You are on page 1of 37

An

Introduction
to

10 MW SOLAR PV PLANT
AT NTPC UNCHAHAR
by

Amit K Gautam
Sr. Manager
(O&M - Solar Plant Commissioning)

Tuesday, June 17, 2014

SYNOPSIS OF THE PRESENTATION


Introduction
 What is SPV Technology
 SPV Technology Fundamentals
 Single Line Diagram
 Combination of Solar Cells, Strings, Inverters &
Inverter Transformer
 The HT Switchboard
 Switchyards (33kV & 220kV)
 Auxiliary Power Scheme
 SCADA & Weather Monitoring System
 Module Washing System
 Fire Fighting System


10 MW Solar PV Plant, NTPC Unchahar

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

INTRODUCTION
 Solar

10 MW Solar PV Plant, NTPC Unchahar

power is the
conversion of sunlight into
electricity, either directly
or indirectly.

 It's

a quiet, clean &


renewable source of
energy

 Photovoltaic

(PV) modules
have no moving or
wearing parts.

 Require

less maintenance

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

SOLAR POWER GENERATION TECHNOLOGIES

Solar Photo Voltaic (direct):




Solar PV

10 MW Solar PV Plant, NTPC Unchahar

PV panels use the


photovoltaic effect to turn
the suns energy directly into
electricity.

Solar Thermal (indirect):




Solar thermal panels use the


suns energy to heat water
that can be used to generate
electricity.

Here, we are using Solar PV technology.

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

WHAT IS SPV TECHNOLOGY?




10 MW Solar PV Plant, NTPC Unchahar

A PV panel is made up of a semiconducting


material, usually silicon-based sandwiched between
two electrical contacts.
The junction of dissimilar materials (n and p
type silicon) creates a voltage.

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

TYPES OF SOLAR PV TECHNOLOGIES


Silicon Crystalline Technology
Mono Crystalline PV Cells

2.

Multi Crystalline PV Cells

10 MW Solar PV Plant, NTPC Unchahar

1.

Thin Film Technology


1.

Amorphous Silicon PV Cells

2.

Poly Crystalline PV Cells


( Non-Silicon based)
Thin Film
Solar Cell

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

SILICON CRYSTALLINE TECHNOLOGY


Currently makes up 86% of PV market
Very stable with module efficiencies 10-16%

Mono Crystalline PV
Cells

10 MW Solar PV Plant, NTPC Unchahar

Made using saw-cut


from single cylindrical
crystal of Si
 Operating efficiency
up to 16%


Multi Crystalline PV
Cells

Caste from ingot of


melted and recrystallized silicon
 Cell efficiency ~12%
 Accounts for 90% of
crystalline Si market


(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

SOLAR CELL FUNDAMENTALS


Solar Cell Characteristics


Short circuit current


(Isc):

10 MW Solar PV Plant, NTPC Unchahar

Maximum current
produced by solar cell
when its terminals are
shorted.


Open circuit voltage


(Voc):
Maximum voltage
that can be obtained
from a solar cell when
its terminals are left
open.
8

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

SOLAR CELL FUNDAMENTALS

10 MW Solar PV Plant, NTPC Unchahar

Fill Factor (FF):


 It is defined as the
square-ness of the I-V
curve
 It is related to the
resistive losses in the
solar cell.
 In ideal condition its
value is 100%.
 For a good solar cell it
is > 80%.

FF = Pm / (Voc x Isc )

(A presentation by Amit K Gautam)

MPPT or Maximum Power Point Tracking is


an algorithm that included in electric power
converter system used for extracting maximum
available power from PV module under certain
conditions.

The voltage at which PV module can produce


maximum power is called maximum power point
(or peak power voltage).

Maximum power varies with solar radiation,


ambient temperature and solar cell temperature.

10 MW Solar PV Plant, NTPC Unchahar

Tuesday, June 17, 2014

MAXIMUM POWER POINT TRACKING


(MPPT)

10

(A presentation by Amit K Gautam)

 The

 MPPT

system is to sample the output of


the cells and apply the proper resistance
(load) to obtain maximum power for any
given environmental conditions.

10 MW Solar PV Plant, NTPC Unchahar

major principle of MPPT is to extract


the maximum available power from PV
module by making them operate at the
most efficient voltage (maximum power
point).

Tuesday, June 17, 2014

HOW MPPT WORKS?

