Professional Documents
Culture Documents
PRO
GENERAL
The purpose of voltage correction is to maintain transmission system voltage at optimum economic
operating levels and to provide a coordinated system wide voltage control plan. Each Division is
responsible for their function in controlling transmission system voltage under the direction of the
System Dispatcher.
All units at Pittsburg are used for voltage correction. This entails the operation of generators at leading
as well as lagging power factor. There is a published voltage schedule for the 230 KV bus that must be
followed. At times it may be amended by direct communication from the System Dispatcher or the
Transmission Operator at Pittsburg. It is the responsibility of the Control operator to maintain this
schedule on the 230 KV bus. The Voltage Control Center (Transmission Operator) will normally handle
all voltage communications.
Leading power factor is the result of “under exciting” the generator field to “buck” system voltage and to
take reactive power (Vars) into the generator.
NOTE: A generator should not be operated in an under excited condition unless the voltage regulator is
in service.
Lagging power factor is the result of “over exciting” the generator field to “boost” system
voltage and to put reactive power (Vars) out into the system.
OPERATION
*The Transmission Operator will communicate with the 1-4 Unit Control Operator who will inform the
5-6-7 Unit Control Operator’s of voltage orders.
-1-
D-108.PRO
NOTE: To have leading power factor (Vars in) on one unit while holding lagging power factor
(Vars out) on other units causes a recirculation of reactive power between the units,
decreasing the voltage correction availability of the station. Incoming vars should be
distributed equally between units as far as possible without exceeding any generator limits.
-2-