NEXT EVO DX

NEXT EVO DX: Direct expansion close control air conditioners


with up-flow or down-flow air delivery.
Cooling Capacity: 7 102 kW

NEWSOFTWARE

NEXT EVO DX
rcgroupairconditioning

MAIN FEATURES
Precision air conditioner.
20 models available, 2 versions for a wide selection opportunity.
EER up to 4,47.
On/off scroll compressors.
Single and double refrigerant circuit.
R410A Refrigerant charge.
rotary compressor (size E1, E2).
AC plug-fans (size E3, E4, E5, E6, E7, E8).
OVER and UNDER versions.
Suitable for indoor installation.
MAIN BENEFITS
Units with single and double refrigerant circuits.
Availability of remote condensers with axial fans (TEAM MATE series)
and with plug fans (TEAM MATE PF series).
High EER.
Availability of EC plug-fans.
Availability of electronic expansion valves.
Availability of electric heater.
Availability of steam humidifier.
Availability of hot water heating coil.
Availability of extra circuit heating coil.
Complete set of optional accessories: filters, plenum, panels, stand.
Easily of maintenance.

R410A

EC

UP
FLOW

AC

DOWN
FLOW

INDOOR INSTALLATION
The machines are designed for indoor installation.
REMOTE CONDENSER
The units are designed to be matched with remote condensers with axial
fans (TEAM MATE series) or plug-fans (TEAM MATE PF series).
WORKING LIMITS
Room air temperature:
14C
minimum temperature with wet bulb.
24C
maximum temperature with wet bulb.
35C
maximum temperature with dry bulb.
Room air humidity:
20%RH minimum relative humidity.
70%RH maximum relative humidity.

f i f t y c o o l y e a r s

RCGROUP SpA G_ITC_RCW8.4

65

NEXT EVO DX
MAIN COMPONENTS
FRAMEWORK
Base in aluminium extrusion, painted with epoxy powders. Colour RAL
9005;
Frame in aluminium profile, painted with epoxy powders. The inner frame is
provided with seals for the panels. Colour RAL 9005;
Panels in galvanized steel sheet with protective surfaces treatment in
compliance with UNI ISO 9227/ASTMB117 and ISO 7253, and painted with
epoxy powders. Colour RAL 7016 hammered;
Panels insulated with polyurethane foam and seals to ensure air tight.
Hinged front panels with quick release removal system.
Total front access for routine maintenance.
Removable lateral and back side panels.
Air flow OVER version:
- Air intake from the front through honeycomb type grille and air delivery
from the top.
Air flow UNDER version:
- Air intake from the top and air delivery from the bottom.
Compartment for electrical panel on unit front for direct access to control
and regulation devices;
FILTER SECTION
Washable air filters with G4 efficiency, with cells in synthetic fibre and
metallic frame (EN 779-2002).
Air filters access:
OVER version
- Frontal access for all machines
UNDER version
- For machines size E1 E2 E3 frontal access
- For machine size E4 E5 E67 E7 E8 access from upper side

IT Cooling
ELECTRICAL PANEL
In accordance with EN60204-1 norms, suitable for indoor installation,
complete wit:
Main switch with door lock safety on frontal panel;.
Magnetothermic switches for supply fans. The supply fans equipped with
EC electric motor and dont require contactors.
Transformer for auxiliary circuit and microprocessor supply.
Terminals:
OUTLETS
- Voltage free deviating contact for General Alarm 1
- Voltage free contact for supply fans status.
INLETS
- Emergency unit stop with signalling on display (external alarm).
- External enabling.
Power supply 400/3/50+N.
CONTROL SYSTEM
Microprocessor control system with graphic display for control and monitor of
operating and alarms status. The system includes:
Built-in clock for alarms date and time displaying and storing;
Built-in memory for the storing of the intervened events (up to 100 events
recorded);
Predisposition for connectivity board housing ( RCcom MBUS/JBUS, LON,
BACnet for Ethernet (SNMP- TCP/IP), BACnet for MS/TP). The electronic
cards are optional accessories;
Main components hour-meter;
Non-volatile Flash memory for data storage in case of power supply faulty;
Menu with protection password;
LAN connection (max 15 units).

