Professional Documents
Culture Documents
Water-Cooled/Condenserless
Liquid Chillers
Nominal cooling capacity 30HZ: 134-783 kW
Nominal cooling capacity 30HZV: 126-735 kW
50 Hz
CONTENTS
1 - INTRODUCTION ....................................................................................................................................................................... 4
1.1 - Installation safety considerations ............................................................................................................................................... 4
1.2 - Equipment and components under pressure ............................................................................................................................... 4
1.3 - Maintenance safety considerations ............................................................................................................................................ 4
1.4 - Repair safety considerations ...................................................................................................................................................... 5
2 - PRELIMINARY CHECKS ........................................................................................................................................................ 6
2.1 - Check equipment received ......................................................................................................................................................... 6
2.2 - Moving and siting the unit ......................................................................................................................................................... 6
3 - DIMENSIONS, CLEARANCES, WEIGHT DISTRIBUTION .............................................................................................. 8
3.1 - 30HZ/HZV 043-065 ................................................................................................................................................................... 8
3.2 - 30HZ/HZV 091-225 ................................................................................................................................................................... 8
3.3 - 30HZ/HZV 250-280 ................................................................................................................................................................... 9
4 - PHYSICAL AND ELECTRICAL DATA FOR 30HZ/HZV (R407C/R22) ......................................................................... 10
4.1 - Physical data (R407C) .............................................................................................................................................................. 10
4.2 - Electrical data (R407C) ............................................................................................................................................................ 10
4.3 - Physical data (R22) .................................................................................................................................................................. 11
4.4 - Electrical data (R22) ................................................................................................................................................................ 12
4.5 - Power supply ............................................................................................................................................................................ 13
4.6 - Voltage phase imbalance (%) ................................................................................................................................................... 13
4.7 - Recommended wire sections .................................................................................................................................................... 14
5 - APPLICATION DATA ............................................................................................................................................................ 15
5.1 - Unit operating range ................................................................................................................................................................. 15
5.2 - Minimum chilled water flow .................................................................................................................................................... 15
5.3 - Maximum chilled water flow ................................................................................................................................................... 15
5.4 - Variable flow evaporator .......................................................................................................................................................... 16
5.5 - System minimum water volume ............................................................................................................................................... 16
5.6 - Evaporator flow rate (l/s) ......................................................................................................................................................... 16
5.7 - Condenser water flow rates ...................................................................................................................................................... 17
5.8 - Condenser water flow restrictor ............................................................................................................................................... 17
6 - WATER CONNECTIONS ....................................................................................................................................................... 18
6.1 - Operating precautions .............................................................................................................................................................. 18
6.2 - Water connections .................................................................................................................................................................... 19
6.3 - Flow control ............................................................................................................................................................................. 19
6.4 - Condenser connections ............................................................................................................................................................. 19
6.5 - Frost protection ........................................................................................................................................................................ 20
6.6 - Refrigerant line connections (30HZV) ..................................................................................................................................... 20
6.7 - Operation of two units in master/slave mode ........................................................................................................................... 24
The cover illustration is for illustrative purposes only and is not part of any offer for sale or contract.
2
CONTENTS (contd)
7 - MAJOR SYSTEM COMPONENTS AND OPERATION DATA FOR STANDARD UNITS .......................................... 24
7.1 - Compressors ............................................................................................................................................................................. 24
7.2 - Lubricant .................................................................................................................................................................................. 24
7.3 - Pressure vessels ........................................................................................................................................................................ 24
7.4 - Electronic expansion device (EXV) ......................................................................................................................................... 25
7.5 - Refrigerant ................................................................................................................................................................................ 25
7.6 - High-pressure safety switch ..................................................................................................................................................... 25
7.7 - Moisture indicator .................................................................................................................................................................... 25
7.8 - Filter drier ................................................................................................................................................................................. 25
8 - MAIN OPTIONS AND ACCESSORIES ................................................................................................................................ 26
8.1 - Units for low evaporator outlet temperature applications (options 5 and 6) ............................................................................ 26
8.2 - Electrical protection to IP 44 (option 20) ................................................................................................................................. 26
8.3 - High- and low-pressure gauges (option 26) ............................................................................................................................. 26
8.4 - Compressor oil pressure safety device ..................................................................................................................................... 26
8.5 - Condenser with copper-nickel tubes (option 33) ..................................................................................................................... 26
8.6 - RS 485 communication interface (option 148) ........................................................................................................................ 26
8.7 - Additional capacity step 30HZ/HZV 043 to 065 (option 94) .................................................................................................. 26
8.8 - Evaporator pump starter (options 84 and 84D) ........................................................................................................................ 26
8.9 - Condenser pump starter (option 84R) ...................................................................................................................................... 26
9 - MAINTENANCE ...................................................................................................................................................................... 27
9.1 - Soldering and welding .............................................................................................................................................................. 27
9.2 - Maintenance of the refrigerant circuit ...................................................................................................................................... 27
9.3 - Electrical maintenance ............................................................................................................................................................. 28
9.4 - Evaporator maintenance ........................................................................................................................................................... 29
9.5 - Corrosion control ..................................................................................................................................................................... 30
10 - START-UP CHECKLIST FOR 30HZ/HZV LIQUID CHILLERS ................................................................................... 31
1 - INTRODUCTION
Prior to the initial start-up of the 30HZ/HZV units, the people
involved in the on-site installation, start-up, operation, and
maintenance of this unit should be thoroughly familiar with these
instructions and the specific project data for the installation site.
The 30HZ/HZV liquid chillers are designed to provide a very
high level of safety during installation, start-up, operation and
maintenance. They will provide safe and reliable service when
operated within their application range.
This manual provides the necessary information to familiarize
yourself with the control system before performing start-up
procedures. The procedures in this manual are arranged in the
sequence required for machine installation, start-up, operation
and maintenance.
Be sure you understand and follow the procedures and safety
precautions contained in the instructions supplied with the
machine, as well as those listed in this guide.
