Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.1 Maximum Number of Conductors or Fixture Wires in Electrical Metallic


Tubing (EMT) (Based on Table 1, Chapter 9)
CONDUCTORS
Conductor
Size (AWG
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

14
12
10
8
6

4
3
2
1
1

7
6
5
2
1

11
9
8
4
3

20
17
13
7
5

27
23
18
9
8

46
38
30
16
13

80
66
53
28
22

120
100
81
42
34

157
131
105
55
44

201
167
135
70
56

4
3
2
1

1
1
1
0

1
1
1
1

2
1
1
1

4
4
3
1

6
5
4
3

10
9
7
5

17
15
13
9

26
23
20
13

34
30
26
17

44
38
33
22

1/0
2/0
3/0
4/0

0
0
0
0

1
1
0
0

1
1
1
1

1
1
1
1

2
2
1
1

4
4
3
3

7
6
5
5

11
10
8
7

15
13
11
9

19
17
14
12

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
1
1
1
0

1
1
1
1
1

1
1
1
1
1

3
3
3
2
2

5
5
4
4
3

7
6
6
5
4

9
8
7
7
6

600
700
750
800
900

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
0
0
0
0

1
1
1
1
1

1
1
1
1
1

3
2
2
2
1

4
3
3
3
3

5
4
4
4
3

1000
1250
1500
1750
2000

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
0
0
0
0

1
1
1
1
1

1
1
1
1
1

2
1
1
1
1

3
2
1
1
1

TW

14
12
10
8

8
6
5
2

15
11
8
5

25
19
14
8

43
33
24
13

58
45
33
18

96
74
55
30

168
129
96
53

254
195
145
81

332
255
190
105

424
326
243
135

RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2

14

10

16

28

39

64

112

169

221

282

RHH*, RHW*,
RHW-2*,
THHW, THW

12

13

23

31

51

90

136

177

227

10

10

18

24

40

70

106

138

177

RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2

10

14

24

42

63

83

106

RHH*, RHW*,
RHW-2*, TW,
THW, THHW,
THW-2

6
4
3
2
1

1
1
1
1
1

3
1
1
1
1

4
3
3
2
1

8
6
5
4
3

11
8
7
6
4

18
13
12
10
7

32
24
20
17
12

48
36
31
26
18

63
47
40
34
24

81
60
52
44
31

Type
RHH, RHW,
RHW-2

(Continues)

National Electrical Code Handbook

2011

1353

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.1 Continued


CONDUCTORS

Type

THHN,
THWN,
THWN-2

FEP, FEPB,
PFA, PFAH,
TFE

1354

Metric Designator (Trade Size)