ON / OFF COMPRESSORS SECTION


Units size E1 and E2:
Rotary vane compressors for R410A refrigerant
2-pole 3-phase electric motor with direct on line starting.
Crankcase heater.
Rubber supports.
Units size E3, E4, E5, E6, E7 and E8
Scroll rotary compressors with spiral profile optimized for R410A refrigerant.
2-pole 3-phase electric motor with direct on line starting.
Crankcase heater.
Rubber supports.
COOLING SECTION
Heat exchanger coil with internally corrugated copper tubes and high
efficiency aluminium fins, specifically developed to provide high heat
transfer and lower pressure drops.
Frame in galvanized steel or peralluman.
Condensate tray in peralluman with PVC flexible discharge pipe.
Temperature sensors on air intake with control and regulation functions.
Temperature sensors on air delivery with function of temperature display.
REFRIGERANT CIRCUIT
Components for each refrigerant circuit:
Mechanical expansion valve.
Sight glass.
Filter dryer on liquid line.
Pressure transducers with indication, control and protection functions, on
low and high refrigerant pressure.
High pressure safety switch with manual reset.
Liquid receiver with accessories.
Refrigerant circuit with copper tubing with anticondensate insulation of the
suction line.
Plastic capillary hoses for pressure sensors connection.
R410A refrigerant charge and lubricant oil.
Valves on gas delivery and liquid return for coupling to remote air cooled
condenser.
010V proportional signal to manage the condensing control system of the
remote air cooled condenser.
FANS SECTION
The fan section is contained within the machine and includes:
Centrifugal fans with backward curved blades with wing profile, single
suction and without scroll housings (Plug-fans), directly coupled to external
rotor electric motor.
Impeller in composite material exempt from rust formation.
AC type electric motor with fixed speed.
Fan guard with rubber support (UNDER version)

66

TO BE MATCHED WITH REMOTE CONDENSER


The units are designed to be matched with remote condensers with axial fans
(TEAM MATE series) or plug-fans (TEAM MATE PF series).

TEAM MATE

TEAM MATE PF

G_ITC_RCW8.4 RCGROUP SpA 19632013 fiftycoolyears

NEXT EVO DX

IT Cooling
COMMON OPTIONAL ACCESSORIES
SIZE
TEAM MATE remote condenser
TEAM MATE PF remote condenser
213 - Team Mate electrical power supply by internal unit
810 - Floor stand Hmax=350 mm
811 - Floor stand Hmax=450 mm
812 - Floor stand Hmax=510 mm
215 - Disposal F5 efficiency air filter
832 - Air supply plenum with F6 filters
833 - Air supply plenum with F7 filters
835 - Air supply plenum with F9 filters
836 - Air supply plenum with sound absorber
Air discharge plenum with frontal and lateral grilles
Air discharge plenum with frontal grille
761 - Air supply plenum with 5 closed sides
808 - Sandwich panels
945 -Air return plenum with Free Cooling damper
405 - Extra-Circuit system
514 - Water heater + 2 way valve
321 - Steam humidifier
1015 - Incresed umidifier
865 - Phases sequence relay
310 - Electric heater
1014- Increased electrical heater
909 - Clogged filters alarm
911 - Water presence alarm
913 - Additional water sensor (kit)
860 - T/rH sensor on air return
866 - T/rH external sensor
867 - T/rH remote sensor
610 - Noise deading cup on compressor
606 - Compr. power factor capacitor - 0,9
260 - Liquid solenoid valve
220 - Electronic expansion valve
101 - EC fan
923 - RC-Com MBUS/JBUS Serial board
926 - LON Serial board
931 - BACnet Ethernet - SNMP - TCP/IP Serial board
932 - BACnet MS/TP Serial board
1011 - Double serial interface
958 - Emergency microprocessor supply
863 - Remote terminal shared
930 - Remote graphic terminal kit
962 - Kit modem GSM
957 - Plantwatch without modem
RC CLOUD PLATFORM

