
Histrico
defectos

Tipo de alarma

Ii

S1
fecha
Ii 7200 A
I1 =
I2 =
I3 =
In =

0A
0A
0A
0A

Umn

Selecc. tipo
S2
Selecc. tipo
Repetir para todos
los contactos
Configurar

Fecha
12:03:33
Umn 100 V
Repetir para todos
los histricos
Histrico
alarmas

Selecc. modo
S2
Selecc. modo

Umn
Fecha
12:03:33
Umn 100 V
Repetir para todos
los histricos
Contador de
maniobras
Estado de
contactos

Idioma
Deutsch
English US
English UK
Espaol
Franais
Fecha / hora
Fecha
02 / 01 / 2000
Hora
06:12:35

Configurar
medidas
Tipo de red

Repetir para todos


los contactos

Seleccin
interruptor

Clculo I media

Baud rate

Mtodo
de clculo
Tipo ventana
Duracin
Clculo P media

S1
S2
Reset (- / +)

Mtodo
de clculo
Tipo ventana

interruptor

Duracin

Nmero de
interruptor

Reset

Parmetros com
Direccin

Norma

tipo

Configurar
Com.

Selecc. tipo

S1

I
fecha
I 7200 A
I1 = 0 A
I2 = 0 A
I3 = 0 A
In = 0 A

Configurar
Micrologic

ESPAOL

Contactos
M2C / M6C
Configurar
Micrologic
Configurar
medidas
Configurar
Com.

Paridad
Regulacin a
distancia
Autorizacin
de acceso
Cdigo de
acceso
Mando a
distancia

Convencin
de signos
Selecc.
convencin
de signos

Signo potencia
Selecc. direcc.
de la corriente
Transfo de
tensin
Primario
Secundario
Frecuencia
de red
Selecc. frecuencia

20002012 Schneider Electric Reservados todos los derechos

73-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice ADiagramas de flujo de visualizacin de grficos

48049-137-05
Rev. 01, 07/2012

Diagrama de flujo del men de


protecciones
Proteccin
corriente
Proteccin
de tensin
Otras
proteccion.

ESPAOL

Proteccin
corriente

Desconex.
Reconex.

Desconex.
Reconex.

P
Desconex.
Reconex.

Modo
(on/off)

Modo (Disparo
Alarma/Off)

Activacin

Activacin

Activacin

Activacin

Desactivacin

Desactivacin

Desactivacin

Desactivacin

(V)

(A)

Idmtl

(A)

Modo (Disparo
Alarma/Off)

(A)

Ineutro

(A)

Alarma

Modo
(on/off)

Umn

Desconex.
Reconex.

Otras
proteccion.

Proteccin
de tensin

Umx

(V)

rPmax (W)

Fmn

(Hz)

Ideseq.

(%)

Modo (Disparo
Alarma/Off)

Modo (Disparo
Alarma/Off)

I1mx

(A)

Activacin

Activacin

I2mx

(A)

Desactivacin

Desactivacin

I3mx

(A)

Inmx

(A)

Udeseq.(%)

Fmx (Hz)

Modo (Disparo
Alarma/Off)

Modo (Disparo
Alarma/Off)

Activacin

Activacin

Desactivacin

Desactivacin
Rotacin
de fases
Modo
(Alarma/Off)
Orden de fases

74-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice BAjustes de fbrica y tolerancias

APNDICE BAjustes de fbrica y tolerancias

Tabla 12:

Tabla 11:

Ajustes de fbricaSelectores

Valor de fbrica

Smbolo

Valor de fbrica

Activacin de tiempo largo

Ir

Mximo

Retardo de tiempo largo

tr

Mnimo

Activacin de tiempo corto

Isd

Mnimo

Retardo de tiempo corto

tsd

Mnimo

Activacin de falla a tierra

Ig

Mnimo

Retardo de falla a tierra

tg

Mnimo

Instantneo

Ii

Mnimo

ESPAOL

Ajustes de fbrica

Ajustes de fbricaMen de servicio de mantenimiento

Submen

Valor de fbrica

Elemento de lnea

Valor de fbrica

Contactos M2C/M6C

Tipo de alarma

S#

No seleccionado

No seleccionado, Isd, Ir, Ideseq. (Consulte la tabla 9)

Con enganche

Contacto de enganche, retardo de tiempo, contacto


sin enganche, forzado a 0, forzado 1

English US

Deutsch, English US, English UK, Espaol, Franais

Norma

NA

No def, ANSI, IEC, UL, IEC/GB

interruptor

NA

Configurar
Configurar Micrologic

S#

Idioma

Gama de ajustes

Fecha/hora
Seleccin interruptor

tipo

NA

Nmero de interruptor

0000

0000FFFF

P+

P+, P-

Signo de potencia
Transfo. de tensin

Configurar medidas

Primario

690

000 a 690

Secundario

690

000 a 690

Frecuencia de red

50 a 60 Hz

50-60 Hz, 400 Hz

Tipo de sistema

3) 4 hilos 4 TC

3) 4hilos 4TC, 3) 4hilos 3TC, 3) 3hilos 3TC

Clculo I media

Duracin

15 min.

5 a 60 minutos

Clculo P media

Tipo ventana

deslizante

deslizante, fijo

Duracin

15 min.

5 a 60 minutos

IEEE

IEEE, IEEE alt, IEC

Convencin de signos
Configurar Com.

Parmetros com.
Regulacin a distancia

No

S, no

Mando a distancia

Auto

Auto, manual

20002012 Schneider Electric Reservados todos los derechos

75-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice BAjustes de fbrica y tolerancias

Tabla 13:
Submen

48049-137-05
Rev. 01, 07/2012

Ajustes de fbricaMen de proteccin


Valor de fbrica

Elemento
Valor de fbrica
de lnea

Gama de
ajustes

Submen

Tolerancia

Activacin de tiempo largo

Ir

Mximo

10%

Retardo de tiempo largo

tr

Mnimo

-20%, +0%
10%

Activacin de tiempo corto

Isd

Mnimo

Retardo de tiempo corto

tsd

Mnimo

Instantneo

Ii

Mnimo

Falla de tierra (unidad de


disparo 5.0P)

ESPAOL

Falla de tierra (unidad de


disparo 6.0P)

Corriente neutra

Alarma de falla a tierra

Desequilibrio de corriente

Sin proteccin

Modo

Disparo

Disparo

Activacin

Configuracin del
selector

In d 400 A: 30%100% In
400 < In d 1200 A: 20%100% In
1200 A < In: 500 A1200 A

10%

Retardo de activacin

Configuracin del
selector

1 a 40 s

-20%, +0%

Ineutro

10%

alarma

Ideseq.

Proteccin de
corriente

Demanda de corriente mx.


I1mx
en la fase 1

Demanda de corriente mx.


I2mx
en la fase 2

Demanda de corriente mx.


I3mx
en la fase 3

Demanda de corriente mx.


Inmx
en el neutro

Off

Off, N/2, N, 1.6N

Modo

Off

Alarma, off

Activacin

1200 A

20 x In1200 A

Retardo de activacin

10.0 s

1.010.0 s

-20%, +0%

Desactivacin

1200 A

20 Aactivacin

15%
-20%, +0%

Retardo de desactivacin

1.0 s

1.010.0 s

Modo

Off

Alarma, disparo, off

15%

% de activacin

60%

560%

-10%, +0%

Retardo de activacin

40 s

140 s

-20%, +0%

% de desactivacin

% de activacin:
Ideseq.

5%% de activacin

-10%, +0%
-20%, +0%

Retardo de desactivacin

10 s

10360 s

Modo

Off

Alarm, disparo, off

Activacin

In

0.2 x In In

6,6%

Retardo de activacin

1500 s

151500 s

-20%, +0%

Desactivacin

Activacin: I1mx

0.2 x Inactivacin

6,6%

Retardo de desactivacin

15 s

153000 s

-20%, +0%

Modo

Off

Alarm, disparo, off

Activacin

In

0.2 x InIn

6,6%

Retardo de activacin

1500 s

151500 s

-20%, +0%

Desactivacin

Activacin: I2mx

0.2 x Inactivacin

6,6%

Retardo de desactivacin

15 s

153000 s

-20%, +0%

Modo

Off

Alarm, disparo, off

Activacin

In

0.2 x InIn

6,6%

Retardo de activacin

1500 s

151500 s

-20%, +0%

Desactivacin

Activacin: I3mx

0.2 x Inactivacin

6,6%

Retardo de desactivacin

15 s

153000 s

-20%, +0%

Modo

Off

Alarm, disparo, off

Activacin

In

0.2 x InIn

6,6%

Retardo de activacin

1500 s

151500 s

-20%, +0%

Desactivacin

Activacin: Inmx

0.2 x Inactivacin

6,6%

Retardo de desactivacin

15 s

153000 s

-20%, +0%
Tabla contina en la siguiente pgina

76-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Submen

Ajustes de fbricaMen de proteccin (continuacin)


Valor de fbrica

Tensin (baja) mnima

Proteccin de
tensin

Tensin (sobre) mxima

Desequilibrio de tensin

Potencia inversa

Otras
protecciones

Frecuencia (baja) mnima

Umn

Umx

Udeseq.

rP

Fmn

Frecuencia (sobre) mxima Fmx

Rotacin de
fases

Rotacin de fases

Gama de
ajustes

Submen

Modo

Off

Alarma, disparo, off

Activacin

100 V

100 Vactivacin de Umx

Retardo de activacin

5s

1.25 s

-0%, +20%

Desactivacin

Activacin Umn

Activacin Umn1200 A

-5%, +0%
-0%, +20%

Elemento
Valor de fbrica
de lnea

Desconexin I

1.2 s

1.236 s

Modo

Off

Alarma, disparo, off

Activacin

725 V

Umn1200 A

-0%, +5%

Retardo de activacin

5s

1.25 s

-0%, +20%

Desactivacin

Activacin Umx

100activacin de Umx

-0%, +5%

Retardo de desactivacin

1.2 s

1.236 s

-0%, +20%

Modo

Off

Alarma, disparo, off

Activacin

20%

220%*

Retardo de activacin

40 s

140 s

-20%, +0%

Desactivacin

Activacin Udeseq. 2%activacin de Udeseq.

-10%, +0%

Retardo de desactivacin

10 s

10360 s

-20%, +0%

Modo

Off

Alarma, disparo, off

Activacin

500 kW

5500kW

2,5%

Retardo de activacin

20 s

0.220 s

-0%, +20%

Desactivacin

Activacin rP

5kWactivacin de rP

2,5%

Retardo de desactivacin

1s

1360 s

-0%, +20%

Desconexin P

-10%, +0%

Modo

Off

Alarma, disparo, off

Activacin

45 Hz

45 HzActivacin de Fmx

Retardo de activacin

5s

0.25 s

-0%, +20%

Desactivacin

Activacin Fmn

Activacin de Fmn440 Hz

0,5 Hz
-0%, +20%

0,5 Hz

Retardo de desactivacin

1s

136 s

Modo

Off

Alarma, disparo, off

Activacin

65 Hz

Activacin de Fmn440 Hz

Retardo de activacin

5s

0.25 s

-0%, +20%

Desactivacin

Activacin Fmx

45 HzActivacin de Fmx

0,5 Hz

Retardo de desactivacin

1s

136 s

-0%, +20%

Secuencia

Sentido de
rotacin: fase 1,
fase 3, fase 2

Sentido de rotacin: fase 1, fase 2,


fase 3 o fase 1, fase 3, fase 2

Modo

Off

Off, alarma

Modo

Off

Off, on

% de activacin

100% Ir

50% Ir100% Ir

6%

2080% tr

-20%, +0%

30%% de activacin de I de
desconexin de carga

6%
-20%, +0%

% de desactivacin

Desconexin P

-5%, +0%

Retardo de desactivacin

% de retardo de activacin 80% tr


Desconexin I

Tolerancia

Activacin de I de
desconexin de
carga

0,5 Hz

Retardo de desactivacin

10 s

10600 s

Modo

Off

Off, On

Activacin

10,000 kW

20010,000 kW

2,5%

Retardo de activacin

3600 s

103600 s

-20%, +0%

Desactivacin

Activacin de P de
desconexin de
carga

100 kW% de activacin de P de


desconexin de carga

2,5%

Retardo de desactivacin

10 s

103600 s

-20%, +0%

No ajuste por encima del 20%

20002012 Schneider Electric Reservados todos los derechos

77-ES

ESPAOL

Tabla 13:

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice BAjustes de fbrica y tolerancias

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice BAjustes de fbrica y tolerancias

48049-137-05
Rev. 01, 07/2012

Gama de medicin y precisin


Tabla 14:

Gama de medicin y precisin

Art.

ESPAOL

Corriente instantnea

Demanda de corriente

Tensin

Potencia instantnea

Factor de potencia

Demanda de potencia

Total de energa

Energa consumida

Energa generada
Frecuencia

78-ES

Descripcin

Smbolo

Gama

Tolerancia

Corriente instantnea en la fase 1

I1

032 kA

1,5%

Corriente instantnea en la fase 2

I2

032 kA

1,5%

Corriente instantnea en la fase 3

I3

032 kA

1,5%

Corriente instantnea en el neutro

In

032 kA

1,5%

Corriente instantnea en tierra

032 kA

1,5%

Corriente instantnea mx. en la fase 1

I1mx

032 kA

1,5%

Corriente instantnea mx. en la fase 2

I2mx

032 kA

1,5%

Corriente instantnea mx. en la fase 3

I3mx

032 kA

1,5%

Corriente instantnea mx. en el neutro

Inmx

032 kA

1,5%

Corriente instantnea mx. en tierra

032 kA

1,5%

mx

Demanda de corriente en la fase 1

I1

032 kA

1,5%

Demanda de corriente en la fase 2

I2

032 kA

1,5%

Demanda de corriente en la fase 3

I3

032 kA

1,5%

Demanda de corriente en el neutro

In

032 kA

1,5%

Demanda de corriente mx. en la fase 1

I1mx

032 kA

1,5%

Demanda de corriente mx. en la fase 2

I2mx

032 kA

1,5%

Demanda de corriente mx. en la fase 3

I3mx

032 kA

1,5%

Demanda de corriente mx. en el neutro

Inmx

032 kA

1,5%

Tensin eficaz entre las fases 1 y 2

U12

01200 V

0,5%

Tensin eficaz entre las fases 2 y 3

U23

01200 V

0,5%

Tensin eficaz entre las fases 3 y 1

U31

01200 V

0,5%

Tensin eficaz entre la fase 1 y el neutro

V1n

01200 V

0,5%

Tensin eficaz entre la fase 2 y el neutro

V2n

01200 V

0,5%

Tensin eficaz entre la fase 3 y el neutro

V3n

01200 V

0,5%

Tensin promedio de fase a fase

Umedia 3)

01200 V

0,5%

Desequilibrio de tensin

Udeseq.3)

0100 V

0,5%

Potencia activa instantnea

032 MW

2%

Potencia reactiva instantnea

032 Mvar

2%

Potencia aparente instantnea

032 MVA

2%

Factor de potencia

PF

-11

0,01%

Demanda de potencia activa

032 MW

2%

Demanda de potencia reactiva

032 Mvar

2%

Demanda de potencia aparente

032 MVA

2%
2%

Demanda de potencia activa mx. desde el ltimo restablecimiento

Pmx

032 MW

Demanda de potencia reactiva mx. desde el ltimo restablecimiento

Qmx

032 Mvar

2%

Demanda de potencia aparente mx. desde el ltimo restablecimiento

Smx

032 MVA

2%
2%

Total de potencia activa

E. P

-10101010 Kwh

Total de potencia reactiva

E. Q

-10101010 Kvarh

2%

Total de potencia aparente

E. S

-10101010 KVAh

2%

Total de potencia activa consumida

E. P

-1010 1010 Kwh

2%

Total de potencia reactiva consumida

E. Q

-10101010 Kvarh

2%

Total de potencia activa generada

E. P

-10101010 Kwh

2%

Total de potencia reactiva generada

E. Q

-10101010 Kvarh

2%

Frecuencia del sistema

45440 Hz

0,1 Hz

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

APNDICE CAcceso a la red/Com

Tabla 15:
Art.

Es posible acceder a distancia a la unidad de


disparo Micrologic a travs de la opcin de
comunicacin utilizando el System Manager
Software (SMS) (versin 3.3 o posterior) o
cualquier otro software de gestin de sistemas
de red. Consulte el catlogo de productos para
obtener ms informacin sobre el software
SMS.

Corriente

Valores de lectura remota


Descripcin

Smbolo

Corriente instantnea 1

I1

Corriente instantnea 2

I2

Corriente instantnea 3

I3

Corriente instantnea N

In

Corriente instantnea en tierra

Corriente media en la fase 1

I1media

Corriente media en la fase 2

I2media

Corriente media en la fase 3

I3media

Corriente media en neutro

Inmedia

Corriente media en tierra

Corriente instantnea mxima 1

I1mx

Corriente instantnea mxima 2

I2mx

Corriente instantnea mxima 3

I3mx

ESPAOL

Valores de lectura remota

media

Corriente instantnea mxima N

Inmx

Corriente instantnea mxima en tierra

Desequilibrio de corriente instantnea 1

I1deseq.

Desequilibrio de corriente instantnea 2

I2deseq.

mx

Desequilibrio de corriente instantnea 3

I3deseq.

Desequilibrio de corriente instantnea N

Indeseq.

Desequilibrio de corriente instantnea mx.

Ideseq.mx

Demanda de corriente 1

I1

Demanda de corriente 2

I2

Demanda de corriente 3

I3

Demanda de corriente N

In

Demanda de corriente mx. desde el ltimo restablecimiento


(reset) 1

I1mx

Demandas
de corriente Demanda de corriente mx. desde el ltimo restablecimiento
(reset) 2

I2mx

Demanda de corriente mx. desde el ltimo restablecimiento


(reset) 3

I3mx

Demanda de corriente mx. desde el ltimo restablecimiento


(reset) N

Inmx

Estampado de hora de demanda de corriente mx.

Tensin

Tensin instantnea entre las fases 1 y 2

Uinst U12

Tensin instantnea entre las fases 2 y 3

Uinst U23

Tensin instantnea entre las fases 3 y 1

Uinst U31

Tensin instantnea entre la fase 1 y el neutro

Uinst U1n

Tensin instantnea entre la fase 2 y el neutro

Uinst U3n

Tensin instantnea entre la fase 3 y el neutro

Uinst U3n

Tensin media de fase a fase

Umedia Uff

Tensin media de fase a neutro

Umedia Ufn

Desequilibrio de tensin entre U12 y la media

Udeseq. U12

Desequilibrio de tensin entre U23 y la media

Udeseq. U23

Desequilibrio de tensin entre U31 y la media

Udeseq. U31

Desequilibrio de tensin entre U1n y la media

Udeseq. U1n

Desequilibrio de tensin entre U2n y la media

Udeseq. U2n

Desequilibrio de tensin entre U3n y la media

Udeseq. U3n

Desequilibrio de tensin mx. de fase a fase

Umx deseq. Uff

Desequilibrio de tensin mx. de fase a neutro

Umx deseq. Ufn

Tabla contina en la siguiente pgina

20002012 Schneider Electric Reservados todos los derechos

79-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

Tabla 15:

48049-137-05
Rev. 01, 07/2012

Valores de lectura remota (continuacin)

Art.

Descripcin

Smbolo

Potencia
activa

Potencia activa instantnea por fase

Demanda de potencia activa

Demanda de potencia reactiva

Demanda de potencia aparente

Demanda de potencia activa mx. desde el ltimo restabl.


(reset)

Pmx

ESPAOL

Demanda de potencia reactiva mx. desde el ltimo restabl.


Demanda
(reset)
de potencia
Demanda de potencia aparente mx. desde el ltimo restabl.
(reset)

Qmx
Smx

Demanda de potencia activa pronosticada al fin del intervalo


Demanda de potencia reactiva pronosticada al fin del intervalo
Demanda de potencia aparente pronosticada al fin del intervalo
Estampado de hora de demanda de potencia mx.
Energa activa total
Energa

Energa activa consumida


Energa activa generada

Valores de
falla
Frecuencia

Tipo de falla
Valores de corriente interrumpida
Frecuencia del sistema

Intervalo entre la ltima actualizacin de los valores de tiempo


real y la tabla de corrientes

Fechas de
actualizacin Fecha de actualizacin de demandas de corriente, demanda de
potencia y energa
Historial de disparo
Historial

Historial de alarmas
Historial de eventos
Desgaste de contactos

Contador de maniobras desde el ltimo restabl. (reset)


Contadores Fecha/hora desde el ltimo restabl, del contador de
operaciones
Contador de maniobras total (vida til)
Configuracin de fecha y hora
Contrasea
Cdigo de identificacin de la unidad de disparo
Nombre de identificacin de la unidad de disparo
Algoritmo para el clculo de medicin
Convencin de signos
Modo de medicin de energa total
Configuraci
n

Factores de escala
Intervalo de ventana para el clculo de demanda de corriente
Indicacin de calidad de la potencia
Modo de clculo de demanda de potencia
Intervalo de ventana para el clculo de demanda de potencia
Indicacin de carga de la pila
Asignacin de los contactos programables
Configuracin de los contactos programables
Tabla contina en la siguiente pgina

80-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

Tabla 15:
Art.

Valores de lectura remota (continuacin)


Descripcin

Smbolo

Corriente nominal del interruptor


Tipo de proteccin del neutro
Ajustes de proteccin de tiempo largo
Ajustes de proteccin de tiempo corto
Ajustes de proteccin instantnea
Proteccin

Ajustes de proteccin contra fallas a tierra


Ajustes de proteccin de desequilibrio de corriente
Ajustes de la alarma de I

ESPAOL

Ajustes de proteccin de la corriente mxima


Ajustes de proteccin de la tensin
Ajustes de las funciones de otro tipo de proteccin

20002012 Schneider Electric Reservados todos los derechos

81-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

Lista de registros
Las cantidades figuran en orden alfabtico de
acuerdo con el nombre de tema de SMS.
NOTA: Se recomienda una velocidad de
exploracin del sistema de 500 ms o mayor
para disminuir los tiempos lmite de
desconexin de las comunicaciones.

48049-137-05
Rev. 01, 07/2012

Utilice el siguiente esquema de direcciones para acceder a los


registros disponibles.
Mdulo Nombre del mdulo

Ecuacin

Gama de
direcciones

MCI

Mdulo de comunicacin del interruptor

147

MCC

Mdulo de comunicacin de la cuna

MCI + 50

5197

MP

Mdulo de proteccin (interno a la


unidad de disparo)

MCI + 100

101147

MM

Mdulo de medicin (interno a la unidad


MCI + 200
de disparo)

201247

ESPAOL

Tabla 16: Lista de Registros1


Nombre de tema
Descripcin del usuario
de SMS

Nmero de
Registro
registros

Mdulo

810D_LDPU

Interruptor LDPU en curso

8862

MP

Escala N/A

810DBrkrStatus

Estado del interruptor

661

MCI

Bit 0; ON = cerrado; OFF = abierto

810DBrkrTripStat

Estado de la unidad de disparo del


interruptor

661

MCI

Bit 2; ON = disparado; OFF = no


disparado

BCM_SN

Nmero de serie del MCI

516

MCI

Texto ASCII

BkrPos

Posicin del interruptor

661

MCC

Bit 8 = desconectado
Bit 9 = conectado
Bit 10 = posicin de prueba

CFVAB

Tensin del factor de cresta 1-2

1119

MM

Ninguna

CFVAN

Tensin del factor de cresta 1-N

1122

MM

Ninguna

Cientos

CFVBC

Tensin del factor de cresta 2-3

1120

MM

Ninguna

Cientos

Unidades Escala

Cientos

CFVBN

Tensin del factor de cresta 2-N

1123

MM

Ninguna

Cientos

CFVCA

Tensin del factor de cresta 3-N

1121

MM

Ninguna

Cientos

Ninguna

Cientos

CFVCN

Tensin del factor de cresta 3-N

1124

MM

DT_3Regs

Fecha/hora del reloj del dispositivo

679

MCI

DTLastTrip

Fecha y hora del ltimo disparo

693

MCI

2
Formato de fecha/hora de 3 registros
2
Formato de fecha/hora de 3 registros

DTPkIAD

Fecha y hora de demanda de corriente


pico 1

3005

MM

2
Formato de fecha/hora de 3 registros

DTPkIBD

Fecha y hora de demanda de corriente


pico 2

3008

MM

2
Formato de fecha/hora de 3 registros

DTPkICD

Fecha y hora de demanda de corriente


pico 3

3011

MM

2
Formato de fecha/hora de 3 registros

DTPkIND

Fecha y hora de demanda de corriente


pico N

3014

MM

2
Formato de fecha/hora de 3 registros

DTPkKFDA

Fecha y hora de demanda pico del


factor K 1

3041

MM

Ninguna

2
Formato de fecha/hora de 3 registros

DTPkKFDB

Fecha y hora de demanda pico del


factor K 2

3044

MM

Ninguna

2
Formato de fecha/hora de 3 registros

DTPkKFDC

Fecha y hora de demanda pico del


factor K 3

3047

MM

Ninguna

2
Formato de fecha/hora de 3 registros

DTPkKFDN

Fecha y hora de demanda pico del


factor K N

3050

MM

Ninguna

2
Formato de fecha/hora de 3 registros

DTPkkVAD

Fecha y hora de demanda pico de potencia


aparente

3023

MM

2
Formato de fecha/hora de 3 registros
Tabla contina en la siguiente pgina

1Para las entradas de registro que no estn en la lista e informacin del factor de escala, consulte el boletn 0613IB1201, Sistema de comunicaciones Modbus.
2Formato de fecha/hora de 3 registros: registro 1: mes (byte 1) = 112; da (byte 2) = 131; registro 2: ao (byte 1) = 0199 (agregue 1900 para determinar el

ao actual); hora (byte 2) = 023; registro 3: minutos (byte 1) = 059; segundos (byte 2) = 059
Nota: Bits 14 y 15 del registro de mes/da debern enmascararse.
3
Formato del factor de potencia: 1 a 999 para los factores de potencia de retraso, 1000 para el factor de potencia de la unidad 1.000 y 1 a 999 para el factor de
potencia de avance.
4
Formato del mdulo 10,000: registro secuencial de 1 a 4. Cada registro es un mdulo 10,000 (gama = 9,999 a +9,999).
El resultado es [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. La gama es de cero a 9,999,999,999,999,999.

82-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

Tabla 16: Lista de Registros1


Nmero de
Registro
registros

Mdulo

Unidades Escala

DTPkkVARD

Fecha y hora de demanda pico de potencia


reactiva

3020

MM

2
Formato de fecha/hora de 3 registros

DTPkkWD

Fecha y hora de demanda pico de potencia


activa

3017

MM

2
Formato de fecha/hora de 3 registros

DTResetEnergy

Fecha y hora del ltimo restablecimiento de


energas acumuladas

3038

MM

2
Formato de fecha/hora de 3 registros

DTResetMinMax

Fecha y hora del ltimo restablecimiento de


Mn/Mx

3032

MM

2
Formato de fecha/hora de 3 registros

DTResetPkID

Fecha y hora del ltimo restablecimiento de


demanda de corriente pico

3026

MM

2
Formato de fecha/hora de 3 registros

DTResetPkkWD

Fecha y hora del ltimo restablecimiento de


demanda de potencia pico

3029

MM

2
Formato de fecha/hora de 3 registros

EnableCloseBkr

Cierre remoto activado

669

MCI

Bit 2; ON = activado, OFF = no activado

EnableOpenBkr

Apertura remota activada

669

MCI

Bit 1; ON = activado; OFF = no activado

EnableRemCtrl

Control remoto activado

669

MCI

Bit 3; ON = automtico (activado);


OFF = manual (no activado)

fkVAA

Potencia aparente del fundamental 1

1084

MM

kVA

Escala E

fkVAB

Potencia aparente del fundamental 2

1085

MM

kVA

Escala E

fkVAC

Potencia aparente del fundamental 3

1086

MM

kVA

Escala E

fkVATtl

Potencia aparente total del fundamental

1087

MM

kVA

Escala E
Dcimos

fVAngA

ngulo de tensin del fundamental 1-2/1-N 1

1133

MM

Grados

fVAngB

ngulo de tensin del fundamental 2-3/2-N 1

1134

MM

Grados

Dcimos

fVAngC

ngulo de tensin del fundamental 3-1/3-N 1

1135

MM

Grados

Dcimos

GFAlarmStatus

Estado de la alarma de falla a tierra

8860

MP

Bit 0; ON = activa; OFF = inactiva

GFPreAlarmStatus

Estado de la pre-alarma de la alarma de falla


1
a tierra

8864

MP

Bit 0; ON = activa; OFF = inactiva

Hz

Frecuencia

1054

MM

Hz

IA

Corriente 1

1016

MM

Escala A - Corriente de fases

IA_PCT

% de carga de la corriente 1

8837

MP

Unidad

IAD

Demandas de corriente 1

2200

MM

Escala A

IAppA

Corriente aparente 1

1023

MM

Escala A

Escala F

IAppB

Corriente aparente 2

1024

MM

Escala A

IAppC

Corriente aparente 3

1025

MM

Escala A

IAppN

Corriente aparente N

1026

MM

Escala B

IAvg

Corriente media

1027

MM

Escala A - Corriente de fases

IB

Corriente 2

1017

MM

Escala A - Corriente de fases

IB_PCT

% de carga de la corriente 2

8838

MP

Unidad

IBD

Demanda de corriente 2

2201

MM

Escala A

IC

Corriente 3

1018

MM

Escala A - Corriente de fases

IC_PCT

% de carga de la corriente 3

8839

MP

Unidad

ICD

Demandas de corriente 3

2202

MM

Escala A

IDatPkKFD_A

Demanda de corriente pico del factor K 1

2270

MM

Escala A

IDatPkKFD_B

Demanda de corriente pico del factor K 2

2271

MM

Escala A

IDatPkKFD_C

Demanda de corriente pico del factor K 3

2272

MM

Escala A

IDatPkKFD_N

Demanda de corriente pico del factor K N

2273

MM

Escala B

IG

Corriente G

1021

MM

Escala C

1
Para las entradas de registro que no estn en la lista e informacin del factor de escala, consulte el boletn 0613IB1201, Sistema de comunicaciones Modbus.
2

Formato de fecha/hora de 3 registros: registro 1: mes (byte 1) = 112; da (byte 2) = 131; registro 2: ao (byte 1) = 0199 (agregue 1900 para determinar el
ao actual); hora (byte 2) = 023; registro 3: minutos (byte 1) = 059; segundos (byte 2) = 059
Nota: Bits 14 y 15 del registro de mes/da debern enmascararse.
3 Formato del factor de potencia: 1 a 999 para los factores de potencia de retraso, 1000 para el factor de potencia de la unidad 1.000 y 1 a 999 para el factor de
potencia de avance.
4
Formato del mdulo 10,000: registro secuencial de 1 a 4. Cada registro es un mdulo 10,000 (gama = 9,999 a +9,999).
El resultado es [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. La gama es de cero a 9,999,999,999,999,999.

20002012 Schneider Electric Reservados todos los derechos

83-ES

ESPAOL

Nombre de tema
Descripcin del usuario
de SMS

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

48049-137-05
Rev. 01, 07/2012

Tabla 16: Lista de Registros1


Nombre de tema
Descripcin del usuario
de SMS

Nmero de
Registro
registros

Mdulo

Unidades Escala

IG_PCT

MP

Tabla contina en la siguiente pgina


% de carga de la corriente G

8841

Unidad

IG_PCT_VIGI

% de carga de la corriente G (VIGI)

8842

MP

Cientos

IG_VIGI

Corriente G (VIGI)

8826

MP

Miles

IMax

Corriente mxima actual

1020

MM

Escala A - Corriente de fases

ENTRADA

Corriente N

1019

MM

Escala B - Corriente neutra

ESPAOL

IN_PCT

% de carga de la corriente N

8840

MP

Unidad

IND

Demanda de corriente N

2203

MM

Escala B

IUnbalA

Desequilibrio de corriente 1

1028

MM

Dcimos

IUnbalAlrm

Estado de la alarma de desequilibrio de


corriente

8859

MP

IUnbalB

Desequilibrio de corriente 2

1029

MM

Dcimos

IUnbalC

Desequilibrio de corriente 3

1030

MM

Dcimos

IUnbalPreAlrm

Estado de la pre-alarma de desequilibrio de


corriente

8863

MP

Bit 0; ON = activa; OFF = inactiva

Bit 0; ON = activa; OFF = inactiva

IUnbalW

Peor desequilibrio de corriente

1032

MM

Dcimos

KFDatPkID_A

Demanda de corriente pico del factor K 1

2254

MM

Ninguna

Dcimos

KFDatPkID_B

Demanda de corriente pico del factor K 2

2255

MM

Ninguna

Dcimos

KFDatPkID_C

Demanda de corriente pico del factor K 3

2256

MM

Ninguna

Dcimos

KFDatPkID_N

Demanda de corriente pico del factor K N

2257

MM

Ninguna

Dcimos

KFDN

Demanda del factor K N

2215

MM

Ninguna

Dcimos
Dcimos

KFN

Factor K N

1118

MM

Ninguna

kVAA

Potencia aparente 1

1042

MM

kVA

Escala E

kVAB

Potencia aparente 2

1043

MM

kVA

Escala E

kVAC

Potencia aparente 3

1044

MM

kVA

Escala E

kVAD

Demanda de potencia aparente

2236

MM

kVA

Escala D

kVAD_PkkVARD

Demanda coincidente en kVA con la


demanda pico en kVAR

2235

MM

kVA

Escala D

kVAD_PkkWD

Demanda coincidente en kVA con la


demanda pico en kW

2229

MM

kVA

Escala D

kVAHr

Energa aparente

2024

MM

kVAH

Unidad

kVARA

Potencia reactiva 1

1038

MM

kVAR

Escala E

kVARB

Potencia reactiva 2

1039

MM

kVAR

Escala E

kVARC

Potencia reactiva 3

1040

MM

kVAR

Escala E

kVARD

Demanda de potencia reactiva

2230

MM

kVAR

Escala D

kVARD_PkkVAD

Demanda coincidente en kVAR con la


demanda pico en kVA

2241

MM

kVAR

Escala D

kVARD_PkkWD

Demanda coincidente en kVAR con la


demanda pico en kW

2228

MM

kVAR

Escala D

kVARHr

Energa r eactiva

2004

MM

kVARH

Unidad

kVARHr_I

Energa reactica dentro de la carga

2016

MM

kVARH

Unidad

kVARHr_O

Energa reactica fuera de la carga

2020

MM

kVARH

Unidad

kVARTtl

Potencia reactiva total

1041

MM

kVAR

Escala E
Escala E

kVATtl

Potencia aparente total

1045

MM

kVA

kWA

Potencia activa 1

1034

MM

kW

Escala E

kWB

Potencia activa 2

1035

MM

kW

Escala E

1Para las entradas de registro que no estn en la lista e informacin del factor de escala, consulte el boletn 0613IB1201, Sistema de comunicaciones Modbus.
2Formato de fecha/hora de 3 registros: registro 1: mes (byte 1) = 112; da (byte 2) = 131; registro 2: ao (byte 1) = 0199 (agregue 1900 para determinar el

ao actual); hora (byte 2) = 023; registro 3: minutos (byte 1) = 059; segundos (byte 2) = 059
Nota: Bits 14 y 15 del registro de mes/da debern enmascararse.
3 Formato del factor de potencia: 1 a 999 para los factores de potencia de retraso, 1000 para el factor de potencia de la unidad 1.000 y 1 a 999 para el factor de
potencia de avance.
4Formato del mdulo 10,000: registro secuencial de 1 a 4. Cada registro es un mdulo 10,000 (gama = 9,999 a +9,999).
El resultado es [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. La gama es de cero a 9,999,999,999,999,999.

84-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

Tabla 16: Lista de Registros1


Nombre de tema
Descripcin del usuario
de SMS

Nmero de
Registro
registros

Mdulo

Unidades Escala

kWC

Potencia activa 3

1036

MM

kW

Escala E

kWD

Demanda de potencia activa

2224

MM

kW

Escala D

kWD_PkkVAD

Demanda coincidente en kW con la


demanda pico en kVA

2240

MM

kW

Escala D

kWD_PkkVARD

Demanda coincidente en kW con la


demanda pico en kVAR

2234

MM

kW

Escala D

Tabla contina en la siguiente pgina

Energa activa

2000

MM

kWH

Unidad

Energa actica dentro de la carga

2008

MM

kWH

Unidad

kWHr_O

Energa actica fuera de la carga

2012

MM

kWH

Unidad

kWTtl

Potencia activa total

1037

MM

kW

Escala E

LDPUValue

Valor de activacin de retardo largo

8756

MP

Unidad

LSCurrAlrm

Estado de la alarma de corriente de


desconexin de carga

8859

MP

Bit 13; ON = activa; OFF = inactiva

LSCurrPreAlrm

Estado de la pre-alarma de corriente de


desconexin de carga

8863

MP

Bit 13; ON = activa; OFF = inactiva

LSPwrAlrm

Estado de la alarma de potencia de


desconexin de carga

8859

MP

Bit 14; ON = activa; OFF = inactiva

LSPwrPreAlrm

Estado de la pre-alarma de potencia de


desconexin de carga

8863

MP

Bit 14; ON = activa; OFF = inactiva

M2C_M6CR1Status

Estado del mdulo de rel R1

8857

MP

Bit 0; ON = conectado; OFF =


desconectado

M2C_M6CR2Status

Estado del mdulo de rel R2

8857

MP

Bit 1; ON = conectado; OFF =


desconectado

M2C_M6CR3Status

Estado del mdulo de rel R3

8857

MP

Bit 2; ON = conectado; OFF =


desconectado

M2C_M6CR4Status

Estado del mdulo de rel R4

8857

MP

Bit 3; ON = conectado; OFF =


desconectado

M2C_M6CR5Status

Estado del mdulo de rel R5

8857

MP

Bit 4; ON = conectado; OFF =


desconectado

M2C_M6CR6Status

Estado del mdulo de rel R6

8857

MP

Bit 5; ON = conectado; OFF =


desconectado

MaxCFVAB

Tensin mxima del factor de cresta 1-2

1719

MM

Ninguna

MaxCFVAN

Tensin mxima del factor de cresta 1-N

1722

MM

Ninguna

Cientos

MaxCFVBC

Tensin mxima del factor de cresta 2-3

1720

MM

Ninguna

Cientos

ESPAOL

kWHr
kWHr_I

Cientos

MaxCFVBN

Tensin mxima del factor de cresta 2-N

1723

MM

Ninguna

Cientos

MaxCFVCA

Tensin mxima del factor de cresta 3-N

1721

MM

Ninguna

Cientos

MaxCFVCN

Tensin mxima del factor de cresta 3-N

1724

MM

Ninguna

Cientos

MaxfkVAA

Potencia aparente mx. del fundamental 1 1

1684

MM

kVA

Escala E

MaxfkVAB

Potencia aparente mx. del fundamental 2 1

1685

MM

kVA

Escala E

MaxfkVAC

Potencia aparente mx. del fundamental 3 1

1686

MM

kVA

Escala E

MaxfkVATtl

Potencia aparente mxima total del


fundamental

1687

MM

kVA

Escala E

MaxfVMagAB

Tensin mxima del fundamental 1-2

1656

MM

Escala D

MaxfVMagAN

Magnitud de la tensin mxima del


fundamental 1-N

1659

MM

Escala D

MaxfVMagBC

Magnitud de la tensin mxima del


fundamental 2-3

1657

MM

Escala D

1
Para las entradas de registro que no estn en la lista e informacin del factor de escala, consulte el boletn 0613IB1201, Sistema de comunicaciones Modbus.
2Formato de fecha/hora de 3 registros: registro 1: mes (byte 1) = 112; da (byte 2) = 131; registro 2: ao (byte 1) = 0199 (agregue 1900 para determinar el

ao actual); hora (byte 2) = 023; registro 3: minutos (byte 1) = 059; segundos (byte 2) = 059
Nota: Bits 14 y 15 del registro de mes/da debern enmascararse.
3 Formato del factor de potencia: 1 a 999 para los factores de potencia de retraso, 1000 para el factor de potencia de la unidad 1.000 y 1 a 999 para el factor de
potencia de avance.
4Formato del mdulo 10,000: registro secuencial de 1 a 4. Cada registro es un mdulo 10,000 (gama = 9,999 a +9,999).
El resultado es [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. La gama es de cero a 9,999,999,999,999,999.