1.1 - Installation safety considerations
After the unit has been received, when it is ready to be installed
or reinstalled, and before it is started up, it must be inspected
for damage. Check that the refrigerant circuit(s) is (are) intact,
especially that no components or pipes have shifted (e.g. following a shock). If in doubt, carry out a leak tightness check and
verify with the manufacturer that the circuit integrity has not
been impaired. If damage is detected upon receipt, immediately
file a claim with the shipping company.
Do not remove the skid or the packaging until the unit is in its
final position. These units can be moved with a fork lift truck,
as long as the forks are positioned in the right place and
direction on the unit.
The units can also be lifted with slings, using only the designated lifting points marked on the unit.
These units are not designed to be lifted from above. Use
slings with the correct capacity, and always follow the lifting
instructions on the certified drawings supplied with the unit.
Safety is only guaranteed, if these instructions are carefully
followed. If this is not the case, there is a risk of material
deterioration and injuries to personnel.
Never cover any safety devices.
This applies to the globe valve in the water circuit and the
globe valve(s) in the refrigerant circuit(s).
Ensure that the valves are correctly installed, before
operating the unit.
In certain cases the globe stops are installed on ball valves.
These valves are factory-supplied lead-sealed in the open
position. This system permits isolating and removing the
globe stop for checking and replacing. The globe stops are
designed and installed to ensure protection against fire risk.
Removing the globe stops is only permitted if the fire risk is
fully controlled and the responsibility of the user.
4
Ensure that you are using the correct refrigerant type before
recharging the unit (see unit name plate).
Charging any refrigerant other than the original charge type
will impair machine operation and can even lead to a
destruction of the compressors.
Do not use air for leak testing. Use only refrigerant or dry
nitrogen.
Do not unweld or flamecut the refrigerant lines or any refrigerant circuit component until all refrigerant (liquid and
vapour) has been removed from chiller. Traces of vapour
should be displaced with dry air nitrogen. Refrigerant in
contact with an open flame produces toxic gases.
The necessary protection equipment must be available, and
appropriate fire extinguishers for the system and the refrigerant
type used must be within easy reach.
Do not siphon refrigerant.
Avoid spilling liquid refrigerant on skin or splashing it into
the eyes. Use safety goggles. Wash any spills from the skin
with soap and water. If liquid refrigerant enters the eyes,
immediately and abundantly flush the eyes with water and
consult a doctor.
Never apply an open flame or live steam to a refrigerant
container. Dangerous overpressure can result. If it is
necessary to heat refrigerant, use only warm water.
During refrigerant removal and storage operations follow
applicable regulations. These regulations, permitting conditioning and recovery of halogenated hydrocarbons under optimum quality conditions for the products and optimum safety
conditions for people, property and the environment are
described in standard NFE 29795.
Any refrigerant transfer and recovery operations must be
carried out using a transfer unit. A 3/8 SAE connector on
the manual liquid line valve is supplied with all units for
connection to the transfer station. The units must never be
modified to add refrigerant and oil charging, removal and
purging devices. All these devices are provided with the units.
Please refer to the certified dimensional drawings for the units.
Do not re-use disposable (non-returnable) cylinders or attempt
to refill them. It is dangerous and illegal. When cylinders are
empty, evacuate the remaining gas pressure, and move the
cylinders to a place designated for their recovery. Do not
incinerate.
2 - PRELIMINARY CHECKS
2.1 - Check equipment received
CAUTION: Lift and set down the unit with great care. Tilting
and jarring can damage the unit and impair unit operation.
If 30HZ/HZV units are hoisted with rigging, it is advisable to
protect the control box against accidental shocks. Do not tilt a
unit more than 15.
1.
WARNING: Never push or lever the chassis or the control
box of the unit.
2.
3.
Remove the centre bolt (A) from each spring mounting, so that
the compressor support can float freely.
3 - DIMENSIONS, CLEARANCES
3.1 - 30HZ/HZV 043-065
750
600
2200
600
800
800
2550
3
800
1
2
850
2750
1000
3
800
Legend:
30HZ - units with condenser
043
052
065
091
101
111
121
141
161
195
225
250-280
2452
2750
2750
2630
2940
2940
2940
3350
3350
4255
4255
4070
1520
1505
1505
1915
1915
1915
1915
1915
1915
1950
1950
2150
915
915
915
950
950
950
950
950
950
950
950
1275
043
052
065
091
101
111
121
141
161
195
225
250-280
1260
1245
1245
1300
1300
1300
1300
1300
1300
1340
1340
1680
904
904
904
950
950
950
950
950
950
950
950
1275
2452
2750
2750
2630
2940
2940
2940
3350
3350
4255
4255
4070
Evaporator
Condensers
Power supply
Water inlet
Water outlet
Dimensions in mm
NOTE:
Non-contractual drawings. Certified dimensional drawings, available on
request.
FLOOR MOUNTING
For the positioning of the fixing points, weight distribution and centre of gravity coordinates, refer to the certified drawings.