11

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

MAXIMUM POWER POINT TRACKING

10 MW Solar PV Plant, NTPC Unchahar

12

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

SOLAR CELL CHARACTERISTICS


Efficiency ():
Solar cell efficiency is
the ratio of the electrical
output of a solar cell to
the incident energy in

the form of sunlight.

is the efficiency

Efficiency up-to 14-16%

Voc is the open-circuit voltage

are normally achieved

Isc is the short-circuit current

by crystalline Si cells.

FF is the fill factor

10 MW Solar PV Plant, NTPC Unchahar

13

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

LOSSES IN SOLAR CELLS


1. Unavoidable losses:
Loss of low energy photons (23%)

Loss due to excess energy of photons (33%)

Voltage loss (0.65 0.72)

Fill factor loss

2. Avoidable losses:


Reflection losses

Incomplete absorption losses

Recombination losses

10 MW Solar PV Plant, NTPC Unchahar

14

(A presentation by Amit K Gautam)

the PV cell

temperature
increases above
25C, the module
Vmp decreases by
approximately

10 MW Solar PV Plant, NTPC Unchahar

 As

Tuesday, June 17, 2014

EFFECTS OF TEMPERATURE

0.5% per C
15

(A presentation by Amit K Gautam)

 As

insolation decreases
amperage decreases
while voltage remains
roughly constant

10 MW Solar PV Plant, NTPC Unchahar

is the solar
radiation that reaches
the earth's surface. It is
measured by the amount
of solar energy received
per cm2 / min.

 Insolation

Tuesday, June 17, 2014

EFFECTS OF LOW INSOLATION

16

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014

EFFECT OF SOLAR ORIENTATION

10 MW Solar PV Plant, NTPC Unchahar

17

(A presentation by Amit K Gautam)

 To

receive maximum intensity of sunrays the

to sunrays.
 Max

performance is achieved when panels

are perpendicular to the suns rays.


 Panels

should be tracking the sun all the

10 MW Solar PV Plant, NTPC Unchahar

solar panel surface should be perpendicular

Tuesday, June 17, 2014

SOLAR TRACKING

time, during day and during different


seasons.

18

(A presentation by Amit K Gautam)

 Automatic

solar tracking makes the system

 If

the SPV panel is not tracking the sun then

it should be inclined to an angle equal to the


latitude of the location.
(28.81 for Unchahar)
 Solar

10 MW Solar PV Plant, NTPC Unchahar

very costly.

Tuesday, June 17, 2014

SOLAR TRACKING

tracking allows to collect 30% extra

energy with the same SPV panel.

19

(A presentation by Amit K Gautam)

 Whenever

10 MW Solar PV Plant, NTPC Unchahar

any cell is under shed then it


will become reverse biased.
 This reverse bias can be strong depending
upon the shadowing.
 The strong reverse bias may force the
shaded cell to break down.
 The extra power generated by the non
shaded cells will be dissipated in the
shaded cell.
 This creates hot spots in the module.

Tuesday, June 17, 2014

BYPASS DIODE

20

(A presentation by Amit K Gautam)

A bypass diode is used to pass the excess current.

Ideally this should be connected to each cell in


parallel with opposite polarity.

Normally one bypass diode is used for every 12-20


cells (20 in case of Unchahar).

10 MW Solar PV Plant, NTPC Unchahar

Tuesday, June 17, 2014

BYPASS DIODE

21

(A presentation by Amit K Gautam)

Inverter-A

Inverter
Transformer

(630 kVA)

(1.6 MVA)

(Total 08
Nos.)

Solar
Panels

Outdoor
VCB

(Total 08
Nos.)

(Total 16
Nos.)

Tuesday, June 17, 2014

SINGLE LINE DIAGRAM OF SOLAR PLANT AT NTPC UNCHAHAR

350 V AC
800-550 V DC

33kV U/G Cable

350 V AC

800-550 V DC

(Total 08
Incomers)

Inverter-B

Incomers

Isolator

12.5 MVA
Transformer
(33/230 kV)

Note: For more details refer NTPC Drawing No. 5708-004-PVE-P-034

33kV Switchyard
(Solar Plant)

Outgoing-2

Outgoing-1

33kV HT
Panel
200kVA
Aux. Trans.

220 kV
Breaker

33kV
Breaker

Bus
Isolators

Line
Isolator

33/220 kv Switchyard
(Bay-5)

Transmission
Line
(0.8km O/H
& 3.75 km U/G

Bus-1
Bus-2
TBC

(630 kVA)

10 MW Solar PV Plant, NTPC Unchahar

33 kV

33 kV

415 V

ACDB

22

(A presentation by Amit K Gautam)

 Solar

 Photovoltaic

cells are typically sold in


modules (or panels) of 12, 24, 36, 48, 60
volts with power outputs of 50 to 200+
watts.
are then combined into arrays to
give the desired power or watts.