20002012 Schneider Electric Reservados todos los derechos

85-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

48049-137-05
Rev. 01, 07/2012

Tabla 16: Lista de Registros1


Nombre de tema
Descripcin del usuario
de SMS

Nmero de
Registro
registros

Mdulo

Unidades Escala
Tabla contina en la siguiente pgina

MaxfVMagBN

Magnitud de la tensin mxima del


fundamental 2-N

1660

MM

Escala D

MaxfVMagCA

Magnitud de la tensin mxima del


fundamental 3-N

1658

MM

Escala D

MaxfVMagCN

Magnitud de la tensin mxima del


fundamental 3-N

1661

MM

Escala D

ESPAOL

MaxHz

Frecuencia mxima

1654

MM

Hz

Escala F

MaxIA

Corriente mxima

1616

MM

Escala A - Corriente de fases

MaxIAppA

Corriente aparente mxima 1

1623

MM

Escala A

MaxIAppB

Corriente mxima aparente 2

1624

MM

Escala A

MaxIAppC

Corriente aparente mxima 3

1625

MM

Escala A

MaxIAppN

Corriente mxima aparente N

1626

MM

Escala B

MaxIAvg

Media de la corriente mxima

1627

MM

Escala A - Corriente de fases

MaxIB

Corriente mxima 2

1617

MM

Escala A - Corriente de fases

MaxIC

Corriente mxima 3

1618

MM

Escala A - Corriente de fases

MaxIG

Corriente mxima G

1621

MM

Escala C

MaxIG_VIGI

Corriente mxima G (VIGI)

8832

MP

Miles

MaxIN

Corriente mxima N

1619

MM

Escala B - Corriente neutra

MaxIUnbalA

Desequilibrio de la corriente mxima 1

1628

MM

Dcimos

MaxIUnbalB

Desequilibrio de la corriente mxima 2

1629

MM

Dcimos
Dcimos

MaxIUnbalC

Desequilibrio de la corriente mxima 3

1630

MM

MaxIUnbalW

Peor desequilibrio de la corriente mx.

1632

MM

Dcimos

MaxKFN

Factor K mximo del neutro

1718

MM

Ninguna

Dcimos

MaxkVAA

Potencia aparente mxima 1

1642

MM

kVA

Escala E

MaxkVAB

Potencia aparente mxima 2

1643

MM

kVA

Escala E

MaxkVAC

Potencia aparente mxima 3

1644

MM

kVA

Escala E

MaxkVARA

Potencia reactiva mxima 1

1638

MM

kVAR

Escala E

MaxkVARB

Potencia reactiva mxima 2

1639

MM

kVAR

Escala E

MaxkVARC

Potencia reactiva mxima 3

1640

MM

kVAR

Escala E

MaxkVARTtl

Potencia reactiva mxima total

1641

MM

kVAR

Escala E

MaxkVATtl

Potencia aparente mxima total

1645

MM

kVA

Escala E

MaxkWA

Potencia activa mxima 1

1634

MM

kW

Escala E
Escala E

MaxkWB

Potencia activa mxima 2

1635

MM

kW

MaxkWC

Potencia activa mxima 3

1636

MM

kW

Escala E

MaxkWTtl

Potencia activa mxima total

1637

MM

kW

Escala E

MaxPFA

Factor de la potencia mxima 1

1646

MM

MaxPFB

Factor de la potencia mxima 2

1647

MM

MaxPFC

Factor de la potencia mxima 3

1648

MM

MaxPFTtl

Factor de la potencia mxima total

1649

MM

MaxVAB

Tensin mxima 1-2

1600

MM

Escala D Tensin

MaxVAN

Tensin mxima 1-N

1603

MM

Escala D Tensin

MaxVBC

Tensin mxima 2-3

1601

MM

Escala D Tensin

MaxVBN

Tensin mxima 2-N

1604

MM

Escala D Tensin

Formato FP

3
Formato FP
3
Formato FP
3
Formato FP

1
Para las entradas de registro que no estn en la lista e informacin del factor de escala, consulte el boletn 0613IB1201, Sistema de comunicaciones Modbus.
2Formato de fecha/hora de 3 registros: registro 1: mes (byte 1) = 112; da (byte 2) = 131; registro 2: ao (byte 1) = 0199 (agregue 1900 para determinar el

ao actual); hora (byte 2) = 023; registro 3: minutos (byte 1) = 059; segundos (byte 2) = 059
Nota: Bits 14 y 15 del registro de mes/da debern enmascararse.
3 Formato del factor de potencia: 1 a 999 para los factores de potencia de retraso, 1000 para el factor de potencia de la unidad 1.000 y 1 a 999 para el factor de
potencia de avance.
4Formato del mdulo 10,000: registro secuencial de 1 a 4. Cada registro es un mdulo 10,000 (gama = 9,999 a +9,999).
El resultado es [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. La gama es de cero a 9,999,999,999,999,999.

86-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

Tabla 16: Lista de Registros1


Nombre de tema
Descripcin del usuario
de SMS

Nmero de
Registro
registros

Mdulo

Unidades Escala

MaxVCA

Tensin mxima 3-N

1602

MM

Escala D Tensin

MaxVCN

Tensin mxima 3-N

1605

MM

Escala D Tensin

MaxVLLAvg

Media de la tensin mxima de L-L

1606

MM

Escala D Tensin

MaxVLNAvg

Media de la tensin mxima de L-N

1607

MM

Escala D Tensin

MaxVUnbalAB

Desequilibrio de la tensin mxima 1-2

1608

MM

Dcimos

MaxVUnbalAN

Desequilibrio de la tensin mxima 1-N

1611

MM

Dcimos

MaxVUnbalBC

Desequilibrio de la tensin mxima 2-2

1609

MM

Dcimos

MaxVUnbalBN

Desequilibrio de la tensin mxima 2-N

1612

MM

Dcimos

MaxVUnbalCA

Desequilibrio de la tensin mxima 3-N

1610

MM

Dcimos

MaxVUnbalCN

Desequilibrio de la tensin mxima 3-N

1613

MM

Dcimos

MaxVUnbalLLW

Desequilibrio de la peor tensin mx. de L-L 1

1614

MM

Dcimos

MaxVUnbalLNW

Desequilibrio de la peor tensin mx. de L-N 1

1615

MM

Dcimos

MinCFVAB

Tensin mnima del factor de cresta 1-2

1419

MM

Ninguna

Cientos

MinCFVAN

Tensin mnima del factor de cresta 1-N

1422

MM

Ninguna

Cientos

MinCFVBC

Tensin mnima del factor de cresta 2-3

1420

MM

Ninguna

Cientos

MinCFVBN

Tensin mnima del factor de cresta 2-N

1423

MM

Ninguna

Cientos

MinCFVCA

Tensin mnima del factor de cresta 3-1

1421

MM

Ninguna

Cientos

MinCFVCN

Tensin mnima del factor de cresta 3-N

1424

MM

Ninguna

Cientos

MinfkVAA

Potencia aparente mn. del fundamental 1

1384

MM

kVA

Escala E

MinfkVAB

Potencia aparente mn. del fundamental 2

1385

MM

kVA

Escala E

MinfkVAC

Potencia aparente mn.del fundamental 3

1386

MM

kVA

Escala E

MinfkVATtl

Potencia aparente mn. total del fundamental 1

1387

MM

kVA

Escala E

MinfVMagAB

Magnitud de la tensin mnima del


fundamental 1-2

1356

MM

Escala D

MinfVMagAN

Magnitud de la tensin mnima del


fundamental 1-N

1359

MM

Escala D

MinfVMagBC

Magnitud de la tensin mnima del


fundamental 2-3

1357

MM

Escala D

MinfVMagBN

Magnitud de la tensin mnima del


fundamental 2-N

1360

MM

Escala D

MinfVMagCA

Magnitud de la tensin mnima del


fundamental 3-1

1358

MM

Escala D

MinfVMagCN

Magnitud de la tensin mnima del


fundamental 3-N

1361

MM

Escala D

MinHz

Frecuencia mnima

1354

MM

Hz

Scale F

MinIA

Corriente mnima 1

1316

MM

Escala A - Corriente de fases

MinIAppA

Corriente aparente mnima 1

1323

MM

Escala A

MinIAppB

Corriente aparente mnima 2

1324

MM

Escala A

MinIAppC

Corriente aparente mnima 3

1325

MM

Escala A

MinIAppN

Corriente aparente mnima N

1326

MM

Scale B

MinIAvg

Media de la corriente mnima 1

1327

MM

Escala A - Corriente de fases

MinIB

Corriente mnima 2

1317

MM

Escala A - Corriente de fases

MinIC

Corriente mnima 3

1318

MM

Escala A - Corriente de fases

MinIN

Corriente mnima N

1319

MM

Scale B - Corriente del neutro

ESPAOL

Tabla contina en la siguiente pgina

1
Para las entradas de registro que no estn en la lista e informacin del factor de escala, consulte el boletn 0613IB1201, Sistema de comunicaciones Modbus.
2Formato de fecha/hora de 3 registros: registro 1: mes (byte 1) = 112; da (byte 2) = 131; registro 2: ao (byte 1) = 0199 (agregue 1900 para determinar el

ao actual); hora (byte 2) = 023; registro 3: minutos (byte 1) = 059; segundos (byte 2) = 059
Nota: Bits 14 y 15 del registro de mes/da debern enmascararse.
3 Formato del factor de potencia: 1 a 999 para los factores de potencia de retraso, 1000 para el factor de potencia de la unidad 1.000 y 1 a 999 para el factor de
potencia de avance.
4Formato del mdulo 10,000: registro secuencial de 1 a 4. Cada registro es un mdulo 10,000 (gama = 9,999 a +9,999).
El resultado es [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. La gama es de cero a 9,999,999,999,999,999.

20002012 Schneider Electric Reservados todos los derechos

87-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

48049-137-05
Rev. 01, 07/2012

Tabla 16: Lista de Registros1


Nombre de tema
Descripcin del usuario
de SMS

Nmero de
Registro
registros

Mdulo

Unidades Escala

MinIUnbalA

Desequilibrio de la corriente mnima 1

1328

MM

Dcimos

MinIUnbalB

Desequilibrio de la corriente mnima 2

1329

MM

Dcimos

MinIUnbalC

Desequilibrio de la corriente mnima 3

1330

MM

Dcimos

Tabla contina en la siguiente pgina

MinIUnbalW

Desequilibrio de la peor corriente mnima

1332

MM

Dcimos

MinKFN

Factor K mnimo N

1418

MM

Ninguna

Dcimos

ESPAOL

MinkVAA

Potencia aparente mnima 1

1342

MM

kVA

Escala E

MinkVAB

Potencia aparente mnima 2

1343

MM

kVA

Escala E

MinkVAC

Potencia aparente mnima 3

1344

MM

kVA

Escala E

MinkVARA

Potencia reactiva mnima 1

1338

MM

kVAR

Escala E

MinkVARB

Potencia reactiva mnima 2

1339

MM

kVAR

Escala E

MinkVARC

Potencia reactiva mnima 3

1340

MM

kVAR

Escala E

MinkVARTtl

Potencia reactiva mnima total

1341

MM

kVAR

Escala E

MinkVATtl

Potencia aparente mnima total

1345

MM

kVA

Escala E

MinkWA

Potencia activa mnima 1

1334

MM

kW

Escala E

MinkWB

Potencia activa mnima 2

1335

MM

kW

Escala E

MinkWC

Potencia activa mnima 3

1336

MM

kW

Escala E

MinkWTtl

Potencia activa mnima total

1337

MM

kW

Escala E

MinPFA

Factor de potencia mnimo 1

1346

MM

MinPFB

Factor de potencia mnimo 2

1347

MM

MinPFC

Factor de potencia mnimo 3

1348

MM

MinPFTtl

Factor de potencia mnimo total

1349

MM

MinVAB

Tensin mnima 1-2

1300

MM

MinVAN

Tensin mnima 1-N

1303

MM

Escala D - Tensin

MinVBC

Tensin mnima 2-3

1301

MM

Escala D - Tensin

3
Formato FP
3
Formato FP
3
Formato FP
3
Formato FP
Escala D - Tensin

MinVBN

Tensin mnima 2-N

1304

MM

Escala D - Tensin

MinVCA

Tensin mnima 3-1

1302

MM

Escala D - Tensin

MinVCN

Tensin mnima 3-N

1305

MM

Escala D - Tensin

MinVLLAvg

Media de tensin mnima L-L

1306

MM

Escala D - Tensin

MinVLNAvg

Media de tensin mnima L-N

1307

MM

Escala D - Tensin

MinVUnbalAB

Desequilibrio de tensin mnima 1-2

1308

MM

Dcimos

MinVUnbalAN

Desequilibrio de tensin mnima 1-N

1311

MM

Dcimos

MinVUnbalBC

Desequilibrio de tensin mnima 2-3

1309

MM

Dcimos

MinVUnbalBN

Desequilibrio de tensin mnima 2-N

1312

MM

Dcimos

MinVUnbalCA

Desequilibrio de tensin mnima 3-1

1310

MM

Dcimos

MinVUnbalCN

Desequilibrio de tensin mnima 3-N

1313

MM

Dcimos

MinVUnbalLLW

Desequilibrio de la peor tensin mnima L-L

1314

MM

Dcimos

MinVUnbalLNW

Desequilibrio de la peor tensin mnima L-N

1315

MM

Dcimos

Unidades

NominalCurrent

Corriente nominal del interruptor

8750

PM

OverFreqAlrm

Estado de la alarma de sobrefrecuencia

8859

PM

Bit 11; ON = activa, OFF = inactiva

OverFreqPreAlrm

Estado de la pre-alarma de sobrefrecuencia

8863

PM

Bit 11; ON = activa, OFF = inactiva

OverIAAlrm

Estado de la alarma de sobredemanda I1

8859

PM

Bit 1; ON = activa, OFF = inactiva

OverIAPreAlrm

Estado de la pre-alarma de sobredem. I1

8863

PM

Bit 1; ON = activa, OFF = inactiva

OverIBAlrm

Estado de la alarma de sobredemanda I2

8859

PM

Bit 2; ON = activa, OFF = inactiva

1Para las entradas de registro que no estn en la lista e informacin del factor de escala, consulte el boletn 0613IB1201, Sistema de comunicaciones Modbus.
2Formato de fecha/hora de 3 registros: registro 1: mes (byte 1) = 112; da (byte 2) = 131; registro 2: ao (byte 1) = 0199 (agregue 1900 para determinar el

ao actual); hora (byte 2) = 023; registro 3: minutos (byte 1) = 059; segundos (byte 2) = 059
Nota: Bits 14 y 15 del registro de mes/da debern enmascararse.
3 Formato del factor de potencia: 1 a 999 para los factores de potencia de retraso, 1000 para el factor de potencia de la unidad 1.000 y 1 a 999 para el factor de
potencia de avance.
4Formato del mdulo 10,000: registro secuencial de 1 a 4. Cada registro es un mdulo 10,000 (gama = 9,999 a +9,999).
El resultado es [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. La gama es de cero a 9,999,999,999,999,999.

88-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

Tabla 16: Lista de Registros1


Nombre de tema
Descripcin del usuario
de SMS

Nmero de
Registro
registros

Mdulo

Unidades Escala

OverIBPreAlrm

Estado de la pre-alarma de sobredem. I2

8863

PM

Bit 2; ON = activa, OFF = inactiva

OverICAlrm

Estado de la alarma de sobredemanda I3

8859

PM

Bit 3; ON = activa, OFF = inactiva

OverICPreAlrm

Estado de la pre-alarma de sobredem. I3

8863

PM

Bit 3; ON = activa, OFF = inactiva

OverINAlrm

Estado de la alarma de sobredemanda IN

8859

PM

Bit 4; ON = activa, OFF = inactiva

OverINPreAlrm

Estado de la pre-alarma de sobredem. IN

8863

PM

Bit 4; ON = activa, OFF = inactiva

OverVoltAlrm

Estado de la alarma de sobretensin

8859

PM

Bit 6; ON = activa, OFF = inactiva

OverVoltPreAlrm

Estado de la pre-alarma de sobretensin

8863

PM

Bit 6; ON = activa, OFF = inactiva

PF_PkkVAD

FP coincidente con la demanda pico en kVA 3

2239

MM

Miles

PF_PkkVARD

FP coincidente con la dem. pico en kVAR

2233

MM

Miles

PF_PkkWD

FP coincidente con la demanda pico en kW

2227

MM

Miles

PFA

Factor de potencia 1

1046

MM

PFB

Factor de potencia 2

1047

MM

PFC

Factor de potencia 3

1048

MM

3
Formato FP
3
Formato FP
3
Formato FP
3
Formato FP

PFTtl

Factor de potencia total

1049

MM

PhaRotAlrm

Estado de la alarma de rotacin de fases

8859

PM

PkIAD

Corriente de demanda pico 1

2204

MM

Escala A

PkIBD

Corriente de demanda pico 2

2205

MM

Escala A

Bit 12; ON = activa, OFF = inactiva

PkICD

Corriente de demanda pico 3

2206

MM

Escala A

PkIND

Corriente de demanda pico N

2207

MM

Escala A
Dcimos

PkKFDA

Demanda pico del factor K 1

2216

MM

Ninguna

PkKFDB

Demanda pico del factor K 2

2217

MM

Ninguna

Dcimos

PkKFDC

Demanda pico del factor K 3

2218

MM

Ninguna

Dcimos

PkKFDN

Demanda pico del factor K N

2219

MM

Ninguna

Dcimos

PkkVAD

Demanda pico de potencia aparente

2237

MM

kVA

Escala A

PkkVARD

Demanda pico de potencia reactiva

2231

MM

kVAR

Escala A

PkkWD

Demanda pico de potencia activa

2225

MM

kW

Escala A

PredIAD

Demanda de corriente pronosticada 1

2208

MM

Escala A

PredIBD

Demanda de corriente pronosticada 2

2209

MM

Escala A

PredICD

Demanda de corriente pronosticada 3

2210

MM

Escala A

PredIND

Demanda de corriente pronosticada N

2211

MM

Escala A

PredKFDA

Demanda del factor K pronosticada 1

2220

MM

Ninguna

Dcimos

PredKFDB

Demanda del factor K pronosticada 2

2221

MM

Ninguna

Dcimos

PredKFDC

Demanda del factor K pronosticada 3

2222

MM

Ninguna

Dcimos

PredKFDN

Demanda del factor K pronosticada N

2223

MM

Ninguna

Dcimos

PredkVAD

Demanda pronosticada en kVA

2238

MM

kVA

Escala A

PredkVARD

Demanda pronosticada en kVAR

2232

MM

kVAR

Escala A

PredkWD

Demanda pronosticada en kW

2226

MM

kW

Escala A

R1OpsCounter

Contador de maniobras del rel 1

9081

PM

Unidad

R2OpsCounter

Contador de maniobras del rel 2

9082

PM

Unidad

R3OpsCounter

Contador de maniobras del rel 3

9083

PM

Unidad

R4OpsCounter

Contador de maniobras del rel 4

9084

PM

Unidad

R5OpsCounter

Contador de maniobras del rel 5

9085

PM

Unidad

R6OpsCounter

Contador de maniobras del rel 6

9086

PM

Unidad

1Para las entradas de registro que no estn en la lista e informacin del factor de escala, consulte el boletn 0613IB1201, Sistema de comunicaciones Modbus.
2Formato de fecha/hora de 3 registros: registro 1: mes (byte 1) = 112; da (byte 2) = 131; registro 2: ao (byte 1) = 0199 (agregue 1900 para determinar el

ao actual); hora (byte 2) = 023; registro 3: minutos (byte 1) = 059; segundos (byte 2) = 059
Nota: Bits 14 y 15 del registro de mes/da debern enmascararse.
3 Formato del factor de potencia: 1 a 999 para los factores de potencia de retraso, 1000 para el factor de potencia de la unidad 1.000 y 1 a 999 para el factor de
potencia de avance.
4Formato del mdulo 10,000: registro secuencial de 1 a 4. Cada registro es un mdulo 10,000 (gama = 9,999 a +9,999).
El resultado es [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. La gama es de cero a 9,999,999,999,999,999.

20002012 Schneider Electric Reservados todos los derechos

89-ES

ESPAOL

Tabla contina en la siguiente pgina

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice CAcceso a la red/Com

48049-137-05
Rev. 01, 07/2012

Tabla 16: Lista de Registros1


Nombre de tema
Descripcin del usuario
de SMS

Nmero de
Registro
registros

Mdulo

Unidades Escala

ReadyToClose

Interruptor listo para cerrar

661

BCM

Bit 5; ON = s, OFF = no

RevPwrAlrm

Estado de la alarma de potencia inversa

8859

PM

Bit 9; ON = activa; OFF = inactiva

RevPwrPreAlrm

Estado de la pre-alarma de potencia inversa 1

8863

PM

Bit 9; ON = activa; OFF = inactiva

TimeToTrip

Tiempo para dispararse segn el retardo de


2
tiempo largo

8865

PM

TU_BATT_PCT

% de vida til de la pila de la unidad de


disparo

8843

PM

TU_SN

Nmero de serie de la unidad de disparo

8700

PM

Texto ASCII

TUCommStatus

Estado de comunicacin de la unidad de


disparo

552

BCM

Bit 11; ON = no responde; OFF = OK

Tabla contina en la siguiente pgina


Dcimos
%

Unidades

ESPAOL

UnderFreqAlrm

Estado de la alarma de baja frecuencia

8859

PM

Bit 10; ON = activa; OFF = inactiva

UnderFreqPreAlrm

Estado de la pre-alarma de baja frecuencia

8863

PM

Bit 10; ON = activa; OFF = inactiva

UnderVoltAlrm

Estado de la alarma baja tensin

8859

PM

Bit 5; ON = activa; OFF = inactiva

UnderVoltPreAlrm

Estado de la pre-alarma baja tensin

8863

PM

Bit 5; ON = activa; OFF = inactiva

VAB

Tensin 1-2

1000

MM

VAN

Tensin 1-N

1003

MM

Escala D - Tensin
Escala D - Tensin

VBC

Tensin 2-3

1001

MM

Escala D - Tensin

VBN

Tensin 2-N

1004

MM

Escala D - Tensin

VCA

Tensin 3-1

1002

MM

Escala D - Tensin

VCN

Tensin 3-N

1005

MM

Escala D - Tensin

VigiAlarm

Estado de la alarma Vigi

8860

PM

Bit 1; ON = activa; OFF = inactiva

VigiPreAlrm

Estado de la pre-alarma Vigi

8864

PM

Bit 1; ON = activa; OFF = inactiva

VLLAvg

Media de tensin de L-L

1006

MM

VLNAvg

Media de tensin de L-N

1007

MM

Escala D - Tensin
Escala D - Tensin

VUnbalAB

Desequilibrio de tensin 1-2

1008

MM

Dcimos

VUnbalAlrm

Estado de la alarma de desequilibrio de


tensin

8859

PM

Bit 7; ON = activa, OFF = inactiva

VUnbalAN

Desequilibrio de tensin 1-N

1011

MM

VUnbalBC

Desequilibrio de tensin 2-3

1009

MM

Dcimos
Dcimos

VUnbalBN

Desequilibrio de tensin 2-N

1012

MM

Dcimos

VUnbalCA

Desequilibrio de tensin 3-1

1010

MM

Dcimos

VUnbalCN

Desequilibrio de tensin 3-N

1013

MM

Dcimos

VUnbalLLW

Peor desequilibrio de tensin L-L

1014

MM

Dcimos

VUnbalLNW

Peor desequilibrio de tensin L-N

1015

MM

Dcimos

VUnbalPreAlrm

Estado de la pre-alarma de desequilibrio de


tensin

8863

PM

Bit 7; ON = activa, OFF = inactiva

1Para las entradas de registro que no estn en la lista e informacin del factor de escala, consulte el boletn 0613IB1201, Sistema de comunicaciones Modbus.
2Formato de fecha/hora de 3 registros: registro 1: mes (byte 1) = 112; da (byte 2) = 131; registro 2: ao (byte 1) = 0199 (agregue 1900 para determinar el

ao actual); hora (byte 2) = 023; registro 3: minutos (byte 1) = 059; segundos (byte 2) = 059
Nota: Bits 14 y 15 del registro de mes/da debern enmascararse.
3
Formato del factor de potencia: 1 a 999 para los factores de potencia de retraso, 1000 para el factor de potencia de la unidad 1.000 y 1 a 999 para el factor de
potencia de avance.
4Formato del mdulo 10,000: registro secuencial de 1 a 4. Cada registro es un mdulo 10,000 (gama = 9,999 a +9,999).
El resultado es [R4*10,000^3 + R3*10,000^2 + R2*10,000^1] + R1. La gama es de cero a 9,999,999,999,999,999.

90-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice DArquitectura de la tensin de alimentacin de la unidad de disparo

APNDICE DArquitectura de la tensin de alimentacin de la unidad


de disparo

La unidad de disparo viene equipada con una


fuente de tensin de alimentacin interna de
tres fases que aparece al sistema como una
carga de tres fases configurada en tringulo
(figura 101). Esta fuente de alimentacin es en
realidad una carga de tres fases e inyectar
tensin a una fase abierta (figura 102). El
impacto de una carga de tres fases configurada
en tringulo sobre las funciones de proteccin
basadas en la tensin es el siguiente:

La funcin de proteccin de (baja) tensin


mnima se base en la medicin de tensin de
fase a fase.

Si se ajusta la proteccin de baja tensin (Umn) por debajo del 80% o el


desequilibrio de tensin (Udeseq.) por encima del 20% es posible que no
funcione correctamente la unidad de disparo.
El incumplimiento de esta instruccin puede causar dao al equipo.

Figura 101: Fuente de alimentacin interna de tres fases, incorporada


U1
Fuente de
alimentacin
de 3 fases
incorporada

U2
U3

Cadena de
medicin
VN

Figura 102: Fase abierta en la fuente de alimentacin de tres fases


06134077

En la configuracin 1 (figura 103), 2 (figura 104)


o 3 (figura 105), si un fusible se abre la unidad
de disparo inyectar tensin en la fase abierta.
Por lo tanto, la unidad de disparo medir
exactamente la tensin que se inyecta en la
fase abierta. La medicin de la tensin de fase a
fase (VLL) ser mayor que la de la fase abierta
en cero volts. La unidad de disparo tambin
medir exactamente la tensin de fase a neutro
(VLN) inyectada en la fase abierta y mostrar un
valor mayor que cero.

Fusible

En la configuracin de circuitos 4 (figura 106), la


unidad de disparo tiene una trayectoria de
retorno a travs del transformador y la tensin
inyectada en la fase abierta ser cero. En esta
configuracin, la unidad de disparo medir
exactamente cero volts en VLN.

Fusible

U1
Fuente de
alimentacin
de 3 fases
incorporada

U2
U3

Cadena de
medicin
VN

Figura 103: Configuracin de circuitos 1


06134062

Para asegurar que el sistema de disparo


Micrologic funcione como se espera,
independientemente de la configuracin del
sistema, el usuario deber limitar la gama de
activacin de baja tensin entre el 80% y 100%
de tensin nominal del sistema, fase a fase.

Fusible

Abierto
Fusible
Fusible

Motor

Fusible
Contactor

20002012 Schneider Electric Reservados todos los derechos

91-ES

ESPAOL

PELIGRO DE DAO AL EQUIPO

06134076

Proteccin de tensin mnima

AVISO

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice DArquitectura de la tensin de alimentacin de la unidad de disparo

La funcin de proteccin de desequilibrio de


tensin se base en la medicin de tensin de
fase a fase.

Figura 104: Configuracin de circuitos 2


Abierto
06134064

Proteccin de desequilibrio de
tensin

Motor
Contactor
Fusible
Fusible
Fusible

06134165

Figura 105: Configuracin de circuitos 3

En la configuracin de circuitos 4 (figura 106), la


unidad de disparo tiene una trayectoria de
retorno a travs del transformador y la tensin
inyectada en la fase abierta ser cero. En esta
configuracin, la unidad de disparo medir
exactamente cero volts en VLN.

Carga

Fusible

Fusible

Fusible

Para asegurar que el sistema de disparo


Micrologic funcione como se espera,
independientemente de la configuracin del
sistema, el usuario deber limitar los ajustes de
proteccin de desequilibrio de la tensin entre el
0 y 20%.

Dispositivos de
medicin del
sistema y rels de
protec. adicionales

Prdida de fases mltiples


No utilice la proteccin de tensin mnima ni la
proteccin de desequilibrio de la tensin para
determinar la prdida de fases mltiples.

La fuente de alimentacin de tensin interna


requiere tensin de dos fases para su
funcionamiento. (la fuente de alimentacin
de tensin tiene una gama de
funcionamiento entre 100 V~(ca) y 690
V~(ca)].
En las configuraciones de circuitos 1 (figura
103), 2 (figura 104) y 3 (figura 105), cuando
se pierden fases mltiples, la unidad de
disparo medir la tensin del sistema de la
fase restante en todas las tres fases. Por
ejemplo, si se pierden dos fases en un
sistema en delta de tres fases y 480 V~ (ca),
la unidad de disparo medir VLL en las tres
fases.

92-ES

Figura 106: Configuracin de circuitos 4


Abierto
06134063

ESPAOL

En la configuracin 1 (figura 103), 2 (figura 104)


o 3 (figura 105), si un fusible se abre la unidad
de disparo inyectar tensin en la fase abierta.
Por lo tanto, la unidad de disparo medir
exactamente la tensin que se inyecta en la
fase abierta.
La medicin de la tensin de fase a fase (VLL)
ser mayor que la de la fase abierta en cero
volts. La unidad de disparo tambin medir
exactamente la tensin de fase a neutro (VLN)
inyectada en la fase abierta y mostrar un valor
mayor que cero.

48049-137-05
Rev. 01, 07/2012

Fusible
Motor
Fusible

Contactor

Fusible

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice EAjustes de la unidad de disparo

APNDICE EAjustes de la unidad de disparo

Anote los valores de ajustes en las tablas.

Tabla 17:

AjustesSelectores

Descripcin

Smbolo

Ajuste

Activacin de tiempo
Ir
largo
tr

ESPAOL

Retardo de tiempo
largo

Activacin de tiempo
Isd
corto
Retardo de tiempo
corto

tsd

Activacin de falla a
tierra

Ig

Retardo de falla a
tierra

tg

Tabla 18:

AjustesMen de servicio de mantenimiento

Submen

Descripcin

Contactos M2C/M6C Tipo de alarma


Configurar

Elemento de lnea

Ajuste de la unidad
de disparo

S#
S#

Configurar Micrologic Idioma


Fecha/hora
Seleccin interruptor Norma
interruptor
tipo
Nmero de interruptor
Signo de potencia
Transfo. de tensin

Primario
Secundario

Frecuencia de red
Configurar medidas

Tipo de sistema
Clculo I media
Clculo P media

Duracin
Tipo ventana
Duracin

Convencin de
signos
Configurar Com.

Parmetros com.
Regulacin a
distancia
Mando a distancia

20002012 Schneider Electric Reservados todos los derechos

93-ES

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice EAjustes de la unidad de disparo

Tabla 19:

48049-137-05
Rev. 01, 07/2012

AjustesMen de proteccin

Submen

Descripcin

Smbolo

Activacin de tiempo largo

Ir

Retardo de tiempo largo

tr

Activacin de tiempo corto

Isd

Retardo de tiempo corto

tsd

Instantneo

Ii

Activacin de tiempo largo Idmtl

Idmtl Ir

Retardo de tiempo largo Idmtl

Idmtl tr

Elemento de lnea

Trip Unit Setting

Modo Idmtl

ESPAOL

Activacin de tiempo corto Idmtl

Idmtl Isd

Retardo de tiempo corto Idmtl

Idmtl tsd

Idmtl instantnea

Idmtl Ii
Modo

Falla de tierra (unidad de disparo


I
6.0P)

Activacin
Retardo de activacin

Corriente neutra

Ineutro
Modo
Activacin

Alarma de falla a tierra

alarma

Retardo de activacin
Desactivacin
Retardo de desactivacin
Modo
% de activacin

Proteccin de corriente

Desequilibrio de corriente

Ideseq.

Retardo de activacin
% de desactivacin
Retardo de desactivacin
Modo
Activacin

Demanda de corriente mx. en la


I1mx
fase 1

Retardo de activacin
Desactivacin
Retardo de desactivacin
Modo
Activacin

Demanda de corriente mx. en la


I2mx
fase 2

Retardo de activacin
Desactivacin
Retardo de desactivacin
Modo
Activacin

Demanda de corriente mx. en la


I3mx
fase 3

Retardo de activacin
Desactivacin
Retardo de desactivacin
Modo
Activacin

Demanda de corriente mx. en el


Inmx
neutro

Retardo de activacin
Desactivacin
Retardo de desactivacin
Tabla contina en la siguiente pgina

94-ES

20002012 Schneider Electric Reservados todos los derechos

48049-137-05
Rev. 01, 07/2012

Tabla 19:

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Apndice EAjustes de la unidad de disparo

AjustesMen de proteccin (continuacin)

Submen

Descripcin

Smbolo

Elemento de lnea

Trip Unit Setting

Activacin
Tensin (baja) mnima

Umn

Retardo de activacin
Desactivacin
Retardo de desactivacin
Activacin

Proteccin de tensin

Tensin (sobre) mxima

Umx

Retardo de activacin
Desactivacin
Retardo de desactivacin

Desequilibrio de tensin

Udeseq.