Conductor
Size (AWG
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

1/0
2/0
3/0
4/0

0
0
0
0

1
1
1
0

1
1
1
1

2
1
1
1

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

1
1
0
0
0

600
700
750
800
900

0
0
0
0
0

0
0
0
0
0

1000
1250
1500
1750
2000

0
0
0
0
0

14
12
10
8
6

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

3
3
2
1

6
5
4
3

10
9
7
6

16
13
11
9

20
17
15
12

26
22
19
16

1
1
1
1
1

1
1
1
1
1

3
2
1
1
1

5
4
4
3
3

7
6
6
5
4

10
8
7
7
6

13
11
10
9
7

0
0
0
0
0

1
0
0
0
0

1
1
1
1
0

1
1
1
1
1

2
1
1
1
1

3
3
3
3
2

4
4
4
3
3

6
5
5
5
4

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
1
1
0
0

1
1
1
1
1

2
1
1
1
1

3
2
1
1
1

4
3
2
2
1

12
9
5
3
2

22
16
10
6
4

35
26
16
9
7

61
45
28
16
12

84
61
38
22
16

138
101
63
36
26

241
176
111
64
46

364
266
167
96
69

476
347
219
126
91

608
443
279
161
116

4
3
2
1

1
1
1
1

2
1
1
1

4
3
3
1

7
6
5
4

10
8
7
5

16
13
11
8

28
24
20
15

43
36
30
22

56
47
40
29

71
60
51
37

1/0
2/0
3/0
4/0

1
0
0
0

1
1
1
1

1
1
1
1

3
2
1
1

4
3
3
2

7
6
5
4

12
10
8
7

19
16
13
11

25
20
17
14

32
26
22
18

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

1
1
1
0
0

1
1
1
1
1

1
1
1
1
1

3
3
2
1
1

6
5
4
4
3

9
7
6
6
5

11
10
9
8
6

15
13
11
10
8

600
700
750
800
900
1000

0
0
0
0
0
0

0
0
0
0
0
0

0
0
0
0
0
0

1
1
0
0
0
0

1
1
1
1
1
1

1
1
1
1
1
1

2
2
1
1
1
1

4
3
3
3
3
2

5
4
4
4
3
3

7
6
5
5
4
4

14
12
10
8

12
9
6
3

21
15
11
6

34
25
18
10

60
43
31
18

81
59
42
24

134
98
70
40

234
171
122
70

354
258
185
106

462
337
241
138

590
430
309
177

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.1 Continued


CONDUCTORS
Conductor
Size (AWG
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

6
4
3
2

2
1
1
1

4
3
2
1

7
5
4
3

12
9
7
6

17
12
10
8

28
20
16
13

50
35
29
24

75
53
44
36

98
69
57
47

126
88
73
60

PFA, PFAH,
TFE

16

25

33

42

PFAH, TFE
PFA, PFAH,
TFE, Z

1/0
2/0
3/0
4/0

1
0
0
0

1
1
1
1

1
1
1
1

3
3
2
1

5
4
3
2

8
6
5
4

14
11
9
8

21
17
14
11

27
22
18
15

35
29
24
19

14
12
10
8
6

14
10
6
4
3

25
18
11
7
5

41
29
18
11
8

72
51
31
20
14

98
69
42
27
19

161
114
70
44
31

282
200
122
77
54

426
302
185
117
82

556
394
241
153
107

711
504
309
195
137

4
3
2
1

1
1
1
1

3
2
1
1

5
4
3
2

9
7
6
4

13
9
8
6

21
15
13
10

37
27
22
18

56
41
34
28

74
54
45
36

94
69
57
46

14
12
10
8

8
6
5
2

15
11
8
5

25
19
14
8

43
33
24
13

58
45
33
18

96
74
55
30

168
129
96
53

254
195
145
81

332
255
190
105

424
326
243
135

6
4
3
2

1
1
1
1

3
2
1
1

6
4
3
3

10
7
6
5

14
10
8
7

22
16
14
11

39
28
24
20

60
43
36
31

78
56
48
40

100
72
61
51

1
1/0
2/0
3/0
4/0

1
1
0
0
0

1
1
1
1
1

1
1
1
1
1

4
3
2
1
1

5
4
3
3
2

8
7
6
5
4

15
13
10
9
7

23
19
16
13
11

30
25
21
17
14

38
32
27
22
18

250
300
350
400
500
600
700
750
800
900

0
0
0
0
0
0
0
0
0
0

0
0
0
0
0
0
0
0
0
0

1
1
1
0
0
0
0
0
0
0

1
1
1
1
1
1
0
0
0
0

1
1
1
1
1
1
1
1
1
1

3
3
2
1
1
1
1
1
1
1

6
5
4
4
3
2
2
1
1
1

9
8
7
6
5
4
3
3
3
3

12
10
9
8
6
5
4
4
4
3

15
13
11
10
8
6
6
5
5
4

1000
1250
1500
1750
2000

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
1
1
0
0

1
1
1
1
1

2
1
1
1
1

3
2
1
1
1

4
3
3
2
1

Type

XHH, XHHW,
XHHW-2, ZW

XHH, XHHW,
XHHW-2

(Continues)