kW
Operating weight**
30HZ
30HZV
kg
Refrigerant charge***
Circuit A
Circuit B
kg
043
052
065
091
101
111
121
141
161
195
225
250
280
134
126
153
144
199
194
230
216
270
260
300
278
316
297
371
352
415
388
533
500
626
588
719
677
783
735
1090
880
1183
968
1252
1018
2039
1672
2370
1960
2460
2000
2510
2040
2730
2260
2830
2300
3505
2975
3805
3267
4470
3780
4900
4106
R-407C
15.7
17.5
15.7
17.5
21.0
21.0
38.2
19.5
29.5
29.5
34.5
29.5
33.5
33.5
38.0
38.0
42.0
42.0
54.0
46.5
54.0
54.0
62.5
60.5
62.5
62.5
Compressors
Quantity - Circuit A
Quantity - Circuit B
2
2
2
2
2
2
2
2
3
2
3
3
4
3
4
4
Capacity control
No. of control steps
Minimum step capacity
11
20
11
18
11
16
11
19
11
16
5
20
6
16
7
14
8
12
154
2
154
2
154
2
199
2
199
2
242
2
242
2
276
2
276
2
3 gas threaded
NFE 03005
3/8
3/8
1000
1000
PN16DN100
NFE 29203
3/8
1000
PN16DN125
NFE 29203
3/8
3/8
1000
1000
3/8
1000
PN16DN150
NFE29203
3/8
3/8
1000
1000
3/8
1000
3/8
1000
3/8
1000
3/8
1000
10
10
10
10
Gas threaded
1-1/2
1-1/2
1-1/2
1-1/2
3/8
3/8
1000
1000
25
18
12
18
Flat flange, brazed
2-1/2
2
2
2
3/8
3/8
1000
1000
25
18
25
25
25
25
30
30
37
30
37
37
51
37
51
51
2-1/2
2
3/8
1000
2-1/2
2-1/2
3/8
1000
2-1/2
2-1/2
3/8
1000
2-1/2
2-1/2
3/8
1000
2-1/2
2-1/2
3/8
1000
2-1/2
2-1/2
3/8
1000
3
2-1/2
3/8
1000
3
3
3/8
1000
Evaporator
Net water volume
No. of refrigerant circuits
Water connections
Inlet/outlet
%
l
3/8
1000
in
in
kPa
12
12
2
2
3/8
1000
Notes:
*
Nominal Eurovent conditions:
evaporator entering/leaving water temperature = 12C/7C, condenser entering/leaving water temperature = 30C/35C
evaporator and condenser fouling factor = 0.000044 m2 K/W
condensing temperature dew point 45C
fluid temperature = condensing temperature at dew point - refrigerant glide - 5 K subcooling.
Net cooling capacity = gross cooling capacity minus the capacity corresponding to the evaporator pressure drop (flow x drop/0.3)
** The weights given are guidelines only. For the correct unit charge refer to the unit nameplate.
*** The 30HZV units have a nitrogen holding charge only.
043
065
091
101
111
121
141
161
195
225
250
280
V-ph-Hz 400-3-50
V
360-440
kW
kW
052
38.5
38.5
48.9
48.6
68
65
69
70
78
77
86
86
92
94
112
112
131
135
165
165
201
200
239
234
270
266
63.8
63.8
81.1
80.6
112
108
114
116
129
127
142
142
152
156
185
185
217
224
273
273
333
332
396
388
448
441
45
54
-
55
65
-
77
90
-
82
98
-
90
107
-
100
119
-
109
130
-
132
155
-
155
180
-
194
225
-
232
270
-
155
116
180
135
155
155
180
180
87
101
-
105
123
-
150
170
-
158
185
-
174
203
-
192
224
-
211
246
-
255
293
-
299
340
-
374
425
-
449
509
-
299
224
340
255
299
299
340
340
Standard Eurovent conditions: Evaporator entering/leaving water temperature 12C/7C, condenser entering/leaving water temperature 30C/35C.
Nominal operating power input: unit power input (compressors, control) plus the capacity corresponding to the evaporator and condenser pressure drop (flow x drop/0.3).
** Power input, compressors, at unit operating limits (saturated evaporating temperature (dew point) = 12C, saturated condensing temperature (dew point) = 52C
(30HZ)/66C (30HZV), and a nominal voltage of 400 V (data given on the unit name plate).
*** Maximum unit operating current at maximum unit power input.
Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor).
Current and power inputs not included in the values above.
10
043
052
065
091
101
111
121
141
161
195
225
250
280
78
91
-
95
111
-
135
153
-
142
166
-
157
182
-
173
202
-
190
221
-
230
264
-
269
306
-
336
382
-
404
458
-
269
202
306
229
269
269
306
306
182
188
-
198
207
-
273
283
-
245
263
-
227
251
-
275
299
-
291
318
-
330
360
-
404
436
-
470
513
-
536
589
-
404
338
436
360
404
404
436
436
A
A
2.33
-
2.09
-
2.03
-
1.72
-
1.45
-
1.59
-
1.53
-
1.44
-
1.50
-
1.40
-
1.33
-
1.50
1.68
1.50
1.50
A
A
2.06
-
1.87
-
1.85
-
1.58
-
1.37
-
1.48
-
1.44
-
1.37
-
1.43
-
1.34
-
1.28
-
1.43
1.57
1.43
1.43
kA
15
15
-
15
15
-
15
15
-
15
15
-
20
20
-
20
20
-
20
20
-
20
20
-
20
20
-
25
25
-
25
25
-
25
25
25
25
25
25
25
25
6
-
8
-
10
-
10
-
10
-
10
-
10
-
12
-
15
-
24
-
32
-
25
20
32
20
Standard Eurovent conditions: Evaporator entering/leaving water temperature 12C/7C, condenser entering/leaving water temperature 30C/35C.
Nominal operating power input: unit power input (compressors, control) plus the capacity corresponding to the evaporator and condenser pressure drop (flow x drop/0.3).
** Power input, compressors, at unit operating limits (saturated evaporating temperature (dew point) = 12C, saturated condensing temperature (dew point) = 52C
(30HZ)/66C (30HZV), and a nominal voltage of 400 V (data given on the unit name plate).
*** Maximum unit operating current at maximum unit power input.
Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor).
Current and power inputs not included in the values above.