ESPAOL

Activacin
Retardo de activacin
Desactivacin
Retardo de desactivacin
Activacin
Potencia inversa

rP

Retardo de activacin
Desactivacin
Retardo de desactivacin
Activacin

Frecuencia (baja) mnima

Fmx

Otras protecciones

Retardo de activacin
Desactivacin
Retardo de desactivacin
Activacin

Frecuencia (sobre) mxima

Fmn

Retardo de activacin
Desactivacin
Retardo de desactivacin

Rotacin de fases

Modo
Secuencia
Modo
% de activacin

Desconexin I

Desconexin I

% de retardo de
activacin
% de desactivacin
Retardo de desactivacin
Modo
Activacin

Desconexin P

Desconexin P

Retardo de activacin
Desactivacin
Retardo de desactivacin

20002012 Schneider Electric Reservados todos los derechos

95-ES

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


ndice

ndice

Acceso remoto 43
Activacin
falla a tierra 13
instantnea 13
tiempo corto 12
tiempo largo 10
Ajuste de fecha 36
Ajuste de hora 36
Ajustes de fbrica
selectores 75
Ajustes de la unidad de disparo
proteccin de tiempo largo 10
Ajustes de los selectores de configuracin

32, 4546
Alarma de la corriente mxima 33
Alarmas
descripcin 17
historial 56
Archivos cronolgicos de historial
descripcin 2829
verificacin 55
Arquitectura de la tensin de alimentacin 91

B
Baja corriente. Consulte Proteccin de
corriente mnima
Baja frecuencia. Consulte Proteccin de
frecuencia mnima
Baja tensin. Consulte Proteccin de tensin
mnima
Botn de introduccin de valores 25
Botn de prueba/restablecimiento 23
Botn de restablecimiento 48
Botn del men de servicio de
mantenimiento 25
Botn flecha abajo 25
Botn flecha arriba 25
Botones
introducir valores 25
men de medicin 25
men de proteccin 25
men de servicio de mantenimiento 25
navegacin 25
prueba de falla a tierra 49
prueba/restablecimiento 23

C
Calibrador
descripcin 7, 11
sustitucin 69
Calibrador ajustable Consulte calibrador
Configuracin de idioma 35
Configuracin de la razn del transformador
de tensin 38

D
Demanda de corriente 41
Demanda de potencia 41
Desconexin de carga de la alimentacin
alarma 33
men 31
verificacin 62
Desconexin de carga de la corriente 33, 62
alarma 17
descripcin 20
men 31
verificacin 62
Desequilibrio de corriente
alarma 33
proteccin 19
Desequilibrio de tensin
alarma 33
arquitectura de la tensin 92
proteccin 19
Designacin de proteccin 7
Diagrama de flujo
men de mediciones 72
men de protecciones 74
men de servicio de mantenimiento 73

E
Enchufe de pruebas 48
Enchufe sensor 7
Enclavamiento selectivo de zona
cableado 48
descripcin 21
instalacin 47
puentes 47
Estado
pila 50
unidad de disparo 50

F
Frecuencia
alarma 33
configuracin 39
men 28
verificacin 55
Funcionamiento 51

20002012 Schneider Electric Reservados todos los derechos

Funciones de disparo 7

H
Historial de disparo 55

I
I2t off 12
I2t on 12
Idmtl. Consulte Proteccin de tiempo largo
Ig. Consulte Selector de activacin de
proteccin contra fallas a tierra
Ii. Consulte Proteccin instantnea
Imagen trmica 11
In. Consulte Tamaos de sensor
Indicador de desgaste de los contactos
configuracin del cdigo 37
medidor 37
verificacin 56
Indicadores de disparo
Ig 23
Isd/Ii 23
luces 23
verificacin de estado 50
Informacin sobre el interruptor 37
Inversin de fases
alarma 33
verificacin 61
Ir. Consulte Selector de activacin de tiempo
largo
Isd. Consulte Selector de activacin de la
proteccin de tiempo largo

L
LSIG Consulte Unidad de disparo 6.0P
Luz indicadora
autoproteccin 23
disparo 23
falla a tierra 23
proteccin avanzada 23
sobrecarga 22
Luz indicadora de disparo por
sobrecalentamiento 23

M
Mando a distancia 44
Medicin
gama 78
precisin 78
Men de configuracin de comunicaciones

29
Men de configuracin de mediciones
configuracin 39
descripcin 29
Men de configuracin de Micrologic
configuracin 35
descripcin 29
Men de mediciones
botn 25

96-ES

ESPAOL

Contactos de alarma. Consulte Contactos


programables M2C/M6C
Contactos programables M2C/M6C
configuracin 32
descripcin del accesorio 21
men 29
Contador de maniobras
descripcin 22
men 56
Convencin de signos 42
Cubierta de los selectores
ilustracin 7
ranura de apertura 44

descripcin 26
diagrama de flujo 72
verificacin 51
Men de otro tipo de proteccin 31
Men de proteccin
botn 25
descripcin 30
verificacin 57
Men de proteccin de la tensin 30
Men de protecciones
diagrama de flujo 74
Men de servicio de mantenimiento
configuracin 32
descripcin 28
diagrama de flujo 73
Mens
archivos cronolgicos de historial 2829
configuracin de comunicaciones 29
configuracin de mediciones 29
configuracin de Micrologic 29
contactos programables M2C/M6C 29
contador de maniobras 56
de red 55
desconexin de carga de la alimentacin

31, 62
desconexin de carga de la corriente 31,

62
desgaste de contactos 56
historial de alarmas 56
historial de disparo 55
medicin 26
niveles de corriente 27, 51
niveles de energa 28, 54
niveles de potencia 27, 53
niveles de tensin 27, 52
otro tipo de proteccin 31, 61
proteccin 30
proteccin de corriente 30, 57
proteccin de tensin 30, 60
servicio de mantenimiento 28
Mdulo de comunicacin 7, 43

N
Niveles de activacin, ajuste 44, 47
Niveles de corriente
men 27
verificacin 51
visualizacin 24
Niveles de energa
men 28
verificacin 54
Niveles de potencia
men 27
verificacin 53
Niveles de tensin
men 27
verificacin 52
Nombre del producto 7

O
Otro tipo de proteccin
descripcin 14
verificacin 61

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


ndice

P
Prdida de fases mltiples 92
Pila
sustitucin 70
verificacin de estado 50
Proteccin
alarmas 17
avanzada 14
corriente 57
corriente mxima neutra 18
demanda de corriente mnima 18
desconexin de carga 20
desconexin de carga de la alimentacin

31
desconexin de carga de la corriente 31
desequilibrio de corriente 19
desequilibrio de tensin 19
falla a tierra 13
frecuencia mxima 19
frecuencia mnima 19
instantnea 13
neutra 16
otro tipo 61
potencia inversa 19
rotacin de fases 20
tensin 60
tensin mxima 18
tensin mnima 18
tiempo corto 12
tiempo largo 10
Proteccin avanzada
descripcin 14
verificacin de valores 51
Proteccin contra fallas a tierra
alarma 33
descripcin 13
funcin de prueba 49
selector de activacin 13
selector de retardo 13
Proteccin contra fallas a tierra del equipo 49
Proteccin de corriente 30
verificacin 57
Proteccin de demanda de corriente mxima

18
Proteccin de demanda de corriente mnima

18
Proteccin de frecuencia mxima 19
Proteccin de frecuencia mnima 19
Proteccin de la potencia inversa
alarma 33
Proteccin de potencia inversa
descripcin 19
Proteccin de rotacin de fases 20
Proteccin de tensin
alarma 33
verificacin 60
Proteccin de tensin mxima 18
Proteccin de tensin mnima 18
Proteccin de tiempo corto
alarma 33
descripcin 12
selector de activacin 12
selector de retardo 12
Proteccin de tiempo largo

20002012 Schneider Electric Reservados todos los derechos

alarma 33
descripcin 10
retardo I2t 10
retardo Idmtl
selector de activacin 10
selector de retardo 10
Proteccin instantnea
descripcin 13
selector de activacin 13
Proteccin neutra 16
Pruebas
equipo 48
funcin de disparo por falla a tierra 49
inyeccin primaria 22
inyeccin secundaria 22
unidad de disparo 22
Pruebas de inyeccin primaria 22
Pruebas de inyeccin secundaria 22

R
Razn del transformador de tensin 38
Repuesto
unidad de disparo 63
Restablecimiento de la unidad de disparo 48
Retardo
falla a tierra 13
tiempo corto 12
tiempo largo 10
rPmx Consulte Proteccin de potencia
inversa

S
Selectores
activacin de falla a tierra 13
activacin de tiempo corto 12
activacin de tiempo largo 10
activacin instantnea 13
ajuste 44
retardo de falla a tierra 13
retardo de tiempo corto 12
retardo de tiempo largo 10
Selectores ajustables. Consulte Selectores
Sentido de potencia
configuracin de la convencin de signos
de la potencia reactiva 42
configuracin de la direccin del signo de
potencia 38
Sobrecorriente Consulte Proteccin de
corriente mxima
Sobrefrecuencia Consulte Proteccin de
frecuencia mxima
Sobretensin. Consulte Proteccin de
tensin mxima
Sustitucin
calibrador 69
pila 70

T
Tipo de red 40
Tr. Consulte Selector de retardo de la
proteccin de tiempo largo
Tsd. Consulte Selector de retardo de la
proteccin de tiempo corto

97-ES

ESPAOL

48049-137-05
Rev. 01, 07/2012

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


ndice

48049-137-05
Rev. 01, 07/2012

U
Unidad de disparo
5.0P 8
6.0P 9
ajustes
cdigo de desgaste de los contactos

37

ESPAOL

familia de interruptores 37
fecha 36
frecuencia 39
hora 36
idioma 35
normas 37
proteccin contra fallas a tierra 13
proteccin de tiempo corto 12
proteccin de tiempo largo 10
proteccin instantnea 13
tablas de registro 93
tipo de interruptor 37
arquitectura de la tensin de
alimentacin 91
configuracin 35
designacin de serie 7
historial 55
pruebas 22
repuesto 63
restablecimiento 48
verificacin de estado 50
verificacin del funcionamiento 48

V
Valores de com. de Modbus 43
Valores de lectura remota 79
Verificacin del funcionamiento de la unidad
de disparo 48
Visualizacin de grficos
diagrama de flujo 72
mens 26
navegacin 25
pantalla 24

Z
ZSI. Consulte Enclavamiento selectivo de
zona

98-ES

20002012 Schneider Electric Reservados todos los derechos

ESPAOL

Unidades de disparo electrnico Micrologic 5.0P y 6.0P


Boletn de instrucciones

ESPAOL
Solamente el personal especializado deber instalar, hacer funcionar y prestar servicios de
mantenimiento al equipo elctrico. Schneider Electric no asume responsabilidad alguna por las
consecuencias emergentes de la utilizacin de este material.
Importado en Mxico por:

Schneider Electric
Calz. J. Rojo Gmez 1121-A
Col. Gpe. del Moral 09300 Mxico, D.F.
Tel. 55-5804-5000
www.schneider-electric.com.mx

Square D, Schneider Electric, Micrologic y Masterpact son marcas comerciales o marcas


registradas de Schneider Electric. Cualquier otra marca comercial utilizada en este documento
pertenece a sus respectivos propietarios.
48049-137-05 Rev. 01, 07/2012
Reemplaza 48049-137-05 07/2008
20002012 Schneider Electric Reservados todos los derechos

Dclencheurs lectroniques MicrologicMC 5.0P et


6.0P
v PLogic-2002-AA et ultrieures

Directives d'utilisation
48049-137-05
Rev. 01, 07/2012

FRANAIS

conserver pour usage ultrieur.

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P

Catgories de dangers et
symboles spciaux

48049-137-05
Rev. 01, 07/2012

Lisez soigneusement ces directives et examinez lappareillage afin de vous


familiariser avec lui avant son installation, son fonctionnement ou son
entretien. Les messages spciaux qui suivent peuvent apparatre dans ce
document ou sur lappareillage. Ils vous avertissent de dangers potentiels
ou attirent votre attention sur des renseignements pouvant claircir ou
simplifier une procdure.
Lajout de lun ou lautre des symboles une tiquette de scurit Danger
ou Avertissement vous indique quun danger lectrique existe et quil
pourra y avoir des blessures corporelles si les directives ne sont pas suivies.

ANSI

Ceci est le symbole dune alerte de scurit. Il sert vous avertir dun
danger potentiel de blessures corporelles. Respectez toutes les consignes
de scurit accompagnant ce symbole pour viter toute situation potentielle
de blessure ou de mort.

DANGER
IEC

DANGER indique une situation de danger qui, si elle nest pas vite,
entranera la mort ou des blessures graves.

AVERTISSEMENT
FRANAIS

AVERTISSEMENT indique une situation de danger qui, si elle nest pas


vite, peut entraner la mort ou des blessures graves.

ATTENTION
ATTENTION indique une situation de danger qui, si elle nest pas vite,
peut entraner des blessures mineures ou modres.

AVIS
AVIS est utilis pour commenter des pratiques sans rapport avec les
blessures physiques. Le symbole d'alerte de scurit n'est pas employ
avec ce mot de signalement.
REMARQUE : Fournit des renseignements complmentaires pour clarifier
ou simplifier une procdure.

Veuillez noter

Seul un personnel qualifi doit effectuer linstallation, lutilisation, lentretien


et la maintenance du matriel lectrique. Schneider Electric nassume
aucune responsabilit des consquences ventuelles dcoulant de
lutilisation de cette documentation.

Avis FCC

Cet appareil a subi des essais et a t reconnu conforme aux limites


des appareils numriques de classe A, selon le paragraphe 15 de la
rglementation FCC (Commission fdrale des communications des .-U.).
Ces limites sont conues pour fournir une protection raisonnable contre les
interfrences nuisibles lorsquun appareil est employ dans un milieu
commercial. Cet appareil produit, utilise et peut rayonner de lnergie
radiofrquence et, sil nest pas install ou utilis conformment au mode
demploi, il peut provoquer des interfrences nuisibles aux communications
radio. Le fonctionnement de cet appareil dans une zone rsidentielle est
susceptible de provoquer des interfrences nuisibles, auquel cas
lutilisateur devra corriger les interfrences ses propres frais. Cet appareil
numrique de la classe A est conforme la norme NMB-003 du Canada.

2-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Table des matires

SECTION 1:

GNRALITS

...................................................................................................................... 7
Introduction ................................................................................................. 7
Communications ......................................................................................... 7
Rglages de la puissance et des contrles ................................................ 7
Rglages des commutateurs ...................................................................... 7
Dclencheur Micrologic 5.0P ................................................................. 8
Dclencheur Micrologic 6.0P ................................................................. 9
Protection LSIG ......................................................................................... 10
Protection de longue dure ................................................................. 10
Protection de courte dure .................................................................. 12
Protection instantane ......................................................................... 13
Protection des appareils contre les dfauts la terre ......................... 14
Configuration du dclencheur Micrologic .................................................. 15
Alimentation de contrle ...................................................................... 15
Alimentation externe ............................................................................ 16
Configuration du dclencheur Micrologic .................................................. 16
Protection volue .................................................................................... 17
Protection du neutre ............................................................................ 17
Alarmes ............................................................................................... 18
Valeurs minimales et maximales de la protection de courant moyen (demande) et de la protection de tension ................................................. 19
Protection contre le dsquilibre de courant ou de tension ................ 20
Protection contre l'inversion de puissance (rPmax) ............................ 20
Protection de frquence minimale (sous) et maximale (sur) ............... 20
Dlestage de charge (Dlestage relestage) ........................................ 21
Protection du sens de rotation des phases ......................................... 21
Kits de contacts programmables M2C/M6C ............................................. 22
Interverrouillage slectif de zone .............................................................. 22
Mesure ...................................................................................................... 23
Essai du dclencheur ................................................................................ 23
Compteur de manuvres ......................................................................... 23
Voyants ..................................................................................................... 23
Voyant de surcharge ........................................................................... 23
Voyants de dclenchement ................................................................. 24
Bouton dessai/de remise zro ............................................................... 24
cran daffichage graphique ..................................................................... 25
Voyant dusure des contacts ..................................................................... 25

SECTION 2:

NAVIGATION SUR L'AFFICHEUR GRAPHIQUE ............................................................................................. 26


Afficheur graphique ................................................................................... 26
Graphique barres et menus ................................................................... 27
Menu Mesures ..................................................................................... 27
Menu Entretien .................................................................................... 29
Menu Protections ................................................................................ 31

SECTION 3:

CONFIGURATION DU DCLENCHEUR ........................................................................................................... 33


Configuration des paramtres du dclencheur ......................................... 33
Contacts programmables M2C/M6C ................................................... 33
Configuration du dclencheur Micrologic ............................................ 36
Configuration des mesures ................................................................. 40
Configuration du module de communication ....................................... 44
Affinement des rglages des commutateurs ............................................. 45
Exemples .................................................................................................. 47
Dclencheur Micrologic 5.0P ............................................................... 47
Dclencheur Micrologic 6.0P ............................................................... 47
Interverrouillage slectif de zone (ZSI) ..................................................... 48
Vrification du fonctionnement du dclencheur ........................................ 49

20002012 Schneider Electric Tous droits rservs

3-FR

FRANAIS

48049-137-05
Rev. 01, 07/2012

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Table des matires

48049-137-05
Rev. 01, 07/2012

Rarmement du dclencheur .................................................................... 49


Vrification de la fonction de dclenchement de l'appareil sur dfaut la terre
................................................................................................................... 50
Vrification de ltat du dclencheur ......................................................... 51
SECTION 4:

FONCTIONNEMENT

.................................................................................................................... 52

FRANAIS

Valeurs mesures ..................................................................................... 52


Niveaux des courants .......................................................................... 52
Niveaux des tensions .......................................................................... 53
Niveaux des puissances ...................................................................... 54
Niveaux des nergies .......................................................................... 55
Frquence ........................................................................................... 56
Historique du dclencheur ........................................................................ 56
Historiques dfauts .............................................................................. 56
Historiques des alarmes ...................................................................... 57
Compteur de manuvres .................................................................... 57
Usure des contacts .............................................................................. 57
Configuration des protections ................................................................... 58
Protections en courant ......................................................................... 58
Protections en tension ......................................................................... 61
Autres protections ................................................................................ 62
Dlestage de charge en courant ......................................................... 63
Dlestage de charge en puissance ..................................................... 63
SECTION 5:

REMPLACEMENT DU DCLENCHEUR ........................................................................................................... 64


Outils ncessaires ..................................................................................... 64
Prparation ................................................................................................ 64
Noter les rglages des commutateurs ................................................. 64
Dconnexion du disjoncteur ................................................................ 64
Retrait du couvercle des accessoires du disjoncteur .......................... 65
Retrait de la fiche de valeur nominale. ................................................ 65
Retrait du dclencheur ........................................................................ 65
Remplacement du dclencheur ................................................................ 65
Installation de la pile ............................................................................ 65
Installation du dclencheur .................................................................. 66
Remise en place du couvercle des accessoires du disjoncteur ................ 67
Vrification de linstallation du dclencheur .............................................. 68
Essai d'injection secondaire ................................................................ 68
Essai d'injection primaire ..................................................................... 68
Vrification du fonctionnement des accessoires ................................. 68
Configuration du dclencheur ................................................................... 68
Reconnexion du disjoncteur ...................................................................... 68

SECTION 6:

REMPLACEMENT DE LA FICHE DE LA VALEUR NOMINALE RGLABLE .................................................. 69


Retrait de la fiche de la valeur nominale ................................................... 69
Installation de la nouvelle fiche de la valeur nominale rglable ................ 69

SECTION 7:

REMPLACEMENT DE LA PILE

.................................................................................................................... 70
Dconnexion du disjoncteur ...................................................................... 70
Dplacement du module de tenue ............................................................ 70
Remplacement de la pile ........................................................................... 70
Remise en place du module de tenue ....................................................... 71
Remise en place du couvercle des accessoires ....................................... 71
Reconnexion du disjoncteur ...................................................................... 71

ANNEXE A:

ORGANIGRAMMES DES AFFICHAGES GRAPHIQUES ................................................................................. 72


Organigramme du menu mesures ............................................................ 72

4-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Table des matires

48049-137-05
Rev. 01, 07/2012

Organigramme du menu entretien ............................................................ 73


Organigramme du menu Protections ........................................................ 74
ANNEXE B:

RGLAGES PAR DFAUT ET TOLRANCES ................................................................................................ 75


Rglages par dfaut .................................................................................. 75
Gamme des mesures et prcision ............................................................ 78

ANNEXE C:

ACCS RSEAU/COMMUNICATION ............................................................................................................... 79


Valeurs lisibles distance ......................................................................... 79
Liste des registres ..................................................................................... 82

ANNEXE D:

ARCHITECTURE DE L'ALIMENTATION EN TENSION DU DCLENCHEUR ................................................ 91


Protection en tension minimale ................................................................. 91
Protection en dsquilibre de tension ....................................................... 92
Perte de plusieurs phases ........................................................................ 92

ANNEXE E:

RGLAGES DU DCLENCHEUR .................................................................................................................... 93


.................................................................................................................... 96

FRANAIS

Index :

20002012 Schneider Electric Tous droits rservs

5-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Table des matires

48049-137-05
Rev. 01, 07/2012

FRANAIS
6-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Section 1Gnralits

Type de protection
2Protection de base IEC (LSO)
3Protection de base UL (LI)
5Protection slective (LSI)
6Protection slective plus protection des
appareils contre les dfauts la terre (LSIG)

A
B

ANom du produit
BVoyants de dclenchement
CLogement de la pile
DCommutateurs rglables
ECouvercle des commutateurs
FLanguette de scellement
GFiche de la valeur nominale rglable
HBouton de remise zro des voyants
de vrification de l'tat de la pile et de
dclenchement
IBornier pour raccordement externe

H
0P

5.
logic
Micro

C
F

G
alarm

time
long

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

Srie du dclencheur
0Indique la premire version
Type de mesure
AucuneNe fournit que la protection
AFournit la protection plus les mesures de courant
PFournit la protection plus les mesures de puissance
HFournit la protection plus les mesures
dharmoniques

Dclencheur Micrologic

tr

(s) 4

2
1
.5

8 12
16
20
24
Ir
at 6

FRANAIS

Les dclencheurs MicrologicMC offrent des


fonctions de dclenchement rglables pour les
disjoncteurs dclenchement lectronique. Le
nom du produit (A) spcifie le niveau de
protection fourni par le dclencheur.
Micrologic 5.0P

Figure 1 :

06134748

Introduction

Les dclencheurs Micrologic sont remplaables


sur place, pour permettre lamlioration des
perfomances du dclencheur. Pour obtenir tous
les renseignements sur les modles de
disjoncteurs, les capacits de chssis, les
valeurs nominales d'interruption, les fiches de
capteurs, les fiches de la valeur nominale et les
dclencheurs disponibles, consulter le
catalogue de produits.

Communications

Les dclencheurs Micrologic peuvent communiquer avec d'autres


dispositifs par l'intermdiaire du protocole ModbusMC grce un module
de communication du disjoncteur (BCM). Pour plus de renseignements sur
le module de communication, voir le catalogue de produits et le bulletin de
d'information, 0613IB1201, du systme de communication ModbusMC.

Rglages de la puissance et des


contrles

l'aide de l'cran d'affichage graphique et du clavier du dclencheur, il est


possible de dfinir des options pour le dclencheur ou de vrifier les
mesures du systme. Se reporter la section 2 Navigation sur l'afficheur
graphique pour de plus amples renseignements. Les mesures du systme
peuvent tre galement vrifies avec le logiciel System Manager Software
(SMS), version 3.2 ou ultrieures, ou tout autre logiciel de gestion de
systmes en rseau.

Rglages des commutateurs

Sur la face avant du dclencheur, il y a des commutateurs rglables permettant


de modifier les caractristiques de dclenchement LSI ou LSIG du
dclencheur. Les dclencheurs sont expdis avec le commutateur
d'enclenchement de longue dure rgl 1.0 et tous les autres commutateurs
leurs rglages les plus bas. Tous les rglages de protection volue sont
dsactivs (off).

20002012 Schneider Electric Tous droits rservs

7-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Des ajustements mticuleux des commutateurs peuvent tre effectus


laide des touches de navigation, voir page 46.

Dclencheur Micrologic 5.0P

Le dclencheur Micrologic 5.0P fournit une protection slective (LSI) et la


mesure de la puissance.

A. cran d'affichage graphique

Figure 2 :

Dclencheur Micrologic 5.0P

B. Touche d'accs au menu protection*

R Q
06134749

C. Touche d'accs au menu d'entretien*


D. Touche d'accs au menu de mesure*
E. Touche de dfilement vers le bas
F. Touche de dfilement vers le haut

Micrologic 5.0 P

4260A

G. Touche d'entre des donnes (validation ou


slection)

N 1 2 3
100

H. Commutateur d'enclenchement de longue


dure (Ir)

I.

Commutateur de retard de longue dure (tr)

J. Commutateur d'enclenchement de courte


dure (Isd)

FRANAIS

M. Prise d'essai
N. Voyant de surcharge d'enclenchement de
longue dure
O. Bouton dextinction des voyants de
vrification de l'tat de la pile et de
dclenchement

tr

C
D

K. Commutateur de retard de courte dure (tsd)


L. Commutateur d'enclenchement instantan
(Ii)

Ir

06134751

50

Isd
tsd

Ii

F
H

G
I
J

.7
.6
.5
.4

.8

x In

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

Ir

Isd

Ii

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
8
2
1.5
10
x Ir
setting

K
L

long time

Ir

tsd
(s)

Ii

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

4
3

6 8 10
12
15
off
2
x In

delay

P. Voyant d'auto-protection et de protection


volue
Q. Voyant de dclenchement court retard ou
instantan
R. Voyant de dclenchement long retard

*La touche inorpore une DL indiquant le menu actif.

8-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Dclencheur Micrologic 6.0P

Le dclencheur Micrologic 6.0P fournit une protection slective et une


protection d'appareils contre les dfauts la terre (d 1 200 A) (LSIG) et la
mesure de la puissance.

A. cran d'affichage graphique

Figure 3 :

Dclencheur Micrologic 6.0P

B. Touche d'accs au menu protection*

V U T S
06134750

C. Touche d'accs au menu d'entretien*


E. Touche de dfilement vers le bas
F. Touche de dfilement vers le haut

4260A
100

Isd

Ii

C
t
06134752

D
E
F

M. Commutateur d'enclenchement de
protection contre les dfauts la terre (Ig)

G
I

K
M

I2t on
Ir
.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

tg

Ig

tsd

. 4 .4 .3
.2
.3
.1
.2
.1 2 0

on

I t

off

delay

F
G
H

4
3

6 8 10
12
15
off
2
x In
test

tg

Ii

(s)

setting

I2t off

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

D
C
B
A

Ig

@ 6 Ir

long time

.4 .4 . 3
.2
.3
.1
.2
.1 2 0

Ig

(s)

on

I t

off

ground fault

Q. Voyant de surcharge d'enclenchement de


longue dure
R. Bouton dextiction des voyants de
vrification de l'tat de la pile et de
dclenchement
S. Voyant d'auto-protection et de protection
volue
T. Voyant de dclenchement sur dfaut la
terre
U. Voyant de dclenchement court retard ou
instantan
V. Voyant de dclenchement long retard

*La touche incorpore une DL indiquant le menu actif.

20002012 Schneider Electric Tous droits rservs

9-FR

FRANAIS

L. Commutateur d'enclenchement instantan


(Ii)

P. Bouton pousser-pour-dclencher de dfaut


la terre

Ir

50

K. Commutateur de retard de courte dure (tsd)

O. Prise d'essai

Ii
0

Commutateur de retard de longue dure (tr)

N. Commutateur de retard de protection contre


les dfauts la terre (tg)

Isd
tsd

N 1 2 3

H. Commutateur d'enclenchement de longue


dure (Ir)
J. Commutateur d'enclenchement de courte
dure (Isd)

Ir
tr

G. Touche d'entre des donnes (validation ou


slection)

I.

Micrologic 6.0 P

06134751

D. Touche d'accs au menu de mesure*

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Protection LSIG
Protection de longue dure
La protection de longue dure protge les
appareils contre les surcharges.

REMARQUE : Les dclencheurs Micrologic sont aliments par le circuit de


faon toujours offrir une protection contre les dfauts. Toutes les autres
fonctions (affichage, mesurage, communications, etc.) exigent une
alimentation externe. Voir la 16 pour des informations supplmentaires.

Figure 4 :

FRANAIS

Dclencheur Micrologic 6.0P

06134754

L'enclenchement de longue dure (Ir) (A)


dfini le niveau maximum de courant (en
fonction de la valeur nominale de la prise
du capteur In) que le disjoncteur porte
continuellement. Si le courant dpasse
cette valeur, le disjoncteur se dclenche
aprs la temporisation prdfinie. La
valeur de l'enclenchement de longue
dure (Ir) est rglable entre 0,4 1,0
fois la valeur nominale de la prise du
capteur (In) (D).

Commutateurs de protection de longue dure

Dclencheur Micrologic 5.0P

06134753

La protection de longue dure est une


fonction standard sur tous les
dclencheurs.

long time

Ir
.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

setting

Ir
.7
.6
.5
.4

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

tsd
(s)

Ii

.4 .4 .3

.3
.2
.1
on

.2
.1

4
3

0
2
I t off

long time
alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

6 8 10
12
15
off
2
x In

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

on

setting

delay

Ig
D
C
B
A

I t

off

4
3

6 8 10
12
15
off
2
x In

delay

tg
F
G
H
J

Ii

(s)

(s)

test

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

ground fault

In 2000 A

In 2000 A

Le retard de longue dure (tr) (B) dfinit la


dure pendant laquelle le disjoncteur
portera une surintensit en dessous du
niveau de courant d'enclenchement de
courte dure ou instantan avant de se
dclencher. Deux options sont
disponibles :
Courbe de retard de longue dure I2t
standard. Voir le tableau 1 pour les
rglages de retard de longue dure
I2t.
La pente des courbes de retard de
longue dure Idmtl (dcalage inverse
minimum dtermin) varie pour
renfoncer la slectivit.

Tableau 1 : Valeurs du retard de longue dure I2t du


dclencheur Micrologic

Option Description

Courbe

Rglage1

Retard de longue dure en secondes2

DT

Dure dtermine

Constante

tr 1,5 x Ir

12,5

25

50

100

200

300

400

500

600

SIT

Dure inverse standard

I0,5t

tr 6 x Ir

0,5

12

16

20

24

0,343

0,69

1,38

2,7

5,5

8,3

11

13,8

16,6

VIT

Dure inverse forte

It

tr 7,2 x Ir

EIT

Dure inverse extrme

I2t

1Ir

HVF

Compatible avec fusibles


haute tension

I4t

Le voyant de surcharge (C) indique que le


seuil de l'enclenchement de longue dure
Ir a t dpass.

Pour les disjoncteurs MasterpactMC NT et


NW, la valeur du capteur (In) peut tre
change en remplaant la prise de capteur
(D) situe sous le dclencheur. Pour
obtenir des informations supplmentaires,
voir les directives jointes au kit de
remplacement de la prise du capteur.

10-FR

= In x enclenchement de longue dure. In = valeur nominale de la prise du capteur.


Seuil de dclenchement entre 1,05 et 1,20 Ir.
2Prcision de la temporisation +0/-20 %.
3Lorsque tsd est rgl 0,4 dsactiv (off), alors tr = 0,5 au lieu de 0,34.

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

La protection du neutre n'est pas


disponible lorsque la protection Idmtl est
slectionne.

Les slections Idmtl n'utilisent pas la


mme caractristique d'image thermique
que la fonction de protection de longue
dure I2t. La protection de longue dure
de base et la dure inverse forte (EIT)
Idmtl sont toutes les deux courbes I2t,
mais les diffrentes caractristiques des
images thermiques aboutissent des
performances diffrentes du systme.
Pour les applications de soudage, il est
recommand d'utiliser la protection de
longue dure de base I2t afin d'assurer la
performance du systme attendue.

Lenclenchement de longue dure et le


retard de longue dure sont tous les deux
situs sur la fiche de la valeur nominale
rglable et remplaable sur place. Pour
modifier les rglages en vue de cerner
plus prcisment lapplication, des fiches
de diverses valeurs nominales sont
disponibles. Pour les directives de
remplacement de la fiche de la valeur
nominale, voir la section 6
Remplacement de la fiche de la valeur
nominale rglable.
La protection de longue dure utilise une
mesure efficace vraie (RMS).

Limage thermique fournit en permanence


l'tat d'chauffement du cblage, avant et
aprs les dclenchements du dispositif. Cela
permet au disjoncteur de rpondre une
suite de conditions de surcharge qui
pourraient entraner la surchauffe des
conducteurs, mais qui resteraient
indtectables si le circuit de longue dure
tait remis zro chaque retour de la
charge en dessous du rglage de
l'enclenchement ou aprs chaque vnement
de dclenchement.

Tableau 2 : Valeurs du retard de longue dure Idmtl du dclencheur


Micrologic
Option Rglage1 Retard de longue dure en secondes

Tolrance

tr 1,5 x Ir

0,52

12

16

20

24

+0/-20 %

tr 6 x Ir

0,52

12

16

20

24

+0/-20 %

tr 7,2 x Ir

0,52

12

16

16,6

16,6

+0/-20 %

tr 10 x Ir

0,52

12

16

16,6

16,6

+0/-20 %

tr 1,5 x Ir

1,9

3,8

7,6

15,2

30,4

45,5

60,7

75,8

91

+0/-30 %

tr 6 x Ir

0,7

12

16

20

24

+0/-20 %

tr 7,2 x Ir

0,7

0,88

1,77

3,54

7,08

10,6

14,16 17,7

21,2

+0/-20 %

tr 10 x Ir

0,72

0,8

1,43

2,86

5,73

8,59

11,46 14,33 17,19 +0/-20 %

tr 1,5 x Ir

1,9

7,2

14,4

28,8

57,7

86,5

115,4 144,2 173,1 +0/-30 %

tr 6 x Ir

0,7

12

16

20

tr 7,2 x Ir

0,7

0,81

1,63

3,26

6,52

9,8

13,1

16,34 19,61 +0/-20 %

tr 10 x Ir

0,72

0,75

1,14

2,28

4,57

6,86

9,13

11,42 13,70 +0/-20 %

tr 1,5 x Ir

12,5

25

50

100

200

300

400

500

600

+0/-30 %

tr 6 x Ir

0,73

12

16

20

24

+0/-20 %

tr 7,2 x Ir

0,72

0,69

1,38

2,7

5,5

8,3

11

13,8

16,6

+0/-20 %

tr 10 x Ir

0,72

0,73

0,73

1,41

2,82

4,24

5,45

7,06

8,48

+0/-20 %

tr 1,5 x Ir

164,5 329

658

1316 2632 3950 5265 6581 7900 +0/-30 %

tr 6 x Ir

0,73

12

16

20

24

tr 7,2 x Ir

0,72

0,73

1,13

1,42

3,85

5,78

7,71

9,64

11,57 +0/-20 %

tr 10 x Ir

0,72

0,72

0,73

0,73

1,02

1,53

2,04

2,56

3,07

DT

SIT

24

+0/-20 %

VIT

EIT

+0/-20 %

HVF
+0/-20 %

1Ir

= In x enclenchement de longue dure. In = valeur nominale de la prise du capteur. Seuil de


dclenchement entre 1,05 et 1,20 Ir.
2Tolrance = +0/-60 %
3Tolrance = +0/-40 %

REMARQUE : Lors de la vrification des


temps de dclenchement, attendre un
minimum de 15 minutes aprs le
dclenchement du disjoncteur avant de le
rarmer, pour permettre limage thermique
de se remettre compltement zro ou
utiliser une trousse dessais pour inhiber
limage thermique.

20002012 Schneider Electric Tous droits rservs

11-FR

FRANAIS

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

Protection de courte dure

48049-137-05
Rev. 01, 07/2012

Figure 5 :

Commutateurs de protection de courte dure


Dclencheur Micrologic 6.0P

06134753

La protection de courte dure est une


fonction standard sur les dclencheurs 5.0P
et 6.0P.
Lenclenchement de courte dure (Isd) (A)
dfinit le niveau de courant (en dessous du
niveau de dclenchement instantan)
auquel le disjoncteur se dclenchera aprs
la temporisation prdfinie.

long time

Ir
.7
.6
.5
.4

.8

x In

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
setting

long time

Ir
.7
.6
.5
.4

@ 6 Ir

instantaneous

short time

06134754

Dclencheur Micrologic 5.0P

La protection de courte dure protge les


appareils contre les courts-circuits.

tsd
(s)

.3
.2
.1
on

.2
.1
2

I t

0
off

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

Ii

.4 . 4 .3

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

6 8 10
4
12
3
15
off
2
x In

delay

(s)

D
C
B
A

Ii

. 4 .4 .3

.3
.2
.1
on

setting

Ig

tsd

.2
.1
2

I t

0
off

4
3

6 8 10
12
15
off
2
x In

delay

test

tg
F
G
H
J

.4 . 4 . 3
.2
.3
.1
.2
.1 2 0

(s)

on

I t

off

ground fault

In 2000 A

In 2000 A

FRANAIS

Le retard de courte dure (tsd) (B) dfinit la


dure pendant laquelle le disjoncteur portera
une surintensit au-dessus du niveau de
courant d'enclenchement de courte dure
avant de se dclencher.

Tableau 3 : Valeurs du retard de courte dure du dclencheur


Micrologic

Loption I2t activ/I2t dsactiv fournit une


slectivit amliore avec les dispositifs de
protection en aval :

Rglage

Retard de courte dure

I2t dsactiv (ms 10 Ir)


(secondes)

0,1

0,2

0,3

0,4

I2t activ (ms 10 Ir) (secondes)

0,1

0,2

0,3

0,4

tsd (dclenchement min.)


(millisecondes)

20

80

140

230

350

tsd (dclenchement max.)


(millisecondes)

80

140

200

320

500

Avec I2t dsactiv slectionn, une


temporisation fixe est fournie.
I2 t

activ slectionn, une


Avec
protection retard inverse I2t est fournie
jusqu 10 x Ir. Au-dessus de 10 x Ir, une
temporisation fixe est fournie.

Des courants intermittents dans la gamme


des dclenchements court retard qui ne
durent pas suffisamment longtemps pour
provoquer un dclenchement sont
accumuls et raccourcissent le retard de
dclenchement de faon adquate.

Linterverrouillage slectif de zone (ZSI) peut


tre utilis avec la protection de courte dure
pour les disjoncteurs en amont ou en aval.
Le rglage de tsd 0 dsactive
linterverrouillage slectif de zone.

La protection de courte dure utilise la


mesure efficace vraie (RMS).

L'enclenchement et le retard de courte dure


peuvent tre rgls pour fournir la slectivit
avec des disjoncteurs en amont ou en aval.

REMARQUE : Utiliser la fonction I2t dsactiv


avec ZSI pour une bonne coordination.
L'utilisation de la fonction I2t avec ZSI n'est pas
recommande puisque le retard avec lequel le
dispositif en amont recevra un signal d'entrave
peut entraner le dclenchement du dclencheur
en un temps plus court que la courbe de
dclenchement publie.

12-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Protection instantane

Figure 6 :

Commutateurs de protection instantane

long time

Ir
.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

La protection instantane (Ii) (A) est une


fonction standard sur tous les dclencheurs.
La protection instantane est base sur la
valeur nominale de capteur (In) du
disjoncteur.
La commande douverture du disjoncteur est
donne aussitt que le courant de seuil est
dpass.
La protection instantane utilise la mesure
de courant de crte.

Quand le commutateur de protection


instantane est mis hors tension (off), la
protection instantane est dsactive.

setting

.7
.6
.5
.4

instantaneous

tsd
(s)

.3
.2
.1
on

.2
.1
0
2
I t off

x In

@ 6 Ir

instantaneous

short time

Ii

. 4 .4 .3

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

6 8 10
4
12
3
15
off
2
x In

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

delay

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

on

setting

Ig
D
C
B
A

Ii

(s)

I t

off

delay

4
3

6 8 10
12
15
off
2
x In

test

tg
F
G
H
J

.4 .4 .3
.2
.3
.1
.2
.1 2 0

(s)

on

I t

off

ground fault

In 2000 A

In 2000 A

Tableau 4 : Valuers de protection instantane du dclencheur


Micrologic
Rglage

Courant d'interruption

Ii (= In x..)

10

12

15

off

Ii = instantane In = valeur nominale du capteur


Prcision d'enclenchement 10 %

FRANAIS

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

long time

Ir

@ 6 Ir

short time

Dclencheur Micrologic 6.0P


06134754

La protection instantane protge les appareils


contre les courts-circuits sans retard
intentionnel.

06134753

Dclencheur Micrologic 5.0P

20002012 Schneider Electric Tous droits rservs

13-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

Figure 7 :

La protection des appareils contre les dfauts


la terre protge les conducteurs contre la
surchauffe et les dfauts en provenance de
courants de dfaut la terre (d1 200 A).

FRANAIS

Le retard de dfaut la terre (tg) (B) dfinit


la dure pendant laquelle le disjoncteur
portera un courant de dfaut la terre audessus du niveau de courant de dfaut la
terre avant de se dclencher.
Linterverrouillage slectif de zone (ZSI) peut
tre utilis avec la protection contre les
dfauts la terre pour les disjoncteurs en
amont ou en aval. Le rglage du retard de
dfaut la terre (tg) 0 dsactive
linterverrouillage slectif de zone.
La protection du neutre et la protection
dappareil contre les dfauts la terre sont
indpendantes et peuvent fonctionner en
mme temps.

REMARQUE : Utiliser la fonction I2t dsactiv


avec ZSI pour une bonne coordination.
L'utilisation de la fonction I2t avec ZSI n'est pas
recommande puisque le retard avec lequel le
dispositif en amont recevra un signal d'entrave
peut entraner le dclenchement du dclencheur
en un temps plus court que la courbe de
dclenchement publie.

14-FR

long time

Ir
.7
.6
.5
.4

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

La protection des appareils contre les


dfauts la terre est une fonction standard
sur les dclencheurs 6.0P.
Lenclenchement sur dfaut la terre (Ig) (A)
dfinit le niveau de courant de dfaut la
terre auquel le disjoncteur se dclenche
aprs la temporisation prdfinie.

Commutateurs de protection contre les dfauts la terre

Dclencheur Micrologic 6.0P


06134754

Protection des appareils contre les


dfauts la terre

48049-137-05
Rev. 01, 07/2012

tsd
(s)

.3
.2
.1
on

setting

Ig
D
C
B
A

A
B

Ii

.4 .4 . 3
.2
.1
2

I t

0
off

4
3

6 8 10
12
15
off
2
x In

delay

test

tg
F
G
H
J

.4 .4 .3
.2
.3
.1
.2
.1 2 0

(s)

on

I t

off

ground fault

In 2000 A

Tableau 5 : Valeurs denclenchement sur dfaut la terre du


dclencheur Micrologic
Ig (= In x....)

In d 400 A

0,3

0,3

0,4

0,5

0,6

0,7

0,8

0,9

400 A < In d 1 200 A

0,2

0,3

0,4

0,5

0,6

0,7

0,8

0,9

In > 1 200 A

500 A 640 A 720 A 800 A 880 A 960 A 1 040 A 1 120 A 1 200 A

In = valeur nominale du capteur. Ig = enclenchement sur dfaut la terre

Tableau 6 : Valeurs du retard sur dfaut la terre du dclencheur


Micrologic
Rglage

Retard de dfaut la terre

I2t dsactiv (ms In) (secondes)

0,1

0,2

0,3

0,4

I2t activ (ms In) (secondes)

0,1

0,2

0,3

0,4

tsd (dclenchement min.) (millisecondes)

20

80

140

230

350

tsd (dclenchement max.) (millisecondes)

80

140

200

320

500

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Configuration du dclencheur
Micrologic
Alimentation de contrle

Le dclencheur P est conu pour tre utilis avec une alimentation externe
de 24 Vcc. Le grand afficheur LCD utilis par le dclencheur P ncessite
trop de courant pour tre aliment par un courant venant du disjoncteur.
Le dclencheur P possde une alimentation de tension qui alimentera le
dclencheur lorsquil existe environ 150 Vca ou plus entre deux phases. La
configuration standard des sondes de tension lintrieur du disjoncteur se
trouve aux raccordements infrieurs. Si le disjoncteur est ouvert dans une
application aliment par le haut, il ny a pas de tension au bas du disjoncteur
et le dclencheur ne sera pas aliment.

Protection contre les dfauts pour les fonctions LSIG. Le dclencheur P


est totalement aliment par le circuit pour assurer la protection contre
les dfauts.

Indication de dclenchement par un voyant DL (aliment par une pile


embarque). La seule fonction de la pile est de fournir une indication par
la DL si toute autre alimentation est coupe.