National Electrical Code Handbook

2011

1355

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.1 Continued


FIXTURE WIRES
Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

FFH-2, RFH-2,
RFHH-3

18
16

8
7

14
12

24
20

41
34

56
47

92
78

SF-2, SFF-2

18
16
14

10
8
7

18
15
12

30
25
20

52
43
34

71
58
47

116
96
78

SF-1, SFF-1

18

18

33

53

92

125

206

RFH-1, RFHH-2,
TF, TFF, XF, XFF

18

14

24

39

68

92

152

RFHH-2, TF, TFF,


XF, XFF

16

11

19

31

55

74

123

XF, XFF

14

15

25

43

58

96

TFN, TFFN

18
16

22
17

38
29

63
48

108
83

148
113

244
186

PF, PFF, PGF,


PGFF, PAF, PTF,
PTFF, PAFF

18
16
14

21
16
12

36
28
21

59
46
34

103
79
60

140
108
81

231
179
134

ZF, ZFF, ZHF, HF,


HFF

18
16
14

27
20
14

47
35
25

77
56
41

133
98
72

181
133
98

298
220
161

KF-2, KFF-2

18
16
14
12
10

39
27
19
13
8

69
48
33
23
15

111
78
54
37
25

193
136
93
64
43

262
185
127
87
58

433
305
209
144
96

KF-1, KFF-1

18
16
14
12
10

46
33
22
14
9

82
57
38
25
16

133
93
63
41
27

230
161
108
72
47

313
220
148
98
64

516
362
244
161
105

XF, XFF

12
10

4
3

8
6

13
10

23
18

31
24

51
40

Type

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.1(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*Types RHH, RHW, and RHW-2 without outer covering.

1356

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.1(A) Maximum Number of Compact Conductors in Electrical Metallic Tubing


(EMT) (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN,
THWN,
THWN-2

XHHW,
XHHW-2

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
5
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

6
5
4
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0

7
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
8
6
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0

11
9
6
5
3
3
2
1
1
1
1
1
1
1
1
1
0
0
0

13
8
6
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0
15
11
8
6
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0

16
12
9
7
4
4
3
3
2
1
1
1
1
1
1
1
1
1
1

18
11
8
6
5
4
3
3
1
1
1
1
1
1
1
1
1
1
20
15
11
8
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1

26
20
15
11
8
7
5
5
4
3
3
2
1
1
1
1
1
1
1

29
18
13
10
8
7
6
5
4
3
3
2
1
1
1
1
1
1
34
25
18
13
10
8
7
6
5
4
3
3
2
1
1
1
1
1
1

46
35
26
19
13
12
10
8
7
5
5
4
4
3
2
2
1
2
1

52
32
23
17
14
12
10
8
6
5
5
4
4
3
2
2
2
1
59
44
32
23
17
14
12
10
8
7
6
5
4
4
3
2
2
2
1

69
53
40
29
21
18
15
13
11
8
7
6
6
5
4
3
3
3
2

78
48
34
26
22
18
15
12
10
8
7
6
5
4
4
4
3
3
90
66
48
34
26
22
18
15
13
10
9
8
7
6
4
4
3
3
3

90
70
52
38
27
23
20
17
14
11
9
8
8
6
5
4
4
4
3

102
63
45
34
29
24
20
16
13
11
10
9
7
6
5
5
4
3
117
87
63
45
34
29
24
20
17
13
11
10
9
7
6
5
5
4
4

115
89
67
49
34
30
25
21
18
14
12
11
10
8
7
6
5
5
4

130
81
58
43
37
30
25
21
16
14
12
11
9
7
7
6
5
4
149
111
81
58
43
37
31
25
21
17
14
13
11
9
8
7
6
5
5

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

National Electrical Code Handbook

2011

1357

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.2 Maximum Number of Conductors or Fixture Wires in Electrical Nonmetallic


Tubing (ENT) (Based on Table 1, Chapter 9)
CONDUCTORS
Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

14
12
10
8
6

3
2
1
1
1

6
5
4
1
1

10
9
7
3
3

19
16
13
6
5

26
22
17
9
7

43
36
29
15
12

4
3
2
1

1
1
0
0

1
1
1
1

2
1
1
1

4
3
3
1

6
5
4
3

9
8
7
5

1/0
2/0
3/0
4/0

0
0
0
0

0
0
0
0

1
1
1
1

1
1
1
1

2
1
1
1

4
3
3
2

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
1
1
1
0

1
1
1
1
1

1
1
1
1
1

600
700
750
800
900

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
0
0
0
0

1
1
1
1
1

1000
1250
1500
1750
2000

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
0
0
0
0

TW

14
12
10
8

7
5
4
1

13
10
7
4

22
17
13
7

40
31
23
13

55
42
32
17

92
71
52
29

RHH*, RHW*,
RHW-2*, THHW,
THW, THW-2

14

15

27

37

61

RHH*, RHW*,
RHW-2*, THHW,
THW

12

12

21

29

49

10

17

23

38

RHH*, RHW*,
RHW-2*, THHW,
THW, THW-2

10

14

23

RHH*, RHW*,
RHW-2*, TW,
THW, THHW,
THW-2

6
4
3
2
1

1
1
1
1
0

2
1
1
1
1

4
3
2
2
1

7
5
5
4
3

10
8
7
6
4

17
13
11
9
6

Type
RHH, RHW,
RHW-2

1358

53
(2)

