Block 07

Calculation sheet

Two 400mm pipes are used to handle the condenser water of Block 07(supply & return). We use a base platform at LL3 to cater the total weight of the pipes.
1. Calculations for base platform
Data
- Selected beam for base platform

150x150
B
D
t
Ix-x

Data sheet is attached (Annex 01)


150
150
7
1623

mm
mm
mm
cm4

Figure 1 : I - Beam detail


- Yield strength of steel

S 275

- Technical data for anchor bolts are taken from fischer catalog
- Condensor water riser height (m)
- Linear density of pipe (400mm),sch 40 with water

16 mm
275 Mpa
46.667 m
237.3 kg/m

Data sheet is attached (Annex 02)

Refer attached drawing (Annex 03)


data sheet attached (Annex 04)

Notes/Assumptions:
- Self weight of I - beam is negligible
- Load on the platform is considered as an UDL
- Concreate wall is considered as cracked concreate
- Beam is considered as simply supported beam

Designed by : Chathura Siriwardhana

Block 07

Calculation sheet

w
A
RA

l
x

RB

Figure 2 : Forces on base platform at LL3

a. Calculation for the beam


Nos of beams
Beam length
Load per pipe with water
Nos of pipes
Total load
With 1.5 safety factor (2W)
UDL (w)
UDL (w) per beam
Nos of brackets
Considering vertical forces on the beams RA = RB (=wl/2)

5
2.5
108.64
2
217.27
326
130.40
26.08
9
32.60

Maximum bending moment on the beam (wl /8)


Maximum bending stress of the beam ( = -My/I)

m
kN
kN
kN/m
kN/m
Nos
kN

20.38 kNm
188.31 Mpa

< 275 Mpa

OK

b. Base plate design (refer ASD procedure)


Allowable bearing stress on the MS plate (0.7 f'c)
192.5 Mpa
f'c is compressive strengh of steel (=275Mpa)
Required plate area (Axial force/bearing stress)
0.0008468 m2
N'xB'
0.03 0.029 m
N and B are the diamentions of the base plate
Considering vertical 250 mm pipe,
300
x 300
x
16 mm
plate is selected.
Plate thickness according to the Allowable Stree Design (ASD) Procedure (tp= max{m or n} (fp/(0.25Fy)))
0.0041 m
4.18 mm
<
16 mm
OK

Designed by : Chathura Siriwardhana

Block 07

Calculation sheet

The base plate is checked for bending


Note/ Assumptions:
- Plate is considered as cantilevered beam
- Axial force due to pipe riser act on the base plate as an UDL.

250

UDL (w)
543.33 kN/m
2
Maximum moment (wl /8)
0.04 kNm
Bending stress
3.32 Mpa
Therefore plate does not fail due to bending

< 0.75x275 Mpa

OK

wl
Figure 3 : Bending moment on base plate

c. Anchor bolts for vertical wall


Note:
- Nos of required bolts are calculated considering shear load
- Fischer model FAZ ll 16 is considered for the analysis.
- Friction force between concrete wall and the end plate has not been considered.

Data sheet is attached (Annex 05)

Designed by : Chathura Siriwardhana

Block 07

Fischer
model
FAZ ll
16

Permissible
shear load V
perm

Calculation sheet

Nos of
bolts
per
beam
RA (RA/Vpe Required
(kN)
min bolts
rm)

31.4 32.60

OK

10

RA
C2

C1
Figure 4 : Shear force on side plate of the base platform at LL3

Designed by : Chathura Siriwardhana