Le bouton de dclenchement (pousser-pour-dclencher) de dfaut la


terre simule un dfaut la terre quand le dclencheur est aliment par
lalimentation de tension du circuit. Le bouton de dclenchement par
dfaut la terre est galement fonctionnel si une trousse dessai
portative ou une trousse dessai des fonctions compltes alimente le
dclencheur.

Les fonctions suivantes seront alimentes et fonctionnelles avec une


alimentation externe :

20002012 Schneider Electric Tous droits rservs

Toutes les fonctions ci-dessus qui sont fonctionnelles sans alimentation


externe.

Lafficheur LCD et le rtro-clarage sont fonctionnels. Lintensit du


rtro-clairage nest pas contrl ou rglable et peut tre diffrente dun
dclencheur un autre.

Tous les journaux de mesure, de surveillance et historiques sont


fonctionnels.

Les communications du dclencheur vers les modules de contact


programmables M2C et M6C sont alimentes par une alimentation de
24 Vcc F1 et F2. Le M6C exige aussi une alimentation externe de
24 Vcc.

Les communications Modbus sont fonctionnelles, utilisant une


alimentation spare de 24 Vcc pour le module de communication du
disjoncteur. Cette alimentation spare de 24 Vcc est requise pour
maintenir lisolation entre le dclencheur et les communications.

Le bouton de dclenchement de dfaut la terre est galement


fonctionnel si une trousse dessai portative ou une trousse dessai des
fonctions compltes alimente le dclencheur.

15-FR

FRANAIS

Les fonctions suivantes seront alimentes et fonctionnelles mme si le


dclencheur nest pas aliment de faon externe :

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Alimentation externe
Le dclencheur peut tre aliment par :

ATTENTION
RISQUE D'LECTROCUTION, D'CLAIR
D'ARC OU DE DOMMAGES MATRIELS
Le dclencheur et le module de communication
doivent utiliser des alimentations spares.
Si cette directive nest pas respecte, cela
peut entraner des blessures ou des
dommages matriels.

Alimentation externe 24 Vcc (recommande).


Plus de 150 V sur les bornes infrieures du disjoncteur sur deux phases.
Plus de 150 V sur les bornes suprieures du disjoncteur avec option de
tension externe.

Tableau 7 : Caractristiques de l'alimentation


Fonction

Spcifications

Alimentation pour le dclencheur seul

24 Vcc, 50 mA

Isolation minimale entre-sortie

2400 V

Sortie (y compris londulation max. de 1 %)

5 %

Rsistance dilectrique (entre/sortie)

3 kV rms

Raccordements

Connexions UC3
F1 (-)
F2 (+)

24 Vcc

Lalimentation est utilise pour :

FRANAIS

cran daffichage graphique lorsque le disjoncteur est ouvert et aliment


par le haut
Option de liaison d'une alarme une sortie relais
Pour maintenir la date et l'heure lorsque le disjoncteur est ouvert.

Configuration du dclencheur Micrologic


REMARQUE : Si le dclencheur est raccord
un rseau de communication qui fournit la
synchronisation de la date et de lheure, la date
et lheure ne peuvent pas tre rgles partir du
dclencheur.
Se reporter la 36 pour les directives pas pas
pour configurer le dclencheur Micrologic.
Voir la Section 3 la page 33 pour dautres
directives de configuration du dclencheur.

16-FR

Utiliser le menu dentretien en appuyant la touche en forme de cl plate


fourche.
Figure 8 :
06133330

Configuration du dclencheur
Micrologic

Configuration du dclencheur Micrologic

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

Configurer
Micrologic
Langue

Slectionne la langue de l'affichage

Date/heure

Rgle la date et l'heure

Slection
disjoncteur

Entre des informations sur le disjoncteur dans


lequel le dclencheur est install

Signe
puissance

Slectionne le sens du signe de la puissance


pour les menus de mesures

Transfo
de U

Slectionne le rapport de tension ; si aucun


transformateur de tension externe nest
prsent, slectionner 690:690

Frquence
rseau

Slectionne la frquence du systme

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Protection volue
Protection du neutre

AVIS

La protection du neutre protge les conducteurs


du neutre contre la surchauffe.

RISQUE DE DOMMAGES MATRIELS

Pour un disjoncteur tripolaire, la protection


du neutre est possible si un transformateur
de courant de neutre est utilis.

Si le commutateur du ple du neutre d'un disjoncteur quadripolaire est


rgl sur 4P3D, le courant du neutre ne doit pas dpasser le courant
nominal du disjoncteur.

Rgler le neutre l'aide du clavier du


dclencheur.

Pour un disjoncteur tripolaire avec protection du neutre surdimensionne


(1.6N), slectionnez un transformateur de courant du neutre
surdimensionn appropri.

Rglages possibles : OFF, N/2, N, ou


1.6N.

Si ces directives ne sont pas respectes, cela peut entraner des


dommages matriels.

Le rglage dusine est OFF.

Pour un disjoncteur quadripolaire, rgler le


type de systme l'aide du slecteur du
neutre du disjoncteur (voir Figure 9).
Effectuer les rglages fins l'aide du
clavier du dclencheur, le rglage du
slecteur du disjoncteur fournissant la
limite suprieure de rglage.

Figure 9 :

06134824

Slecteur du neutre du disjoncteur quadripolaire


Rglages de la protection du
neutre pour un disjoncteur
quadripolaire

4D
4P

Slecteur du
disjoncteur

Rglage du
clavier
disponible

4P 3D

Off, N/2, N

3P N/2

N/2

4P 4D

N/2, N

Le rglage dusine est 4P4D.

La protection du conducteur de neutre offre


quatre rglages possibles suivant le type de
conducteur :

Tableau 8 : Type de conducteurs du dclencheur Micrologic

OffLa protection du neutre est


dsactive.

Rglage

N/2La capacit des conducteurs du


neutre est la moiti de celle des
conducteurs de ligne.
NLa capacit des conducteurs du
neutre est la mme que celle des
conducteurs de ligne.
1.6NLa capacit des conducteurs du
neutre est 1,6 fois celle des conducteurs
de ligne. (Disjoncteur tripolaire
uniquement.)

20002012 Schneider Electric Tous droits rservs

Enclenchement Enclenchement
de longue dure de courte dure

Instantan

Enclenchement
sur dfaut la
terre

Dcl.

Neutre Dcl.

Neutre

Dcl.

Neutre

Dcl.

Neutre

OFF

Ir

Aucun

Isd

Aucun

Ii

Aucun

Ig

Aucun

N/2

Ir

1/2 Ir

Isd

1/2 Isd

Ii

Ii

Ig

Ig

Ir

Ir

Isd

Isd

Ii

Ii

Ig

Ig

1.6N

Ir

1,6 x Ir

Isd

1,6 x Isd*

Ii

Ii

Ig

Ig

*Pour limiter la gamme, limit 10 x In

17-FR

FRANAIS

Une protection du neutre


surdimensionne (1.6N) ncessite
l'emploi d'un transformateur de courant
du neutre surdimensionn appropri.

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Alarmes

Tableau 9 : Alarmes du dclencheur

Les alarmes peuvent tre actives ou


dsactives pour la protection ou le dlestage
de charge.

Alarme

Menu

Symbole

Alarme Dcl.

Enclenchement de longue dure

Protections en courant

Ir

Enclenchement de courte dure

Protections en courant

Isd

Enclenchement instantan

Protections en courant

Ii

Courant de dfaut la terre

Protections en courant

Pour qu'un dclencheur active une alarme,


le niveau d'enclenchement ainsi que la
temporisation choisie doivent tre dpasss.
En consquence, pour la protection LSIG et
la protection avance programmes pour
dclencher le disjoncteur, le dclencheur
n'activera pas l'alarme tant que le disjoncteur
ne sera pas dclench. (Par exemple, si un
relais est programm pour l'enclenchement
de longue dure Ir, le dclencheur ne
signalera pas d'alarme quand le voyant de
surcharge de longue dure s'allume. Le
dclencheur n'activera l'alarme que lorsque
la surcharge de longue dure dpassera la
temporisation choisie et dclenchera le
disjoncteur.)

Alarme de dfaut la terre

Protections en courant

Al

Dsquilibre de courant

Protections en courant

Idsq.

Courant moyen (demande)


maximum pour la phase 1

Protections en courant

I1max

Courant moyen (demande)


maximum pour la phase 2

Protections en courant

I2max

Courant moyen (demande)


maximum pour la phase 3

Protections en courant

I3max

Courant moyen (demande)


maximum pour le neutre

Protections en courant

In max

Tension minimale (sous-tension)

Protections en tension

Umin

Relier les alarmes un signal visuel ou


sonore en programmant les contacts d'un
module optionnel M2C ou M6C, quand une
alimentation externe de 24 V est utilise
avec le dclencheur.

FRANAIS

Si une condition d'alarme se produit, une


entre est effectue dans le journal des
alarmes.

Tension maximale (surtension)

Protections en tension

Umax

Dsquilibre de tension

Protections en tension

Udsq.

Inversion de puissance

Autres protections

rPmax

Frquence minimale (sousfrquence)

Autres protections

Fmin

Frquence maximale
(surfrquence)

Autres protections

Fmax

Sens de rotation des phases

Autres protections

Rotation
phases

Au menu des enregistrements


historiques

Dlestage de charge en courant

Dlestage relestage I

Dlestage
relestage I

l'aide du logiciel de gestion des


systmes en rseau

Dlestage de charge en puissance Dlestage relestage P

Dlestage
relestage P

Visualiser les alarmes :

Caractristiques des contacts des


M2C/M6C :
Charge minimale de 100 mA/24 V
Pouvoir de coupure un facteur de
puissance de 0,7

240 Vca

5A

380 Vca

3A

24 Vcc

1,8 A

48 Vcc

1,5 A

125 Vcc

0,4 A

250 Vcc

0,15 A

Lorsque plusieurs alarmes se trouvent


actives, le temps de rponse/
rafrachissement de l'cran est plus lent.

Voir l'annexe B pour les valeurs par dfaut et les


valeurs de gammes.

18-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

La valeur d'enclenchement (A) est rgle


pour activer une alarme ou un
dclenchement.

La temporisation d'enclenchement (B) est


rgle pour commencer la temporisation une
fois que la valeur d'enclenchement a t
dpasse.

La valeur de retombe (C) est rgle pour


dsactiver l'alarme ou le contact.

La temporisation de retombe (D) est rgle


pour commencer la temporisation une fois
que la valeur de retombe a t dpasse.

La protection de sous tension (Umin) est


active lorsqu'une tension entre phases se
trouve en dessous du rglage minimum de
tension.

La protection de sur tension (Umax) est


active lorsqu'une tension entre phases se
trouve au-dessus du rglage maximum de
tension.

Umin a une valeur de retombe t valeur


d'enclenchement.

Umax a une valeur de retombe d valeur


d'enclenchement.

Si la protection du courant ou de la tension


dclenche le disjoncteur, ce dernier ne peut
pas tre rarm tant que le problme de
courant ou de tension ayant provoqu le
dclenchement ne soit corrig.

Une alarme de dfaut la terre sur les


dclencheurs 5.0P et 6.0P est base sur la
valeur efficace vraie (RMS) du courant dans
la terre.

Un dclenchement sur dfaut la terre sur


le dclencheur 6.0P est base sur la valeur
efficace vraie (RMS) du courant dans la
terre.

Ne pas rgler la protection en sous-tension


en dessous de 80 %*.

Protection maximale

Protection minimale

C
D

A
B

I/VLL

VLL

FRANAIS

Fournit des valeurs d'enclenchement et de


retombe de l'alarme, les contacts ou le
dclenchement pour des valeurs de courant et
de tension. (Il n'y a pas de minimum pour le
courant.)

Figure 10 : Courbes de protection minimale/maximale

06134770

Valeurs minimales et maximales de la


protection de courant moyen (demande)
et de la protection de tension

Pour avoir une explication du comportement de la protection du systme, se reporter l'annexe D

20002012 Schneider Electric Tous droits rservs

19-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

Cette protection s'applique des valeurs non


quilibres pour les courants et tensions triphass.

Les valeurs de dsquilibre sont bases sur


les valeurs efficaces relles des courants
triphass.

ou
Umoyen
0

Ne pas rgler Udsq. au-dessus de 20 %*.

Idsq. = |'max|
Imoyen
I1

I2

Udsq. = |'max|
Umoyen

I3

Figure 12 : Protection contre l'inversion de puissance

Le sens de la puissance est dfini pendant la


configuration du dclencheur.

Protection de frquence minimale


(sous) et maximale (sur)
Fournit les valeurs d'enclenchement et de
retombe pour la frquence.

Protection minimale

La valeur de retombe (C) est rgle pour


dsactiver l'alarme ou le contact.

La temporisation de retombe (D) est rgle


pour commencer la temporisation une fois que
la valeur de retombe a t dpasse.

Fmin a une valeur de retombe t valeur


d'enclenchement.

Fmax a une valeur de retombe d valeur


d'enclenchement.

20-FR

Protection maximale

La valeur d'enclenchement (A) est rgle pour


activer une alarme ou un dclenchement.
La temporisation d'enclenchement (B) est
rgle pour commencer la temporisation une
fois que la valeur d'enclenchement a t
dpasse.

Figure 13 : Courbes de protection de frquence minimale/maximale

06133266

FRANAIS

La temporisation (B) dmarre si la puissance


relle totale des trois phases ne s'coule pas
dans le sens dfini et si elle dpasse le seuil
d'inversion de puissance.

La protection contre l'inversion de puissance


applique une courbe de dclenchement
base sur la valeur totale de la puissance
relle (A) des trois phases.

U + U2 + U3
Umoyen = 1
3

Pour avoir une explication du comportement de la protection du systme, se reporter l'annexe D

La protection contre l'inversion de puissance


protge les alternateurs contre l'absorption de la
puissance relle totale des trois phases en cas
de panne d'un moteur d'entranement.

I +I +I
Imoyen = 1 2 3
3

Ne pas utiliser la protection contre le


dsquilibre de tension pour dterminer la
perte de phases multiples*.

Protection contre l'inversion de


puissance (rPmax)

max

Imoyen

06134771

Figure 11 : Protection contre le dsquilibre de courant ou de


tension
06134769

Protection contre le dsquilibre de


courant ou de tension

48049-137-05
Rev. 01, 07/2012

C
D

Fmin

Fmax

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Lorsque la frquence du systme est rgle 400


Hz, la protection de frquence est dsactive.

Le dlestage de charge ne dclenche pas le


disjoncteur, mais peut tre utilis pour activer
une alarme relie un contact M2C ou M6C
(contrle de charges de rseau non prioritaires).

Figure 14 : Dlestage de charge (Dlestage relestage)


06134771

Dlestage de charge (Dlestage


relestage)

C
D

Courbe de
protection
de longue
dure

C
A
D
B

Le dlestage de charge est dfini par un


seuil et une temporisation :
0

ASeuil d'activation

BTemporisation d'activation
CSeuil de retombe

Le dlestage de charge en puissance


dpend du sens de l'coulement tabli
pendant la configuration du dclencheur.

Le dlestage de charge en courant est


connect aux valeurs de retard des
protections I2t ou Idmtl longue dure.

Le dlestage de charge en courant ne peut


pas tre activ si un commutateur de valeur
nominale arrt de longue dure est
install.

Protection du sens de rotation des


phases

20002012 Schneider Electric Tous droits rservs

FRANAIS

DTemporisation de retombe

Protge le circuit lorsque deux des trois phases sont inverses.

Si l'une des phases est dfectueuse, cette protection est inactive.

Ne pas utiliser la protection du sens de rotation des phases pour dterminer


la perte de phases multiples dans des systmes raccords en triangle.

Les options sont 123 ou 132.


Lorsque la frquence du systme est rgle 400 Hz, la protection du sens
de rotation des phases est dsactive.

21-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

S1 S2

FRANAIS

REMARQUE : Le dclencheur et les modules


de communication (BCM et CCM) doivent
utiliser des alimentations spares. Les kits de
contacts M2C et M6C peuvent partager
l'alimentation auxiliaire du dclencheur.

Interverrouillage slectif de zone


Les protections de courte dure et contre les
dfauts la terre peuvent tre interverrouille
pour fournir linterverrouillage slectif de zone.
Un cblage de commande relie plusieurs
dclencheurs du rseau de distribution et, en
cas de dfaut, un dclencheur nobit au temps
du retard tabli que sil reoit un signal dun
dclencheur en aval.

471

Une alimentation auxiliaire de 24 Vcc, 5W est


ncessaire pour le fonctionnement de chaque
combinaison dclencheur/kit de contacts M2C
ou M6C.

M6C : Alimentation externe de 24 Vcc exige


06133934

M2C : alimentation de
24 Vcc fournie par le
dclencheur
484

Une ou plusiers alarmes peuvent tre actives


l'aide d'un kit de contacts programmables
optionnel M2C ou M6C. Le kit de contacts M2C
fournit deux contacts de type A avec neutre
commun. Le kit de contacts M6C fournit six
contacts de type C. Chaque contact peut tre
programm pour une condition d'alarme au
moyen du dclencheur.

Figure 15 : Schmas de cblage de M2C/M6C

474

Kits de contacts programmables


M2C/M6C

48049-137-05
Rev. 01, 07/2012

Caractristiques des modules de


V
contacts programmables M2C et M6C

Charge minimale

24 Vcc

100 mA

240 Vca

5A

380 Vca

3A

24 Vcc

1,8 A

48 Vcc

1,5 A

125 Vcc

0,4 A

250 Vcc

0,15 A

Pouvoir de coupure au facteur de puissance


(f.p.) de 0,7

REMARQUE : Utiliser la fonction I2t dsactiv avec ZSI pour une bonne
coordination. L'utilisation de la fonction I2t avec ZSI n'est pas recommande
puisque le retard avec lequel le dispositif en amont recevra un signal
d'entrave peut entraner le dclenchement du dclencheur en un temps plus
court que la courbe de dclenchement publie.
REMARQUE : Le rglage dun retard de courte dure (tsd) ou dun retard
de dfaut la terre (tg) la valeur 0, limine la slectivit pour ce
disjoncteur.

Si le dclencheur ne reoit pas de signal, le


dclenchement est instantan (sans retard
intentionnel).

Le dfaut est isol instantanment par le


disjoncteur en amont le plus proche.

Les contraintes thermiques (I2t) du rseau


sont minimises, sans avoir deffet sur la
coordination de la temporisation de
linstallation.

22-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Un dfaut en A est dtect par les


disjoncteurs 1 et 2. Le disjoncteur 2 se
dclenche instantanment et informe
galement le disjoncteur 1 dobir aux temps
de retard tablis. En consquence, le
disjoncteur 2 se dclenche et isole le dfaut.
Le disjoncteur 1 ne se dclenche pas.

Un dfaut en B est dtect par le disjoncteur


1. Le disjoncteur 1 se dclenche
instantanment puis quil na pas reu de
signal de la part du disjoncteur 2 en aval. Le
disjoncteur 1 se dclenche et isole le dfaut.
Le disjoncteur 2 ne se dclenche pas.

Mesure

Le dclencheur Micrologic P fournit une mesure continue des valeurs du


systme. Les valeurs mesures peuvent tre vrifies l'aide de l'cran
d'affichage graphique ou du logiciel de gestion des systmes en rseau.

Essai du dclencheur

Les fonctions LSIG du dclencheur peuvent tre vrifies l'aide d'un essai
d'injection primaire ou secondaire. Vrifier le dclencheur avec la trousse
d'essai des fonctions compltes ou la trousse d'essais portative. (Voir
Vrification de linstallation du dclencheur la page 68 pour des
informations supplmentaires.)

Compteur de manuvres

Le module de communication du disjoncteur est ncessaire pour afficher le


nombre total d'ouvertures du disjoncteur depuis son installation initiale et
depuis son dernier rarmement et le jour/l'heure du dernier rarmement.

Voyants
Figure 17 : Voyant de surcharge
06134753

Dclencheur Micrologic 5.0P

Le voyant de surcharge (A) s'allume lorsque le


niveau d'enclenchement de longue dure (Ir) a
t dpass.

Dclencheur Micrologic 6.0P

long time

Ir
.7
.6
.5
.4

.8

x In

alarm

tr

8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

@ 6 Ir

setting

long time

Ir
.7
.6
.5
.4

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

06134754

Voyant de surcharge

tsd

.4 .4 .3
.2
.3
.1
.2
.1 2 0

Ii

(s)

on

I t

off

4
3

6 8 10
12
15
off
2
x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

delay

tsd

.4 .4 . 3
.2
.3
.1
.2
.1 2 0

on

setting

Ig
D
C
B
A

I t

off

delay

tg
F
G
H
J

Ii

(s)

(s)

4
3

6 8 10
12
15
off
2
x In
test

.4 .4 .3

.3
.2
.1
on

.2
.1
2

I t

0
off

ground fault

20002012 Schneider Electric Tous droits rservs

23-FR

FRANAIS

Figure 16 : Interverrouillage slectif de zone

06133376

La figure 16 montre linterverrouillage slectif de


zone des disjoncteurs 1 et 2 .

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

Voyants de dclenchement

AVIS

Un voyant de dclenchement s'allume sur le


dclencheur lorsque le disjoncteur se
dclenche. Si le dclencheur possde une
connexion d'alimentation auxiliaire, le
dclencheur affiche les informations concernant
le dclenchement.

Le voyant de dclenchement Ir (B) s'allume


lorsque l'enclenchement de longue dure (Ir)
signale au disjoncteur de se dclencher.

Si le disjoncteur reste ferm et le voyant Ap reste allum aprs un


rarmement, ouvrez le disjoncteur et contactez votre bureau des ventes.
Si cette directive nest pas respecte, cela peut entraner des
dommages matriels.
Figure 18 : Voyants de dclenchement
B C
06134251

Le voyant de dclenchement reste allum


jusqu' sa remise zro en appuyant sur le
bouton de remise zro (A). La cause du
dclenchement doit tre corrige avant tout
rarmement.

RISQUE DE DOMMAGES MATRIELS

E A

Micrologic 6.0 P

Le voyant de dclenchement Isd/Ii (C) s'allume


lorsque l'enclenchement de courte dure (Isd)
ou l'enclenchement instantan (Ii) signale au
disjoncteur de se dclencher.

Le voyant d'auto-protection/de protection


volue Ap (E) s'allume lorsque les
caractristiques de la protection volue
provoquent un dclenchement, le dclencheur
surchauffe, le niveau de forage instantan est
dpass ou lorsqu'une panne d'alimentation du
dclencheur se produit.

Bouton dessai/de remise zro


Il faut appuyer sur le bouton d'essai/de remise
zro (Test/Reset) (A) aprs un dclenchement
pour remettre zro l'information de dfaut sur
l'affichage graphique et teindre le voyant de
dclenchement.

24-FR

REMARQUE : Dans les cas o des causes multiples peuvent aboutir un


dclenchement, la DL signalant la dernire cause est la seule rester
allume.

Figure 19 : Bouton de remise zro


06134251

FRANAIS

Le voyant de dclenchement Ig (D) s'allume


lorsque l'enclenchement de dfaut la terre (Ig)
signale au disjoncteur de se dclencher.

Micrologic 6.0 P

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 1Gnralits

48049-137-05
Rev. 01, 07/2012

L'cran d'affichage graphique fonctionne


seulement si le dclencheur est aliment. Le
dclencheur est sous tension :

si le disjoncteur est sous tension et a une


tension de charge de plus de 150 V sur deux
phases (le disjoncteur est ferm ou aliment
par ses bornes infrieures).

si la trousse d'essais des fonctions compltes


ou portative est raccorde et sous tension.

si l'alimentation externe de 24 V cc est


raccorde.

si un drivateur de tension externe est install


et si une tension de plus de 150 V est prsente
sur deux phases.

Voyant dusure des contacts

20002012 Schneider Electric Tous droits rservs

Micrologic 5.0 P

4260A

N 1 2 3
100

50

Le dclencheur conserve la trace de l'usure des contacts du disjoncteur


lorsqu'un disjoncteur du type Masterpact est choisi. Le niveau de l'usure des
contacts du disjoncteur peut tre transfr lors du remplacement du
dclencheur. (Une alimentation externe est ncessaire pour le
dclencheur.)

25-FR

FRANAIS

L'cran d'affichage graphique (A) donne les


rglages et les informations concernant le
dclencheur. Les touches de navigation (B) sont
utilises pour afficher et modifier les indications
de l'cran. L'affichage des niveaux des courants
est l'affichage par dfaut.

Figure 20 : cran daffichage graphique


06134749

cran daffichage graphique

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 2Navigation sur l'afficheur graphique

48049-137-05
Rev. 01, 07/2012

Section 2Navigation sur l'afficheur graphique

Afficheur graphique
L'afficheur graphique (A) fonctionne si le
dclencheur est raccord une alimentation
externe de 24 Vcc ou si la tension est de 150 V
sur au moins deux phases. Le courant (de
l'ensemble d'essais d'injection primaire ou du
systme lectrique) alimentera uniquement les
fonctions de protection LSIG mais pas
l'afficheur.
Touches de navigation (B) :

Figure 21 : Afficheur graphique

4260A
N 1 2 3

100

50

Touche d'accs au menu Mesures


Donne accs aux menus des mesures

FRANAIS

Touche d'accs au menu Entretien


Donne accs aux menus d'entretien
Touche d'accs au menu Protection
Donne accs aux menus de protection
Touche de dfilement vers le bas
Dplace le curseur vers le bas ou diminue
la valeur du rglage
Touche de dfilement vers le haut
Dplace le curseur vers le haut ou
augmente la valeur du rglage
Touche d'entre (validation ou
slection)Slectionne une option dans
une liste ou valide les valeurs rgles

26-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 2Navigation sur l'afficheur graphique

48049-137-05
Rev. 01, 07/2012

Figure 22 : Menus

A. Graphique barresFournit en temps rel


un affichage graphique barres des
courants d'alimentation et de la mesure du
courant de ligne et du courant du neutre (le
cas chant) (affichage par dfaut)

4260A

(A)
(V)

50

U
P
E

(kWh)

(Hz)

N 1 2 3
100

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

(kW)

06133331

B
06134267

06134792

A
Le dclencheur Micrologic P possde un
affichage graphique barres des courants par
dfaut et trois menus diffrents dont l'accs se
fait l'aide de boutons de navigation :

06133330

Graphique barres et menus

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

B. Menu MesuresDonne accs aux valeurs


mesures de courant (intensit), de la
tension, de la puissance, de l'nergie et de la
frquence
C. Menu EntretienPermet l'utilisateur de
modifier la configuration du dclencheur et
donne accs aux journaux (enregistrements)
historiques

FRANAIS

D. Menu ProtectionsPermet d'effectuer des


rglages prcis des protections de base et
volues
Lorsque le couvercle des commutateurs est
ferm, le dclencheur retourne au graphique
barres (affichage par dfaut) aprs 3 minutes et
demie sans entre. (Si le couvercle des
commutateurs est ouvert, l'affichage reste la
fentre slectionne.) Pour accder un autre
menu, appuyer sur la touche qui correspond au
menu dsir. Le menu apparat sur l'afficheur et
la DL verte sous la touche du menu s'allume.

Utiliser la touche des mesures pour accder aux


valeurs mesures suivantes :
A. Courant
B. Tension
C. Alimentation
D. nergie
E. Frquence

20002012 Schneider Electric Tous droits rservs

Figure 23 : Menu Mesures


06134267

Menu Mesures

(A)

Dplace le curseur vers le bas

U
P
E

(V)

Dplace le curseur vers le haut

(kW)

Slectionne l'article encadr

(kWh)

Retourne l'cran prcdent

(Hz)

Retourne au graphique
de barres

27-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 2Navigation sur l'afficheur graphique

Figure 24 : Niveaux des courants


06134267

Courant

48049-137-05
Rev. 01, 07/2012

(A)

U
P
E

(V)
(kWh)

(Hz)

(A)

instant.

(kW)

I1, I2, I3, In

Affiche le courant pour les phases 1, 2, 3


et le neutre (selon le type de rseau)

Max.

Affiche et rtablit les valeurs


maximales de courant

moyen
Affiche le courant moyen (demande) pour
les phases 1, 2, 3 et le neutre (selon le type
de rseau)

I1, I2, I3, In

Max.

Figure 25 : Niveaux des tensions


06134267

Tension

FRANAIS
28-FR

I
U
P
E

(kWh)

(Hz)

(V)

(A)
(V)
(kW)

instant.

Affiche la tension instantane entre phases


(U12, U23, U31) et les tensions instantanes
phase-neutre (V1n, V2n, V3n)
(triphas, 4 fils avec un TC du neutre)

moyen 3)

Affiche la moyenne des tensions entre phases

dsq. 3)

Affiche le dsquilibre de tension entre phases

Rotation
phases

Affiche la squence de rotation des phases

Figure 26 : Niveaux des puissances


06134267

Puissance

Affiche et rtablit les valeurs de


demande maximales

(A)

U
P
E

(V)
(kWh)

(Hz)

(kW)

(kW)
instant.
P, Q, S

Affiche la puissance active totale (P)


Affiche la puissance ractive totale (Q)
Affiche la puissance apparante totale (S)

Facteur de
puissance

Affiche le facteur de puissance

moyen
P, Q, S

Affiche la demande de puissance active (P)


Affiche la demande de puissance ractive (Q)
Affiche la demande de puissance apparante (S)

Max.

Affiche et rtablit les valeurs de


demande maximales

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 2Navigation sur l'afficheur graphique

48049-137-05
Rev. 01, 07/2012

Figure 27 : Niveaux des nergies


06134267

nergie

(A)

(kWh)
Affiche la puissance active totale (E. P.)
Affiche la puissance ractive totale (E. Q.)
Affiche la puissance apparante totale (E. S.)

E totale

Menu Entretien

(kWh)

(Hz)

(V)
(kW)

(A)

U
P
E

(V)

Affiche la puissance active totale (E. P.) fournie


Affiche la puissance ractive totale (E. Q.) fournie

Reset
nergies

Remet toutes les valeurs d'nergie zro.

(kWh)

(Hz)

Affiche la frquence (F)

FRANAIS

(kW)

Figure 29 : Menu Entretien


06133330

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

A. Pour accder au journal historique


B. Pour configurer les contacts M2C/M6C
C. Pour configurer le dclencheur Micrologic
D. Pour configurer les paramtres de mesure
E. Pour configurer le module de communication

Dplace le curseur vers le bas

Dplace le curseur vers le haut

Slectionne l'article encadr

Retourne l'cran prcdent

Retourne au graphique de
barres

06133330

Figure 30 : Historiques
Historiques

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

20002012 Schneider Electric Tous droits rservs

EFournie

Utiliser la touche dentretien pour accder au


menu Entretien.

Historiques

Affiche la puissance active totale (E. P.)


E+
Consomme consomme
Affiche la puissance ractive totale (E. Q.)
consomme

Figure 28 : Frquence
06134267

Frquence

U
P
E

Historiques
dfauts

Affiche le journal des dix derniers


dfauts enregistrs

Historiques
alarmes

Affiche le journal des dix dernieres


alarmes actives

Compteur de Affiche le nombre de manuvres


manuvres
(ouvertures et dclenchements)
Usure des
contacts

Affiche l'tat d'usure des contacts du disjoncteur

29-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 2Navigation sur l'afficheur graphique

Seulement disponibles si les contacts


M2C/M6C sont installs.

Figure 31 : Configuration des contacts M2C/M6C


06133330

Contacts programmables M2C/M6C

48049-137-05
Rev. 01, 07/2012

Une alarme par contact.

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

Peut slectionner les contacts configurs en


tant que alarme ou trip
(dclenchement) au menu Protections.

Contacts
M2C/M6C
Type
d'alarme
S#

Configurer
S#

Reset

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

Langue

Slectionne la langue de l'affichage

Date/heure

Rgle la date et l'heure

Slection
disjoncteur

Entre les informations concernant le


disjoncteur sur lequel le dclencheur
est install

Signe
puissance

Slectionne le sens du signe de puissance


pour les menus de mesures

Frquence
rseau

Configurer mesures

Slectionne le rapport de tension; en


cas d'absence de transformateur de
tension externe, slectionner 690:690
Slectionne la frquence du systme

Figure 33 : Configurer mesures


Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

30-FR

Remet les contacts zro aprs une alarme

Configurer
Micrologic

Transfo de U

06133330

FRANAIS

REMARQUE : Si le dclencheur est raccord


un rseau de communication qui fournit la
synchronisation de la date et de l'heure, la
date/lheure ne peuvent pas tre rgles partir
du dclencheur.

Rgle le mode pour le contact S#


# est gal 1 ou 2 pour un contact M2C
# est gal 1 6 pour un contact M6C

Figure 32 : Configurer Micrologic


06133330

Configurer Micrologic

Affecte une alarme de protection


un contact S#
# est gal 1 ou 2 pour un contact M2C
# est gal 1 6 pour un contact M6C

Configurer
mesures
Type de
rseau

Slectionne le type de rseau

Calcul
I moyen

Rgle le courant moyen (demande)

Calcul
P moyen

Rgle la demande de puissance

Convention
de signe

Slectionne la convention de signe

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 2Navigation sur l'afficheur graphique

48049-137-05
Rev. 01, 07/2012

Figure 34 : Configuration du module de communication


06133330

Configurer
Com.

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

Rgle le module de communication

Rglage
distance

Dtermine l'accs aux rglages du dclencheur


via le module de communication

Commande
distance

Dtermine si le disjoncteur peut tre mis sous


ou hors tension via le module de communication

Figure 35 : Menu Protections


06133331

Menu Protections

Paramtre
com.

Utiliser la touche de protection pour accder


ces menus.
A. Pour afficher et rgler la protection en
courant
B. Pour afficher et rgler la protection en
tension
C. Pour afficher et rgler toute autre protection
D. Pour rgler le dlestage de charge pour le
courant

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

Dplace le curseur vers le bas

Dplace le curseur vers le haut

Slectionne l'article encadr

Retourne l'cran prcdent

Retourne au graphique de
barres

E. Pour rgler le dlestage de charge pour la


puissance
Figure 36 : Protections en courant
06133331

Protections en courant

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

Protections
en courant

at affine le rglage des protections


(A) Affiche
2

I dmtl

(A) Affiche at affine le rglage des protections

(A)

I t longue et courte dure et instantane

Idmtl longue et courte dure et instantane

I neutre (A)
I

20002012 Schneider Electric Tous droits rservs

Affiche et affine le rglage de la protection


de dfaut la terre (Micrologic 6.0P seulement)
Rgle le courant du neutre (Off, N, N/2, 1.6N)

Alarme Rgle les valeurs de l'alarme de dfaut la terre

Idsq. (%)

Rgle le dsquilibre de courant admissible

I1max (A)

Rgle la demande de courant max. de


la phase 1

I2max (A)

Rgle la demande de courant max. de


la phase 2

I3max (A)

Rgle la demande de courant max. de


la phase 3

Inmax (A)

Rgle la demande de courant max. pour


le neutre

31-FR

FRANAIS

Configuration de la communication

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 2Navigation sur l'afficheur graphique

Figure 37 : Protections en tension


06133331

Protections en tension

48049-137-05
Rev. 01, 07/2012

FRANAIS
32-FR

Rgle la protection en tension minimale


(soustension)

Umax (V)

Rgle la protection en tension maximale


(surtension)

Udsq. (%)

Rgle la protection en tension dsquilibre

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

Autres
protections

rPmax (W)

Rgle la protection contre l'inversion


de puissance

F min. (Hz)

Rgle la protection minimale de frquence


(sousfrquence)

Fmax (Hz)

Rgle la protection maximale de frquence


(surfrquence)

Rotation
phases

Rgle la protection du sens de rotation


des phases

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

Dlestage
relestage I

Rgle les valeurs de dlestage de charge


en courant (alarme seulement)

Figure 40 : Dlestage de charge en puissance


06133331

Dlestage de charge en puissance

Umin. (V)

Figure 39 : Dlestage de charge en courant


06133331

Dlestage de charge en courant

Protection
en tension

Figure 38 : Autres protections


06133331

Autres protections

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

Dlestage
relestage P

Rgle les valeurs de dlestage de charge


en puissance (alarme seulement)

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

Section 3Configuration du dclencheur

06133330
5.0
ogic

1. Ouvrir le couvercle des commutateurs (A).

Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

06133334

06133330

Historiques

Bas

20002012 Schneider Electric Tous droits rservs

Figure 42 : Configuration des kits de contacts M2C/M6C


06133330

Si un kit de contacts M2C ou M6C est install,


utiliser le menu Contacts M2C/M6C pour
choisir le type d'alarme et le mode de
fonctionnement. Le kit M2C est muni des
contacts S1 et S2. Le kit M6C comprend les
contacts S1, S2, S3, S4, S5 et S6.

Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

2. Appuyer sur la touche dentretien (B) pour


afficher le menu Entretien (C).

Contacts programmables M2C/M6C

Historiques

Microl

Contacts
M2C / M6C

FRANAIS

REMARQUE : Les rglages du menu


Protections ne peuvent pas tre effectus tant
que le couvercle des commutateurs n'est pas
ouvert. Aprs avoir effectu les rglages,
appuyer sur l'un des boutons de menu pour
enregistrer les nouvelles valeurs.

Figure 41 : Menu Entretien

06134825

Configuration des paramtres du


dclencheur

Type
d'alarme
Configurer
Reset

Entre

33-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

IrEnclenchement de longue dure

Contacts
M2C / M6C

IiEnclenchement instantan

Type
d'alarme

IsdEnclenchement de courte dure

Configurer

I Courant de dfaut la terre

Reset

06133336

Figure 43 : Configuration du type d'alarme des contacts M2C/M6C


06133334

1. Entrer le type d'alarme des contacts


M2C/M6C dans la mmoire du dclencheur.
Les alarmes suivantes sont disponibles :

48049-137-05
Rev. 01, 07/2012

Type
d'alarme

S1

S1

S1

Ii

Isd

S2

AI Alarme de dfaut la terre


Idsq.Dsquilibre de courant

Entre

Entre

I1maxSurintensit en phase 1

Entre

I2maxSurintensit en phase 2
06133336

InmaxSurintensit du neutre

Sortie
06133335

I3maxSurintensit en phase 3

Voulez-vous
enregistrer
les
modifications?
non

UminLa tension est en-dessous du


rglage minimum choisi

Type
d'alarme

S2

S1

Non
affect

S2

rPmaxInversion de puissance
FminLa frquence est en dessous du
rglage minimum choisi

Dlestage PDlestage de charge en


puissance
Non affectAucune alarme slectionne

IsdIsd

Haut/
Bas

Entre

Bas

Bas

Entre

Entre

Entre
Sortie

06133336

FmaxLa frquence est au-dessus du


rglage maximum choisi

Dlestage IDlestage de charge en


courant

S2

oui

Udsq.Dsquilibre de tension

06133335

FRANAIS

UmaxLa tension est au-dessus du rglage


maximum choisi

)rotSens de rotation des phases

Haut/
Bas

Entre

Voulez-vous
enregistrer
les
modifications?
non

Type
d'alarme
S1
S2

oui
Bas

Sortie

Entre

34-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

Accrochage permanentReste activ


jusqu' la remise zro

Contacts
M2C / M6C

06133337

Figure 44 : Configuration du mode d'alarme des contacts M2C/M6C


06133334

2. Configurer le mode d'alarme des contacts


M2C/M6C. Modes disponibles pour les
contacts :

Type
d'alarme

Sans accrochageSe dclenche aprs


l'limination du dfaut

Configurer
M2C/M6C

S1

S1

Contact

Contact

S1

Forc 1

Temporisation

S2

Configurer

Tempo

Reset

1s

TemporisationRetard plac sur les


contacts
Haut/
Bas

Entre

Entre

Entre

Pour les besoins de dpannage seulement,


les modes suivants sont disponibles :

Pour les alarmes de courte dure,


instantane ou sur dfaut la terre (alarme
SIG) uniquement :

S1
Contact

Temporisation

Temporisation

Tempo

Tempo

06133335

Forc 1Les contacts sont bloqus


ferms

S1
Contact

06133337

Entre

Forc 0Les contacts sont bloqus


ouverts

Voulez-vous
enregistrer
les
modifications?
non

Configurer
M2C/M6C
S1
S2

5s

1s

Haut/
Bas

Bas
Entre

Quelque soit le mode choisi durant la


configuration de lalarme accrochage
ou sans accrochage des contacts, ce
comportement daccrochage est prsent.