10 MW Solar PV Plant, NTPC Unchahar

cells can be electrically connected in


series (voltage add) or in parallel (current
add) to give any desired voltage and
current (or power).

Tuesday, June 17, 2014

COMBINING SOLAR CELLS

 These

23

(A presentation by Amit K Gautam)

MODULE PARMETER

(60 cells in series)

STRING PARMETER

(24 modules in series)


Open Circuit Voltage (VOC)
= 24 36 = 864 VOC
/ STRING

Short Circuit Current (ISC) = 8.5 A


Peak Power (Pmax) = 5762.88 Wp
Voltage at peak power point (Vmax) = 696 V

10 MW Solar PV Plant, NTPC Unchahar

Open Circuit Voltage (VOC) = 60 0.6 = 36 V


Short Circuit Current (ISC) = 8.5 A
Peak Power (Pmax) = 240 Wp
Voltage at peak power point (Vmax) = 29 V
Current at peak power point (Imax) = 8.28 A

Tuesday, June 17, 2014

COMBINING SOLAR CELLS (AT UNCHAHAR)

Current at peak power point (Imax) = 8.28 A


At Unchahar
Total No. of Modules = 42,240
Total No. of Strings = 1,760

24

(A presentation by Amit K Gautam)

SMU PARMETER

22 Strings in parallel
String-22

String-02

Voc = 864 V
Vmax= 696 V
ISC = 8.5 22 A=187 Amp
Imax = 8.28 22 A =182.16 Amp
INVERTER PARMETER

SMU
-1

SMU
-3
SMU
-2

SMU
-5
SMU
-4

(05 SMU in parallel)


Voc = 864 V
Vmax = 696 Volts
ISC = 187 5 A=935 Amp
Imax = 182.16 5 A =910.8 Amp

10 MW Solar PV Plant, NTPC Unchahar

String-01

(22 strings in parallel)

Tuesday, June 17, 2014

COMBINING STRINGS

25

Inverter
(A presentation by Amit K Gautam)

Inverter-A

Inverter-B

350 V AC
5
33 kV

33 kV
Outdoor VCB

33 kV
Indoor VCB

33kV HT Panel

10 MW Solar PV Plant, NTPC Unchahar

350 V AC

Two inverters are


giving output to one
transformer.
 The transformer
contains two
primary(LT)& one
secondary(HT)
winding.
 The transformer out
put is fed to HT panel
as shown in the
diagram


Tuesday, June 17, 2014

COMBINING INVERTERS

26

(A presentation by Amit K Gautam)

Incomer-9
(SPARE)
Panel-12

Incomer-8
(Panel-10)

Incomer-7
(Panel-9)

Incomer-6
(Panel-8)

Incomer-5
(Panel-7)

Incomer-4
(Panel-5)

33 kV HT Panel

Metering

BUS PT
(Panel-1)
Protection

Outgoing Feeder
to
33kV Switchyard
(Solar Plant)
Panel No. 6

33kV
Feeder
To 200 kVA
Auxiliary
Transformer

10 MW Solar PV Plant, NTPC Unchahar

Incomer-1
(Panel-2)

Incomer-3
(Panel-4)

All the 8 incomers are feeding power to the HT panel.


One outgoing feeder is for power evacuation/back-charging.
The other outgoing feeder is for auxiliary supplies.
Incomer-2
(Panel-3)

Tuesday, June 17, 2014

THE HT SWITCH-BOARD

27

(33kV/415V)
Panel No. 7
(A presentation by Amit K Gautam)

TO 220 KV
NTPC, UNCHAHAR,
SWITCHYARD

10 MW Solar PV Plant, NTPC Unchahar

LIGHTNING
ARRESTER

METERING PT

EARTH SWITCH

EARTH SWITCH

METERING CT

METERING PT

METERING CT

FROM 33KV
SWITCHGEAR

ISOLATOR

Tuesday, June 17, 2014

33 KV SWITCHYARD (AT SOLAR PLANT)

28

(A presentation by Amit K Gautam)

Bus
Isolators

(ONAN
Dyn11)