E2

E3

E4

E5

E6

E7

E8

H0

H1

H2

H3

H4

H5

H5

H0

H1

H2

H3

H4

H5

H5

OPTIONAL ACCESSORIES - OVER VERSION ONLY


SIZE
848 - Condensate discharge system (kit)
807 - Blind frontal pannel
831 - Plenum with frontal grille and sound absorber
805 - Bottom panel

OPTIONAL ACCESSORIES - UNDER VERSION ONLY


SIZE
Air return plenum with sound absorber
848 - Condensate discharge system (kit)
849 - Condensate discharge system
843 - Motorized damper with frame

available accessory; - not available accessory

19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4

67

NEXT EVO DX

IT Cooling

TECHNICAL DATA
MODEL

007 P1

009 P1

011 P1

014 P1

016 P1

020 P1

022 P1

026 P1

032 P1

037 P1

041 P1

SIZE
E1
E1
E1
E2
E2
E3
E3
E3
E4
E4
E4
COOLING CAPACITY (1)
Total
kW
7,3
8,8
10,2
13,5
14,5
19,7
21,7
25,8
31,9
36,0
40,7
Sensible
kW
7,0
8,4
9,7
12,8
13,8
18,8
20,6
24,3
30,4
33,0
38,8
SHR
kW/kW
0,95
0,95
0,95
0,95
0,95
0,95
0,95
0,94
0,95
0,92
0,95
Unit power input
kW
1,73
2,16
2,62
3,39
3,78
4,41
5,34
6,55
7,42
8,35
9,78
Supply fans
n.
1
1
1
1
1
1
1
1
1
1
1
Air flow
m3/h
2500
2700
2800
4000
4200
5700
6100
6400
8450
8450
10350
Nominal external static pressure
Pa
20
20
20
20
20
20
20
20
20
20
20
Fans max external static pressure Pa
180
130
110
100
55
310
240
190
20
20
20
Compressors
rotary
rotary
rotary
rotary
rotary
scroll
scroll
scroll
scroll
scroll
scroll
Quantity
n.
1
1
1
1
1
1
1
1
1
1
1
Capacity steps
n.
1
1
1
1
1
1
1
1
1
1
1
Air filters
n.
1
1
1
1
1
2
2
2
2
2
2
Efficiency
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
G4
Refrigerant
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Refrigerant charge (2)
kg
3,2
3,2
3,2
3,4
3,4
4,0
4,0
4,0
5,7
5,7
8,6
Gas circuits
n.
1
1
1
1
1
1
1
1
1
1
1
Power supply (**)
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
Max operating current (FLA)
A
6,1
7,0
7,2
8,5
9,1
15,4
18,8
20,1
22,2
25,7
30,4
Unit starting current (LRA)
A
33,3
40,3
37,5
54,5
54,5
66,9
77,9
103,9
130,9
141,9
122,0
Energy efficiency indexes (1)
EER
kW/kW
4,22
4,07
3,89
3,98
3,84
4,47
4,06
3,94
4,30
4,31
4,16
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over
dB(A)
58,0
59,6
60,4
62,6
63,6
63,5
65,0
66,0
72,0
75,1
71,2
On air intake Over
dB(A)
49,8
50,2
51,9
51,3
53,0
53,9
57,7
55,1
57,8
58,9
58,8
Irradiated Over
dB(A)
40,2
41,4
42,4
40,4
41,7
42,4
45,5
44,0
48,6
51,3
49,4
On air intake Under
dB(A)
50,1
52,3
52,3
50,5
52,0
52,5
55,2
54,3
58,9
61,4
59,7
On front side Under
dB(A)
40,9
42,1
43,2
41,3
42,9
43,4
46,3
45,1
49,6
52,0
50,5
Net weight Over
kg
220
221
228
260
265
300
305
305
410
415
427
Net weight Under
kg
230
231
238
270
275
320
325
325
420
425
437
Remote condenser (4)
n.
TEAM MATE
Mod.
M 11
M 11
M 11
M 14
M 17
M 25
M 25
M 30
M 35
M 45
M 45
TEAM MATE PF
Mod.
T 11
T 11
T 11
T 14
T 21
T 24
T 24
T 33
T 38
T 44
T 44
Refrigerant connections
Gas delivery
ODS
16
16
16
16
16
18
18
18
22
22
28
Liquid return
ODS
12
12
12
12
12
16
16
16
16
16
22
Hydraulic connections - Condensate discharge F
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
MODEL