Entre

Bas

Bas

Entre

Entre

FRANAIS

oui

Chaque dclenchement d'alarme active


le relais, signale et continue signaler
une alarme jusqu' ce que le bouton
d'alarme/remise zro (Test/Reset) du
dclencheur soit enfonc.

Sortie

3. Remettre zro les tats d'affichage des


relais et permettre leur rinitialisation.
REMARQUE : Slectionner loption Reset
(Rinitialization) au menu Contacts M2C/M6C
pour remettre toutes les alarmes zro. Le
bouton d'alarme/remise zro du dclencheur
rarme le dclencheur de sorte qu'il arrte
d'activer l'alarme, mais il ne retourne pas les
contacts M2C/M6C leur position initiale.

S2

S2

S2

S2

Contact

Contact

Contact

Contact

Forc 1

Temporisation

Temporisation

Temporisation

Tempo

Tempo

Tempo

360s

360s

Haut/
Bas

Entre

1s

Haut/
Bas

Bas
Entre

Entre

Entre

Voulez-vous
enregistrer
les
modifications?
non

Configurer
M2C/M6C
S1
S2

06133334

06133335

06133337

Sortie

Contacts
M2C / M6C
Type
d'alarme
Configurer

Mode temporisation
uniquement

Reset

oui
Bas

Sortie

Sortie

Entre

20002012 Schneider Electric Tous droits rservs

35-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.
Bas

Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.
Entre

Langue
Date / heure
Slection
disjoncteur
Signe
puissance
Transfo
de U
Frquence
rseau

Figure 46 : Configuration de la langue


06133339

1. Rgler la langue de l'affichage.

Historiques

06133338

Historiques

06133330

Utiliser le menu Configurer Micrologic pour


choisir la langue des affichages, la date et
l'heure, les informations sur le disjoncteur, le
sens du signe de puissance, le rapport TT
(Transfo de U) et la frquence du rseau.

Figure 45 : Configuration du dclencheur Micrologic


06133330

Configuration du dclencheur
Micrologic

48049-137-05
Rev. 01, 07/2012

Langue
Date / heure
Slection
disjoncteur

FRANAIS

Signe
puissance
Transfo
de U
Entre

Langue
Deutsch
English US
English UK
Espaol
Franais
Haut/
Bas
Entre

36-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

REMARQUE : Dans langlais utilis aux


tats-Unis, le format de la date est
mois/jour/anne. Dans toutes les autres
langues, le format de la date est
jour/mois/anne.
Aprs l'emploi de la trousse d'essais pour
effectuer un essai d'injection secondaire,
d'inhibition de limage thermique, des essais
ZSI ou du dfaut de mise la terre, le
rglage de l'heure doit tre refait si le
dclencheur n'est pas reli un rseau de
communication assurant la synchronisation
de la date et de l'heure.
REMARQUE : Si l'heure n'est pas
synchronise par un surveillant se servant
du logiciel de gestion des systmes en
rseau, rgler l'heure tous les six mois ou
plus souvent si ncessaire.

Langue
Date / heure

Date

Date

Date

25 / 01 / 2001

28
02 / 01 / 2001

02 / 2001
28 / 28

Slection
disjoncteur

Heure

Heure

Heure

Signe
puissance

18:12:35

18:12:35

18:12:35

Transfo
de U
Entre

Entre

Haut/
Bas

Haut/
Bas
Entre

Entre

Date

Date

Date

Date

2001
28 / 02 / 2001

28 / 02 / 2001

28 / 02 / 2001

28 / 02 / 2001

Heure

Heure

Heure

Heure

18:12:35

Haut/
Bas

18:12:35

Bas

Entre

Entre

Date

Date

28 / 02 / 2001

28 / 02 / 2001

Heure

Heure

25
19:11:35

Haut/
Bas

18:12:35
18

Haut/
Bas
Entre

11
19:12:35

FRANAIS

REMARQUE : Si le dclencheur est


raccord un rseau de communication qui
fournit la synchronisation de la date et de
l'heure, la date/l'heure ne peuvent pas tre
rgles partir du dclencheur. Si le
dclencheur n'est pas reli un rseau de
communication qui assure la
synchronisation de la date et de l'heure, la
date et l'heure devront tre entres de
nouveau aprs chaque mise hors tension du
dclencheur.

Figure 47 : Configuration de la date et l'heure


06133339

2. Rgler la date et l'heure du dclencheur.

Haut/
Bas
Entre

19:11:25

Sortie

Entre

20002012 Schneider Electric Tous droits rservs

37-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

Figure 48 : Configuration des informations du disjoncteur


06133339

3. Entrer les informations du disjoncteur dans


la mmoire du dclencheur. Les
informations suivantes doivent tre entres
pour identifier correctement le disjoncteur
sur le rseau de communication :

48049-137-05
Rev. 01, 07/2012

Date / heure

NormeANSI, UL, IEC ou IEC/GB

Slection
disjoncteur

Famille du disjoncteurMasterpact (ANSI,


UL, IEC ou IEC/GB), Powerpact (UL ou IEC)
ou Compact NS (IEC)

Signe
puissance

Type de disjoncteurCes renseignement se


trouvent sur la plaque avant du disjoncteur
Code d'usure des contacts du disjoncteur
N'est modifi qu' l'occasion du
remplacement d'un dclencheur existant,
ayant loption d'usure des contacts.
REMARQUE : Le dispositif de mesure de
l'usure des contacts n'est actif que pour un
disjoncteur de type Masterpact.

a. Lire le code sur le dclencheur


remplacer. (Le code est un nombre
hexadcimal.)
b. Retirer lancien dclencheur et installer le
dclencheur neuf sur le disjoncteur.
c. Entrer le code lu sur l'ancien
dclencheur, sur le dclencheur neuf.

Transfo
de U

Norme
UL
disjoncteur
Masterpact
type
NW32H2
0000

HLogic2002AA

HLogic2002AA
Haut/
Bas

HLogic2002AA

Entre

Entre

Slection
disjoncteur

Slection
disjoncteur

Slection
disjoncteur

Norme
ANSI
disjoncteur
Masterpact
type
NW32H2
0000

Entre

Entre

Slection
disjoncteur

Norme
ANSI
disjoncteur
Masterpact
type
NW32H2
0000

Norme
UL
disjoncteur
Masterpact
type
NW32H2
0000

Norme
UL
disjoncteur
Masterpact
type
NW40H2
0000

HLogic2002AA
Haut/
Bas

HLogic2002AA

HLogic2002AA
Haut/
Bas

Entre

Entre

Entre

Slection
disjoncteur

Slection
disjoncteur

Slection
disjoncteur

Bas

Bas

Slection
disjoncteur

Norme
UL
disjoncteur
Masterpact
type
NW32H2
0000

Slection
disjoncteur

Norme
UL
disjoncteur
Masterpact
type
NW40H2
0000

Norme
UL
disjoncteur
Masterpact
type
NW40H2
0000

Norme
UL
disjoncteur
Masterpact
type
NW40H2
1000

Norme
UL
disjoncteur
Masterpact
type
NW40H2
10
200

HLogic2002AA

HLogic2002AA

HLogic2002AA

HLogic2002AA

Haut/
Bas

Bas
Entre

Entre

Bas
Entre

Haut/
Bas
Entre
Rpter pour chaque
chiffre rgler.

Slection
disjoncteur
Norme
UL
disjoncteur
Masterpact
type
NW40H2
1234

06133335

FRANAIS

Pour maintenir les informations d'indication


d'usure des contacts lors du remplacement
d'un dclencheur :

Slection
disjoncteur

Langue

Voulez-vous
enregistrer
les
modifications?
non

Ne modifier le code dusure des contacts


qu'en cas de remplacement du disjoncteur.

oui

HLogic2002AA
Sortie

Bas
Entre

38-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

Signe
puissance

Langue

Signe
puissance

Date / heure

P+ : Puissance absorbe d'amont en


aval (alimentation par les bornes
suprieures)

P-

Slection
disjoncteur

P+

Signe
puissance

P- : Puissance absorbe d'aval en amont


(alimentation par les bornes infrieures)

Voulez-vous
enregistrer
les
modifications?
non
oui

Transfo
de U

La valeur par dfaut est P+

06133335

Choisir la convention du signe utiliser pour


la mesure de la puissance, de l'nergie et du
dlestage-relestage :

Figure 49 : Configuration du signe de la puissance


06133339

4. Slectionner le signe de la puissance.

Entre

Haut/
Bas

Entre

Bas
Entre

Entre
Sortie

Transfo
de U

Langue
Date / heure
Slection
disjoncteur

Transfo
de U

Transfo
de U

Primaire

Primaire

690V

690V

660V

Secondaire

Secondaire

Secondaire

690V

690V

690V

Signe
puissance

Primaire

FRANAIS

Si la tension d'alimentation du dclencheur


dpasse 690 V, un transformateur de
tension externe est requis.

Figure 50 : Configuration du rapport du transformateur de tension


06133339

5. Entrer le rapport du transformateur de


tension (Transfo de U) externe dans la
mmoire du dclencheur. En l'absence d'un
tel transformateur, rgler les deux valeurs
(primaire et secondaire) 690 V.

Transfo
de U
Entre

Entre

Haut/
Bas

Transfo
de U
Primaire

660V
Secondaire

690V

Entre

06133335

Entre

Bas

Voulez-vous
enregistrer
les
modifications?
non
oui

Haut/
Bas
Entre

Bas
Entre

Sortie

20002012 Schneider Electric Tous droits rservs

39-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

Date / heure
Slection
disjoncteur

La valeur absolue de la puissance


ractive sera correcte, mais son signe
sera incorrect.

Signe
puissance
Transfo
de U
Frquence
rseau

La valeur absolue du facteur de


puissance sera correcte, mais son signe
sera incorrect.

Frquence
rseau

50-60Hz

50-60Hz

Voulez-vous
enregistrer
les
modifications?
non
oui

Haut/
Bas

Entre

Entre

La valeur de la frquence peut ne pas


tre prcise.

Frquence
rseau

06133335

REMARQUE : Lorsque la frquence du


systme est rgle 400 Hz :

Figure 51 : Configuration de la frquence du rseau


06133340

6. Entrer la frquence du rseau dans la


mmoire du dclencheur.

48049-137-05
Rev. 01, 07/2012

Entre

La protection en frquence est


dsactive.

Bas
Entre

Sortie

La protection du sens de rotation des


phases est dsactive.

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.
Bas

40-FR

06133330

FRANAIS

Utiliser le menu Configurer mesures pour


configurer les paramtres de mesure du courant
et de la puissance du systme.

Figure 52 : Configuration des mesures


06133330

Configuration des mesures

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

Type de
rseau
Calcul
I moyen
Calcul
P moyen
Convention
de signe

Entre

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

Type de rseau

Neutre

Courant de
phase

Triphas, 3 fils, 3 TC
(utilise 2 wattmtres)

Non

I1, I2 , et I3
msurs

Triphas, 4 fils, 4 TC*


(utilise 3 wattmtres)

Oui

I1, I2 , I3 et In
msurs

Non

I1, I2, et I3
msurs

Triphas, 4 fils, 3 TC
(utilise 3 wattmtres)

Type de
rseau
Calcul
I moyen.
Calcul
P moyen.
Convention
de signe

Entre
*Ne pas utiliser le type triphas, 4 fils, 4 TC sauf si le
neutre est effectivement raccord au dispositif de
dclenchement (la connexion de la tension du neutre
est externe au disjoncteur tripolaire). (Voir les directives
d'installation du TC du neutre.)

Type de
rseau

Type de
rseau

3) 4fils
3 TC

3) 3fils
3 TC

06133335

Trois options de mesure sont disponibles :

Figure 53 : Configuration du type de rseau


06133311

1. Slectionner le type de rseau.

Voulez-vous
enregistrer
les
modifications?
non
oui

Haut/
Bas

Entre

Entre

Bas
Entre

Sortie

REMARQUE : Dans le cas d'un disjoncteur


quadripolaire, la possibilit de rgler le neutre
est limite par le rglage du commutateur du
type de neutre du disjoncteur.

FRANAIS

La mesure de In n'est pas disponible pour les


rseaux de type triphas, 4 fils, 3 TC et
les mesures de tension simple V1n, V2n et
V3n ne sont pas disponibles pour les rseaux
de type triphas, 3 fils, 3 TC.
Si ces mesures sont dsires et si le rseau
connect est un systme en toile ( 4 fils),
slectionner triphas, 4 fils, 4 TC et
raccorder la borne de tension du neutre
(Vn ) sur le TC du neutre.

20002012 Schneider Electric Tous droits rservs

41-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

La mthode de calcul peut tre moyenne


arithmtique ou modle thermique.

Figure 54 : Configuration de la mthode de calcul du courant moyen


(demande de courant)
06133311

2. Rgler la mthode de calcul de la demande


de courant (Calcul Imoyen.) et sa dure.

48049-137-05
Rev. 01, 07/2012

Le type de fentre de dure est rgl


l'usine comme fentre glissante.
La dure peut tre rgle de 5 60 minutes
en incrments d'une minute.

Type de
rseau
Calcul
I moyen.
Calcul
P moyen.
Convention
de signe

Entre

Calcul
Imoyen.

Calcul
Imoyen.

Mthode
de calcul
moyenne
arithm.
Type fentre
glissante
Dure

Mthode
de calcul
modle
thermique
Type fentre
glissante
Dure

Mthode
de calcul
modle
thermique
Type fentre
glissante
Dure

15 min

15 min

15 min

Haut/
Bas

Entre

Entre

Calcul
Imoyen.

FRANAIS

Mthode
de calcul
modle
thermique
Type fentre
fixe
Dure

Mthode
de calcul
modle
thermique
Type fentre
fixe
Dure

25 min

25 min

Haut/
Bas

oui
Bas

Sortie

Entre

Le type de fentre de dure par dfaut est


glissante.
La dure peut tre rgle de 5 60 minutes
en incrments d'une minute.

Type de
rseau
Calcul
I moyen.
Calcul
P moyen.
Convention
de signe

Entre

Calcul
Pmoyen.

Calcul
Pmoyen.

Mthode
de calcul
moyenne
arithm.
Type fentre
glissante
Dure

Mthode
de calcul
modle
thermique
Type fentre
glissante
Dure

Mthode
de calcul
modle
thermique
Type fentre
glissante
Dure

15 min

15 min

15 min

Haut/
Bas

Entre

Entre

Calcul
Pmoyen.

Calcul
Pmoyen.

Mthode
de calcul
modle
thermique
Type fentre
fixe
Dure
25 min

Mthode
de calcul
modle
thermique
Type fentre
fixe
Dure

Haut/
Bas
Entre

42-FR

Calcul
Pmoyen.

Bas
Bas
Entre

06133335

REMARQUE : La synchronisation par


communication n'est disponible qu'avec
l'option de communication. La puissance
moyenne est determine partir d'un
signal synchronis par le module de
communication.

Figure 55 : Configuration de la mthode de calcul de la puissance


moyenne
06133311

La mthode de calcul peut tre moyenne


arithmtique, modle thermique ou
synchronisation par communication.

Entre

Voulez-vous
enregistrer
les
modifications?
non

Entre

3. Rgler la mthode de calcul de la demande


de puissance (Calcul Pmoyen.) et sa dure.

Bas
Bas

06133335

Calcul
Imoyen.

Calcul
Imoyen.

Voulez-vous
enregistrer
les
modifications?
non
oui

25 min
Sortie

Bas
Entre

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

IEEE
IEC
IEEE alternate

Figure 56 : Configuration de la convention de signe


Type de
rseau
Calcul
I moyen.
Calcul
P moyen.
Convention
de signe

Convention
de signe

Convention
de signe

IEEE

IEC

06133335

Choisir la convention de signe utiliser pour


la mesure de la puissance ractive (VARS),
de l'nergie ractive (VARhrs) et du facteur
de puissance :

06133311

4. Slectionner la convention de signe.

Voulez-vous
enregistrer
les
modifications?
non
oui
Haut/
Bas

Entre

Entre

Entre

Bas
Entre

Sortie
Convention de signe IEEE
Puissance
ractive

coul. P normal

coul. P inverse

Quadrant 3
Watts ngatifs (-)
VAR ngatifs (-)
Dphasage arr. FP (-)

FRANAIS

Quadrant 1
Quadrant 2
Watts positifs (+)
Watts ngatifs (-)
VAR positifs (+)
VAR positifs (+)
Dphasage av. FP (+) Dphasage arr. FP (-)
Puiss.
active

Quadrant 4
Watts positifs (+)
VAR ngatifs (-)
Dphasage av. FP (+)

Convention de signe IEC


Puissance
ractive

Quadrant 2
Watts ngatifs (-)
VAR positifs (+)
Dphasage av. FP (-)

Quadrant 1
Watts positifs (+)
VAR positifs (+)
Dphasage arr. FP (+)
coul. P normal

coul. P inverse

Puiss.
active

Quadrant 3
Quadrant 4
Watts ngatifs (-)
Watts positifs (+)
VAR ngatifs (-)
VAR ngatifs (-)
Dphasage arr. FP (-) Dphasage av. FP (+)

Convention de signe IEEE alternate


Puissance
ractive

Quadrant 1
Quadrant 2
Watts positifs (+)
Watts ngatifs (-)
VAR ngatifs (-)
VAR ngatifs (-)
Dphasage av. FP (+) Dphasage arr. FP (-)
coul. P inverse

Quadrant 3
Watts ngatifs (-)
VAR positifs (+)
Dphasage arr. FP (-)

20002012 Schneider Electric Tous droits rservs

coul. P normal

Puiss.
active

Quadrant 4
Watts positifs (+)
VAR positifs (+)
Dphasage av. FP (+)

43-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

REMARQUE : Les paramtres de configuration


de la communication ne peuvent tre entrs que
si un module de communication de disjoncteur
(BCM) est install.

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

Figure 58 : Configuration des valeurs de Com ModbusMC


06133459

Adresse = 47

Paramtre
com.
Rglage
distance
Commande
distance

Entre

Bas

1. Rgler les paramtres de communication.


Les valeurs par dfaut sont les suivantes :

06133459

Utiliser le menu Configurer Com. pour


effectuer la configuration du module de
communication.

06133330

Figure 57 : Configuration du module de communication


06133330

Configuration du module de
communication

48049-137-05
Rev. 01, 07/2012

Vitesse de communication (Baud-rate) =


19,2k
Parit = paire

Paramtre
com.
Rglage
distance
Commande
distance

Com
Modbus

Com
Modbus

Adresse

Adresse

Adresse

FRANAIS

Baud-rate

Baud-rate

19200

19200

Baud-rate

19200

Parit

Parit

Parit

Paire

Paire
Entre

Com
Modbus

Paire
Haut/
Bas

Entre

Bas
Entre

Com
Modbus
Adresse

Com
Modbus
Adresse

Adresse

Baud-rate

19200
Parit

Baud-rate

19200
Parit

Paire

Entre

Baud-rate

19200
Parit

Paire
Haut/
Bas

Com
Modbus

Haut/
Bas

Entre

Voulez-vous
enregistrer
les
modifications?
non
oui

Paire

Bas

06133335

Entre

Entre

Bas
Entre

Sortie

L'accs distance est confugur l'usine et


ne demande aucun rglage.
REMARQUE : Le rglage de l'accs
distance peut tre modifi pour permettre
aux rglages de protection d'tre modifis au
moyen du rseau de communication.
Contacter votre bureau de vente local
concernant le logiciel disponible pour utiliser
cette particularit.

Figure 59 : Vrification de laccs distance


06133459

2. Rglage distance.

Paramtre
com.
Rglage
distance
Commande
distance

Rglage
distance
Autorisation
d'accs

Non
Code
accs

0000
Entre

44-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

Automatique : Le disjoncteur peut tre


ouvert ou ferm par l'intermdiaire du logiciel
de gestion des systmes en rseau.
REMARQUE : Pour le fonctionnement
distance du disjoncteur, le BCM doit tre
rgl de faon permettre l'ouverture ou la
fermeture, et le disjoncteur doit tre muni de
bobines shunt de communication avec leurs
faisceaux de cbles installs.

Paramtre
com.
Rglage
distance
Commande
distance

Commande
distance
Manu

Commande
distance

06133335

Manuelle : Le disjoncteur ne peut pas tre


ouvert ou ferm par l'intermdiaire du logiciel
de gestion des systmes en rseau.

Figure 60 : Configuration de la commande distance


06133459

3. Rgler la commande distance.

Voulez-vous
enregistrer
les
modifications?
non

Auto

oui
Entre

Haut/
Bas

Entre

Entre

Bas
Entre

Sortie

AVIS
RISQUE DES DOMMAGES MATRIELS
L'emploi des commutateurs pour dfinir les valeurs du dclencheur
annule les rglages effectus l'aide du clavier.
La modification des rglages des commutateurs pour les surcharges
temps court ou instantanes ou le changement du slecteur de
protection du neutre sur un disjoncteur quadripolaire annule tous les
affinements des rglages prcdemment effectus l'aide du clavier
pour la protection contre les surcharges temps court et instantane.
La modification du rglage des commutateurs pour le dfaut de mise
la terre annule tous les affinements des rglages effectus avec le
clavier pour la protection contre les dfauts la terre.
Si l'ergot situ sur la face interne du couvercle des commutateurs
manque, contacter votre bureau de vente pour obtenir un couvercle de
rechange.
Si ces directives ne sont pas respectes, cela peut entraner des
dommages matriels.

20002012 Schneider Electric Tous droits rservs

45-FR

FRANAIS

Affinement des rglages des


commutateurs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

5.0 P

5.0 P

06134826

5.0
logic
Micro

D
F

3. Rgler les commutateurs (C) appropris aux


valeurs dsires. L'cran (D) affiche
automatiquement la courbe de rglage (E)
adquate. La valeur rgle est affiche en
encadr en ampres et en secondes.

4. Effectuer les rglages mticuleux l'aide


des touches de navigation (F) ou du logiciel
de gestion des systmes en rseau. Tous
ces rglages sont stocks dans une
mmoire non volatile.

B
Courbe de
dclenchement Idmtl

Idmtl (A)

Idmtl (A)
Trip

Trip
1000 A

Ir

1000 A

1.0 s

tr

1.0 s
EIT

2000 A
0.2 s

2000 A
0.2 s

Isd
tsd
Ii

4000 A

Les rglages mticuleux des commutateurs


se font par les incrments suivants :

Courbe de dclenchement
sur dfaut la terre

06134767

06134765

Courbe de
dclenchement I2t

4000 A

I (A)
Trip

Ir
tr

1200A

Ig

0.5s

tg

Idmtl
Isd
tsd
Ii

Enclenchement de longue dure = 1 A


Exemple

Retard de longue dure = 0,5 s

06134768

Enclenchement de courte dure = 10 A


Retard de courte dure = 0,1 s
log
Micro

Enclenchement instantan = 10 A
Enclenchement sur dfaut la
terre = 1 A
Retard de dfaut la terre = 0,1 s

46-FR

06134826

FRANAIS

REMARQUE : Les rglages mticuleux ne


peuvent tre effectus que pour des valeurs
infrieures celles rgles avec les
commutateurs. L'emploi des commutateurs
pour rgler les valeurs aprs avoir effectu
des rglages mticuleux l'aide du clavier
annule les rglages au clavier.

logic

Micro

06134755

ogic

Microl

06134766

2. Confirmer que l'ergot (B) du couvercle se


trouve bien sur la face interne du couvercle
de protection. Cet ergot est ncessaire pour
verrouiller les rglages du dclencheur
lorsqu'ils sont configurs pour le mode Trip
(Dclenchement).

Figure 61 : Affinement des rglages des commutateurs

06134825

1. Ouvrir le couvercle des commutateurs (A).

48049-137-05
Rev. 01, 07/2012

ic 5.0

I(A)

I(A)

I(A)

Trip

Trip

Trip

1000 A

1000 A

995 A

1.0 s

1.0 s

1.0 s

2000 A
0.2 s

2000 A
0.2 s

2000 A
0.2 s

4000 A

4000 A

4000 A

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

logic

5.0 P

logic

06134756

REMARQUE : Lorsque le couvercle est


ferm, les touches de navigation ne peuvent
plus tre employes pour ajuster les
rglages du dclencheur si elles sont
rgles pour le mode Trip (dclenchement).

Figure 62 : Vrification des rglages des commutateurs

Micro

06134828

5. Replacer le couvercle des commutateurs.


Utiliser un kit de scellement fils
MICROTUSEAL (A, non fourni), pour fournir
une preuve d'effraction, si ncessaire.

5.0 P

Micro

6. Vrifier les rglages l'aide du clavier (B) et


de l'afficheur graphique ou du logiciel de
gestion des systmes en rseau.
B

Exemples
Figure 63 : Configuration des niveaux d'enclenchement

BRetard de longue dure (tr)


CEnclenchement de courte dure (Isd)
DRetard de courte dure (tsd)

A
B

.7
.6
.5
.4

.8

x In

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5
@ 6 Ir

C
D

tsd
(s)

.3
.2
.1

I t

setting

.2
.1
0
off

6 8 10
4
12
3
15
off
2
x In

delay

Ii
0

2. Affiner le rglage l'aide du clavier et de


l'cran d'affichage graphique ou du logiciel
de gestion des systmes en rseau.

BRetard de longue dure (tr)


CEnclenchement de courte dure (Isd)
DRetard de courte dure (tsd)
EEnclenchement instantan (Ii)
FEnclenchement sur dfaut la terre (Ig)
GRetard de dfaut la terre (tg)

Ir

Ii

A
B
C
D
F
G

long time

Ir
.7
.6
.5
.4

alarm

tr
8
(s) 4
.9
12
16
.95 2
.98 1
20
24
1
.5

.8

x In

@ 6 Ir

tsd
(s)

on

setting

D
C
B
A

.2
.1
2

I t

0
off

delay

tg
F
G
H
J

(s)

Ii

.4 .4 .3

.3
.2
.1

A
tr

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir
Ig

Ir

06134751

06134754

Figure 64 : Configuration des niveaux d'enclenchement

6 8 10
4
12
3
15
off
2
x In
test

Isd C
tsd

Ii

.4 .4 .3

.3
.2
.1
on

.2
.1
0
I t off

Ir

Isd

D
E

Ii

ground fault

In 2000 A

t
I2t on
Ig

2. Affiner le rglage l'aide du clavier et de


l'cran d'affichage graphique ou du logiciel
de gestion des systmes en rseau.

F
tg

20002012 Schneider Electric Tous droits rservs

Isd

D
E

In 2000 A

1. Rgler les commutateurs :


AEnclenchement de longue dure (Ir)

Isd C
tsd

EEnclenchement instantan (Ii)

Dclencheur Micrologic 6.0P

Ii

.4 .4 .3

on

A
tr

instantaneous

short time

Isd
4
5
3
2.5
6
2
8
1.5
10
x Ir

Ir

06134758

AEnclenchement de longue dure (Ir)

long time

Ir

FRANAIS

1. Rgler les commutateurs :

06134751

06134753

Dclencheur Micrologic 5.0P

Ig

I2t off

47-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

Dclencheurs Federal Pioneer USRC et USRCM

Dclencheurs Merlin Gerin STR58

Appareil en aval
(envoie une sortie au RIM)

Relais de dfaut la terre GC-200 de Square D


pour la protection des appareils

Appareil en amont
(reoit une entre du RIM)

Relais de dfaut la terre GC-100 de Square D


pour la protection des appareils

Le nombre d'appareils pouvant tre


interverrouills est indiqu au tableau 10.

Dclencheurs Micrologic srie B de Square D

Tableau 10 : Combinaisons ZSI

Dclencheurs Micrologic no .0x

Interverrouillage slectif de zone


(ZSI)

48049-137-05
Rev. 01, 07/2012

FRANAIS

Dclencheurs Micrologic no .0x

15

15

15

Dclencheurs Micrologic srie B de


Square D

26

15

Relais de dfaut la terre GC-100 de


Square D pour la protection des
appareils

Relais de dfaut la terre GC-200 de


Square D pour la protection des
appareils

15

15

15

Dclencheurs Merlin Gerin STR58

15

15

15

Dclencheurs Merlin Gerin STR53

15

15

15

Dclencheurs Federal Pioneer USRC et


R
USRCM

15

15

Module de dfaut la terre


supplmentaire de Square D pour la
protection des appareils

RUne module d'interface retardateur (RIM) est requis pour retarder n'importe quel appareil.
Rfrences numriquesLe nombre maximum de disjoncteurs en amont qui peuvent tre
retards sans l'installation d'un module dinterface retardateur (RIM).

Les bornes des disjoncteurs sont expdies


avec les bornes Z3, Z4 et Z5 relies par cavalier
pour produire une auto-entrave des fonctions de
courte dure et de dfaut la terre. Retirer les
cavaliers lors de l'activation de l'interverrouillage
slectif de zone.

Figure 65 : Bornes relies par cavalier

UC1
Z5
M1
Z3

Z4

Z1

Z2

Connexions auxiliaires

48-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

Figure 66 : Exemple de cblage de ZSI

REMARQUE : Utiliser la fonction I2t dsactiv


avec ZSI pour une bonne coordination.
L'utilisation de la fonction I2t avec ZSI n'est pas
recommande puisque le retard avec lequel le
dispositif en amont recevra un signal d'entrave
peut entraner le dclenchement du dclencheur
en un temps plus court que la courbe de
dclenchement publie.

Z4

Z1

Z2

UC1
Z5
M1

Position
connecteur
secondaire
Z1
Z2
Z3
Z4
Z5

Z3

Z4

Z1

Z2

Description
Signal de sortie ZSI
Sortie ZSI
Signal d'entre ZSI
Entre de courte dure ZSI
Entre de dfaut la terre ZSI

Z4

Z1

Z2

Figure 67 : Vrification du fonctionnement du dclencheur

5.0
ogic

ogic

Microl

Microl

5.0 P

Figure 68 : Rarmement du dclencheur


06134781

Lorsque le disjoncteur se dclenche, le voyant


de dfaut reste allum jusqu'au rarmement du
dclencheur.

Z3

Connexions
auxiliaires 3

REMARQUE : Pour vrifier le fonctionnement


du disjoncteur et du dclencheur, utiliser un
essai d'injection primaire. (Voir Vrification de
linstallation du dclencheur la page 68 pour
des informations supplmentaires.)

Rarmement du dclencheur

UC1
Z5
M1

Connexions
auxiliaires 2

FRANAIS

Utiliser une trousse dessais raccorde la prise


d'essai (A) du dclencheur pour vrifier si le
dclencheur fonctionne comme il faut. Consulter
les directives fournies avec la trousse d'essai
pour effectuer les essais de vrification.

Z3

Connexions
auxiliaires 1

06134825

Vrification du fonctionnement
du dclencheur

UC1
Z5
M1

06134086

Cbler les disjoncteurs pour l'interverrouillage


slectif de zone.

Micrologic 6.0P

Ne pas remettre le disjoncteur sous tension


sans avoir dtermin la cause du
dclenchement. Pour plus d'informations, se
reporter aux directives d'installation du
disjoncteur expdies avec ce dernier.
Appuyer sur le bouton de remise zro/d'essai
(Test/Reset) (A) pour rarmer le dclencheur
aprs un dclenchement.

20002012 Schneider Electric Tous droits rservs

49-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

Vrification de la fonction de
dclenchement de l'appareil sur
dfaut la terre
Figure 69 : Vrification de la fonction de dclenchement de lappareil
sur dfaut la terre

06134784

Le paragraphe 230-95(c) du Code national de


llectricit (NEC; .-U.) requiert que tous les
systmes de protection des appareils contre les
dfauts la terre soient vrifis quand ils sont
installs la premire fois.

logic

5.0 P

Micro

Avec le dclencheur sous tension et le


disjoncteur ferm, vrifier la fonction de
dclenchement de lappareil sur dfaut la terre
(dclencheur Micrologic 6.0P).
Le dclencheur est sous tension si :

FRANAIS

si le disjoncteur est sous tension et a une


tension de charge de plus de 150 V sur deux
phases (le disjoncteur est ferm ou aliment
par ses bornes infrieures).

si la trousse d'essais des fonctions


compltes ou portative est raccorde et sous
tension.

si l'alimentation externe de 24 V cc est


raccorde.

si le drivateur de tension externe est


install et si une tension de plus de 150 V
est prsente sur deux phases.

Pour obtenir les directives de fermeture du


disjoncteur, se reporter aux directives
d'installation expdies avec le disjoncteur.
Pour essayer la fonction de dclenchement,
appuyer sur le bouton d'essai de dfaut la
terre (A). Le disjoncteur doit se dclencher.
Si le disjoncteur ne se dclenche pas, contacter
votre bureau de service local.

50-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 3Configuration du dclencheur

48049-137-05
Rev. 01, 07/2012

Vrification de ltat du
dclencheur
Vrifier la pile du dclencheur et les voyants de
dclenchement.
1. S'assurer que le dclencheur est sous
tension. Le dclencheur est sous tension :
si le disjoncteur est sous tension et a une
tension de charge de plus de 150 V sur
deux phases (le disjoncteur est ferm ou
aliment par ses bornes infreiures).

2. Appuyer sur le bouton dessai/de remise


zro (A).

Micrologic 6.0P

Pile charge
Pile moiti charge

FRANAIS

si le drivateur de tension externe est


install et si une tension de plus de
150 V est prsente sur deux phases.

06133380

si l'alimentation externe de 24 V cc est


raccorde.

Figure 70 : Vrification de ltat du dclencheur

06134782

si la trousse d'essais des fonctions


compltes ou portative est raccorde et
sous tension.

Remplacer la pile

Tous les voyants de dclenchement (B)


s'allument
L'tat de la pile s'affiche
Le relev du graphique en barres de la
pile est valide aprs avoir relch le
bouton de rarmement.
3. Si le graphique en barres de la pile indique
que la pile a besoin dtre remplace, utiliser
le numro de catalogue S33593 Square D :
pile au lithium
1,2AA, 3,6 V, 800 ma/h
Pour les directives de remplacement de la pile,
voir le chapitre 7Remplacement de la pile.

20002012 Schneider Electric Tous droits rservs

51-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

48049-137-05
Rev. 01, 07/2012

Section 4Fonctionnement

Figure 71 : Menu Mesures


06134267

Valeurs mesures
Utiliser les menus de mesures pour surveiller le
courant (I), la tension (U), la puissance (P),
l'nergie (E) et la frquence (F) du disjoncteur.
REMARQUE : Les caractristiques du systme
peuvent tre galement vrifies distance
avec le logiciel System Manager Software
(SMS), version 3.3 ou ultrieures, ou autre
logiciel de gestion de systmes en rseau.

I1Courant instantan de la phase 1

FRANAIS

I2Courant instantan de la phase 2


I3Courant instantan de la phase 3
InCourant instantan du neutre
I Courant instantan la terre
I1maxCourant instantan maximum de la
phase 1
I2maxCourant instantan maximum de la
phase 2
I3maxCourant instantan maximum de la
phase 3

(A)

U
P
E

(V)
(kWh)

(Hz)

(Hz)

I (A)

Iinst.

instant.

I1 , I2 , I3 , In

moyen

Max.

Iinst.

Imax

I1 , I2 , I3 , I n
Max

I1 =

301 A

I2 =
I3 =
In =
I =

309 A
309 A
307 A
17 A

Entre

Iinst.

Bas

Entre
(Rz)

Entre

Sortie

Imoyen

Imoyen

I1, I2, I3, In


Max

I3maxDemande de courant max. de la


phase 3

52-FR

I1 =
I2 =
I3 =

0A
0A
0A

In =
I =

0A
0A

Sortie

I (A)

I1 , I2 , I3 , In

instant.

Max

moyen

15 min
I1 =
I2 =
I3 =

356 A
148 A
159 A

In =

84 A

Sortie

Bas
Entre

Imoyen
I1, I2, I3, In
Max

InmaxDemande de courant max. du neutre


Les mesures maximales peuvent tre
galement remises zro.

Iinst.

Reset (- / +)

I2 Demande de courant de la phase 2

I2maxDemande de courant max. de la


phase 2

(kWh)

(kW)

Entre

I1 Demande de courant de la phase 1

I1maxDemande de courant max. de la


phase 1

(V)

Entre

I maxCourant instantan maximum la terre

In Demande de courant du neutre

U
P
E

(kW)

InmaxCourant instantan maximum du neutre

I3 Demande de courant de la phase 3

(A)

Figure 72 : Vrification des niveaux des courants


06134267

Niveaux des courants

Imax

moyen
15 min
I1 = 357 A
I2 = 148 A
I3 = 185 A
1A
In =
Reset (- / +)

Entre

Sortie

Bas

Entre
(Rz)

Entre

Sortie

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

48049-137-05
Rev. 01, 07/2012

U23Tension instantane entre les phases 2


et 3
U31Tension instantane entre les phases 3
et 1
V1nTension instantane entre la phase 1 et le
neutre

V3nTension instantane entre la phase 3 et le


neutre

(A)

U
P
E

(kWh)

(Hz)

(V)
(kW)

Entre
06133858

V2nTension instantane entre la phase 2 et le


neutre

U (V)
instant.
moyen 3

06133858

U12Tension instantane entre les phases 1


et 2

Figure 73 : Vrification des niveaux des tensions


06134267

Niveaux des tensions

U Inst.

U (V)
instant.

U12 = 430 V
U23 = 401 V
U31 = 431 V

moyen 3
dsq. 3

V1n = 245 V
V2n = 242 V
V3n = 242 V

Rotation
phases
Entre

Sortie

Umoyen
3)
421 V

dsq. 3

Bas

FRANAIS

Rotation
phases
Sortie

06133858

Entre

U (V)
instant.
moyen 3

Udsq.
3)
-4 %

dsq. 3
Rotation
phases

Bas

Sortie

U (V)

Rotation phases

instant.
moyen 3

') 1, 2, 3

06133858

06133858

Entre

U (V)
instant.
moyen 3

dsq. 3

dsq. 3

Rotation
phases

Rotation
phases

Bas

Sortie

Sortie

Entre

20002012 Schneider Electric Tous droits rservs

53-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

PPuissance active instantane

Figure 74 : Vrification des niveaux des puissances


06134267

Niveaux des puissances

48049-137-05
Rev. 01, 07/2012

(A)
(V)

Facteur de puissanceFacteur de puissance


instantan

U
P
E

(kWh)

P Demande de puissance active

(Hz)

QPuissance ractive instantane


SPuissance apparente instantane

QDemande de puissance ractive

Pinst.

instant.

P, Q, S

moyen

Facteur de
puissance

(kW)
0

(kvar)
0

(kVA)
0

(kW)

Entre

Pinst.

P (kW)

Entre

Entre

Sortie

SDemande de puissance apparente

Pinst.

PmaxDemande de puissance active


maximale

P, Q, S

QmaxDemande de puissance ractive


maximale

Facteur de
puissance

SmaxDemande de puissance apparente


maximale

-0.16
Lag
(Ind.)