kW
Operating weight**
30HZ
30HZV
kg
Refrigerant charge***
Circuit A
Circuit B
kg
043
052
065
091
101
111
121
141
161
195
225
250
280
144
136
166
157
215
208
250
234
292
280
323
300
342
321
402
380
447
417
578
538
677
633
779
729
847
792
1090
880
1183
968
1252
1018
2039
1672
2370
1960
2460
2000
2510
2040
2730
2260
2830
2300
3505
2975
3805
3267
4470
3780
4900
4106
R22
13.5
13.5
14
14
16.2
15.3
33.5
17.5
25.5
25.5
30
25.5
30
30
34
34
40
40
48
43.5
48
50
59
47
59
56
Compressors
Quantity - Circuit A
Quantity - Circuit B
2
2
2
2
2
2
2
2
3
2
3
3
4
3
4
4
Capacity control
No. of control steps
Minimum step capacity
11
20
11
18
11
16
11
19
11
16
5
20
6
16
7
14
8
12
154
2
154
2
154
2
199
2
199
2
242
2
242
2
276
2
276
2
3 gas threaded
NFE 03005
3/8
3/8
1000
1000
PN16DN100
NFE 29203
3/8
1000
PN16DN125
NFE 29203
3/8
3/8
1000
1000
3/8
1000
PN16DN150
NFE29203
3/8
3/8
1000
1000
3/8
1000
3/8
1000
3/8
1000
3/8
1000
10
10
10
10
Gas threaded
1-1/2
1-1/2
1-1/2
1-1/2
3/8
3/8
1000
1000
25
18
12
18
Flat flange, brazed
2-1/2
2
2
2
3/8
3/8
1000
1000
25
18
25
25
25
25
30
30
37
30
37
37
51
37
51
51
2-1/2
2
3/8
1000
2-1/2
2-1/2
3/8
1000
2-1/2
2-1/2
3/8
1000
2-1/2
2-1/2
3/8
1000
2-1/2
2-1/2
3/8
1000
2-1/2
2-1/2
3/8
1000
3
2-1/2
3/8
1000
3
3
3/8
1000
Evaporator
Net water volume
No. of refrigerant circuits
Water connections
Inlet/outlet
%
l
3/8
1000
in
in
kPa
12
12
2
2
3/8
1000
11
043
052
065
091
101
111
121
141
161
195
225
250
280
V-ph-Hz 400-3-50
V
360-440
kW
kW
35.8
38.1
45.5
48
64
65
64
69
72
76
80
85
85
93
104
111
122
133
154
164
189
198
224
233
253
264
59.4
63.2
75.5
79.6
106
108
106
114
119
126
133
141
141
154
172
184
202
221
255
272
313
328
372
387
418
438
46
54
-
55
65
-
79
90
-
83
98
-
91
107
-
101
119
-
111
130
-
134
155
-
158
180
-
198
225
-
237
270
-
158
119
180
135
158
158
180
180
88
101
-
107
123
-
153
170
-
161
185
-
177
203
-
195
224
-
214
246
-
260
293
-
305
340
-
382
425
-
458
509
-
305
229
340
255
305
305
340
340
79
91
-
96
111
-
137
153
-
145
166
-
159
182
-
176
202
-
193
221
-
234
264
-
275
306
-
343
382
-
412
458
-
275
206
306
229
275
275
306
306
183
188
-
199
207
-
274
283
-
246
263
-
229
251
-
277
299
-
293
318
-
333
360
-
408
436
-
475
513
-
542
589
-
408
341
436
360
408
408
436
436
A
A
2.3
-
2.07
-
1.99
-
1.7
-
1.44
-
1.57
-
1.52
-
1.43
-
1.49
-
1.38
-
1.32
-
1.49
1.66
1.49
1.49
A
A
2.06
-
1.87
-
1.85
-
1.58
-
1.37
-
1.48
-
1.44
-
1.37
-
1.43
-
1.34
-
1.28
-
1.43
1.57
1.43
1.43
kA
15
15
-
15
15
-
15
15
-
15
15
-
20
20
-
20
20
-
20
20
-
20
20
-
20
20
-
25
25
-
25
25
-
25
25
25
25
25
25
25
25
6
-
8
-
10
-
10
-
10
-
10
-
10
-
12
-
15
-
24
-
32
-
25
20
32
20
Standard Eurovent conditions: Evaporator entering/leaving water temperature 12C/7C, condenser entering/leaving water temperature 30C/35C.
Nominal operating power input: unit power input (compressors, control) plus the capacity corresponding to the evaporator and condenser pressure drop (flow x drop/0.3).
** Power input, compressors, at unit operating limits (saturated evaporating temperature (dew point) = 12C, saturated condensing temperature (dew point) = 53C
(30HZ)/68C (30HZV), and a nominal voltage of 400 V (data given on the unit name plate).
*** Maximum unit operating current at maximum unit power input.
Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor).
Current and power inputs not included in the values above.
12
30HZ/HZV 043 to 225 units have a single power connection point; 30HZ/HZV
250 to 280 units have two connection points.
Field connections:
All connections to the system and the electrical installations must be in full
accordance with all applicable codes.
The Carrier 30HZ/HZV chillers are designed and built to ensure conformance
with local codes. The recommendations of European standard EN 60204-1
(corresponds to IEC 60204-1) (machine safety - electrical machine
components - part 1: general regulations) are specifically taken into account,
when designing the electrical equipment.
2.
3.
4.
5.
6.
indoor installation*
presence of water: class AD2* (possibility of water droplets)
presence of hard solids, class AE2* (no significant dust present)
presence of corrosive and polluting substances, class AF1 (negligible)
vibration and shock, class AG2, AH2
b. Competence of personnel, class BA4* (trained personnel - IEC 60364)
Power supply frequency variation: 2 Hz.
The neutral (N) conductor must not be connected directly to the unit (if
necessary use a transformer).
Over-current protection of the power supply conductors is not provided with
the unit.
The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type
suitable for power interruption in accordance with EN 60947.
The units are designed for connection to TN networks (IEC 60364). For IT
networks the earth connection must not be at the network earth. Provide a
local earth, consult competent local organisations to complete the electrical
installation.
IMPORTANT:
1.