045 P1

039 P2
D
E5

048 P2
D
E5

055 P2
D
E6

062 P2
D
E6

075 P2
D
E7

082 P2
D
E7

092 P2
D
E8

102 P2
D
E8

SIZE
E4
COOLING CAPACITY (1)
Total
kW
44,3
36,5
47,1
54,5
61,3
74,6
81,3
89,9
102,0
Sensible
kW
40,5
34,1
42,9
51,9
58,4
71,1
76,2
81,4
89,6
SHR
kW/kW
0,91
0,93
0,91
0,95
0,95
0,95
0,94
0,91
0,88
Unit power input
kW
10,78
8,59
11,69
13,20
14,77
17,68
19,59
21,56
25,37
Supply fans
n.
1
1
1
2
2
2
2
2
2
Air flow
m3/h
10350
8750
10850
15000
15600
20000
20000
20900
20900
20
20
20
20
20
20
20
20
20
Nominal external static pressure
Pa
20
20
20
137
70
20
20
20
20
Fans max external static pressure Pa
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
scroll
Compressors
1
2
2
2
2
2
2
2
2
Quantity
n.
1
2
2
2
2
2
2
2
2
Capacity steps
n.
2
3
3
3
3
4
4
5
5
Air filters
n.
G4
G4
G4
G4
G4
G4
G4
G4
G4
Efficiency
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
R410A
Refrigerant
8,6
9,0
9,0
9,8
9,8
16,2
16,2
17,4
17,4
Refrigerant charge (2)
kg
Gas circuits
n.
1
2
2
2
2
2
2
2
2
Power supply (**)
400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N 400/3/50+N
Max operating current (FLA)
A
36,7
27,8
35,7
40,1
44,3
53,7
60,9
73,5
79,8
Unit starting current (LRA)
A
144,0
78,7
94,0
123,0
152,0
168,6
151,0
179,0
216,0
Energy efficiency indexes (1)
EER
kW/kW
4,11
4,25
4,03
4,13
4,15
4,22
4,15
4,17
4,02
Sound pressure level - ISO 3744 (3)
On air delivery Under/Over
dB(A)
71,2
75,2
74,1
71,8
72,6
72,3
72,3
74,7
74,7
On air intake Over
dB(A)
57,6
59,0
59,2
58,5
60,3
60,6
61,3
62,6
63,4
Irradiated Over
dB(A)
48,0
51,5
50,5
48,7
49,9
50,7
51,0
53,0
53,3
On air intake Under
dB(A)
59,9
61,6
60,8
59,0
60,1
61,0
61,3
63,3
63,6
On front side Under
dB(A)
50,8
52,1
51,4
49,7
50,9
51,8
52,2
54,1
54,4
Net weight Over
kg
435
520
530
610
630
688
695
785
785
Net weight Under
kg
435
530
540
620
640
745
750
845
845
Remote condenser (4)
n.
TEAM MATE
Mod.
M 50
M 25
M 25
M 30
M 35
M 45
M 45
M 50
M 60
TEAM MATE PF
Mod.
T 58
T 24
T 33
T 33
T 38
T 38
T 58
T 58
T69
Refrigerant connections
Gas delivery
ODS
28
2x18
2x18
2x18
2x18
2x22
2x28
2x28
2x28
Liquid return
ODS
22
2x12
2x16
2x16
2x16
2x16
2x22
2x22
2x22
Hydraulic connections - Condensate discharge F
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
1/2"
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to entering air at 24C-45%RH; 45C condensing temperature.
2. Unit refrigerant charge. Remote condenser, connections pipes and optional are excluded.
3. Noise level at 1 meter in free field (external static pressure 50 Pa)
4. For matching to other remote air cooled condensers please refer to RC WORLD selection program
(**) The remote condenser has separated power supply
68