FRANAIS

Les mesures maximales peuvent tre


galement remises zro.
REMARQUE : Pour assurer des mesures
fiables de la puissance et du facteur de
puissance, Signe puissance, page 39, et
Convention de signe, page 43, doivent tre
rgls.

Facteur de
puissance

Bas

Sortie

Entre

Sortie

P (kW)

P, Q, S

moyen

Max

Bas

Entre

Entre

Pmax
moyen
(kW)
26
(kvar)
Q
86
S
(kVA)
92
Reset (- / +)
P

54-FR

Pmoyen

Pmoyen

instant.

(kW)
26

(kvar)
83

(kVA)
87

Sortie

Pmoyen
P, Q, S
Max

Bas
Entre

Pmoyen
P, Q, S
Max

Entre
(Rz)

Sortie

Sortie

Sortie

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

48049-137-05
Rev. 01, 07/2012

nergie active totale (P)


nergie ractive totale (Q)
nergie apparente totale (S)
nergie active consomme (+) (E.P.)
nergie ractive consomme (+) (E.Q.)
nergie active fournie (-) (E.P.)
nergie ractive fournie (-) (E.Q.)
Les mesures d'energie peuvent tre galement
remises zro.
REMARQUE : Pour assurer des mesures
fiables d'nergie, Signe puissance, page 39,
et Convention de signe, page 43, doivent tre
rgls.

Figure 75 : Vrification des niveaux des nergies


06134267

Niveaux des nergies

(A)

U
P
E

(V)
(kWh)

(Hz)

(kW)

Entre

E (kW)
E totale
E+
Consomme
EFournie

E (kW)
E totale
E+
Consomme
EFournie
Reset
nergies

Entre

E totale
E. P

(kWh)
0

E. Q (kvarh)
0
E. S

(kVAh)
0

Sortie

E+
Consomme
E. P

(kWh)
0

E. Q (kvarh)
0

FRANAIS

Reset
nergies
Sortie

Bas
Entre

E (kW)
E totale
E+
Consomme
EFournie

E - Fournie
E. P

(kWh)
0

E. Q (kvarh)
0

Reset
nergies
Bas

Sortie

Entre

E (kW)
E totale
E+
Consomme
EFournie
Reset
nergies

20002012 Schneider Electric Tous droits rservs

Reset
nergies
Voulez-vous
remettre
zro les
nergies ?

E totale
Pour
confirmer
appuyer
sur
entre

oui
Bas
(Rz)

Entre

Entre

Entre

(kWh)
0

E. Q (kvarh)
0
E. S

non

Bas

E. P

(kVAh)
0

Sortie

55-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

Figure 76 : Vrification de la frquence


06134267

(A)

U
P
E

(V)
(kWh)

(Hz)

(kW)

Entre

60.0

Sortie

Figure 77 : Menu Historiques


06133330

Historique du dclencheur

F (Hz)

Utiliser le menu Entretien pour consulter


l'historique du dclencheur stock dans les
journaux historiques.

06133467

Frquence

48049-137-05
Rev. 01, 07/2012

Historiques

FRANAIS

Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

Historiques
dfauts
Historiques
alarmes
Compteur de
manuvres
Usure des
contacts

Entre

Le dclencheur stocke les informations sur le


dfaut LSIG ayant occasionn les dix derniers
dclenchements. Pour chaque dfaut, les
renseignements suivants sont mis en mmoire :

Les valeurs de courant de Ir, Isd, Ii et Ig


Point de consigne d'enclenchement pour la
tension et les autres protections

Figure 78 : Vrification des Historiques de dfauts


06133467

Historiques dfauts

Historiques
dfauts
Historiques
alarmes
Compteur de
manuvres
Usure des
contacts

Historiques
dfauts

Entre

Entre

Date
Heure (heure, minutes et secondes)

REMARQUE : Les dclenchements par suite de


l'utilisation d'une trousse d'essais ne sont pas
enregistrs dans le journal historique des
dclenchements.

Ii
28 / 04 / 00
Umin
28 / 04 / 00

I1 =
I2 =
I3 =
In =

7800 A
7800 A
7800 A
7800 A

Entre

Historiques
dfauts
Ii
20 / 05 / 00
Ii
28 / 04 / 00
Umin
28 / 04 / 00
Bas
Entre

Dfaut
28 / 04 / 00
Ii 7200A
I1 =
I2 =
I3 =
In =

7500 A
7500 A
7500 A
7500 A

Entre

56-FR

Ii
20 / 05 / 00

Dfaut
20 / 05 / 00
10:23:42
Ii 7200 A

Historiques
dfauts
Ii
20 / 05 / 00

Dfaut
28 / 04 / 00
12:03:33
U min 100V

Ii
28 / 04 / 00
Umin
28 / 04 / 00
Bas

Sortie

Entre

Sortie

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

48049-137-05
Rev. 01, 07/2012

Indication et valeur du rglage de l'alarme


Date

Historiques
alarmes
Al
20 / 05 / 00

Heure (heure, minutes et secondes)

Dfaut
20 / 05 / 00
Al

06133983

Historiques
dfauts
Historiques
alarmes
Compteur de
manuvres
Usure des
contacts

06133983

Le dclencheur enregistre les mesures pour


chacune des dix dernires alarmes actionnes.
Pour chaque alarme, les renseignements
suivants sont mis en mmoire :

Figure 79 : Vrification des Historiques des alarmes


06133467

Historiques des alarmes

Historiques
alarmes

996A

Al
20 / 05 / 00

Al
28 / 02 / 00

Al
28 / 02 / 00

Al
26 / 02 / 00

Al
26 / 02 / 00

Entre

Entre

Entre

Bas

Dfaut
28 / 02 / 00
Al

996A

06133983

Entre

Historiques
alarmes
Al
20 / 05 / 00

Dfaut
26 / 02 / 00
Al

996A

Al
28 / 02 / 00

Entre

Ce menu affiche le nombre maximum de


manuvres (dclenchements ou ouvertures du
disjoncteur) depuis l'installation du disjoncteur.
Le nombre est obtenu partir du module de
communication de disjoncteur (BCM).

Sortie

Entre

Sortie

Figure 80 : Vrification du compteur de manuvres


06133467

Compteur de manuvres

Bas

FRANAIS

Al
26 / 02 / 00

Historiques
dfauts
Historiques
alarmes
Compteur de
manuvres
Usure des
contacts

Nombre de
manuvres
Total
19
Depuis le
dernier reset
7

Entre

Ce menu affiche le niveau de l'usure des


contacts pour le contact dmontrant le plus
d'usure. Lorsque ce nombre atteint 100, il est
recommand de procder une inspection
visuelle des contacts. Cette fonction ne
fonctionne que sur les disjoncteurs
MasterpactMC NT et NW.

Figure 81 : Vrification de l'usure des contacts


06133467

Usure des contacts

Sortie

Historiques
dfauts
Historiques
alarmes
Compteur de
manuvres
Usure des
contacts

Entre

Usure des
contacts
63

Sortie
Sortie

20002012 Schneider Electric Tous droits rservs

57-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

Figure 82 : Menu Protections


06133331

Utiliser les menus de protection pour vrifier la


configuration des protections portant sur les
courants, les tensions, les autres protections, le
dlestage de charge en courant et le dlestage
de charge en puissance.
Consulter l'annexe B pour les rglages par
dfaut et les gammes de rglage.

Entre

(A)

Idmtl

(A)

(A)

I(A)
Remplacer
les rglages
Idmtl (A) par
I(A)?

Ineutre (A)
I

non
oui

Alarme

Idsq. (%)

Bas

I1 max

(A)

Entre

I2 max

(A)

I3 max

(A)

In max

(A)

Idmtl (A)
Trip
1000 A
1.0 s
2000 A
0.2 s
4000 A

Sortie

Entre

(A)

Idmtl

(A)

(A)

Ineutre (A)
I

Alarme

Idmtl(A)
Remplacer
les rglages
I(A) par
Idmtl(A)?

non
oui

06133472

REMARQUE : La protection du neutre est


dsactive si la protection Idmtl est
slectionne.

06133471

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

L'cran Remplacer les rglages I (A) par Idmtl


(A) n'apparat que si des ajustements de
longue dure, de courte dure ou instantans
ont t pralablement effectus l'cran du
menu I (A). Si l'utilisateur rpond Oui, les
rglages de I (A) seront perdus lorsque le menu
passe l'cran d'ajustement de Idmtl (A). Si
aucun ajustement n'a t effectu l'cran du
menu Idmtl (A), le menu va directement
l'cran d'ajustement de I (A).
06133474

FRANAIS

L'cran Remplacer les rglages Idmtl (A) par


I(A) n'apparat que si des ajustements de
longue dure, de courte dure ou instantans
ont t pralablement effectus l'cran du
menu Idmtl (A). Si l'utilisateur rpond Oui, les
rglages de Idmtl (A) seront perdus lorsque le
menu passe l'cran d'ajustement de I (A). Si
aucun ajustement n'a t effectu l'cran du
menu Idmtl (A), le menu va directement
l'cran d'ajustement de I (A).

Figure 83 : Vrification de protections en courant


06133331

Protections en courant

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

06133474

Configuration des protections

48049-137-05
Rev. 01, 07/2012

I dmtl (A)
Trip
1000 A
1.0 s
EIT
2000 A
0.2 s
4000 A

Sortie

Bas

Bas

Entre

Entre
Page suivante

58-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

48049-137-05
Rev. 01, 07/2012

(A)

06133473

Figure 83 : Vrification de protections en courant (suite)


06133474

Protections en courant (suite)

(A)
Trip

Idmtl

(A)

(A)

1200 A

Ineutre (A)
Alarme

REMARQUE : Le choix du type de TC dfinit la


protection Ineutre du menu Protections.

Tous

Ttrapolaire

aucun TC

TC interne

Ineutre (A)

(A)

Idmtl

(A)

Type de
TC neutre

(A)

TC externe

dsactive

Ineutre (A)

OFF : pas de protection du


neutre

Protection
OFF

Choix des protections

Alarme

N/2 : neutre moiti proteg

Bas

N : neutre plein protg

Entre

OFF : pas de protection du


neutre

Sortie

II

(A)
(A)

N : neutre plein protg

Idmtl
Idmtl

(A)
(A)

1.6N : protection du neutre


surdimensionne

II

(A)
(A)

N/2 : neutre moiti proteg


Tripolaire

Sortie

06133474
06133474

Type de
Disjoncteur TC du
neutre

06133474

Entre

TC externe

FRANAIS

0.5s

I Alarme
Alarme

(A)
IIneutre
neutre (A)
II

Alarme
Alarme

Activation
996A
1.0s
Retombe
996A
1.0s
Sortie

Bas
Entre

Idmtl

(A)

(A)

Ineutre

(A)

Alarme

Idsq. (%)
Bas

I dsq. (%)
Off
Activation
60%
40.0s
Retombe
60%
1.0s
Sortie

Entre
Page suivante

20002012 Schneider Electric Tous droits rservs

59-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

Protections en courant (suite)

48049-137-05
Rev. 01, 07/2012

Figure 83 : Vrification de protections en courant (suite)

(A)

I1 max (A)
Off

Ineutre (A)
I

Alarme

Idsq. (%)
I1 max

(A)

Activation
240A
1500s
Retombe
240A
15s
Sortie

Bas
Entre

Ineutre (A)

I2 max (A)
Off

Alarme

Idsq. (%)
FRANAIS

I1 max

(A)

I2 max

(A)

Activation
240A
1500s
Retombe
240A
15s
Sortie

Bas
Entre

Alarme

I dsq. (%)
I1 max

(A)

I2 max

(A)

I3 max

(A)

I3 max (A)
Off
Activation
240A
1500s
Retombe
240A
15s
Sortie

Bas
Entre

REMARQUE : Pour rgler Inmax , le TC de


neutre doit tre rgl externe ou interne sous
la configuration de Micrologic dans le menu
Entretien
.

I dsq. (%)
I1 max

Off

(A)

I2 max (A)
I3 max (A)
In max (A)

60-FR

In max (A)
Activation
240A
1500s
Retombe
240A
15s

Bas

Sortie

Entre

Sortie

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

48049-137-05
Rev. 01, 07/2012

Protections en tension

Si cette prcaution nest pas respecte,


cela peut entraner des dommages
matriels.
06133476

Les rglages de l'activation de la protection en


tension sont des valeurs entre phases.

Entre

Les valeurs de dsquilibre sont bases sur les


valeurs efficaces relles des courants triphass.

Umin

(V)

Umax

(V)

REMARQUE : Ne pas rgler la protection en


sous-tension en dessous de 80 %. Ne pas rgler
Udsq. au-dessus de 20 %*.

(V)

Umax

(V)

Umin (V)
Off

Udsq. (%)

Entre

Activation
100V
5.00s
Retombe
100V
0.20s
Sortie

Umax (V)
Off

Udsq. (%)

L'alarme de sous-tension retombe la perte


de la deuxime phase.

Umin

Activation
725V
5.00s
Retombe
725V
0.20s

FRANAIS

Le rglage de la protection contre la soustension (Umin) en dessous de 80 % ou contre


le dsquilibre de tension (Udsq.) au-dessus
de 20 % peut faire que le dclencheur ne
fonctionne pas comme prvu.

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

06133476

RISQUE DE DOMMAGES MATRIELS

Figure 84 : Vrification des protections en tension


06133331

AVIS

Sortie

Bas

06133476

Entre

Umin

(V)

Umax

(V)

Off

Udsq. (%)

Udsq. (%)
Activation
30%
40.0s
Retombe
30%
10.0s

Bas

Sortie

Entre

Sortie

Pour avoir une explication du comportement de la protection du systme, se reporter l'annexe D

20002012 Schneider Electric Tous droits rservs

61-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

06133484

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

06133484

Figure 85 : Vrification d'autres protections


06133331

Autres protections

48049-137-05
Rev. 01, 07/2012

rPmax (W)
F min (Hz)
F max (Hz)
Rotation
phases

Entre

Entre

rPmax (W)

Fmin (Hz)

F min (Hz)
F max (Hz)
Rotation
phases

FRANAIS

Bas

rPmax (W)
Off
Activation
500kW
5.00s
Retombe
500kW
1.0s
Sortie

Off
Activation
45.0Hz
5.00s
Retombe
45.0Hz
1.00s
Sortie

06133484

Entre

rPmax (W)
F min (Hz)
F max (Hz)
Rotation
phases

Bas

Fmax (Hz)
Off
Activation
65.0Hz
5.00s
Retombe
65.0Hz
1.00s
Sortie

06133484

Entre

rPmax (W)

Rotation
phases

F min (Hz)

Off

F max (Hz)

'): 1, 2, 3

Phase
rotation

62-FR

Bas

Sortie

Entre

Sortie

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 4Fonctionnement

48049-137-05
Rev. 01, 07/2012

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P
Entre

Le dlestage de charge en puissance peut tre


configur pour l'alarme seulement. Il ne peut
pas tre utilis pour dclencher le disjoncteur.

20002012 Schneider Electric Tous droits rservs

Activation
100% Ir
80% tr
Retombe
100% Ir
10s
Sortie

Figure 87 : Vrification du dlestage de charge en puissance


06133331

Dlestage de charge en puissance

Dlestage
relestage
Off

Dlestage
relestage

Protections
en courant
Protections
en tension
Autres
protections
Dlestage I
relestage
Dlestage
relestage P

Activation
10.00MW
3600s
Retombe
10.00MW
10s

Entre

Sortie

Off

FRANAIS

Le dlestage de charge en courant peut tre


configur pour l'alarme seulement. Il ne peut
pas tre utilis pour dclencher le disjoncteur.

Figure 86 : Vrification du dlestage de charge en courant


06133331

Dlestage de charge en courant

63-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 5Remplacement du dclencheur

48049-137-05
Rev. 01, 07/2012

Section 5Remplacement du dclencheur

Le remplacement du dclencheur doit tre


effectu par des personnes qualifies, selon la
dfinition du Code national de l'lectricit
(.-U.), qui sont familiarises avec l'installation
et l'entretien des disjoncteurs de puissance.

RISQUE D'LECTROCUTION, D'EXPLOSION OU DCLAIR DARC

Avant de remplacer le dclencheur, s'assurer que


le disjoncteur est en bon tat de fonctionnement.
Si la condition du disjoncteur n'est pas connue, ne
pas continuer. Pour obtenir de l'assistance
concernant l'valuation de la condition du
disjoncteur, appeler l'assistance technique.

Portez un quipement de protection personnelle (PP) appropri et


observez les mthodes de travail lectrique scuritaire. Voir NFPA 70E
ou CSA Z462.

DANGER
L'inobservation de ces directives d'installation, d'essai de
dclenchement et d'essai d'injection primaire peut aboutir la
dfaillance de certaines fonctions de protection.

Le remplacement ou la mise niveau d'un dclencheur sur place doit


tre effectu par des personnes qualifies, selon la dfinition du Code
national de l'lectricit (.-U.), qui sont familiarises avec l'installation et
l'entretien des disjoncteurs de puissance.

Lire cette section en entier avant d'entamer la


procdure de remplacement.

FRANAIS

REMARQUE : Si le dclencheur remplacer est


un Micrologic 2.0, 3.0 ou 5.0, commander un bloc
connecteur S33101 et un faisceau de cbles de
disjoncteur ou de berceau si ncessaire.

Avant de remplacer ou de mettre niveau un dclencheur, assurez-vous


que le disjoncteur est en bon tat de fonctionnement. Si la condition du
disjoncteur n'est pas connue, ne pas continuer. Pour obtenir de
l'assistance concernant l'valuation du disjoncteur, appelez l'assistance
technique.

Le remplacement du dclencheur doit tre


effectu par des personnes qualifies, selon la
dfinition du Code national de l'lectricit
(.-U.), qui sont familiarises avec l'installation
et l'entretien des disjoncteurs de puissance.

Si le disjoncteur cesse de fonctionner correctement d'une manire


quelconque aprs avoir termin l'installation du dclencheur, arrtez
immdiatement d'utiliser le disjoncteur et appelez les services
d'intervention sur place.
Coupez lalimentation de lappareil avant dy travailler. Suivez les
directives expdies avec le disjoncteur pour le dbrancher et le
rebrancher.

Avant de remplacer le dclencheur, s'assurer


que le disjoncteur est en bon tat de
fonctionnement. Si la condition du disjoncteur
n'est pas connue, ne pas continuer. Pour obtenir
de l'assistance concernant l'valuation de la
condition du disjoncteur, appeler l'assistance
technique.

Replacez tous les dispositifs, les portes et les couvercles avant de


remettre l'appareil sous tension.
Si ces prcautions ne sont pas respectes, cela entranera la mort ou
des blessures graves.

Lire cette section en entier avant d'entamer la


procdure de remplacement.
REMARQUE : Si le dclencheur remplacer est
un Micrologic 3.0 ou 5.0, commander un bloc
connecteur S33101 et un faisceau de cbles de
disjoncteur ou de berceau si ncessaire.

Outils ncessaires

Tournevis dynamomtrique micro-rglable, rgl 0,8 Nm (7 lb-po)


10 % (tournevis dynamomtrique Lindstrom MAL500-2 ou quivalent)

Trousse d'essai des fonctions compltes Micrologic (no de pice


S33595)

Prparation
Noter les rglages des commutateurs

Noter tous les rglages des commutateurs et de protection volue du


dclencheur pour usage ultrieur.

Dconnexion du disjoncteur

Dbrancher le disjoncteur selon les directives dutilisation du disjoncteur qui


laccompagnent. Le disjoncteur doit tre compltement isol. (Pour les

64-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 5Remplacement du dclencheur

48049-137-05
Rev. 01, 07/2012

Retrait du couvercle des accessoires du


disjoncteur

Retirer le couvercle des accessoires du disjoncteur comme indiqu dans la


section Installation des accessoires des directives dutilisation du
disjoncteur expdies avec ce dernier.

Retrait de la fiche de valeur nominale.

Figure 88 : Retrait de la fiche de valeur nominale rglable

4. Un petit tournevis cruciforme est ncessaire


pour retirer la fiche de valeur nominale
rglable.

06134783

disjoncteurs dbrochables, placer le disjoncteur en position Dconnect.


Pour les disjoncteurs fixes, toutes les sources de tension, notamment une
alimentation auxiliaire, doivent tre dconnectes.)

5.0
Micro

logic
Micro

06134831

logic

06134830

Micro

5.0
logic

5.0 P

1. Ouvrir le couvercle des commutateurs (A).


2. Dvisser la vis de montage (B) de la fiche de
valeur nominale rglable.

3. Retirer la fiche de valeur nominale


rglable (C).

alarm
long

2. Desserrer les deux vis (B) du dclencheur.

(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

06134079

Figure 89 : Retrait du dclencheur existant

06134078

1. Enlever le bloc connecteur (A) du dessus du


dclencheur, si prsent.

tr

FRANAIS

Retrait du dclencheur

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

gic 5.0

Microlo

gic 5.0

Microlo

3. Extraire le dclencheur (D). La mettre de


ct pour linstaller dans le dclencheur de
rechange.
C

Remplacement du dclencheur
Installation de la pile

Figure 90 : Installation de la pile


A
06133375

Installer le logement de la pile avec la pile (A)


dans le dclencheur en respectant la bonne
polarit indique sur le compartiment de la pile.

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

Si un dclencheur neuf est install, installer la


pile du dclencheur.

REMARQUE : Le logement de la pile avec la pile se trouve sous le rabat


latral de la bote d'expdition du dclencheur.

20002012 Schneider Electric Tous droits rservs

65-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 5Remplacement du dclencheur

Figure 91 : Voyants lumineux


B
06133245

Appuyer sur le bouton dessai/de remise zro


(A). Les quatre voyants lumineux (B) doivent
sallumer. Sils ne sallument pas, vrifier la polarit
de la pile et ressayer. Si les voyants lumineux ne
sallument toujours pas lorsquon appuie sur le
bouton dessai/de remise zro, arrter
linstallation et contacter le bureau de vente local
pour obtenir un service autoris par lusine.

48049-137-05
Rev. 01, 07/2012

Micrologic 6.0 A

Installation du dclencheur
1. Inspecter les broches du connecteur et
surfaces du dclencheur. En prsence de
dommage, de broches non alignes ou de
contamination, arrter l'installation et
contacter le bureau de vente local pour
obtenir un service autoris par l'usine.
Figure 92 : Installation du dclencheur
Disjoncteur Masterpact NW

06135452

06135453

FRANAIS

2. Inspecter la base de montage du


dclencheur sur le disjoncteur. Enlever tous
dbris pouvant s'y trouver et s'assurer que
tout le cblage des accessoires est
correctement achemin pour le dclencheur
installer. En prsence de dommage ou de
contamination, arrter l'installation et
contacter le bureau de vente local pour
obtenir un service autoris par l'usine.
3. Pour le disjoncteur Masterpact NW
uniquement : appuyer manuellement sur
l'interverrouillage (A) du dclencheur et le
maintenir en place pendant les points 4 6
ci-dessous.
4. Aligner le rail guide (B) sur le bas du
dclencheur avec la fente (C) de rail guide
sur la base de montage du dclencheur sur
le disjoncteur et faire glisser soigneusement
le dclencheur jusqu' ce qu'il s'arrte.
REMARQUE : Les bases de montage des
dclencheurs pour les disjoncteurs Masterpact
NT et NW sont monts sur amortisseur et
peuvent donc flchir lgrement

logic

5.0

Micro

C
B
A

AVIS
RISQUE DE DOMMAGES MATRIELS
Vrifiez linstallation du dclencheur afin de sassurer que les
raccordements et la mise en place sont corrects.
Si cette directive nest pas respecte, cela peut entraner des
dommages matriels ou le dclenchement inappropri du
disjoncteur.

66-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 5Remplacement du dclencheur

48049-137-05
Rev. 01, 07/2012

Figure 93 : Installation du dclencheur

6. Utiliser un tournevis dynamomtrique microrglable pour serrer la vis infrieure (B) au


couple de 0,8 Nm (7 lb-po) 10 %. L'arrire
du dclencheur doit tre de niveau avec la
base de montage.

Doit tre bien en


place

06134080

5. Aligner le dclencheur de sorte que la vis de


montage suprieure (A) s'aligne avec la
pice encastre filete et visser la vis sur
deux tours complets.

gic 5.0
Microlo

0,8 Nm
[7 lb-po]

7. Utiliser un tournevis dynamomtrique microrglable pour serrer la vis suprieure au


couple de 0,8 Nm (7 lb-po) 10 %. L'onglet
de montage doit tre de niveau avec
l'espaceur de montage et la prise du
capteur.

B
Doit tre de
niveau

REMARQUE : La face avant du couvercle des


commutateurs doit tre de niveau avec les
surfaces de montage adjacentes. Si ces
surfaces ne sont pas de nveau, arrter
l'installation et contacter le bureau de vente
local pour obtenir un service autoris par l'usine.

06134081

C
gic 5.0

FRANAIS

Microlo

REMARQUE : S'il s'agit d'une mise jour


partir d'un dclencheur de base Micrologic 2.0,
3.0 ou 5.0, le bloc connecteur doit tre
command sparment (no de pice S33101).
Consulter les directives expdies avec le bloc
connecteur pour l'installation sur un disjoncteur.
8. Installer le bloc connecteur (C) sur le dessus
du dclencheur.

b. Inspecter la zone de montage pour


s'assurer de l'absence de dbris ou de
contamination.

ic 5.0

log
Micro

06134833

a. Ouvrir le couvercle des commutateurs


(A) sur le dclencheur neuf.

Figure 94 : Installation de la fiche de valeur nominale rglable

06134832

9. Installer la fiche de valeur nominale rglable


sur le dclencheur.

logic

5.0

c. Enfoncer doucement la fiche de valeur


nominale rglable (B) dans le
dclencheur neuf.
d. Serrer la vis de montage (C) de la fiche
de valeur nominale rglable. La fiche se
trouvera mise en place, de niveau avec
la face avant, par le serrage de la vis.
10. Remettre les rglages des commutateurs et
de protection volue du dclencheur aux
valeurs indiques ci-dessus ou en fonction
des rsultats des tudes de coordination.

Micro

alarm
long

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr
(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

11. Fermer le couvercle des commutateurs (A).

Remise en place du couvercle des


accessoires du disjoncteur

20002012 Schneider Electric Tous droits rservs

Replacer le couvercle des accessoires du disjoncteur comme indiqu dans


la section Installation des accessoires des directives dutilisation du
disjoncteur expdies avec ce dernier.

67-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 5Remplacement du dclencheur

48049-137-05
Rev. 01, 07/2012

Vrification de linstallation du
dclencheur
Essai d'injection secondaire

L'installation sur place d'un dclencheur ncessite un essai d'injection


secondaire l'aide d'une trousse d'essai des fonctions compltes. Cela
assurera que le dclencheur nouvellement install fonctionnera correctement.
L'essai impose d'ouvrir et de fermer le disjoncteur. Suivre les procdures
dtailles dans les directives d'utilisation expdies avec le disjoncteur et la
trousse d'essai des fonctions compltes.
1. S'assurer que le disjoncteur est isol de tous les dispositifs en amont et
en aval.
2. Excuter un essai d'injection secondaire comme expliqu dans les
directives d'utilisation expdies avec la trousse d'essai des fonctions
compltes. Vrifier si toutes les fonctions utilisables du dclencheur
fonctionnent correctement.
3. Rpter le point 2 avec le disjoncteur en position ouverte
REMARQUE : Ne pas fermer le disjoncteur pour ce point mme si la
trousse d'essai indique que le disjoncteur doit tre ferm pendant
l'essai.

FRANAIS

4. Si certains essais chouent, ne pas mettre le disjoncteur en service et


contacter le bureau de vente local pour obtenir un service autoris par
l'usine.

Essai d'injection primaire

L'essai d'injection primaire est recommand pour s'assurer que toutes les
connexions du systme de dclenchement ont t correctement effectues.
Effectuer lessai dinjection primaire selon les directives dans le Guide
d'essai sur place et d'entretien, directives dutilisation numro 0600IB1201.

Vrification du fonctionnement des


accessoires

1. Accessoires installs Valider le bon fonctionnement de tous les


accessoires installs. Consulter les directives d'utilisation
correspondantes pour les procdures d'essais de fonctionnement.
2. Module de contacts programmables Si le disjoncteur est muni d'un
module de contacts programmables M2C ou M6C, valider son bon
fonctionnement. Se reporter aux directives d'utilisation des accessoires
correspondantes pour les procdures d'essais de fonctionnement.
3. Interverrouillage slectif de zone Si le disjoncteur fait partie d'un systme
d'interverrouillage slectif de zone (ZSI), suivre les procdures d'essai ZSI
prcises dans la trousse d'essai des fonctions compltes.
4. Communications En prsence de modules de communication, valider
que le disjoncteur a rtabli les communications avec le superviseur.

Configuration du dclencheur

1. Si une alimentation auxiliaire est utilise pour le dclencheur Micrologic,


rebrancher l'alimentation auxiliaire.
2. Remettre les rglages des commutateurs et de protection evolue du
dclencheur leurs valeurs dorigine, telles qu'indiques au dbut de
cette section.

Reconnexion du disjoncteur

68-FR

Rebrancher le disjoncteur selon les directives dutilisation du disjoncteur qui


laccompagnent.

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 6Remplacement de la fiche de la valeur nominale rglable

48049-137-05
Rev. 01, 07/2012

Section 6Remplacement de la fiche de la valeur nominale rglable

REMARQUE : Pour slectionner une fiche de la


valeur nominale de rechange correcte, consulter
le catalogue de produits.

DANGER
RISQUE D'LECTROCUTION, D'EXPLOSION OU DCLAIR DARC
Portez un quipement de protection personnelle (PP) appropri et
observez les mthodes de travail lectrique scuritaire. Voir NFPA 70E
ou CSA Z462.

REMARQUE : La fiche de la valeur nominale


rglable doit tre retire lors d'un essai de
rupture dilectrique. Elle doit tre installe pour
mesurer la tension. Si la fiche est retire, le
disjoncteur se rgle par dfaut la valeur
nominale d'enclenchement de longue dure de
0,4 x calibre du capteur (In) et un retard de
longue dure du rglage slectionn avant le
retrait de la fiche de la valeur nominale.

L'installation et l'entretien de cet appareil ne doivent tre effectus que


par du personnel qualifi.
Coupez lalimentation de lappareil avant dy travailler. Suivez les
directives expdies avec le disjoncteur pour le dbrancher et le
rebrancher.
Replacez tous les dispositifs, les portes et les couvercles avant de mettre
l'appareil sous tension.

logic

5.0
Micro

logic

logic
Micro

06134831

Micro

06134830

1. Dbrancher le disjoncteur selon les


directives dutilisation du disjoncteur qui
laccompagnent.

Figure 95 : Retrait de la fiche de la valeur nominale rglable

06134783

Retrait de la fiche de la valeur


nominale

FRANAIS

Si ces directives ne sont pas respectes, cela entranera la mort ou


des blessures graves.

5.0

5.0 P

2. Ouvrir le couvercle des commutateurs (A).


B

3. Noter tous les rglages du dclencheur dans


lannexe E (rglages des commutateurs et
ceux effectus l'aide de l'cran graphique,
le cas chant).

C
alarm
long

4. Dvisser la vis de montage (B) de la fiche.

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr

(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

5. Retirer la fiche de la valeur nominale


rglable (C).

2. Enfoncer doucement la fiche de valeur


nominale rglable (A) dans le dclencheur
neuf.

logic
Micro

5.0 P

06134833

1. Inspecter la zone de montage pour s'assurer


de l'absence de dbris ou de contamination.

Figure 96 : Installation de la nouvelle fiche de la valeur nominale


rglable

06134832

Installation de la nouvelle fiche


de la valeur nominale rglable

5. Fermer le couvercle (C) des commutateurs.

20002012 Schneider Electric Tous droits rservs

logic

5.0

B
A

3. Serrer la vis de montage (B) de la fiche de la


valeur nominale rglable.
4. Rgler le dclencheur aux valeurs indiques
dans l'annexe E ou en fonction des rsultats
des tudes de coordination.

Micro

alarm
long

time

.8 .9
.7
.95
.6
.98
.5
1
.4 x In

Ir

tr
(s)

2
1

8 12
16
20
24

.5 @ 6 Ir

69-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 7Remplacement de la pile

48049-137-05
Rev. 01, 07/2012

Section 7Remplacement de la pile

Dconnexion du disjoncteur

DANGER
RISQUE D'LECTROCUTION, D'EXPLOSION OU DCLAIR DARC

Dbrancher le disjoncteur selon les directives


dutilisation du disjoncteur qui laccompagnent.

Portez un quipement de protection personnelle (PP) appropri et


observez les mthodes de travail lectrique scuritaire. Voir NFPA 70E
ou CSA Z462.

RETRAIT DU COUVERCLE DES


ACCESSOIRES

L'installation et l'entretien de cet appareil ne doivent tre effectus que


par du personnel qualifi.

Retirer le couvercle des accessoires du


disjoncteur comme indiqu dans la section
Installer les accessoires des directives
dutilisation du disjoncteur expdies avec ce
dernier.

Coupez lalimentation de lappareil avant dy travailler. Suivez les


directives expdies avec le disjoncteur pour le dbrancher et le
rebrancher.
Replacez tous les dispositifs, les portes et les couvercles avant de mettre
l'appareil sous tension.

Figure 97 : Dplacement du module de tenue

REMARQUE : Disjoncteurs chssis R et


NS1600NS3200 uniquement.
Desserrer les vis (A) fixant le module de tenue
(B). Basculer le module sur le ct afin
daccder au couvercle de la pile du
dclencheur. Ne pas retirer le connecteur du
module de tenue.

06134857

1. Insrer le bout d'un petit tournevis plat dans


l'encoche du couvercle du logement de la
pile et le faire pivoter pour dgager le
couvercle (A) de son logement.

Figure 98 : Retrait du couvercle de la pile

06133372

Remplacement de la pile

LITHIUM
LITHIUM BATTERY
BATTERY
3.6V
3.6V -- SL
SL -- 550/S
550/S
SONNENSCHEIN
SONNENSCHEIN

FRANAIS

Dplacement du module de tenue

06134083

Si ces directives ne sont pas respectes, cela entranera la mort ou


des blessures graves.

70-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Section 7Remplacement de la pile

48049-137-05
Rev. 01, 07/2012

06133375

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

06133374

4. Replacer le couvercle (C) du logement de la


pile.

06133373

3. Insrer une pile neuve (B). S'assurer que la


polarit est correcte.

Figure 99 : Remplacer la pile

LITHIUM BATTERY
3.6V - SL - 550/S
SONNENSCHEIN

2. Retirer la pile (A).

REMARQUE : Disjoncteurs chssis R et


NS1600NS3200 uniquement.

Figure 100 : Remettre en place le module de tenue

06124084

Remise en place du module de


tenue

Remettre en place le module de tenue (A).


Serrer les vis (B) fixant le module.

Remise en place du couvercle des


accessoires

Replacer le couvercle des accessoires du disjoncteur comme indiqu dans


la section Installer les accessoires des directives dutilisation du
disjoncteur expdies avec ce dernier.

Reconnexion du disjoncteur

Rebrancher le disjoncteur selon les directives dutilisation du disjoncteur qui


laccompagnent.

20002012 Schneider Electric Tous droits rservs

71-FR

FRANAIS

0,6 Nm
[5 lb-po]

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe AOrganigrammes des affichages graphiques

48049-137-05
Rev. 01, 07/2012

Annexe AOrganigrammes des affichages graphiques


Organigramme du menu mesures

I
U

(V)

(kW)

(kWh)

(Hz)

(A)

(A)

(V)
instant.

instant.
I1, I2, I3, In
=
=
=
=
I =

FRANAIS

I1
I2
I3
In

356 A
147 A
158 A
0A
212 A

Max
I1
I2
I3
In
I

U12 = 429 V
U23 = 430 V
U31 = 399 V

359 A
153 A
188 A
0A
214 A

Reset (- / +)

instant.
P, Q, S

E. Q (kvarh)
513

(kVAR)
83

E. S

(kVA)
86

-0.29
moyen

Max
15 min
I1 = 357 A
I2 = 148 A
I3 = 155 A
In =
0A

(kVAh)
545

E+
Consomme
E. P

(kWh)
155

E. Q (kvarh)
514
EFournie

P, Q, S

E. P

I1, I2, I3, In


15 min
351 A
I1 =
I2 =
145 A
156 A
I3 =
In =
84 A

(kWh)
155

(kW)
27

'): 1,3,2

moyen

E. P

Facteur de
puissance

(Hz)
60.0

dsq. 3)

Rotation
phases

(kWh)
E totale

moyen 3)

-4%

(kW)

V1n = 246 V
V2n = 241 V
V3n = 242 V

419 V
=
=
=
=
=

(kW)
25

(kVAR)
77

(kVA)
83

(kWh)
0

E. Q (kvarh)
0
Reset
nergies
Voulez-vous
remettre zro
les nergies ?

Max
P

(kW)
26

non

(kVAR)
81

oui

(kVA)
86

Reset (- / +)

Reset (- / +)

72-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe AOrganigrammes des affichages graphiques

48049-137-05
Rev. 01, 07/2012

06133330

Organigramme du menu entretien

Historiques
Contacts
M2C / M6C
Configurer
Micrologic
Configurer
mesures
Configurer
Com.

Historique
dfauts

Configurer
Micrologic

Configurer
mesures

Langue

Type de
rseau

Type dalarme

Ii

S1
date
Ii 7200 A
I1 =
I2 =
I3 =
In =

0A
0A
0A
0A

Umin

Choisir type
S2
Choisir type
Rpter pour tous
les contacts
Configurer

Date
12:03:33 am
U min 100 V
Rpter pour tous
les historiques
Historique
alarmes

Choisir mode
S2
Choisir mode

Umin

Date / heure
Date
02 / 01 / 2000
Heure
06:12:35

Choisir type
Calcul I moyen
Mthode
de calcul
Type fentre
Dure
Calcul P moyen

S1

I
dat
I 7200 A
I1 = 0 A
I2 = 0 A
I3 = 0 A
In = 0 A

Deutsch
English US
English UK
Espaol
Franais

Rpter pour tous


les contacts

Slection
disjoncteur
Norme

Type fentre

disjoncteur

Dure

type
Numro du
disjoncteur

Reset
S1
S2
Reset (- / +)

dat
12:03:33
Umin 100 V
Rpter pour tous
les historiques
Compteur de
manuvres
Usure des
contacts

Mthode
de calcul

Configurer
Com.
Paramtre com
Address
Baud rate
Parit
Rglage
distance

FRANAIS

Contacts
M2C / M6C

Historiques

Autorisation
daccs
Code daccs
Commande
distance

Convention
de signe
Choisir
convention
de signe

Signe puissance
Choisir sens
dcoulement
Transfo
de U
Primaire
Secondaire
Frquence
rseau
Choisir frquence

20002012 Schneider Electric Tous droits rservs

73-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe AOrganigrammes des affichages graphiques

48049-137-05
Rev. 01, 07/2012

Organigramme du menu
Protections
Protections
en courant
Protections
en tension
Autres
protections

Protecions
en courant

Dlestage
relestage

Dlestage
relestage

P
Dlestage
relestage

FRANAIS

Mode
(on/off)

Mode
(trip/alarme/off)

Activation

Activation

Activation

Activation

Retombe

Retombe

Retombe

Retombe

(V)

(A)

Idmtl

(A)

Mode
(trip/alarme/off)

(A)

Ineutre

(A)

Alarme

Mode
(on/off)

Umin

Dlestage
relestage

Autres
protections

Protecions
en tension

Umax

(V)

rPmax (W)

Fmin

(Hz)

Idsq.