13
4.7.2 - Selection table of minimum and maximum wire sections for connection by phase to 30HZ/HZV units
MIN. WIRE SECTION
30HZ/HZV
Section (mm2)
Wire type
Section (mm2)
Wire type
043
052
065
091
101
111
121
141
161
195
225
250 circuit A
1x 25
1x 35
1x 50
1x 70
1x 70
1x 70
1x 95
1x 120
1x 150
1x 240
2x 95
1x 150
XLPE Copper
XLPE Copper
XLPE Copper
XLPE Copper
XLPE Copper
XLPE Copper
XLPE Copper
XLPE Copper
XLPE Copper
XLPE Copper
XLPE Copper
XLPE Copper
130
142
162
168
168
168
178
185
188
192
172
188
250 circuit B
1x 95
XLPE Copper
178
280 circuit A
1x 185
XLPE Copper
190
280 circuit B
1x 150
XLPE Copper
188
1x 95
1x 120
1x 120
1x 150
1x 150
1x 185
1x 240
2x 95
2x 120
2x 185
2x 240
2x 120
2x 150
2x 70
1x 240
2x 95
2x 150
2x 120
2x 120
PVC Aluminium
PVC Aluminium
XLPE Aluminium
XLPE Aluminium
XLPE Aluminium
XLPE Aluminium
XLPE Aluminium
XLPE Aluminium
XLPE Aluminium
XLPE Aluminium
XLPE Aluminium
PVC Copper
XLPE Aluminium
PVC Copper
XLPE Aluminium
XLPE Copper
XLPE Aluminium
PVC Copper
XLPE Aluminium
250
260
205
210
210
220
225
195
205
220
225
295
210
270
225
215
210
295
205
14
5 - APPLICATION DATA
Evaporator
Entering water temperature at start-up
Leaving water temperature during operation
C
C
Condenser
Entering water temperature
Leaving water temperature
C
C
Minimum
Maximum
6.8*
4**
30
10
Minimum
Maximum
15
20
45
Notes:
*
For application requiring operation at less than 6.8C, contact Carrier s.a. for
unit selection using the Carrier electronic catalog.
** For operation between 4C and -15C, the unit must be equipped with option 5
or 6, and the use of anti-freeze is required.
For an application, requiring operation up to +15C leaving water temperature,
contact Carrier for the selection of the unit.
Depends on the maximum condenser flow rate.
Maximum outside temperature: For transport and storage of the 30HZ/HZV
units the minimum and maximum allowable temperatures are 20C and
+50C. It is recommended that these temperatures are used for transport by
container.
Legend
1 Evaporator
2 Recirculation
45
44
D
42
40
39
36
35
30
25
20
-15
-10 -6 -5
10
Legend:
A 30HZ
B 30HZ with option 150 (high condensing temperature)
C 30HZ with option 5
D 30HZ with option 150 + 5
E 30HZ with option 6
Notes:
1. Evaporator and condenser T = 5 K
Legend
1 Evaporator
2 Bypass
15
If the flow rate changes more rapidly, the system should contain a
minimum of 6.5 liters of water per kW instead of 3.25 l/kW.
5.5 - System minimum water volume
Bad
Good
Bad
Good
3.25
6.5
30HZ/HZV
043
052-065
091
101-121
141-161
195-280
4.1
5.0
6.0
8.5
9.9
12.0
Legend
1 30HZ/HZV 043
2 30HZ/HZV 052-065
3 30HZ/HZV 091
4 30HZ/HZV 101-121
5 30HZ/HZV 141-161
6 30HZ/HZV 195-225
7 30HZ/HZV 250-280
10
1
2
3
1
-10
10
30
Water flow rate l/s
16
50
Passes
043
052
065
091
101
111
121
141
161
195
225
250
280
2
2
2
2
2
2
2
2
2
2
2
2
2
3.60
3.60
4.20
7.42
7.64
9.13
10.62
10.62
10.62
12.00
13.40
15.14
16.88
14.8
14.8
17
30
31
37
43
43
43
48.00
54
61
68
30HZ/HZV
Passes* OD, mm
Location
043
091
111
195
250
2
2
2
2
2
31
47
47
47
56
Legend:
*
No. of passes
Legend:
*
Based on a water velocity of 0.3 m/s in closed-loop and 0.9 m/s in open-loop
systems.
** Based on a water velocity of 3.6 m/s
10
11
10
3
Legend:
1 30HZ/HZV 043-052
2 30HZ/HZV 065
3 30HZ/HZV 091
4 30HZ/HZV 101
5 30HZ/HZV 111
6 30HZ/HZV 121-141
7 30HZ/HZV 161
8 30HZ/HZV 195
9 30HZ/HZV 225
10 30HZ/HZV 250
11 30HZ/HZV 280
1
0
10
20
30
40
50
17
6 - WATER CONNECTIONS
For size and position of the heat exchanger water inlet and
outlet connections refer to the certified dimensional drawings
supplied with the unit.
The water pipes must not transmit any radial or axial force to
the heat exchangers nor any vibration.
The water supply must be analysed and appropriate water
treatment elements installed: (filters, additives, intermediate
heat exchangers, purges, vents, shut-off valves, etc) to prevent
corrosion, fouling and deterioration of the pump fittings. Consult
either a water treatment specialist or appropriate literature on
the subject.
6.1 - Operating precautions
The water circuit should be designed to have the least number
of elbows and horizontal pipe runs at different levels. Below
the main points to be checked for the connection:
Where there are particles in the fluid that could foul the
heat exchanger, a screen filter should be installed ahead of
the pump. The mesh size of the filter must be 1.2 mm (see
Typical water circuit diagram on the right).
Before the system start-up verify that the water circuits are
connected to the appropriate heat exchangers (e.g. no
reversal between evaporator and condenser).
18
Potentiometer adjustment
3
9
12
10
11
8
6
7
Legend
1 Control valve
2 Air vent
3 Flow switch for the evaporator
4 Flexible connection
5 Heat exchanger
6 Pressure tap
7 Thermostat sleeve
8 Drain
9 Buffer tank
10 Filter (mesh size: 1.2 mm = 20 mesh)
11 Expansion tank
12 Fill valve
Legend
1 Setting potentiometer sensitivity
2 Chain of LEDs
- red LED lights: the unit is not adjusted
- yellow LED lights: the output is switched
- green LED lights: the unit is adjusted
4
8
6
2
Sequence 1: 1 2 3 4
Sequence 2: 5 6 7 8
Bolt size M12 - 71-87 Nm
Bolt size M16 - 171-210 Nm
Bolt size M20 - 171-210 Nm
19
2.
3.
4.
5.
If the water piping is in an area where the ambient temperature
can fall below 0C it is recommended to install a trace heater on
the piping and to add an antifreeze solution to protect the unit
and the water piping to a temperature of 10 K below the lowest
temperature likely to be reached at the installation site. Use
only antifreeze solutions, approved for heat exchanger duty. If
the system is not protected by an antifreeze solution and will
not be used during the freezing weather conditions, draining of
the cooler and outdoor piping is mandatory. Damage due to
freezing is not covered by the warranty.