G_ITC_RCW8.4 RCGROUP SpA 19632013 fiftycoolyears

NEXT EVO DX

IT Cooling
TECHNICAL DATA - OPTIONAL ACCESSORIES
NEXT EVO DX
SIZE
Electric heater
Capacity
Capacity steps
Humidifier
Steam capacity
Power input
Extra circuit coil (1)
Total cooling capacity
Sensible cooling capacity
Heating coil (2)
Heating capacity

007 P1

009 P1

011 P1

014 P1

016 P1

020 P1

022 P1

026 P1

032 P1

037 P1

E1

E1

E1

E2

E2

E3

E3

E3

E4

E4

kW
n.

5,1
1,0

5,1
1,0

5,1
1,0

5,1
1,0

5,1
1,0

6,0
2,0

6,0
2,0

6,0
2,0

9,0
3,0

9,0
3,0

kg/h
kW

3
2,3

3
2,3

3
2,3

3
2,3

3
2,3

3
2,3

3
2,3

3
2,3

8
6,0

8
6,0

kW
kW

10,4
9,6

11,0
10,0

11,3
10,3

16,7
15,3

17,4
15,7

23,7
21,8

25,0
22,7

25,8
23,5

35,8
32,7

35,8
32,7

kW

22,9

24,1

24,7

33,6

34,7

48,8

51,1

52,7

75,1

75,1

041 P1

045 P1

039 P2 D

048 P2 D

055 P2 D

062 P2 D

075 P2 D

082 P2 D

092 P2 D

102 P2 D

E4

E4

E5

E5

E6

E6

E7

E7

E8

E8

kW
n.

9,0
3,0

9,0
3,0

13,5
3,0

13,5
3,0

13,5
3,0

13,5
3,0

18,0
3,0

18,0
3,0

18,0
3,0

18,0
3,0

kg/h
kW

8
6,0

8
6,0

8
6,0

8
6,0

8
6,0

8
6,0

8
6,0

8
6,0

8
6,0

8
6,0

kW
kW

41,5
37,7

41,5
37,7

42,4
36,8

50,0
44,2

61,1
55,4

61,1
55,4

94,2
80,0

94,2
80,0

105,0
87,1

105,0
87,1

kW

86,2

86,2

85,0

98,8

131,0

134,0

160,0

160,0

175,0

175,0

NEXT EVO DX
SIZE
Electric heater
Capacity
Capacity steps
Humidifier
Steam capacity
Power input
Extra circuit coil (1)
Total cooling capacity
Sensible cooling capacity
Heating coil (2)
Heating capacity
1.
2.

Characteristics referred to entering air at 24C 50%RH with chiller water at 7/12,5 C and 0% glycol
Characteristics referred to entering air at 20C with hot water at 75/60C

19632013 fiftycoolyears RCGROUP SpA G_ITC_RCW8.4

69

NEXT EVO DX

IT Cooling

NEXT EVO DX DIMENSIONS (mm)


DIMENSIONS (mm)
SIZE
E1
E2
E3
E4
E5
E6
E7
E8

a
650
785
1085
1305
1630
1875
2175
2499

b
675
675
775
930
930
930
930
930

c
1925
1925
1925
1980
1980
1980
1980
1980

70