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.2 Continued


CONDUCTORS

Type

THHN, THWN,
THWN-2

FEP, FEPB, PFA,


PFAH, TFE

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

1/0
2/0
3/0
4/0

0
0
0
0

1
1
0
0

1
1
1
1

2
1
1
1

3
3
2
1

5
5
4
3

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

1
0
0
0
0

1
1
1
1
1

1
1
1
1
1

2
2
1
1
1

600
700
750
800
900

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
1
1
1
0

1
1
1
1
1

1000
1250
1500
1750
2000

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
1
0
0
0

14
12
10
8
6

10
7
4
2
1

18
13
8
5
3

32
23
15
8
6

58
42
26
15
11

80
58
36
21
15

132
96
60
35
25

4
3
2
1

1
1
1
1

1
1
1
1

4
3
2
1

7
5
5
3

9
8
6
5

15
13
11
8

1/0
2/0
3/0
4/0

0
0
0
0

1
1
1
0

1
1
1
1

3
2
1
1

4
3
3
2

7
5
4
4

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

1
1
0
0
0

1
1
1
1
1

1
1
1
1
1

3
2
2
1
1

600
700
750
800
900
1000

0
0
0
0
0
0

0
0
0
0
0
0

0
0
0
0
0
0

1
0
0
0
0
0

1
1
1
1
1
0

1
1
1
1
1
1

14
12
10
8

10
7
5
3

18
13
9
5

31
23
16
9

56
41
29
17

77
56
40
23

128
93
67
38
(Continues)

National Electrical Code Handbook

2011

1359

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.2 Continued


CONDUCTORS
Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

6
4
3
2

1
1
1
1

4
2
1
1

PFA, PFAH, TFE, Z

1/0
2/0
3/0
4/0

Type

PFA, PFAH, TFE

XHH, XHHW,
XHHW-2, ZW

XHH, XHHW,
XHHW-2

1360

35
(114)

41
(112)

53
(2)