220 kV
Breaker

12.5 MVA
Power Transformer
(33/230 kV)

33 kV

220 kV

220 kV
TBC Breaker

Bus
Isolators

Lightning
Arrester

Current
Transformer

33kV Outdoor
Vacuum
Circuit Breaker

Current
Transformer

Potential
Transformer

Earth Switches

Lightning
Arrester

TBC

Bus-2

Bus-1

Line Isolator

Lightning
Arrester

Line
Isolator

10 MW Solar PV Plant, NTPC Unchahar

33 kV Line
from
Solar Plant

Tuesday, June 17, 2014

33/220 KV SWITCHYARD (AT UNCHAHAR) : BAY-5

29

(A presentation by Amit K Gautam)

Emergency Inverter
215 kVA (CMCS)

150 AH Battery
(60 Min Backup)
230V, 50Hz,1Ph.
AC Supply
Lights, Vent. Exhaust,
Aux. for VCB
Field
Instrument DB

Bore Well Pumps


(3 feeders)

SPARE (6 feeders)

63A MCCB

MCCB, TPN
400A, 25kA

220 V DC,
200 AH

Battery
Charger

16 A MCCB

16 A MCCB

SPARE

ACDB
10 MW Solar PV Plant, NTPC Unchahar

Note: For more detail please refer drawing no. 5708-004-PVE-P-077-03

Power Socket Office Area


(To Computers)

Security Room DB
(Lights, Aux. Sockets, Vent. Exhaust)

32A MCCB

Electronic Interlock

IR-1
1 DB
(Lights, Vent. Exhaust, Aux. for VCB

32A MCCB

16 A MCCB

32A MCCB

63A MCCB

63A MCCB

63A MCCB

63A MCCB

63A MCCB

63A MCCB

MCCB, TPN
400A, 25kA

Water Pumps
Local Starter

IR-7
7 DB

IR-5
5 DB

IR-3
3 DB

IR-8
8 DB

IR-6
6 DB

IR-4
4 DB

63A MCCB

63A MCCB

63A MCCB

200 kVA
Auxiliary Transformer
33/0.415kV
Dyn11

CMCS Room DB
(Lights, AC Units for SCADA Room,
All sockets, Auxiliary power for Main HT panel)

Emergency lights
in CMCS,
SCADA
& Inverter Rooms

IR-2
2 DB

External
illumination

32A MCCB

From 33 kV Main HT Panel

Tuesday, June 17, 2014

AUXILIARY POWER SCHEME

DCDB
30

To all VCBs
220 V DC

(A presentation by Amit K Gautam)

SCADA System Architecture

Tuesday, June 17, 2014

10 MW Solar PV Plant, NTPC Unchahar

31
(A presentation by Amit K Gautam)

 There

are 1760 structures/strings in site, it is

month.
 All

PV modules shall be cleaned in 10 days

(10% per day) and from the 11th day again


the first structure will be cleaned.
 Like

10 MW Solar PV Plant, NTPC Unchahar

planned to clean every PV module thrice a

Tuesday, June 17, 2014

MODULE WASHING SYSTEM

this, the cleaning process will be going

on through out the month.

32

(A presentation by Amit K Gautam)

There are three bore-wells in the Solar Plant

10 MW Solar PV Plant, NTPC Unchahar

Water Balance : Borewell-1, Tank Capacity 3000 litres

Tuesday, June 17, 2014

MODULE WASHING SYSTEM (CONTD.)

33

(A presentation by Amit K Gautam)

Module Washing System (contd.)


Water Balance : Borewell-2, Tank Capacity 4000 litres

Water Balance : Borewell-2, Tank Capacity 4000 litres

(A presentation by Amit K Gautam)34

MODULE WASHING SYSTEM

Tuesday, June 17, 2014


10 MW Solar PV Plant, NTPC Unchahar

35

(A presentation by Amit K Gautam)

Fire Fighting System


CMCS & Inverter Room-1

Inverter
Transformer
-1

Aux.
Trans.

Ladies
Toilet
Gents
Toilet

SCADA
Room

Pantry

OVCB
-1
Inverter
Room-1
Store Room

Battery Room

Legends
Sand filled fire buckets
Smoke detectors
Fire extinguisher (DCP) 10 kg
Fire extinguisher (CO2) 9 kg
Fire extinguisher (Foam) 9 kg

33kV Switchyard (Solar Plant)

Fire extinguisher (hand portable,


pressurized ) 9 kg

36
*Drawing not to scale

(A presentation by Amit K Gautam)

Tuesday, June 17, 2014


10 MW Solar PV Plant, NTPC Unchahar

THANK YOU