IMPORTANT: Depending on the climatic conditions in your
area you must:
Add ethylene glycol with an adequate concentration to
protect the installation up to a temperature of 10 K below
the lowest temperature likely to occur at the installation
site.
If the unit is not used for an extended period, it is
recommended to drain it, and as a safety precaution add
ethylene glycol to the heat exchanger, using the water
entering purge valve connection.
At the start of the next season, refill the unit with water
and add an inhibitor.
For the installation of auxiliary equipment, the installer
must comply with basic regulations, especially for
minimum and maximum flow rates, which must be
between the values listed in the operating limit table
(application data).
6.
Install a valve in the discharge piping (valves are factoryinstalled in sizes 043-063, and supplied non-installed in
sizes 091-280).
Size the discharge and liquid line piping according to the
recommendations in the following paragraphs (if necessary, install a double riser to ensure correct oil circulation
in the refrigerant circuit).
Depending on the layout and the routing of the discharge
piping it may be necessary to install additional silencers
(to reduce pulsations and noise emission) between the
liquid chiller and the condenser.
Select a condenser with an integrated subcooler to obtain
a minimum of 3 K subcooling at the inlet to the expansion
device.
Keep the condensing pressure as stable as possible
(pressostat staging or fan control via Pro-Dialog Plus). A
speed controller may be required for the first fan stage for
operation at low ambient temperature and partial load.
If the system can have several operating modes (summer/
winter, dual set point etc.), it is necessary to install a tank
(or receiver) to absorb the variations in charge.
6.6.2 - General
Refrigerant pipe sizing must be carried out, taking account of
the following constraints:
Oil return to the compressor must be ensured for the majority of
applications. Oil return is ensured by entrainment. A minimum
refrigerant velocity is required to ensure entrainment. This
velocity depends on the pipe diameter, the refrigerant and oil
temperature (these are treated as being the same in most cases).
A reduction of the pipe diameter permits an increase of the
refrigerant velocity. The problem of a minimum entrainment
velocity does not exist for the pipes that carry liquid refrigerant
as the oil is fully miscible here.
The pressure drop at the compressor discharge (pipes linking
the compressor outlet with the condenser inlet) must be limited
to avoid system performance losses (the compressor power
input inceases, and the cooling capacity decreases).
As a first estimate and for standard air conditioning applications, a one degree Celsius pressure drop on the discharge side
decreases the cooling capacity 2% and increases the compressor power input by 3%. Increasing the pipe diameter permits
limiting the pressure drops.
The pressure drop in the liquid line (linking the condenser
outlet to the expansion device) must not result in a change in
phase. The estimate of these pressure drops must include those
for the possible accessories, such as solenoid valves, filters,
filter drier, etc.
20
Special attention must be paid to the liquid line sizing when the
expansion device ist positioned higher than the condenser. It
may now be necessary to increase the pipe diameter to compensate for the additional pressure of the liquid refrigerant
column. If the liquid refrigerant head ist very high, it may even
be necessary to increase the subcooling to prevent an phase
change in the liquid line. This can be done e.g. by a liquidvapour heat exchanger or an additional coil.
At 45C the volume mass of refrigerant R407C in the liquid
phase is approximately 1050 kg/m3. A pressure of 1 bar
corresponds to a liquid head of: 100 000/(1050 x 9.81) = 9.7 m.
21
Cond. temp.
C
-18
S
HG
-12
S
HG
-7
S
HG
-1
S
HG
4
S
HG
10
S
HG
27
32
38
43
49
54
60
66
71
2.01
2.11
2.22
2.34
2.49
2.66
2.87
3.13
3.46
1.36
1.27
1.17
1.09
1.03
0.97
0.93
0.91
0.89
1.09
1.08
1.08
1.08
1.09
1.12
1.16
1.21
1.29
1.61
1.69
1.78
1.88
1.99
2.13
2.29
2.49
2.74
1.34
1.23
1.13
1.06
0.99
0.94
0.90
0.87
0.85
1.07
1.06
1.06
1.06
1.07
1.10
1.13
1.18
1.26
1.31
1.37
1.44
1.52
1.61
1.72
1.85
2.01
2.21
1.30
1.19
1.10
1.02
0.96
0.90
0.86
0.84
0.82
1.06
1.04
1.04
1.04
1.05
1.07
1.11
1.15
1.22
1.07
1.12
1.18
1.24
1.32
1.40
1.50
1.63
1.79
1.26
1.16
1.06
0.99
0.93
0.87
0.83
0.81
0.78
1.04
1.03
1.02
1.02
1.03
1.05
1.08
1.12
1.19
0.89
0.93
0.97
1.03
1.09
1.16
1.24
1.34
1.47
1.23
1.12
1.03
0.96
0.90
0.85
0.81
0.78
0.76
1.03
1.01
1.01
1.00
1.01
1.03
1.06
1.10
1.16
0.74
0.77
0.81
0.85
0.90
0.96
1.03
1.11
1.21
1.19
1.09
1.00
0.93
0.87
0.82
0.78
0.75
0.73
1.01
1.00
0.99
0.99
0.99
1.01
1.04
1.08
1.13
Legend
S Suction
HG Hot gas
L Liquid
Table 2 - Minimum capacity for oil entrainment in the discharge piping (kW) for R407C copper tube
30HZV
5/8
3/4
7/8
1-1/8
1-3/8
1-5/8
2-1/8
2-5/8
3-1/8
3-5/8
4-1/8
0.81
0.84
0.84
0.88
0.88
0.88
0.84
0.84
0.81
1.48
1.51
1.51
1.55
1.55
1.55
1.55
1.51
1.48
2.39
2.46
2.50
2.53
2.53
2.53
2.53
2.46
2.43
3.66
3.76
3.80
3.87
3.87
3.87
3.87
3.80
3.69
7.14
7.28
7.42
7.53
7.56
7.56
7.49
7.39
7.17
12.06
12.34
12.56
12.73
12.80
12.80
12.70
12.45
12.17
18.64
19.06
19.41
19.66
19.77
19.77
19.62
19.27
18.78
37.21
38.09
38.76
39.25
39.50
39.46
39.18
38.44
37.49
63.94
65.42
66.61
67.42
67.84
67.81
67.32
66.08
64.43
99.81
102.13
103.96
105.23
105.90
105.86
105.05
103.12
100.55
145.60
148.94
151.62
153.48
154.43
154.40
153.24
150.42
146.69
201.98
206.66
210.35
212.92
214.26
214.19
212.60
208.66
203.49
-18
0.89
-12
0.92
-7
0.94
22
-1
0.97
4
1.00
10
1.03
Discharge piping
200
50
40
30
20
10
5
4
3
300
400 500
2
3
10
20
30
40
50
100
200
Legend
1 1/2"
2 3/8"
3 3/4"
4 7/8"
5 1 1/8"
6 1 3/8"
7 1 5/8"
8 2 1/8"
1000
Liquid piping
200
100
100
50
40
30
20
10
5
4
3
2
3
10
20
30 40 50
100
200
300 400
Legend
1 3/8"
2 1/2"
3 5/8"
4 3/4"
5 7/8"
6 1 1/8"
7 1 3/8"
1000
23
a discharge valve
a suction valve
anti-vibration mounts
With options 5 and 6 (low leaving brine temperature) each
compressor is equipped with a thermostat controlling the
discharge gas temperature. This sensor is activated, if the
temperature exceeds the safety limit and shuts off the
compressor (cut-out: 146C - cut-in: 115C).