6
4
4
3

12
8
7
5

16
11
9
8

27
19
16
13

0
0
0
0

1
1
1
1

1
1
1
1

3
2
1
1

4
4
3
2

7
6
5
4

14
12
10
8
6

12
8
5
3
1

22
15
9
6
4

38
27
16
10
7

68
48
29
18
13

93
66
40
25
18

154

4
3
2
1

1
1
1
1

3
1
1
1

5
3
3
2

9
6
5
4

12
9
7
6

20
15
12
10

14
12
10
8
6

7
5
4
1
1

13
10
7
4
3

22
17
13
7
5

40
31
23
13
9

55
42
32
17
13

92
71
52
29
21

4
3
2

1
1
1

1
1
1

4
3
2

7
6
5

9
8
6

15
13
11

1
1/0
2/0
3/0
4/0

1
0
0
0
0

1
1
1
1
0

1
1
1
1
1

3
3
2
1
1

5
4
3
3
2

8
7
6
5
4

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

1
1
1
0
0

1
1
1
1
1

1
1
1
1
1

3
3
2
1
1

600
700
750
800
900

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
0
0
0
0

1
1
1
1
1

1
1
1
1
1

1000
1250
1500
1750
2000

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
1
1
0
0

109
67
42
30

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.2 Continued


FIXTURE WIRES

Type

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

FFH-2, RFH-2,
RFHH-3 SF-2,
SFF-2

18
16

6
5

12
10

21
18

39
32

53
45

88
74

18
16
14

8
7
5

15
13
10

27
22
18

49
40
32

67
55
45

111
92
74

SF-1, SFF-1

18

15

28

48

86

119

197

RFH-1, RFHH-2,
TF, TFF, XF, XFF

18

11

20

35

64

88

145

RFHH-2, TF, TFF,


XF, XFF

16

16

29

51

71

117

XF, XFF

14

13

22

40

55

92

TFN, TFFN

18
16

18
13

33
25

57
43

102
78

141
107

233
178

PF, PFF, PGF,


PGFF, PAF, PTF,
PTFF, PAFF

18
16
14

17
13
10

31
24
18

54
42
31

97
75
56

133
103
77

221
171
128

ZF, ZFF, ZHF, HF,


HFF

18
16
14

22
16
12

40
29
22

70
51
38

125
92
68

172
127
93

285
210
154

KF-2, KFF-2

18
16
14
12
10

31
22
15
10
7

58
41
28
19
13

101
71
49
33
22

182
128
88
60
40

250
176
121
83
55

413
291
200
138
92

KF-1, KFF-1

18
16
14
12
10

38
26
18
12
7

69
49
33
22
14

121
85
57
38
24

217
152
102
68
44

298
209
141
93
61

493
346
233
154
101

XF, XFF

12
10

3
3

7
5

12
9

21
17

29
23

49
38

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.2(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*Types RHH, RHW, and RHW-2 without outer covering.

National Electrical Code Handbook

2011

1361

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.2(A) Maximum Number of Compact Conductors in Electrical Nonmetallic


Tubing (ENT) (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN, THWN,
THWN-2

XHHW, XHHW-2

Metric Designator (Trade Size )

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0

4
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
4
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

6
4
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0

7
4
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
8
6
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0

11
8
6
4
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0

12
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0
14
10
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0

15
11
8
6
4
4
3
3
2
1
1
1
1
1
1
1
1
1
0

17
10
7
5
5
4
3
2
1
1
1
1
1
1
1
1
1
1
19
14
10
7
5
5
4
3
3
1
1
1
1
1
1
1
1
1
1

25
19
14
10
7
6
5
4
4
3
2
2
1
1
1
1
1
1
1

28
17
12
9
8
6
5
4
3
3
2
2
1
1
1
1
1
1
32
24
17
12
9
8
7
5
4
3
3
3
2
1
1
1
1
1
1

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

1362

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.3 Maximum Number of Conductors or Fixture Wires in Flexible Metal Conduit
(FMC) (Based on Table 1, Chapter 9)
CONDUCTORS
Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8

4
3
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
9
7
5
3

7
6
5
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
15
11
8
5

11
9
7
4
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
23
18
13
7

17
14
11
6
5
4
3
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
36
28
21
11

25
21
17
9
7
5
5
4
2
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
53
41
30
17

44
37
30
15
12
10
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
94
72
54
30

67
55
45
23
19
14
13
11
7
6
5
5
4
3
2
2
1
1
1
1
1
1
1
1
1
1
1
0
141
108
81
45

96
80
64
34
27
21
18
16
10
9
8
7
6
4
4
3
3
3
2
1
1
1
1
1
1
1
1
1
203
156
116
64

131
109
88
46
37
29
25
22
14
12
11
9
8
6
5
5
4
4
3
3
2
2
2
1
1
1
1
1
277
212
158
88

171
142
115
60
48
37
33
28
19
16
14
12
10
8
7
6
6
5
4
3
3
3
3
3
1
1
1
1
361
277
207
115

RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*,
THHW, THW

14

10

15

24

35

62

94

135

184

240

12

12

19

28

50

75

108

148

193

10

10

15

22

39

59

85

115

151

RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*, TW,
THW, THHW,
THW-2

13

23

35

51

69

90

6
4
3
2
1

1
1
1
1
1

3
1
1
1
1

4
3
3
2
1

7
5
4
4
2

10
7
6
5
4

18
13
11
10
7

27
20
17
14
10

39
29
25
21
15

53
39
34
29
20

69
51
44
37
26

Type
RHH, RHW,
RHW-2

TW

(Continues)