(%)

Mode
(trip/alarme/off)

Mode
(trip/alarme/off)

I1max

(A)

Activation

Activation

I2max

(A)

Retombe

Retombe

I3max

(A)

Inmax

(A)

Udsq.(%)

Fmax (Hz)

Mode
(trip/alarme/off)

Mode
(trip/alarme/off)

Activation

Activation

Retombe

Retombe
Rotation
phases
Mode
(alarme/off)
Sq. de phases

74-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe BRglages par dfaut et tolrances

48049-137-05
Rev. 01, 07/2012

Annexe BRglages par dfaut et tolrances


Rglages par dfaut

Tableau 11 : Rglages par dfautcommutateurs


Description

Symbole

Valeur par dfaut

Enclenchement de longue dure

Ir

Maximum

Retard de longue dure

tr

Minimum

Enclenchement de courte dure

Isd

Minimum

Retard de courte dure

tsd

Minimum

Enclenchement sur dfaut la terre

Ig

Minimum

Retard de dfaut la terre

tg

Minimum

Instantan

Ii

Minimum

Tableau 12 : Rglages par dfautMenu Entretien


Description

Article

Contacts M2C/M6C

Type d'alarme

S#

Non affect

Non affect, Isd, Ir, Idsq. (Voir le tableau 9)

S#

Accrochage
permanent

Accrochage permanent, temporisation, sans


accrochage, forc 0, forc 1

English US

Deutsch, English US, English UK, Espaol, Franais

Norme

s/o

Non def, ANSI, IEC, UL, IEC/GB

disjoncteur

s/o

Configurer
Configurer Micrologic

Langue

Valeur par dfaut Gamme de rglage

Date/heure
Slection disjoncteur

type

s/o

Numro du disjoncteur

0000

Signe puissance
Transfo de U

Primaire
Secondaire

Frquence rseau
Configurer mesures

Type de rseau

P+, P-

690

000690

690

000690

50-60 Hz

50-60 Hz, 400 Hz

3) 4 fils 4 TC

3) 4fils 4TC, 3) 4fils 3TC, 3) 3fils 3TC

Calcul I moyen

Dure

15 min.

560 min.

Calcul P moyen

Type fentre

glissante

glissante, fixe

Dure

15 min.

560 min.

IEEE

IEEE, IEEE alt, IEC

Rglage distance

Non

oui, non

Commande distance

Auto

Auto, manu

Convention de signe
Configurer com.

0000FFFF

P+

Paramtre com.

20002012 Schneider Electric Tous droits rservs

75-FR

FRANAIS

Sous-menu

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe BRglages par dfaut et tolrances

48049-137-05
Rev. 01, 07/2012

Tableau 13 : Rglages par dfautMenu Protections


Sous-menu

Description

Symbole Article

Valeur par
dfaut

Gamme de rglage

Tolrance

Enclenchement de longue dure Ir

Maximum

10%

Retard de longue dure

Minimum

-20%, +0%
10%

tr

Enclenchement de courte dure

Isd

Minimum

Retard de courte dure

tsd

Minimum

Instantan

Ii

Minimum

Dfaut la terre (dclencheur


5.0P)

Dfaut la terre (dclencheur


6.0P)

Courant de neutre

Alarme de dfaut la terre

Aucune protection

Mode

Trip

Trip

Activation

Rglage des
commutateurs

In d 400 A : 30%100% In
400 < In d 1200 A : 20%100% In
1200 A < In : 500 A1200 A

10%

Retard d'activation

Rglage des
commutateurs

140 s

-20%, +0%

Off

Off, N/2, N, 1.6N

Mode

Off

Alarme, off

Ineutre

10%

alarme

FRANAIS

Activation

1200 A

20 x In1200 A

15%

Retard d'activation

10.0 s

1.010.0 s

-20%, +0%

Retombe

1200 A

20 Aactivation

15%

1.010.0 s

-20%, +0%

Retard de retombe 1.0 s

Dsquilibre de courant

Idsq.

Protections en courant

Demande de courant max. de la


I1max
phase 1

Demande de courant max. de la


I2max
phase 2

Demande de courant max. de la


I3max
phase 3

Demande de courant max. pour


le neutre

In max

Mode

Off

Alarme, trip, off

% d'activation

60%

560%

-10%, +0%

Retard d'activation

40 s

1-40 s

-20%, +0%

% de retombe

% d'activation
Idsq.

5%% d'activation

-10%, +0%

Retard de retombe 10 s

10-360 s

-20%, +0%

Mode

Alarme, trip, off

Off

Activation

In

0.2 x InIn

Retard d'activation

1500 s

151500 s

-20%, +0%

Retombe

Activation I1max

0.2 x Inactivation

6,6%
-20%, +0%

6,6%

Retard de retombe 15 s

153000 s

Mode

Off

Alarme, trip, off

Activation

In

0.2 x InIn

Retard d'activation

1500 s

151500 s

-20%, +0%

Retombe

Activation I2max

0.2 x Inactivation

6,6%
-20%, +0%

6,6%

Retard de retombe 15 s

153000 s

Mode

Off

Alarme, trip, off

Activation

In

0.2 x InIn

Retard d'activation

1500 s

151500 s

-20%, +0%

Retombe

Activation I3max

0.2 x Inactivation

6,6%
-20%, +0%

6,6%

Retard de retombe 15 s

153000 s

Mode

Off

Alarme, trip, off

Activation

In

0.2 x InIn

Retard d'activation

1500 s

151500 s

-20%, +0%

Retombe

Activation Inmax

0.2 x Inactivation

6,6%

Retard de retombe 15 s

153000 s

6,6%

-20%, +0%
Page suivante

76-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe BRglages par dfaut et tolrances

48049-137-05
Rev. 01, 07/2012

Tableau 13 : Rglages par dfautMenu Protections (suite)


Description

Tension minimale (sous-tension) Umin

Protections en tension

Tension maximale (surtension)

Dsquilibre de tension

Inversion de puissance

Autres protections

Frquence minimale (sousfrquence)

Frquence maximale
(surfrquence)

Valeur par
dfaut

Gamme de rglage

Mode

Off

Alarme, trip, off

Activation

100 V

100 Vactivation Umax

-5%, +0%

Retard d'activation

5s

1,2-5 s

-0%, +20%

Retombe

Activation Umin

Symbole Article

Umax

Udsq.

rP

Fmin

Fmax

Activation Umin1200 V

-5%, +0%

Retard de retombe 1,2 s

1,2-36 s

-0%, +20%

Mode

Off

Alarme, trip, off

Activation

725 V

Umin1200 A

-0%, +5%

Retard d'activation

5s

1,2-5 s

-0%, +20%

Retombe

Activation Umax

100 Vactivation Umax

-0%, +5%

Retard de retombe 1,2 s

1,2-36 s

-0%, +20%

Mode

Off

Alarme, trip, off

Activation

20%

220%*

-10%, +0%

Retard d'activation

40 s

1-40 s

-20%, +0%

Retombe

Activation
Udsq.

2%activation Udsq.

-10%, +0%

Retard de retombe 10 s

10-360 s

-20%, +0%

Mode

Off

Alarme, trip, off

Activation

500 kW

5500kW

2,5%

Retard d'activation

20 s

0,2-20 s

-0%, +20%

Retombe

Activation rP

5kWactivation rP

2,5%

Retard de retombe 1 s

1-360 s

-0%, +20%

Mode

Off

Alarme, trip, off

Activation

45 Hz

45 Hzactivation Fmax

0,5 Hz

Retard d'activation

5s

0,2-5 s

-0%, +20%

Retombe

Activation Fmin

Activation Fmin440 Hz

0,5 Hz

Retard de retombe 1 s

1-36 s

-0%, +20%

Mode

Off

Alarme, trip, off

Activation

65 Hz

Activation Fmin440 Hz

0,5 Hz

Retard d'activation

5s

0,2-5 s

-0%, +20%

Retombe

Activation Fmax

Retard de retombe 1 s
Sens de rotation des
phases

Dlestage relestage I

Sens de rotation des phases

Dlestage relestage I

Dlestage relestage P Dlestage relestage P

Squence

45 Hzactivation Fmax

0,5 Hz

1-36 s

-0%, +20%

Sens de rotation: Sens de rotation: phase 1, phase


phase 1, phase 3, 2, phase 3 ou sens de rotation:
phase 2
phase 1, phase 3, phase 2

Mode

Off

Alarme, off

Mode

Off

Off, on

% d'activation

100% Ir

50% Ir100% Ir

6%

% de retard
d'activation

80% tr

2080% tr

-20%, +0%

% de retombe

Activation
dlestage
relestage I

30%% d'activation dlestage


relestage I

6%

Retard de retombe 10 s

10-600 s

-20%, +0%

Mode

Off

Off, on

Activation

10.000 kW

20010,000 kW

2.5%

Retard d'activation

3600 s

10-3600 s

-20%, +0%

Retombe

Activation
dlestage
relestage P

100 kW% d'activation dlestage


relestage P

2.5%

10-3600 s

-20%, +0%

Retard de retombe 10 s
*

Tolrance

Ne pas regler au-dessus de 20%.

20002012 Schneider Electric Tous droits rservs

77-FR

FRANAIS

Sous-menu

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe BRglages par dfaut et tolrances

48049-137-05
Rev. 01, 07/2012

Gamme des mesures et prcision


Table 14:
Article

Courant
instantan

Demande de
courant

FRANAIS
Tension

Puissance
instantane
Facteur de
puissance

Demande de
puissance

Total des
nergies
nergie
consomme
nergie fournie
Frquence

78-FR

Gamme des mesures et prcision


Description

Symbole

Gamme

Tolrance

Courant instantan de la phase 1

I1

0 32 kA

1,5%

Courant instantan de la phase 2

I2

0 32 kA

1,5%

Courant instantan de la phase 3

I3

0 32 kA

1,5%

Courant instantan du neutre

In

0 32 kA

1,5%

Courant instantan dans la terre

0 32 kA

1,5%

Courant instantan max. de la phase 1

I1max

0 32 kA

1,5%

Courant instantan max. de la phase 2

I2max

0 32 kA

1,5%

Courant instantan max. de la phase 3

I3max

0 32 kA

1,5%

Courant instantan max. du neutre

Inmax

0 32 kA

1,5%

Courant instantan max. dans la terre

0 32 kA

1,5%

Demande de courant de la phase 1

I1

0 32 kA

1,5%

Demande de courant de la phase 2

I2

0 32 kA

1,5%

Demande de courant de la phase 3

I3

0 32 kA

1,5%

Demande de courant du neutre

In

0 32 kA

1,5%

Demande de courant max. de la phase 1

I1max

0 32 kA

1,5%

Demande de courant max. de la phase 2

I2max

0 32 kA

1,5%

Demande de courant max. de la phase 3

I3max

0 32 kA

1,5%

Demande de courant max. du neutre

Inmax

0 32 kA

1,5%

Tension instantane entre les phases 1 et 2

U12

0 1200 V

0,5%

Tension instantane entre les phases 2 et 3

U23

0 1200 V

0,5%

Tension instantane entre les phases 3 et 1

U31

0 1200 V

0,5%

Tension instantane entre la phase 1 et le neutre

V1n

0 1200 V

0,5%

Tension instantane entre la phase 2 et le neutre

V2n

0 1200 V

0,5%

Tension instantane entre la phase 3 et le neutre

V3n

0 1200 V

0,5%

Tension moyenne entre phases

Umoyen 3)

0 1200 V

0,5%

Dsquilibre de tension

Udsq. 3)

0 100 V

0,5%

Puissance active instantane

0 32 MW

2%

Puissance ractive instantane

0 32 Mvar

2%

Puissance apparente instantane

0 32 MVA

2%

Facteur de puissance

PF

-1 +1

0,01%

max

Demande de puissance active

0 32 MW

2%

Demande de puissance ractive

0 32 Mvar

2%

Demande de puissance apparente

0 32 MVA

2%

Demande de puissance active max. depuis la dernire remise zero

Pmax

0 32 MW

2%

Demande de puissance ractive max. depuis la dernire remise zero

Qmax

0 32 Mvar

2%

Demande de puissance apparente max. depuis la dernire remise


zero

Smax

0 32 MVA

2%

Puissance active totale

E. P

-10101010

2%

Puissance ractive totale

E. Q

-10101010 Kvarh

2%

Puissance apparente totale

E. S

-10101010 KVAh

2%

Puissance active totale consomme

E. P

-1010 1010 Kwh

2%

Puissance ractive totale consomme

E. Q

-10101010 Kvarh

2%

Puissance active totale fournie

E. P

-10101010 Kwh

2%

Puissance ractive totale fournie

E. Q

-10101010 Kvarh

2%

Frquence rseau

45 440 Hz

0,1 Hz

Kwh

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Annexe CAccs rseau/communication

Tableau 15 : Valeurs lisibles distance


Article

L'option de communication peut tre utiliser


pour accder au dclencheur Micrologic
distance l'aide du logiciel System Manager
Software (SMS), version 3.3 ou ultrieures, ou
autre logiciel de gestion de systmes en rseau.
Pour plus d'informations sur le logiciel SMS, voir
le catalogue de produits.

Courant

Demande de
courant

Description

Symbole

Courant instantan de la phase 1

I1

Courant instantan de la phase 2

I2

Courant instantan de la phase 3

I3

Courant instantan du neutre

In

Courant instantan dans la terre

Courant moyen de la phase 1

I1moy

Courant moyen de la phase 2

I2moy

Courant moyen de la phase 3

I3moy

Courant moyen du neutre

Inmoy

Courant moyen dans la terre

Courant instantan max. de la phase 1

I1max

moy

Courant instantan max. de la phase 2

I2max

Courant instantan max. de la phase 3

I3max

Courant instantan max. du neutre

Inmax

Courant instantan max. dans la terre

Dsquilibre de courant instantan de la phase 1

I1dsq.

Dsquilibre de courant instantan de la phase 2

I2dsq.

max

Dsquilibre de courant instantan de la phase 3

I3dsq.

Dsquilibre de courant instantan du neutre

Indsq.

Dsquilibre de courant instantan max.

Idsq. max

Demande de courant de la phase 1

I1

Demande de courant de la phase 2

I2

Demande de courant de la phase 3

I3

Demande de courant du neutre

In

Demande de courant max. depuis la dernire Rz de la phase 1 I1max


Demande de courant max. depuis la dernire Rz de la phase 2 I2max
Demande de courant max. depuis la dernire Rz de la phase 3 I3max
Demande de courant max. depuis la dernire Rz du neutre

Inmax

Chronotimbrage par horodateur de la demande de courant max.

Tension

Puissance
active

Tension instantane entre les phases 1 et 2

U inst.U12

Tension instantane entre les phases 2 et 3

U inst. U23

Tension instantane entre les phases 3 et 1

U inst. U31

Tension instantane entre la phase 1 et le neutre

U inst. U1n

Tension instantane entre la phase 2 et le neutre

U inst. U2n

Tension instantane entre la phase 3 et le neutre

U inst. U3n

Tension moyenne phase-phase

U moy Upp

Tension moyenne phase-neutre

Umoy Upn

Dsquilibre de tension entre U12 et la moyenne

U dsq. U12

Dsquilibre de tension entre U23 et la moyenne

U dsq. U23

Dsquilibre de tension entre U31 et la moyenne

U dsq. U31

Dsquilibre de tension entre V1n et la moyenne

U dsq. U1n

Dsquilibre de tension entre V2n et la moyenne

U dsq. U2n

Dsquilibre de tension entre V3n et la moyenne

U dsq. U12

Dsquilibre de tension phase-phase max.

U max dsq.
Upp

Dsquilibre de tension phase-neutre max.

U max dsq.
Upn

Puissance active instantane par phase

P
Page suivante

20002012 Schneider Electric Tous droits rservs

79-FR

FRANAIS

Valeurs lisibles distance

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 15 : Valeurs lisibles distance (suite)


Article

Description

Symbole

Demande de puissance active

Demande de puissance ractive

Demande de puissance apparente

Demande de puissance active max. depuis la dernire remise


zero

Pmax

Demande de puissance ractive max. depuis la dernire remise


Qmax
zero
Demande de
puissance

Demande de puissance apparente max. depuis la dernire


remise zero

Smax

Demande active de demande prvue la fin de l'intervalle


(fentre)
Demande ractive de demande prvue la fin de l'intervalle
(fentre)
Demande apparente de demande prvue la fin de l'intervalle
(fentre)
Chronotimbrage par horodateur de la demande de puissance
max.
nergie active totale
nergie

nergie active consomme


nergie active fournie

FRANAIS

Valeurs des
dfauts
Frquence
Dates des
mises jours

Type de dfauts
Valeurs des courants interrompus
Frquence rseau

Intervalle entre la dernire mise jour des valeurs en temps rel


et le tableau des courants
Date de mise jour des demandes de courant, de la demande
de puissance et de l'nergie
Historiques de dfauts

Historique

Historiques d'alarme
Historiques des vnements
Usure des contacts

Compteurs

Compteur de manuvres depuis la dernire RAZ


Date/heure de la dernire RAZ du compteur de manuvres
Total du compteur de manuvres (dure de vie)
Configuration de la date et l'heure
Mot de passe
Code d'identification du dclencheur
Nom d'identification du dclencheur
Algorithme de calcul des mesures
Convention de signe
Mode de mesure de l'nergie totale

Configuration Facteurs de proportionnalit


Intervalle des fentres de calcul du courant moyen
Indication de la qualit de l'alimentation
Mode de calcul de la puissance moyenne
Intervalle des fentres de calcul de la puissance moyenne
Indication de charge de la pile
Affectation des contacts programmables
Configuration des contacts programmables
Page suivante

80-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 15 : Valeurs lisibles distance (suite)


Article

Description

Symbole

Courant nominal du disjoncteur


Type de protection du neutre
Rglages de la protection de longue dure
Rglages de la protection de courte dure
Rglages de la protection instantane
Protection

Rglages de la protection contre les dfauts la terre


Rglages de la protection de dsquilibre de courant
Rglages de l'alarme I
Rglages de la protection en courant maximum
Rglages de la protection en tension

FRANAIS

Rglages d'autres fonctions de protection

20002012 Schneider Electric Tous droits rservs

81-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Liste des registres

Pour accder aux registres disponibles, se servir du systme d'adresses


suivant :

Les quantits sont indiques en ordre


alphabtique selon le nom de sujet SMS.

Module Nom du module

quation

BCM

Module de communication de disjoncteur

147

REMARQUE : Une vitesse de balayage de


systme de 500 ms ou plus est recommande
pour minimiser les problmes d'arrt de
communication.

CCM

Module de communication de berceau

BCM + 50

5197

PM

Module de protection (interne au dclencheur)

BCM +100

101147

MM

Module de mesure (interne au dclencheur)

BCM +200

201247

Gamme d'adresse

Tableau 16 : Liste des registres1

FRANAIS

Nom de sujet

Description pour l'utilisateur

Nombre de
Registre
registres

Module

810D_LDPU

Valeur d'enclenchement de retard de longue


dure du disjoncteur en cours

8862

PM

Mise lchelle non disponible

810DBrkrStatus

tat du disjoncteur

661

BCM

Bit 0; ON = ferm; OFF = ouvert

810DBrkrTripStat

tat du dclencheur du disjoncteur

661

BCM

Bit 2; ON = dclench; OFF = pas


dclench

BCM_SN

Numro de srie du BCM

516

BCM

Texte ASCII

BkrPos

Position du disjoncteur

661

CCM

Bit 8 = dconnecte
Bit 9 = connecte
Bit 10 = position d'essai

CFVAB

Facteur de crtetension 1-2

1119

MM

Pas d'units Centimes

CFVAN

Facteur de crtetension 1-N

1122

MM

Pas d'units Centimes

CFVBC

Facteur de crtetension 2-3

1120

MM

Pas d'units Centimes

CFVBN

Facteur de crtetension 2-N

1123

MM

Pas d'units Centimes

CFVCA

Facteur de crtetension 3-1

1121

MM

Pas d'units Centimes

CFVCN

Facteur de crtetension 3-N

1124

MM

Pas d'units Centimes

DT_3Regs

Horloge date/heure de l'appareil

679

BCM

DTLastTrip

Date/heure du dernir dclenchement

693

BCM

DTPkIAD

Date/heure, demande de courant crte 1

3005

MM

DTPkIBD

Date/heure, demande de courant crte 2

3008

MM

DTPkICD

Date/heure, demande de courant crte 3

3011

MM

Units

chelle

Format date/heure de 3 registres2


Format date/heure de 3 registres2
Format date/heure de 3 registres2
Format date/heure de 3 registres2
Format date/heure de 3 registres2
Format date/heure de 3 registres2

DTPkIND

Date/heure, demande de courant crte N

3014

MM

DTPkKFDA

Date/heure, demande de facteur K crte 1

3041

MM

DTPkKFDB

Date/heure, demande de facteur K crte 2

3044

MM

DTPkKFDC

Date/heure, demande de facteur K crte 3

3047

MM

DTPkKFDN

Date/heure, demande de facteur K crte N

3050

MM

Pas d'units Format date/heure de 3 registres2


Pas d'units Format date/heure de 3 registres2

DTPkkVAD

Date/heure, demande de puissance apparante


crte

3023

MM

Format date/heure de 3 registres2

DTPkkVARD

Date/heure, demande de puissance ractive crte

3020

MM

DTPkkWD

Date/heure, demande de puissance active crte

3017

MM

Format date/heure de 3 registres2


Format date/heure de 3 registres2

DTResetEnergy

Date/heure, dernire Rz, nergies cumules

3038

MM

DTResetMinMax

Date/heure, dernire Rz, min./max.

3032

MM

Format date/heure de 3 registres2


Format date/heure de 3 registres2

DTResetPkID

Date/heure, dernire Rz, demande de courant


crte

3026

MM

Format date/heure de 3 registres2

DTPkkVAD

Date/heure, demande de puissance apparante


crte

3023

MM

Format date/heure de 3 registres2

Pas d'units Format date/heure de 3 registres2


Pas d'units Format date/heure de 3 registres2

1 Pour les entres de registres qui ne sont pas indiques et les informations de facteur d'chelle, voir les directives d'utilisation 0613IB1201, Systme de

communications Modbus..
2Format date/heure de 3 registres :registre 1 : mois (octet 1) = 1 12; jour (octet 2) = 1 31; registre 2 : anne (octet 1) = 0 199 (ajouter 1900 pour dterminer

l'anne en cours); heure (octet 2) = 0 23; registre 3 : minutes (octet 1) = 0 59; secondes (octet 2) = 0 59
Remarque : Les bits 14 et 15 du registre mois/jour doivent tre masqus.
3 Format facteur de puissance : 1 999 pour les facteurs de puissance de dphasage arrire, 1000 pour le facteur de puissance unitaire 1,000, et 1 999 pour
les facteurs de puissance de dphasage avant.
4Format modulo 10 000 : registres squentiels 1 4. Chaque registre est de modulo 10 000 (intervalle = 9 999 +9 999).
Rsultat est [R4*10 000^3 + R3*10 ,000^2 + R2*10 000^1] + R1. L'intervalle est de zro 9 999 999 999 999 999.

82-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 16 : Liste des registres1


Nom de sujet

Description pour l'utilisateur

Nombre de
Registre
registres

Module

DTResetPkkWD

Date/heure, dernire Rz, demande de


puissance crte

3029

MM

Format date/heure de 3 registres2

EnableCloseBkr

Fermeture distance active

669

BCM

Bit 2; ON = activ, OFF = desactiv

EnableOpenBkr

Ouverture distance active

669

BCM

Bit 1; ON = activ; OFF = desactiv

EnableRemCtrl

Commande distance active

669

BCM

Bit 3; ON = auto (activ);


OFF = manuel (desactiv)

fkVAA

Puissance apparente fondamentale 1

1084

MM

kVA

fkVAB

Puissance apparente fondamentale 2

1085

MM

kVA

chelle E

fkVAC

Puissance apparente fondamentale 3

1086

MM

kVA

chelle E

Units

chelle

Page suivante

fkVATtl

Puissance apparente fondamentale totale

1087

MM

kVA

chelle E

fVAngA

Tension fondamentale, angle 1-2/1-N

1133

MM

Degrs

Diximes

fVAngB

Tension fondamentale, angle 2-3/2-N

1134

MM

Degrs

Diximes

fVAngC

Tension fondamentale, angle 3-1/3-N

1135

MM

Degrs

Diximes

GFAlarmStatus

tat d'alarme de dfaut la terre

8860

PM

Bit 0; ON = actif; OFF = inactif

GFPreAlarmStatus

tat pr-alarme d'alarme de dfaut la terre

8864

PM

Bit 0; ON = actif; OFF = inactif

Hz

Frquence

1054

MM

Hz

chelle F

IA

Courant 1

1016

MM

chelle A - Courant de phase

IA_PCT

% de charge, courant 1

8837

PM

Unit

IAD

Demande de courant 1

2200

MM

chelle A

IAppA

Courant apparent 1

1023

MM

chelle A

IAppB

Courant apparent 2

1024

MM

chelle A

IAppC

Courant apparent 3

1025

MM

chelle A

IAppN

Courant apparent N

1026

MM

chelle B

IAvg

Courant moyen

1027

MM

chelle A - Courant de phase

IB

Courant 2

1017

MM

chelle A - Courant de phase

IB_PCT

% de charge, courant 2

8838

PM

Unit

IBD

Demande de courant 2

2201

MM

chelle A

IC

Courant 3

1018

MM

chelle A - Courant de phase

IC_PCT

% de charge, courant 3

8839

PM

Unit

ICD

Demande de courant 3

2202

MM

chelle A

IDatPkKFD_A

Demande de courant dem. de facteur K crte 1 1

2270

MM

chelle A

IDatPkKFD_B

Demande de courant dem. de facteur K crte 2 1

2271

MM

chelle A

IDatPkKFD_C

Demande de courant dem. de facteur K crte 3 1

2272

MM

chelle A

IDatPkKFD_N

Demande de courant dem. de facteur K crte N 1

2273

MM

chelle B

IG

Courant G (terre)

1021

MM

chelle C

IG_PCT

% de charge, courant G

8841

PM

Unit

IG_PCT_VIGI

% de charge, courant G (VIGI)

8842

PM

Centimes

IG_VIGI

Courant G (VIGI)

8826

PM

Millimes

IMax

Courant max. prsente

1020

MM

chelle A - Courant de phase

IN

Courant N

1019

MM

chelle B - Courant de neutre

IN_PCT

% de charge, courant N

8840

PM

Unit

IND

Demande de courant N

2203

MM

chelle B

IUnbalA

Dsquilibre de courant 1

1028

MM

Diximes

1 Pour les entres de registres qui ne sont pas indiques et les informations de facteur d'chelle, voir les directives d'utilisation 0613IB1201, Systme de

communications Modbus..
2Format date/heure de 3 registres :registre 1 : mois (octet 1) = 1 12; jour (octet 2) = 1 31; registre 2 : anne (octet 1) = 0 199 (ajouter 1900 pour dterminer

l'anne en cours); heure (octet 2) = 0 23; registre 3 : minutes (octet 1) = 0 59; secondes (octet 2) = 0 59
Remarque : Les bits 14 et 15 du registre mois/jour doivent tre masqus.
3 Format facteur de puissance : 1 999 pour les facteurs de puissance de dphasage arrire, 1000 pour le facteur de puissance unitaire 1,000, et 1 999 pour

les facteurs de puissance de dphasage avant.


4Format modulo 10 000 : registres squentiels 1 4. Chaque registre est de modulo 10 000 (intervalle = 9 999 +9 999).

Rsultat est [R4*10 000^3 + R3*10 ,000^2 + R2*10 000^1] + R1. L'intervalle est de zro 9 999 999 999 999 999.

20002012 Schneider Electric Tous droits rservs

83-FR

FRANAIS

chelle E

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 16 : Liste des registres1


Nom de sujet

Description pour l'utilisateur

Nombre de
Registre
registres

Module

Units

chelle

IUnbalAlrm

tat de l'alarme de dsquilibre de courant

8859

PM

IUnbalB

Dsquilibre de courant 2

1029

MM

Diximes

Bit 0; ON = actif; OFF = inactif

IUnbalC

Dsquilibre de courant 3

1030

MM

Diximes

IUnbalPreAlrm

tat de la pre-alarme de dsquilibre de courant

8863

PM

IUnbalW

Dsquilibre de courant le plus mauvais

1032

MM

KFDatPkID_A

Dem. de facteur K la dem. de courant crte 1

2254

MM

Pas d'units Diximes

KFDatPkID_B

Dem. de facteur K la dem. de courant crte 2

2255

MM

Pas d'units Diximes

KFDatPkID_C

Dem. de facteur K la dem. de courant crte 3

2256

MM

Pas d'units Diximes

KFDatPkID_N

Dem. de facteur K la dem. de courant crte N

2257

MM

Pas d'units Diximes

Page suivante
Bit 0; ON = actif, OFF = inactif
Diximes

KFDN

Demande de facteur K pour N

2215

MM

Pas d'units Diximes

KFN

Facteur K pour N

1118

MM

Pas d'units Diximes

kVAA

Puissance apparente 1

1042

MM

kVA

chelle E

kVAB

Puissance apparente 2

1043

MM

kVA

chelle E

kVAC

Puissance apparente 3

1044

MM

kVA

chelle E

kVAD

Demande de puissance apparente

2236

MM

kVA

chelle D

FRANAIS

kVAD_PkkVARD

Dem. kVA concidente av./dem. kVAR crte

2235

MM

kVA

chelle D

kVAD_PkkWD

Dem. kVA concidente av./dem. kW crte

2229

MM

kVA

chelle D

kVAHr

nergie apparante

2024

MM

kVAH

Unit

kVARA

Puissance ractive 1

1038

MM

kVAR

chelle E

kVARB

Puissance ractive 2

1039

MM

kVAR

chelle E

kVARC

Puissance ractive 3

1040

MM

kVAR

chelle E

kVARD

Demande de puissance ractive

2230

MM

kVAR

chelle D

kVARD_PkkVAD

Dem. kVAR concidente av./dem. kVA crte

2241

MM

kVAR

chelle D

kVARD_PkkWD

Dem. kVAR concidente av./dem. kW crte

2228

MM

kVAR

chelle D

kVARHr

nergie ractive

2004

MM

kVARH

Unit

kVARHr_I

nergie ractive vers la charge

2016

MM

kVARH

Unit

kVARHr_O

nergie ractive de la charge

2020

MM

kVARH

Unit

kVARTtl

Puissance ractive totale

1041

MM

kVAR

chelle E

kVATtl

Puissance apparente totale

1045

MM

kVA

chelle E

kWA

Puissance active 1

1034

MM

kW

chelle E

kWB

Puissance active 2

1035

MM

kW

chelle E

kWC

Puissance active 3

1036

MM

kW

chelle E

kWD

Demande de puissance active

2224

MM

kW

chelle D

kWD_PkkVAD

Dem. kW concidente av./dem. kVA crte

2240

MM

kW

chelle D

kWD_PkkVARD

Dem. kW concidente av./dem. kVAR crte

2234

MM

kW

chelle D

kWHr

nergie active

2000

MM

kWH

Unit

kWHr_I

nergie active vers la charge

2008

MM

kWH

Unit

kWHr_O

nergie active de la charge

2012

MM

kWH

Unit

kWTtl

Puissance active totale

1037

MM

kW

chelle E

LDPUValue

Valeur d'enclenchement de retard de longue


dure

8756

PM

Unit

LSCurrAlrm

tat de l'alarme de courant de dlestage de


charge

8859

PM

Bit 13; ON = actif; OFF = inactif

1 Pour les entres de registres qui ne sont pas indiques et les informations de facteur d'chelle, voir les directives d'utilisation 0613IB1201, Systme de

communications Modbus..
2Format date/heure de 3 registres :registre 1 : mois (octet 1) = 1 12; jour (octet 2) = 1 31; registre 2 : anne (octet 1) = 0 199 (ajouter 1900 pour dterminer

l'anne en cours); heure (octet 2) = 0 23; registre 3 : minutes (octet 1) = 0 59; secondes (octet 2) = 0 59
Remarque : Les bits 14 et 15 du registre mois/jour doivent tre masqus.
3 Format facteur de puissance : 1 999 pour les facteurs de puissance de dphasage arrire, 1000 pour le facteur de puissance unitaire 1,000, et 1 999 pour
les facteurs de puissance de dphasage avant.
4Format modulo 10 000 : registres squentiels 1 4. Chaque registre est de modulo 10 000 (intervalle = 9 999 +9 999).
Rsultat est [R4*10 000^3 + R3*10 ,000^2 + R2*10 000^1] + R1. L'intervalle est de zro 9 999 999 999 999 999.

84-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 16 : Liste des registres1


Nom de sujet

Description pour l'utilisateur

Nombre de
Registre
registres

Module

LSCurrPreAlrm

tat de la pre-alarme de courant de dlestage de


charge

8863

PM

Bit 13; ON = actif; OFF = inactif

LSPwrAlrm

tat de l'alarme de puissance de dlestage de


charge

8859

PM

Bit 14; ON = actif; OFF = inactif

LSPwrPreAlrm

tat de la pre-alarme de puissance de dlestage


de charge

8863

PM

Bit 14; ON = actif; OFF = inactif

M2C_M6CR1Status tat du module de relais R1

8857

PM

Bit 0; ON = activ; OFF = dsactiv

M2C_M6CR2Status tat du module de relais R2

8857

PM

Bit 1; ON = activ; OFF = dsactiv

M2C_M6CR3Status tat du module de relais R3

8857

PM

Bit 2; ON = activ; OFF = dsactiv

M2C_M6CR4Status tat du module de relais R4

8857

PM

Bit 3; ON = activ; OFF = dsactiv

Units

chelle

Page suivante

8857

PM

Bit 4; ON = activ; OFF = dsactiv

8857

PM

Bit 5; ON = activ; OFF = dsactiv

MaxCFVAB

Facteur de crte max.tension 1-2

1719

MM

Pas d'units Centimes

MaxCFVAN

Facteur de crte max.tension 1-N

1722

MM

Pas d'units Centimes

MaxCFVBC

Facteur de crte max.tension 2-3

1720

MM

Pas d'units Centimes

MaxCFVBN

Facteur de crte max.tension 2-N

1723

MM

Pas d'units Centimes

MaxCFVCA

Facteur de crte max.tension 3-1

1721

MM

Pas d'units Centimes

MaxCFVCN

Facteur de crte max.tension 3-N

1724

MM

Pas d'units Centimes

MaxfkVAA

Puissance apparente fondamentale max. 1

1684

MM

kVA

chelle E

MaxfkVAB

Puissance apparente fondamentale max. 2

1685

MM

kVA

chelle E

MaxfkVAC

Puissance apparente fondamentale max. 3

1686

MM

kVA

chelle E

MaxfkVATtl

Puissance apparente fondamentale max. totale

1687

MM

kVA

chelle E

MaxfVMagAB

Ampleur de la tension max. 1-2 fondamentale

1656

MM

chelle D

MaxfVMagAN

Ampleur de la tension max. 1-N fondamentale

1659

MM

chelle D

MaxfVMagBC

Ampleur de la tension max. 2-3 fondamentale

1657

MM

chelle D

MaxfVMagBN

Ampleur de la tension max. 2-N fondamentale

1660

MM

chelle D

MaxfVMagCA

Ampleur de la tension max. 3-1 fondamentale

1658

MM

chelle D

MaxfVMagCN

Ampleur de la tension max. 3-N fondamentale

1661

MM

chelle D

FRANAIS

M2C_M6CR5Status tat du module de relais R5


M2C_M6CR6Status tat du module de relais R6

MaxHz

Frquence max.

1654

MM

Hz

chelle F

MaxIA

Courant max. 1

1616

MM

chelle A - Courant de phase

MaxIAppA

Courant apparent max. 1

1623

MM

chelle A

MaxIAppB

Courant apparent max. 2

1624

MM

chelle A

MaxIAppC

Courant apparent max. 3

1625

MM

chelle A

MaxIAppN

Courant apparent max. N

1626

MM

chelle B

MaxIAvg

Courant moyen max.

1627

MM

chelle A - Courant de phase

MaxIB

Courant max. 2

1617

MM

chelle A - Courant de phase

MaxIC

Courant max. 3

1618

MM

chelle A - Courant de phase

MaxIG

Courant G (terre) max.

1621

MM

chelle C
Millimes

MaxIG_VIGI

Courant G (VIGI) max.

8832

PM

MaxIN

Courant N max.

1619

MM

chelle B - Courant de neutre

MaxIUnbalA

Dsquilibre de courant max. 1

1628

MM

Diximes

MaxIUnbalB

Dsquilibre de courant max. 2

1629

MM

Diximes

MaxIUnbalC

Dsquilibre de courant max. 3

1630

MM

Diximes

1 Pour les entres de registres qui ne sont pas indiques et les informations de facteur d'chelle, voir les directives d'utilisation 0613IB1201, Systme de

communications Modbus..
2Format date/heure de 3 registres :registre 1 : mois (octet 1) = 1 12; jour (octet 2) = 1 31; registre 2 : anne (octet 1) = 0 199 (ajouter 1900 pour dterminer

l'anne en cours); heure (octet 2) = 0 23; registre 3 : minutes (octet 1) = 0 59; secondes (octet 2) = 0 59
Remarque : Les bits 14 et 15 du registre mois/jour doivent tre masqus.
3 Format facteur de puissance : 1 999 pour les facteurs de puissance de dphasage arrire, 1000 pour le facteur de puissance unitaire 1,000, et 1 999 pour
les facteurs de puissance de dphasage avant.
4Format modulo 10 000 : registres squentiels 1 4. Chaque registre est de modulo 10 000 (intervalle = 9 999 +9 999).
Rsultat est [R4*10 000^3 + R3*10 ,000^2 + R2*10 000^1] + R1. L'intervalle est de zro 9 999 999 999 999 999.

20002012 Schneider Electric Tous droits rservs

85-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 16 : Liste des registres1


Nombre de
Registre
registres

Module

Units

chelle

MM

Diximes

MM

Pas d'units Diximes

Nom de sujet

Description pour l'utilisateur

MaxIUnbalW

Dsquilibre de courant max. le plus mauvais

1632

MaxKFN

Facteur K max. neutre

1718

MaxkVAA

Puissance apparente max. 1

1642

MM

kVA

MaxkVAB

Puissance apparente max. 2

1643

MM

kVA

chelle E

MaxkVAC

Puissance apparente max. 3

1644

MM

kVA

chelle E

chelle E

MaxkVARA

Puissance ractive max. 1

1638

MM

kVAR

chelle E

MaxkVARB

Puissance ractive max. 2

1639

MM

kVAR

chelle E

MaxkVARC

Puissance ractive max. 3

1640

MM

kVAR

chelle E

Page suivante

MaxkVARTtl

Puissance ractive totale max.

1641

MM

kVAR

chelle E

MaxkVATtl

Puissance apparente totale max.

1645

MM

kVA

chelle E

MaxkWA

Puissance active max. 1

1634

MM

kW

chelle E

MaxkWB

Puissance active max. 2

1635

MM

kW

chelle E

FRANAIS

MaxkWC

Puissance active max. 3

1636

MM

kW

chelle E

MaxkWTtl

Puissance active totale max.

1637

MM

kW

chelle E

MaxPFA

Facteur de puissance max. 1

1646

MM

MaxPFB

Facteur de puissance max. 2

1647

MM

MaxPFC

Facteur de puissance max. 3

1648

MM

MaxPFTtl

Facteur de puissance total max.