7.2 - Lubricant
Recommended oils:
Legend
1
2
Master unit
Slave unit
Control boxes of the master and slave units
Water inlet
Water outlet
Water pumps for each unit (included as standard for units with hydronic
module)
Additional sensors for leaving water control, to be connected to channel 1 of
the slave boards of each master and slave unit
CCN communication bus
Connection of two additional sensors
R407C compressors:
- Carrier specification: PP 47 26
- Mobiloil EAL 68 (original charge)
R22 compressors:
- Mineral oil, Carrier specification: PP 33 26
- Gargoyle Artic (Mobil Oil, original charge)
- Suniso 3 GS (Sun Oil Co.)
- Capella WF 32-150
- Clavus G32 (Shell Oil Co.)
24
7.3.2 - Evaporator
The evaporator is a shell-and-tube type with two refrigerant
circuits. It has been tested and stamped in accordance with
applicable pressure codes for a maximum operating pressure of
2100 kPa refrigerant-side and 1000 kPa water-side. The seamless copper tubes are finned on the refrigerant side and expanded
onto the tube sheets.
The heat exchanger shell has a thermal insulation of 19 mm
polyurethane foam, and is equipped with a water drain and purge.
The products that may be added for thermal insulation of the
containers during the water piping connection procedure must
be chemically neutral in relation to the materials and coatings
to which they are applied. This is also the case for the products
originally supplied by Carrier s.a.
NOTES: Monitoring during operation, re-qualification, retesting and re-testing dispensation:
Follow the regulations on monitoring pressurised
equipment.
It is normally required that the user or operator sets up
and maintains a monitoring and maintenance file.
Follow the control programmes of EN 378-2, annexes A,
B, C and D.
If they exist follow local professional recommendations.
Regularly inspect the condition of the coating (paint) to
detect blistering resulting from corrosion. To do this,
check a non-insulated section of the container or the
rust formation at the insulation joints.
Regularly check for possible presence of impurities (e.g.
silicon grains) in the heat exchange fluids. These impurities maybe the cause of the wear or corrosion by puncture.
Filter the heat exchange fluid check and carry out
internal inspections as described in EN 378-2, annex C.
In case of re-testing take possible maximum pressure
differences, as indicated in (2) above into consideration.
The reports of periodical checks by the user or operator
must be included in the supervision and maintenance
file.
Repair
Any repair or modification, including the replacement of
moving parts:
must follow local regulations and be made by qualified
operators and in accordance with qualified procedures,
including changing the heat exchanger tubes
must be made in accordance with the instructions of the
original manufacturer. Repair and modification that
necessitate permanent assembly (soldering, welding,
expanding etc.) must be made using the correct
procedures and by qualified operators.
An indication of any modification or repair must be
shown in the monitoring and maintenance file.
Recycling
The unit is wholly or partly recyclable. After use it contains
refrigerant vapours and oil residue. It is coated by paint.
Operating life
This unit is designed for:
prolonged storage of 15 years under nitrogen charge
with a temperature difference of 20 K per day.
The role of the filter drier is to keep the circuit clean and
moisture-free. The moisture indicator shows, when it is
necessary to change the elements. A difference in temperature
between the filter inlet and outlet shows that the elements are
dirty.
25
26
9 - MAINTENANCE
During the unit operating life the service checks and tests must
be carried out in accordance with applicable national
regulations.
Keep the unit itself and the space around it clean and free
of obstructions. Remove all rubbish such as packing
materials, as soon as the installation is completed.
Regularly clean the exposed pipework to remove all dust
and dirt. This makes detection of water leaks easier, and
they can be repaired before more serious faults develop.
Confirm that all screwed and bolted connections and
joints are secure. Secure connections prevent leaks and
vibration from developing.
Check that all insulation joints are securely closed and that
all insulation is firmly in place. Check all heat exchangers
and all pipework.
27
Pressure
Pression
L+V
Enthalpy
Enthalpie
Legend
1
2
3
4
5
6
7
8
L
L+V
V
9.2.4 - Undercharge
If there is not enough refrigerant in the system, this is indicated
by gas bubbles in the moisture sight glass.
If the undercharge is significant, large bubbles appear in the
moisture sight glass, and the suction pressure drops. The
compressor suction superheat is also high. The machine must
be recharged after the leak has been repaired.
Find the leak and completely drain the system with a refrigerant
recovery unit. Carry out the repair, leak test and then recharge
the system.
IMPORTANT: After the leak has been repaired, the circuit
must be tested, without exceeding the maximum low-side
operating pressure shown on the unit name plate.
The refrigerant must always be recharged in the liquid phase
into the liquid line.
The refrigerant cylinder must always contain at least 10% of its
initial charge.