National Electrical Code Handbook

2011

1363

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.3 Continued


CONDUCTORS

Type

THHN,
THWN,
THWN-2

FEP, FEPB,
PFA, PFAH,
TFE

1364

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0

6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0

9
7
6
5
4
3
3
3
2
1
1
1
1
1
1
1
1
1
1

12
10
9
7
6
5
4
4
3
3
2
2
1
1
1
1
1
1
1

17
14
12
10
8
7
6
6
5
4
3
3
3
3
2
1
1
1
1

22
19
16
13
11
9
8
7
6
5
4
4
4
3
3
2
1
1
1

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000

13
9
6
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0

22
16
10
6
4
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0

33
24
15
9
6
4
3
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0

52
38
24
14
10
6
5
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0

76
56
35
20
14
9
7
6
4
4
3
2
1
1
1
1
1
1
1
1
1
1
0
0

134
98
62
35
25
16
13
11
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1

202
147
93
53
38
24
20
17
12
10
9
7
6
5
4
3
3
2
1
1
1
1
1
1

291
212
134
77
55
34
29
24
18
15
12
10
8
7
6
5
5
4
3
3
2
2
1
1

396
289
182
105
76
46
39
33
24
20
17
14
12
9
8
7
6
5
4
4
3
3
3
3

518
378
238
137
99
61
51
43
32
27
22
18
15
12
11
9
8
7
5
5
4
4
4
3

14
12
10
8

12
9
6
4

21
15
11
6

32
24
17
10

51
37
26
15

74
54
39
22

130
95
68
39

196
143
103
59

282
206
148
85

385
281
201
115

502
367
263
151

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.3 Continued


CONDUCTORS
Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

6
4
3
2

2
1
1
1

4
3
2
1

7
5
4
3

11
7
6
5

16
11
9
7

28
19
16
13

42
29
24
20

60
42
35
29

82
57
48
39

107
75
62
51

14

20

27

36

1/0
2/0
3/0
4/0

1
1
0
0

1
1
1
1

1
1
1
1

3
2
1
1

4
3
3
2

8
6
5
4

11
9
8
6

17
14
11
9

23
19
15
13

30
24
20
16

14
12
10
8
6
4
3
2
1

15
11
6
4
3
1
1
1
1

25
18
11
7
5
3
2
1
1

39
28
17
11
7
5
4
3
2

61
43
26
17
12
8
6
5
4

89
63
39
24
17
12
8
7
6

157
111
68
43
30
21
15
12
10

236
168
103
65
45
31
23
19
15

340
241
148
93
65
45
33
27
22

463
329
201
127
89
61
45
37
30

605
429
263
166
117
80
58
49
39

XHH, XHHW,
XHHW-2, ZW

14
12
10
8
6
4
3
2

9
7
5
3
1
1
1
1

15
11
8
5
3
2
1
1

23
18
13
7
5
4
3
3

36
28
21
11
8
6
5
4

53
41
30
17
12
9
7
6

94
72
54
30
22
16
13
11

141
108
81
45
33
24
20
17

203
156
116
64
48
34
29
24

277
212
158
88
65
47
40
33

361
277
207
115
85
61
52
44

XHH, XHHW,
XHHW-2

1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

3
2
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

5
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0

8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0

13
10
9
7
6
5
4
4
3
3
1
1
1
1
1
1
1
1
1
1

18
15
13
10
9
7
6
5
5
4
3
3
2
2
1
1
1
1
1
1

25
21
17
14
12
10
8
7
6
5
4
4
3
3
3
3
1
1
1
1

32
27
23
19
15
13
11
9
8
7
5
5
4
4
4
3
3
2
1
1

Type

PFA, PFAH,
TFE
PFA, PFAH,
TFE, Z

(Continues)

National Electrical Code Handbook

2011

1365

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.3 Continued


FIXTURE WIRES

Type
FFH-2, RFH-2,
RFHH-3
SF-2, SFF-2

SF-1, SFF-1
RFH-1, RFHH-2,
TF, TFF, XF, XFF
RFHH-2, TF, TFF,
XF, XFF
XF, XFF
TFN, TFFN
PF, PFF, PGF,
PGFF, PAF, PTF,
PTFF, PAFF
ZF, ZFF, ZHF, HF,
HFF
KF-2, KFF-2

KF-1, KFF-1

XF, XFF

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

18
16
18
16
14
18
18

8
7
11
9
7
19
14

14
12
18
15
12
32
24

16

11

14
18
16
18
16
14
18
16
14
18
16
14
12
10
18
16
14
12
10
12
10

9
23
17
22
17
12
28
20
15
41
28
19
13
9
48
34
23
15
10
5
4

27
(1)

35
(114)

41
(112)

53
(2)

22
19
28
23
19
50
37

35
29
44
36
29
78
58

51
43
64
53
43
114
84

90
76
113
94
76
201
148

19

30

47

68

120

15
38
29
36
28
21
47
35
25
68
48
33
23
15
82
57
38
25
16
8
6

23
59
45
56
43
32
72
53
39
105
74
51
35
23
125
88
59
39
25
12
10

36
93
71
88
68
51
113
83
61
164
116
80
55
36
196
138
93
61
40
19
15

53
135
103
128
99
74
165
121
89
239
168
116
80
53
285
200
135
89
58
28
22

94
237
181
225
174
130
290
214
157
421
297
204
140
94
503
353
237
157
103
50
39

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.3(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*
Types RHH, RHW, and RHW-2 without outer covering.