1649

MM

MaxVAB

Tension max. 1-2

1600

MM

chelle D - tension

MaxVAN

Tension max. 1-N

1603

MM

chelle D - tension

Format FP3
Format FP3
Format FP3
Format FP3

MaxVBC

Tension max. 2-3

1601

MM

chelle D - tension

MaxVBN

Tension max. 2-N

1604

MM

chelle D - tension

MaxVCA

Tension max. 3-1

1602

MM

chelle D - tension

MaxVCN

Tension max. 3-N

1605

MM

chelle D - tension

MaxVLLAvg

Moyenne de tension entre phases max.

1606

MM

chelle D - tension

MaxVLNAvg

Moyenne de tension phase-neutre max.

1607

MM

chelle D - tension

MaxVUnbalAB

Dsquilibre max. de tension 1-2

1608

MM

Diximes

MaxVUnbalAN

Dsquilibre max. de tension 1-N

1611

MM

Diximes

MaxVUnbalBC

Dsquilibre max. de tension 2-3

1609

MM

Diximes

MaxVUnbalBN

Dsquilibre max. de tension 2-N

1612

MM

Diximes

MaxVUnbalCA

Dsquilibre max. de tension 3-1

1610

MM

Diximes

MaxVUnbalCN

Dsquilibre max. de tension 3-N

1613

MM

Diximes

MaxVUnbalLLW

Dsquilibre max. de tension entre phases le


plus mauvais

1614

MM

Diximes

MaxVUnbalLNW

Dsquilibre max. de tension phase-neutre le


plus mauvais

1615

MM

Diximes

Pas d'units Centimes

MinCFVAB

Facteur de crte min.tension 1-2

1419

MM

MinCFVAN

Facteur de crte min.tension 1-N

1422

MM

Pas d'units Centimes

MinCFVBC

Facteur de crte min.tension 2-3

1420

MM

Pas d'units Centimes

MinCFVBN

Facteur de crte min.tension 2-N

1423

MM

Pas d'units Centimes

MinCFVCA

Facteur de crte min.tension 3-1

1421

MM

Pas d'units Centimes

MinCFVCN

Facteur de crte min.tension 3-N

1424

MM

Pas d'units Centimes

MinfkVAA

Puissance apparente min. fondamentale 1

1384

MM

kVA

chelle E

1 Pour les entres de registres qui ne sont pas indiques et les informations de facteur d'chelle, voir les directives d'utilisation 0613IB1201, Systme de

communications Modbus..
2Format date/heure de 3 registres :registre 1 : mois (octet 1) = 1 12; jour (octet 2) = 1 31; registre 2 : anne (octet 1) = 0 199 (ajouter 1900 pour dterminer

l'anne en cours); heure (octet 2) = 0 23; registre 3 : minutes (octet 1) = 0 59; secondes (octet 2) = 0 59
Remarque : Les bits 14 et 15 du registre mois/jour doivent tre masqus.
3 Format facteur de puissance : 1 999 pour les facteurs de puissance de dphasage arrire, 1000 pour le facteur de puissance unitaire 1,000, et 1 999 pour
les facteurs de puissance de dphasage avant.
4Format modulo 10 000 : registres squentiels 1 4. Chaque registre est de modulo 10 000 (intervalle = 9 999 +9 999).
Rsultat est [R4*10 000^3 + R3*10 ,000^2 + R2*10 000^1] + R1. L'intervalle est de zro 9 999 999 999 999 999.

86-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 16 : Liste des registres1


Nom de sujet

Description pour l'utilisateur

Nombre de
Registre
registres

Module

Units

chelle

MinfkVAB

Puissance apparente min. fondamentale 2

1385

MM

kVA

chelle E

MinfkVAC

Puissance apparente min. fondamentale 3

1386

MM

kVA

chelle E

MinfkVATtl

Puissance apparente fondamentale totale min.

1387

MM

kVA

chelle E

MinfVMagAB

Ampleur de la tension min. 1-2 fondamentale

1356

MM

chelle D

MinfVMagAN

Ampleur de la tension min. 1-N fondamentale

1359

MM

chelle D

MinfVMagBC

Ampleur de la tension min. 2-3 fondamentale

1357

MM

chelle D

MinfVMagBN

Ampleur de la tension min. 2-N fondamentale

1360

MM

chelle D

MinfVMagCA

Ampleur de la tension min. 3-1 fondamentale

1358

MM

chelle D

MinfVMagCN

Ampleur de la tension min. 3-N fondamentale

1361

MM

chelle D

MinHz

Frquence min.

1354

MM

Hz

chelle F

MinIA

Courant min.1

1316

MM

chelle A - Courant de phase

MinIAppA

Courant apparent min. 1

1323

MM

chelle A

MinIAppB

Courant apparent min. 2

1324

MM

chelle A

MinIAppC

Courant apparent min. 3

1325

MM

chelle A

MinIAppN

Courant apparent min. N

1326

MM

chelle B

MinIAvg

Courant moyen min.

1327

MM

chelle A - Courant de phase

MinIB

Courant min. 2

1317

MM

chelle A - Courant de phase

MinIC

Courant min. 3

1318

MM

chelle A - Courant de phase

MinIN

Courant min. N

1319

MM

chelle B - Courant de neutre

MinIUnbalA

Dsquilibre de courant min. 1

1328

MM

Diximes

MinIUnbalB

Dsquilibre de courant min. 2

1329

MM

Diximes

MinIUnbalC

Dsquilibre de courant min. 3

1330

MM

Diximes
Diximes

MinIUnbalW

Dsquilibre de courant min. le plus mauvais

1332

MM

MinKFN

Facteur K min. pour N

1418

MM

Pas d'units Diximes

MinkVAA

Puissance apparente min. 1

1342

MM

kVA

chelle E

MinkVAB

Puissance apparente min. 2

1343

MM

kVA

chelle E

MinkVAC

Puissance apparente min. 3

1344

MM

kVA

chelle E

MinkVARA

Puissance ractive min. 1

1338

MM

kVAR

chelle E

MinkVARB

Puissance ractive min. 2

1339

MM

kVAR

chelle E

MinkVARC

Puissance ractive min. 3

1340

MM

kVAR

chelle E

MinkVARTtl

Puissance ractive totale min.

1341

MM

kVAR

chelle E

MinkVATtl

Puissance apparente totale min.

1345

MM

kVA

chelle E

MinkWA

Puissance active min. 1

1334

MM

kW

chelle E

MinkWB

Puissance active min. 2

1335

MM

kW

chelle E

MinkWC

Puissance active min. 3

1336

MM

kW

chelle E

MinkWTtl

Puissance active totale min.

1337

MM

kW

chelle E

MinPFA

Facteur de puissance min. 1

1346

MM

MinPFB

Facteur de puissance min. 2

1347

MM

MinPFC

Facteur de puissance min. 3

1348

MM

Format FP3
Format FP3
Format FP3
Format FP3

MinPFTtl

Facteur de puissance total min.

1349

MM

MinVAB

Tension min.1-2

1300

MM

chelle D - tension

MinVAN

Tension min. 1-N

1303

MM

chelle D - tension

1 Pour les entres de registres qui ne sont pas indiques et les informations de facteur d'chelle, voir les directives d'utilisation 0613IB1201, Systme de

communications Modbus..
2Format date/heure de 3 registres :registre 1 : mois (octet 1) = 1 12; jour (octet 2) = 1 31; registre 2 : anne (octet 1) = 0 199 (ajouter 1900 pour dterminer

l'anne en cours); heure (octet 2) = 0 23; registre 3 : minutes (octet 1) = 0 59; secondes (octet 2) = 0 59
Remarque : Les bits 14 et 15 du registre mois/jour doivent tre masqus.
3 Format facteur de puissance : 1 999 pour les facteurs de puissance de dphasage arrire, 1000 pour le facteur de puissance unitaire 1,000, et 1 999 pour
les facteurs de puissance de dphasage avant.
4Format modulo 10 000 : registres squentiels 1 4. Chaque registre est de modulo 10 000 (intervalle = 9 999 +9 999).
Rsultat est [R4*10 000^3 + R3*10 ,000^2 + R2*10 000^1] + R1. L'intervalle est de zro 9 999 999 999 999 999.

20002012 Schneider Electric Tous droits rservs

87-FR

FRANAIS

Page suivante

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 16 : Liste des registres1


Nombre de
Registre
registres

Module

Units

chelle

Nom de sujet

Description pour l'utilisateur

MinVBC

Tension min. 2-3

1301

MM

chelle D - tension

MinVBN

Tension min. 2-N

1304

MM

chelle D - tension

MinVCA

Tension min. 3-1

1302

MM

chelle D - tension

MinVCN

Tension min. 3-N

1305

MM

chelle D - tension

MinVLLAvg

Moyenne de tension entre phases min.

1306

MM

chelle D - tension

MinVLNAvg

Moyenne de tension phase-neutre min.

1307

MM

chelle D - tension

MinVUnbalAB

Dsquilibre min. de tension 1-2

1308

MM

Diximes

MinVUnbalAN

Dsquilibre min. de tension 1-N

1311

MM

Diximes
Diximes

MinVUnbalBC

Dsquilibre min. de tension 2-3

1309

MM

MinVUnbalBN

Dsquilibre min. de tension 2-N

1312

MM

Diximes

MinVUnbalCA

Dsquilibre min. de tension 3-1

1310

MM

Diximes

MinVUnbalCN

Dsquilibre min. de tension3-N

1313

MM

Diximes

MinVUnbalLLW

Dsquilibre min. de tension entre phases le


plus mauvais

1314

MM

Diximes

MinVUnbalLNW

Dsquilibre min. de tension phase-neutre le


plus mauvais

1315

MM

Diximes

Courant nominal

Courant nominal du disjoncteur

8750

PM

OverFreqAlrm

tat de l'alarme de sur-frquence

8859

PM

Page suivante

FRANAIS

Unit
Bit 11; ON = actif, OFF = inactif

OverFreqPreAlrm

tat de la pre-alarme de sur-frquence

8863

PM

Bit 11; ON = actif, OFF = inactif

OverIAAlrm

tat de l'alarme de demande de surintensit 1

8859

PM

Bit 1; ON = actif, OFF = inactif

OverIAPreAlrm

tat de la pre-alarme de dem. de surintensit 1

8863

PM

Bit 1; ON = actif, OFF = inactif

OverIBAlrm

tat de l'alarme de demande de surintensit 2

8859

PM

Bit 2; ON = actif, OFF = inactif

OverIBPreAlrm

tat de la pre-alarme de dem. de surintensit 2

8863

PM

Bit 2; ON = actif, OFF = inactif

OverICAlrm

tat de l'alarme de demande de surintensit 3

8859

PM

Bit 3; ON = actif, OFF = inactif

OverICPreAlrm

tat de la pre-alarme de dem.de surintensit 3

8863

PM

Bit 3; ON = actif, OFF = inactif

OverINAlrm

tat de l'alarme de demande de surintensit N

8859

PM

Bit 4; ON = actif, OFF = inactif

OverINPreAlrm

tat de la pre-alarme de dem. de surintensit N

8863

PM

Bit 4; ON = actif, OFF = inactif

OverVoltAlrm

tat de l'alarme de surtension

8859

PM

Bit 6; ON = actif, OFF = inactif

OverVoltPreAlrm

tat de la pre-alarme de surtension

8863

PM

Bit 6; ON = actif, OFF = inactif


Millimes

PF_PkkVAD

FP concidente av./dem. kVA crte

2239

MM

PF_PkkVARD

FP concidente av./dem. kVAR crte

2233

MM

Millimes

PF_PkkWD

FP concidente av./dem. kW crte

2227

MM

Millimes

PFA

Facteur de puissance 1

1046

MM

Format FP3
Format FP3

PFB

Facteur de puissance 2

1047

MM

PFC

Facteur de puissance 3

1048

MM

PFTtl

Facteur de puissance total

1049

MM

PhaRotAlrm

tat de l'alarme de sens de rotation des phases

8859

PM

PkIAD

Demande de courant crte 1

2204

MM

Format FP3
Format FP3
Bit 12; ON = actif, OFF = inactif
A

chelle A

PkIBD

Demande de courant crte 2

2205

MM

chelle A

PkICD

Demande de courant crte 3

2206

MM

chelle A

PkIND

Demande de courant crte N

2207

MM

chelle A

PkKFDA

Demande crtefacteur K 1

2216

MM

Pas d'units Diximes

PkKFDB

Demande crtefacteur K 2

2217

MM

Pas d'units Diximes

1 Pour les entres de registres qui ne sont pas indiques et les informations de facteur d'chelle, voir les directives d'utilisation 0613IB1201, Systme de

communications Modbus..
2Format date/heure de 3 registres :registre 1 : mois (octet 1) = 1 12; jour (octet 2) = 1 31; registre 2 : anne (octet 1) = 0 199 (ajouter 1900 pour dterminer

l'anne en cours); heure (octet 2) = 0 23; registre 3 : minutes (octet 1) = 0 59; secondes (octet 2) = 0 59
Remarque : Les bits 14 et 15 du registre mois/jour doivent tre masqus.
3 Format facteur de puissance : 1 999 pour les facteurs de puissance de dphasage arrire, 1000 pour le facteur de puissance unitaire 1,000, et 1 999 pour
les facteurs de puissance de dphasage avant.
4Format modulo 10 000 : registres squentiels 1 4. Chaque registre est de modulo 10 000 (intervalle = 9 999 +9 999).
Rsultat est [R4*10 000^3 + R3*10 ,000^2 + R2*10 000^1] + R1. L'intervalle est de zro 9 999 999 999 999 999.

88-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 16 : Liste des registres1


Nom de sujet

Description pour l'utilisateur

Nombre de
Registre
registres

Module

Units

chelle

PkKFDC

Demande crtefacteur K 3

2218

MM

Pas d'units Diximes

PkKFDN

Demande crtefacteur K, neutre

2219

MM

Pas d'units Diximes

PkkVAD

Demande crte de puissance apparente

2237

MM

kVA

chelle A

PkkVARD

Demande crte de puissance ractive

2231

MM

kVAR

chelle A

PkkWD

Demande crte de puissance active

2225

MM

kW

chelle A

PredIAD

Demande prvue de courant 1

2208

MM

chelle A

PredIBD

Demande prvue de courant 2

2209

MM

chelle A

PredICD

Demande prvue de courant 3

2210

MM

chelle A
chelle A

PredIND

Demande prvue de courant N

2211

MM

PredKFDA

Demande prvuefacteur K 1

2220

MM

Pas d'units Diximes

PredKFDB

Demande prvuefacteur K 2

2221

MM

Pas d'units Diximes

PredKFDC

Demande prvuefacteur K 3

2222

MM

Pas d'units Diximes

PredKFDN

Demande prvuefacteur K, neutre

2223

MM

Pas d'units Diximes

PredkVAD

Demande prvue kVA

2238

MM

kVA

chelle A

PredkVARD

Demande prvue kVAR

2232

MM

kVAR

chelle A

PredkWD

Demande prvue kW

2226

MM

kW

R1OpsCounter

Compteur de manuvres du relais 1

9081

PM

Page suivante

FRANAIS

chelle A
Unit

R2OpsCounter

Compteur de manuvres du relais 2

9082

PM

Unit

R3OpsCounter

Compteur de manuvres du relais 3

9083

PM

Unit

R4OpsCounter

Compteur de manuvres du relais 4

9084

PM

Unit

R5OpsCounter

Compteur de manuvres du relais 5

9085

PM

Unit

R6OpsCounter

Compteur de manuvres du relais 6

9086

PM

Unit

ReadyToClose

Disjoncteur prt fermer

661

BCM

Bit 5; ON = oui, OFF = non

RevPwrAlrm

tat de l'alarme de puissance inverse

8859

PM

Bit 9; ON = actif; OFF = inactif

RevPwrPreAlrm

tat de la pre-alarme de puissance inverse

8863

PM

Bit 9; ON = actif; OFF = inactif

TimeToTrip

Temps restant jusqu'au dclenchement de


longue dure

8865

PM

Diximes

TU_BATT_PCT

% pile, dclencheur

8843

PM

TU_SN

Numro de srie du dclencheur

8700

PM

Texte ASCII

TUCommStatus

Unit

tat des comm. interne du dclencheur

552

BCM

Bit 11; ON = ne rpond pas;


OFF = OK
Bit 10; ON = actif; OFF = inactif

UnderFreqAlrm

tat de l'alarme de sous-frquence

8859

PM

UnderFreqPreAlrm

tat de la pre-alarme de sous-frquence

8863

PM

Bit 10; ON = actif; OFF = inactif

UnderVoltAlrm

tat de l'alarme de sous-tension

8859

PM

Bit 5; ON = actif; OFF = inactif

UnderVoltPreAlrm

tat de la pre-alarme de sous-tension

8863

PM

VAB

Tension 1-2

1000

MM

Bit 5; ON = actif; OFF = inactif


V

chelle D - tension

VAN

Tension 1-N

1003

MM

chelle D - tension

VBC

Tension 2-3

1001

MM

chelle D - tension

VBN

Tension 2-N

1004

MM

chelle D - tension

VCA

Tension 3-1

1002

MM

chelle D - tension

VCN

Tension 3-N

1005

MM

chelle D - tension

VigiAlarm

tat de l'alarme Vigi

8860

PM

Bit 1; ON = actif; OFF = inactif

VigiPreAlrm

tat de la pre-alarme Vigi

8864

PM

Bit 1; ON = actif; OFF = inactif

1 Pour les entres de registres qui ne sont pas indiques et les informations de facteur d'chelle, voir les directives d'utilisation 0613IB1201, Systme de

communications Modbus..
2Format date/heure de 3 registres :registre 1 : mois (octet 1) = 1 12; jour (octet 2) = 1 31; registre 2 : anne (octet 1) = 0 199 (ajouter 1900 pour dterminer

l'anne en cours); heure (octet 2) = 0 23; registre 3 : minutes (octet 1) = 0 59; secondes (octet 2) = 0 59
Remarque : Les bits 14 et 15 du registre mois/jour doivent tre masqus.
3 Format facteur de puissance : 1 999 pour les facteurs de puissance de dphasage arrire, 1000 pour le facteur de puissance unitaire 1,000, et 1 999 pour
les facteurs de puissance de dphasage avant.
4Format modulo 10 000 : registres squentiels 1 4. Chaque registre est de modulo 10 000 (intervalle = 9 999 +9 999).
Rsultat est [R4*10 000^3 + R3*10 ,000^2 + R2*10 000^1] + R1. L'intervalle est de zro 9 999 999 999 999 999.

20002012 Schneider Electric Tous droits rservs

89-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe CAccs rseau/communication

48049-137-05
Rev. 01, 07/2012

Tableau 16 : Liste des registres1


Description pour l'utilisateur

Nombre de
Registre
registres

Module

Units

chelle

VLLAvg

Tension entre phases moyenne

1006

MM

chelle D - tension

VLNAvg

Tension phase-neutre moyenne

1007

MM

chelle D - tension

VUnbalAB

Dsquilibre de tension 1-2

1008

MM

VUnbalAlrm

tat de l'alarme de dsquilibre de tension

8859

PM

Nom de sujet

Diximes
Bit 7; ON = actif, OFF = inactif

VUnbalAN

Dsquilibre de tension 1-N

1011

MM

Diximes

VUnbalBC

Dsquilibre de tension 2-3

1009

MM

Diximes

VUnbalBN

Dsquilibre de tension 2-N

1012

MM

Diximes

VUnbalCA

Dsquilibre de tension 3-1

1010

MM

Diximes

VUnbalCN

Dsquilibre de tension 3-N

1013

MM

Diximes

VUnbalLLW

Dsquilibre de tension entre phases le plus


mauvais

1014

MM

Diximes

VUnbalLNW

Dsquilibre de tension phase-neutre le plus


mauvais

1015

MM

Diximes

VUnbalPreAlrm

tat de la pre-alarme de dsquilibre de tension

8863

PM

Bit 7; ON = actif, OFF = inactif

1 Pour les entres de registres qui ne sont pas indiques et les informations de facteur d'chelle, voir les directives d'utilisation 0613IB1201, Systme de

communications Modbus..
2Format date/heure de 3 registres :registre 1 : mois (octet 1) = 1 12; jour (octet 2) = 1 31; registre 2 : anne (octet 1) = 0 199 (ajouter 1900 pour dterminer

FRANAIS

l'anne en cours); heure (octet 2) = 0 23; registre 3 : minutes (octet 1) = 0 59; secondes (octet 2) = 0 59
Remarque : Les bits 14 et 15 du registre mois/jour doivent tre masqus.
3 Format facteur de puissance : 1 999 pour les facteurs de puissance de dphasage arrire, 1000 pour le facteur de puissance unitaire 1,000, et 1 999 pour
les facteurs de puissance de dphasage avant.
4Format modulo 10 000 : registres squentiels 1 4. Chaque registre est de modulo 10 000 (intervalle = 9 999 +9 999).
Rsultat est [R4*10 000^3 + R3*10 ,000^2 + R2*10 000^1] + R1. L'intervalle est de zro 9 999 999 999 999 999.

90-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe DArchitecture de l'alimentation en tension du dclencheur

48049-137-05
Rev. 01, 07/2012

Annexe DArchitecture de l'alimentation en tension du dclencheur

Le dclencheur possde une alimentation en


tension triphase interne intgre qui apparat
au systme comme une charge triphase
configure en triangle (Figure 101). Cette
alimentation est une charge triphase par ellemme et elle injecte une tension sur une phase
ouverte (Figure 102). L'impact d'une charge
triphase configure en triangle sur des
fonctions de protection base de tension est le
suivant :

Le rglage de la protection en sous-tension (Umin) en dessous de 80 % ou


en dsquilibre de tension (Udsq.) au-dessus de 20 % peut entraner un
fonctionnement du dclencheur autre que celui prvu.
Si cette prcaution nest pas respecte, cela peut entraner des
dommages matriels.

Figure 101 : Alimentation triphase interne intgre


U1
Alimentation
triphase
intgre

U2
U3

Chane de
mesure
VN

Figure 102 : Phase ouverte sur une alimentation triphase


06134077

Pour la configuration 1 (figure 103), 2 (figure


104) ou 3 (figure 105) du circuit, si un fusible
s'ouvre, le dclencheur injecte une tension sur
la phase ouverte. En consquence, le
dclencheur mesurera avec prcision la tension
injecte sur la phase ouverte. La mesure de la
tension entre phases (ULL) sera plus leve que
lorsque la phase ouverte est zro volt. Le
dclencheur mesurera galement avec
prcision la tension phase-neutre (VLN) injecte
sur la phase ouverte et affichera une valeur
suprieure zro.

Fusible
Fusible
Fusible

Pour la configuration 4 (figure 106) du circuit, le


dclencheur a un chemin de retour via le
transformateur et la tension injecte sur la
phase ouverte sera de zro. Dans cette
configuration, le dclencheur mesurera avec
prcision zro volt sur VLN.

U1
Alimentation
triphase
intgre

U2
U3

Chane de
mesure
VN

Figure 103 : Configuration 1 du circuit


06134062

Pour tre sr que le systme de dclenchement


Micrologic fonctionne comme prvu quelle que
soit la configuration du systme, l'utilisateur doit
limiter la gamme d'enclenchement en soustension entre 80 % et 100 % de la tension
nominale entre phases du systme.

FRANAIS

La fonction de protection minimale en (sous)


tension est base sur le mesure de tension
entre phases.

RISQUE DE DOMMAGES MATRIELS

06134076

Protection en tension minimale

AVIS

Ouverte
Fusible
Fusible

Moteur

Fusible
Contacteur

20002012 Schneider Electric Tous droits rservs

91-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe DArchitecture de l'alimentation en tension du dclencheur

La fonction de protection en dsquilibre de


tension est base sur le mesure de tension
entre phases.

Figure 104 : Configuration 2 du circuit


Ouverte
06134064

Protection en dsquilibre de
tension

Moteur
Contacteur

Pour la configuration 1 (figure 103), 2 (figure


104) ou 3 (figure 105) du circuit, si un fusible
s'ouvre, le dclencheur injecte une tension sur
la phase ouverte. En consquence, le
dclencheur mesurera avec prcision la tension
injecte sur la phase ouverte.

Fusible
Fusible
Fusible

Figure 105 : Configuration 3 du circuit


06134165

La mesure de la tension entre phases (ULL) sera


plus leve que lorsque la phase ouverte est
zro volt. Le dclencheur mesurera galement
avec prcision la tension phase-neutre (VLN)
injecte sur la phase ouverte et affichera une
valeur suprieure zro.

48049-137-05
Rev. 01, 07/2012

Charge

Fusible

Fusible

Fusible

Pour tre sr que le systme de dclenchement


Micrologic fonctionne comme prvu quelle que
soit la configuration du systme, l'utilisateur doit
limiter les rglages de la protection en
dsquilibre de tension entre 0 et 20 %.

Appareils de
mesure et relais
de protection
supplmentaires

Perte de plusieurs phases


Ne pas utiliser la protection en tension minimale
ni la protection en dsquilibre de tension pour
dterminer la perte de plusieurs phases.

L'alimentation de tension interne ncessite


la prsence dune tension sur deux phases
pour fonctionner. (L'alimentation de tension
possde une gamme de fonctionnement de
100 V 690 V.)
Dans les configurations 1 (figure 103), 2
(figure 104) et 3 (figure 105) du circuit,
lorsque plusieurs phases sont perdues, le
dclencheur mesurera la tension du systme
de la phase restante sur l'ensemble des trois
phases. Par exemple, si deux phases sont
perdues sur un systme en triangle triphas
de 480 V, le dclencheur mesurera 480 VLL
sur les trois phases.

92-FR

Figure 106 : Configuration 4 du circuit


Ouverte
06134063

FRANAIS

Pour la configuration 4 (figure 106) du circuit, le


dclencheur a un chemin de retour via le
transformateur et la tension injecte sur la
phase ouverte sera de zro. Dans cette
configuration, le dclencheur mesurera avec
prcision zro volt sur VLN.

Fusible
Moteur
Fusible

Contacteur

Fusible

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe ERglages du dclencheur

48049-137-05
Rev. 01, 07/2012

Annexe ERglages du dclencheur

Entrer les valeurs des rglages dans les


tableaux de configuration.

Tableau 17 : Rglagescommutateurs
Description

Symbole

Enclenchement de
longue dure

Ir

Retard de longue
dure

tr

Enclenchement de
courte dure

Isd

Retard de courte
dure

tsd

Enclenchement sur
dfaut la terre

Ig

Rglages

FRANAIS

Retard de dfaut la
tg
terre

Tableau 18 : RglagesMenu Entretien


Sous-menu

Description

Article

Contacts M2C/M6C

Type d'alarme

S#

Configuration

S#

Rglage du
dclencheur

Configurer Micrologic Langue


Date/heure
Slection disjoncteur Norme
Disjoncteur
Type
Numro du disjoncteur
Signe puissance
Transfo de U

Primaire
Secondaire

Frquence rseau
Configurer mesures

Type de rseau
Calcul I moyen
Calcul P moyen

Dure
Type fentre
Dure

Convention de signes
Configurer com.

Paramtre com.
Rglage distance
Commande
distance

20002012 Schneider Electric Tous droits rservs

93-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe ERglages du dclencheur

48049-137-05
Rev. 01, 07/2012

Tableau 19 : RglagesMenu Protections


Sous-menu

Description

Symbole

Enclenchement de longue dure

Ir

Retard de longue dure

tr

Enclenchement de courte dure

Isd

Retard de courte dure

tsd

Instantan

Ii

Article

Rglage du dclencheur

Enclenchement de longue dure Idmtl Idmtl Ir


Retard de longue dure Idmtl

Idmtl tr

Mode Idmtl
Enclenchement de courte dure Idmtl

Idmtl Isd

Retard de courte dure Idmtl

Idmtl tsd

Instantan Idmtl

Idmtl Ii

Dfaut la terre (dclencheur 6.0P)

Courant de neutre

Ineutre

Mode
Activation
Retard d'activation

Mode
Activation

FRANAIS

Alarme de dfaut la terre

alarme

Retard d'activation
Retombe
Retard de retombe
Mode
% d'activation

Protections en courant

Dsquilibre de courant

Idsq.

Retard d'activation
% de retombe
Retard de retombe
Mode
Activation

Demande de courant max. phase 1

I1max

Retard d'activation
Retombe
Retard de retombe
Mode
Activation

Demande de courant max. phase 2

I2max

Retard d'activation
Retombe
Retard de retombe
Mode
Activation

Demande de courant max. phase 3

I3max

Retard d'activation
Retombe
Retard de retombe
Mode
Activation

Demande de courant max. du neutre

In max

Retard d'activation
Retombe
Retard de retombe
Page suivante

94-FR

20002012 Schneider Electric Tous droits rservs

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Annexe ERglages du dclencheur

48049-137-05
Rev. 01, 07/2012

Tableau 19 : RglagesMenu Protections (suite)


Sous-menu

Description

Symbole

Article

Rglage du dclencheur

Activation
Tension minimale (sous-tension)

Umin

Retard d'activation
Retombe
Retard de retombe
Activation

Protections en tension

Tension maximale (surtension)

Umax

Retard d'activation
Retombe
Retard de retombe
Activation

Dsquilibre de tension

Udsq.

Retard d'activation
Retombe
Retard de retombe
Activation

Inversion de puissance

rP

Retard d'activation
Retombe
Retard de retombe
Activation

Fmax

Autres protections

Retard d'activation

FRANAIS

Frquence maximale (surfrquence)

Retombe
Retard de retombe
Activation

Frquence minimale (sous-frquence) Fmin

Retard d'activation
Retombe
Retard de retombe

Sens de rotation des phases

Mode
Squence
Mode
% d'activation

Dlestage relestage I

Dlestage relestage I

% de retard d'activation
% de retombe
Retard de retombe
Mode
Activation

Dlestage relestage P

Dlestage relestage P

Retard d'activation
Retombe
Retard de retombe

20002012 Schneider Electric Tous droits rservs

95-FR

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Index

48049-137-05
Rev. 01, 07/2012

Index
architecture de l'alimentation en tension

Afficheur graphique
cran 25
menus 27
navigation 26
organigramme 72
Affinement des rglages des commutateurs

47
Alarme de courant maximale 34
Alarmes
description 18
historique 57
Alimentation externe 16
Architecture de l'alimentation en tension 91
Autres protections
vrification 62

B
Bouton 24
d'essai de dfaut la terre 50
dessai/de remise zro 24, 49

C
Calcul I moyen 42
Calcul P moyen 42
Commande distance 45
Commutateurs
description 7
enclenchement de courte dure 12
enclenchement de longue dure 10
enclenchement instantan 13
enclenchement sur dfaut la terre 14
rglages 45
retard de courte dure 12
retard de dfaut la terre 14
retard de longue dure 10
Commutateurs rglables 7, 33
Compteur de manuvres
description 23
menu 57
Contacts d'alarme. Voir Contacts
programmables M2C/M6C
Contacts programmables
description 30
Contacts programmables M2C/M6C
description du kit 22
description du menu 30
rglage du menu 33
Convention de signe 43
Couvercle des commutateurs
fente douverture 45
illustration 7

D
Dclencheur
5.0P 8
6.0P 9

91

F
Fiche de capteur 7
Fiche de la valeur nominale
description 7, 11
remplacement 69
Fiche de la valeur nominale rglable 7, 11
Fonctionnement 52
Fonctions de dclenchement 7
Frquence
alarme 34
entrer 40
menu 29
vrification 56

configuration 36
dsignation de la srie 7
historique 56
rarmement 49
rglages
code dusure des contacts 38
date 37
famille du disjoncteur 38
frquence 40
heure 37
langue 36
normes 38
protection de courte dure 12
protection de longue dure 10
protection des appareils contre les
dfauts la terre 14
protection instantane 13
tableaux d'enregistrement 93
Transfo de U 39
type de disjoncteur 38
remplacement 64
vrification 23
vrification de l'tat 51
vrifier le fonctionnement 49
Dclencheur MICROLOGIC Voir
Dclencheur
Dlestage de charge en courant
alarme 18
description 21
menu 32
vrification 63
Dlestage de charge en puissance
alarme 34
menu 32
vrification 63
Dlestage en courant. Voir Dlestage de
charge en courant
Dsquilibre de courant
alarme 34
protection 20
Dsquilibre de tension
alarme 34
architecture de tension 92
protection 20
Dsignation de la protection 7

I2t activ 12
I2t dsactiv 12
Idmtl. Voir Protection de longue dure
Ig. Voir Commutateur d'enclenchement de
protection contre les dfauts la terre
Ii. Voir Protection instantane
Image thermique 11
In. Voir Fiche du capteur
Indicateur dusure des contacts
dispositif de mesure 38
rglage du code 38
vrification 57
Information du disjoncteur 38
Interverrouillage slectif de zone 48
cblage 49
cavaliers 48
description 22
installation 48
Inversion de phase
alarme 34
vrification 62
Ir. Voir Commutateur d'enclenchement de
longue dure
Isd. Voir Commutateur d'enclenchement de
courte dure

Enclenchement
courte dure 12
dfaut la terre 14
instantan 13
longue dure 10
Essai d'injection primaire 23
Essai d'injection secondaire 23
tat
dclencheur 51
pile 51

LSI. Voir Dclencheur, 5.0P


LSIG Voir Dclencheur 6.0P

20002012 Schneider Electric Tous droits rservs

H
Historiques
description 29
vrification 56
Historiques de dfauts 56

M
Menu Autres protections 32
Menu Configurer Com. 31
Menu Configurer mesures
description 30
rglage 40
Menu Configurer Micrologic

96-FR

FRANAIS

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Index

description 30
rglage 36
Menu Entretien
description 29
organigramme 73
rglage 33
rglages par dfaut 75
Menu Mesures
description 27
organigramme 72
touche 26
vrification 52
Menu Protections
description 31
organigramme 74
rglages par dfaut 76
touche 26
vrification 58
Menu Protections en tension 32
Menus
autres protections 32, 62
compteur de manuvres 57
configurer Com. 31
configurer mesures 30
configurer Micrologic 30
contacts M2C/M6C 30
contacts programmables M2C/M6C 30
dlestage de charge en courant 32, 63
dlestage de charge en puissance 32,

63
entretien 29
frquence 56
historiques 29
historiques dfauts 56
historiques des alarmes 57
mesure 27
niveaux des courants 28, 52
niveaux des nergies 29, 55
niveaux des puissances 28, 54
niveaux des tensions 28, 53
protection 31
protections en courant 31, 58
protections en tension 32, 61
usure des contacts 57
Mesure
gamme 78
prcision 78
Mesures lisibles distance 79
Module de communication 7, 44

N
Niveaux d'enclenchement, rglage 45
Niveaux des courants
affichage 25
menu 28
vrification 52
Niveaux des nergies
menu 29
vrification 55
Niveaux des puissances
menu 28
vrification 54
Niveaux des tensions
menu 28

vrification 53
Nom du produit 7

O
Organigramme
Menu entretien 73
menu mesures 72
menu protections 74

P
Perte de plusieurs phases 92
Pile
remplacement 70
vrification de l'tat 51
Prise d'essai 49
Protection
alarmes 18
autres 62
courte dure 12
dfaut la terre 14
dlestage de charge 21
dlestage de charge en courant 32
dlestage de charge en puissance 32
dsquilibre de courant 20
dsquilibre de tension 20
en courant 58
frquence maximale 20
frquence minimale 20
instantane 13
inversion de puissance 20
longue dure 10
neutre 17
rglages par dfaut 76
sens de rotation des phases 21
tension 61
tension maximale 19
tension minimale 19
Protection contre l'inversion de puissance
alarme 34
description 20
Protection contre les dfauts la terre
alarme 34
commutateur d'enclenchement 14
commutateur de retard 14
vrification de la fonction 50
Protection dappareils contre les dfauts la
terre Voir Protection contre les dfauts
la terre
Protection de courte dure
alarme 34
commutateur d'enclenchement 12
commutateur de retard 12
description 12
Protection de frquence maximale 20
Protection de frquence minimale 20
Protection de longue dure
alarme 34
commutateur d'enclenchement 10
commutateur de retard 10
description 10
retard I2t 10
Retard Idmtl
Protection de tension maximale 19
Protection de tension minimale 19

20002012 Schneider Electric Tous droits rservs

Protection des appareils contre les dfauts


la terre
description 14
Protection du neutre 17
Protection du sens de rotation des phases 21
Protection volue
vrification des valeurs 52
Protection instantane
commutateur d'enclenchement 13
description 13
Protections en courant 31
vrification 58
Protections en tension
alarme 34
vrification 61

R
Rapport du transformateur de tension 39
Rarmement du dclencheur 49
Rglage distance 44
Rglage de l'heure 37
Rglage de la date 37
Rglage des langues 36
Rglages des commutateurs 46
Rglages du dclencheur
protection de longue dure 10
Rglages par dfaut
commutateurs 75
entretien 75
protection 76
Remplacement
de la pile 70
dclencheur 64
fiche de la valeur nominale 69
Retard
courte dure 12
dfaut la terre 14
longue dure 10
rPmax. Voir Protection contre l'inversion de
puissance

S
Sens de lcoulement de la puissance
configuration de la convention de signe
de la puissance ractive 43
configuration du sens du signe de la
puissance 39
Sous-frquence. Voir Protection de
frquence minimale
Sous-intensit. Voir Valeur minimale de la
protection de courant moyen
Sous-tension. Voir Protection de tension
minimale
Surfrquence. Voir Protection de frquence
maximale
Surintensit. Voir Valeur maximale de la
protection de courant moyen
Surtension. Voir Protection de tension
maximale

T
Touche
daccs au menu dentretien 26
dentre 26

97-FR

FRANAIS

48049-137-05
48049-137-05

Dclencheurs lectroniques MicrologicMC 5.0P et 6.0P


Index

48049-137-05
Rev. 01, 07/2012

dfilement vers le bas 26


dfilement vers le haut 26
Menu Entretien 26
Menu Mesures 26
Menu Protections 26
Touches de navigation 26
Tr. Voir Commutateur de retard de longue
dure
Tsd. Voir Commutateur de retard de courte
dure
Type de rseau 41

FRANAIS

Valeur maximale de la protection de courant


moyen 19
Valeur minimale de la protection de courant
moyen 19
Valeurs de Com Modbus 44
Vrification
d'injection primaire 23
d'injection secondaire 23
dclencheur 23
fonction de dclenchement sur dfaut
la terre 50
trousse d'essais 49
Vrification du fonctionnement du
dclencheur 49
Voyant dauto-protection 24
Voyant de protection volue 24
Voyants
auto-protection 24
dclenchement 24
protection volue 24
surcharge 23
Voyants de dclenchement 24
allumer 24
dfaut la terre 24
Ig 24
Isd/Ii 24
vrification de l'tat 51
Voyants de dclenchement de surchauffe 24

Z
zone 48
ZSI. Voir Interverrouillage slectif de zone

98-FR

20002012 Schneider Electric Tous droits rservs

FRANAIS

Dclencheurs lectroniques Micrologic 5.0P et 6.0P


Directives dutilisation

FRANAIS
Seul un personnel qualifi doit effectuer linstallation, lutilisation, lentretien et la maintenance du
matriel lectrique. Schneider Electric nassume aucune responsabilit des consquences
ventuelles dcoulant de lutilisation de cette documentation.

Schneider Electric
5985 McLaughlin Road
Mississauga, ON L5R 1B8 Canada
Tel:1-800-565-6699
www.schneider-electric.ca

Square DMC, Schneider ElectricMC, MicrologicMC et MasterpactMC sont marques commerciales ou


marques dposes de Schneider Electric. Toutes autres marques commerciales utilises dans ce
document sont la proprit de leurs propritaires respectifs.
48049-137-05 Rev. 01, 07/2012