For the refrigerant quantity per circuit, refer to the data on the
unit name plate.
9.2.5 - Characteristics of R407C
See the table on the following page.
Saturated bubble point temperatures (bubble point curve)
Saturated dew point temperatures (dew point curve)
9.3 - Electrical maintenance
When working on the unit comply with all safety precautions
decribed in section 1.2.
28
Bar
(relative)
Saturated bubble
point temp.
Saturated dew
point temp.
Bar
(relative)
Saturated bubble
point temp.
Saturated dew
point temp.
Bar
(relative)
Saturated bubble
point temp.
Saturated dew
point temp.
1
1.25
1.5
1.75
2
2.25
2.5
2.75
3
3.25
3.5
3.75
4
4.25
4.5
4.75
5
5.25
5.5
5.75
6
6.25
6.5
6.75
7
7.25
7.5
7.75
8
8.25
8.5
8.75
9
9.25
9.5
9.75
10
10.25
-28.55
-25.66
-23.01
-20.57
-18.28
-16.14
-14.12
-12.21
-10.4
-8.67
-7.01
-5.43
-3.9
-2.44
-1.02
0.34
1.66
2.94
4.19
5.4
6.57
7.71
8.83
9.92
10.98
12.02
13.03
14.02
14.99
15.94
16.88
17.79
18.69
19.57
20.43
21.28
22.12
22.94
-21.72
-18.88
-16.29
-13.88
-11.65
-9.55
-7.57
-5.7
-3.93
-2.23
-0.61
0.93
2.42
3.85
5.23
6.57
7.86
9.11
10.33
11.5
12.65
13.76
14.85
15.91
16.94
17.95
18.94
19.9
20.85
21.77
22.68
23.57
24.44
25.29
26.13
26.96
27.77
28.56
10.5
10.75
11
11.25
11.5
11.75
12
12.25
12.5
12.75
13
13.25
13.5
13.75
14
14.25
14.5
14.75
15
15.25
15.5
15.75
16
16.25
16.5
16.75
17
17.25
17.5
17.75
18
18.25
18.5
18.75
19
19.25
19.5
19.75
23.74
24.54
25.32
26.09
26.85
27.6
28.34
29.06
29.78
30.49
31.18
31.87
32.55
33.22
33.89
34.54
35.19
35.83
36.46
37.08
37.7
38.31
38.92
39.52
40.11
40.69
41.27
41.85
42.41
42.98
43.53
44.09
44.63
45.17
45.71
46.24
46.77
47.29
29.35
30.12
30.87
31.62
32.35
33.08
33.79
34.5
35.19
35.87
36.55
37.21
37.87
38.51
39.16
39.79
40.41
41.03
41.64
42.24
42.84
43.42
44.01
44.58
45.15
45.71
46.27
46.82
47.37
47.91
48.44
48.97
49.5
50.02
50.53
51.04
51.55
52.05
20
20.25
20.5
20.75
21
21.25
21.5
21.75
22
22.25
22.5
22.75
23
23.25
23.5
23.75
24
24.25
24.5
24.75
25
25.25
25.5
25.75
26
26.25
26.5
26.75
27
27.25
27.5
27.75
28
28.25
28.5
28.75
29
29.25
47.81
48.32
48.83
49.34
49.84
50.34
50.83
51.32
51.8
52.28
52.76
53.24
53.71
54.17
54.64
55.1
55.55
56.01
56.46
56.9
57.35
57.79
58.23
58.66
59.09
59.52
59.95
60.37
60.79
61.21
61.63
62.04
62.45
62.86
63.27
63.67
64.07
64.47
52.55
53.04
53.53
54.01
54.49
54.96
55.43
55.9
56.36
56.82
57.28
57.73
58.18
58.62
59.07
59.5
59.94
60.37
60.8
61.22
61.65
62.07
62.48
62.9
63.31
63.71
64.12
64.52
64.92
65.31
65.71
66.1
66.49
66.87
67.26
67.64
68.02
68.39
Plug
Ring
Components
Part number
---T-853--103500S-*
---T-853--002570S-*
---T-853--1031S-*
---T-853--002631S-*
Loctite
Locquic
No. 75
N
29
16.00 mm
15.87 mm
0.13 mm
14.27 mm
14.48 mm
NOTE: Tubes next to the gasket webs must be flush with the
tube sheets at either end of the cooler.
9.4.4 - Preparation of gaskets
When rebuilding the cooler, new gaskets must always be used.
They must conform to the Carrier specification for compressed
gaskets.
Insert and tighten the six screws in the center of the head.
Not less than one hour later insert and tighten the six bolts
in the centre of the head, using the torque values given.
Stage 1
Stage 2
7
1
5
4
6
2
8
30
10 - START-UP CHECKLIST FOR 30HZ/HZV LIQUID CHILLERS (USE FOR JOB FILE)
Preliminary information
Job name: ................................................................................................................................................................................................
Location: .................................................................................................................................................................................................
Installing contractor: ...............................................................................................................................................................................
Distributor: ..............................................................................................................................................................................................
Start-up preformed by: ...........................................................................................................................................................................
Compressors
Model: ............................................................................................. S/N ..............................................................................................
Compresseurs
Circuit A
1. Model # ......................................................................................
S/N .............................................................................................
Mtr # ...........................................................................................
Circuit B
1. Model # .................................................................................
S/N ..............................................................................................
Mtr # ...........................................................................................
31
Unit start-up
CWP starter has been properly interlocked with the chiller
Oil heaters have been energized for at least 24 hours
Oil level is correct
All discharge, suction and liquid valves are open
Unit has been leak checked (including fittings)
Locate, repair, and report any refrigerant leaks
................................................................................................................................................................................................................
................................................................................................................................................................................................................
................................................................................................................................................................................................................
Check voltage imbalance: AB ..................
Average voltage = .....................................
Maximum deviation = ..............................
Voltage imbalance = .................................
AC ................. BC .................
(see installation instructions)
(see installation instructions)
(see installation instructions) .
32
*If installed
* if installed
NOTES:
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
...............................................................................................................................................................................................................
33