1366

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.3(A) Maximum Number of Compact Conductors in Flexible Metal Conduit


(FMC) (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THHW,
THW-2

THHN,
THWN,
THWN-2

XHHW,
XHHW-2

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
5
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

6
5
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0

7
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
8
6
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0

10
7
5
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0

11
7
5
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0
13
9
7
5
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0

14
11
8
6
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0

16
10
7
5
4
4
3
2
1
1
1
1
1
1
1
1
1
0
19
14
10
7
5
4
4
3
2
1
1
1
1
1
1
1
1
1
1

25
20
15
11
7
6
5
4
4
3
2
2
1
1
1
1
1
1
1

29
18
13
9
8
6
5
4
3
3
3
2
1
1
1
1
1
1
33
24
18
13
9
8
7
5
4
4
3
3
2
1
1
1
1
1
1

38
29
22
16
11
10
8
7
6
4
4
3
3
3
1
1
1
1
1

43
27
19
14
12
10
8
7
5
5
4
3
3
2
1
1
1
1
50
37
27
19
14
12
10
8
7
5
5
4
4
3
2
1
1
2
1

55
43
32
23
16
14
12
10
8
7
6
5
5
4
3
3
2
2
1

62
38
28
21
17
14
12
10
8
7
6
5
4
3
3
3
2
1
71
53
38
28
21
17
15
12
10
8
7
6
5
4
3
3
3
2
2

75
58
43
32
22
19
16
14
11
9
8
7
6
5
4
4
3
3
3

85
52
38
28
24
20
17
14
11
9
8
7
6
5
4
4
3
3
97
72
52
38
28
24
20
17
14
11
9
8
7
6
5
4
4
3
3

98
76
57
42
29
25
21
18
15
12
10
9
8
7
6
5
5
4
4

111
69
49
37
31
26
22
18
14
12
10
9
8
6
6
5
4
4
127
95
69
49
37
31
26
22
18
14
12
11
10
8
6
6
5
4
4

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

National Electrical Code Handbook

2011

1367

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.4 Maximum Number of Conductors or Fixture Wires in Intermediate Metal


Conduit (IMC) (Based on Table 1, Chapter 9)
CONDUCTORS

Type
RHH, RHW,
RHW-2
RHH, RHW,
RHW-2

TW

RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*,
THHW, THW
RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*, TW,
THHW, THW,
THW-2

1368

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
14

4
4
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
10
7
5
3
6

8
6
5
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
17
13
9
5
11

13
11
8
4
3
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
27
21
15
8
18

22
18
15
8
6
5
4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
47
36
27
15
31

30
25
20
10
8
6
6
5
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
64
49
36
20
42

49
41
33
17
14
11
9
8
5
4
4
3
3
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
104
80
59
33
69

70
58
47
24
19
15
13
11
7
6
6
5
4
3
3
2
2
1
1
1
1
1
1
1
1
1
1
1
147
113
84
47
98

108
89
72
38
30
23
21
18
12
10
9
7
6
5
4
4
3
3
2
2
1
1
1
1
1
1
1
1
228
175
130
72
151

144
120
97
50
40
31
28
24
16
14
12
10
9
6
6
5
5
4
3
3
3
3
2
2
1
1
1
1
304
234
174
97
202

186
154
124
65
52
41
36
31
20
18
15
13
11
8
7
7
6
5
4
4
4
3
3
3
2
1
1
1
392
301
224
124
261

12

14

25

34

56

79

122

163

209

10

11

19

26

43

61

95

127

163

12

16

26

37

57

76

98

12

20

28

43

58

75

15

21

32

43

56

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.4 Continued


CONDUCTORS

Type
RHH*, RHW*,
RHW-2*, TW,
THW, THHW,
THW-2

THHN,
THWN,
THWN-2

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

3
2
1
1/0
2/0
3/0
4/0

1
1
1
1
0
0
0

1
1
1
1
1
1
1

3
3
1
1
1
1
1

6
5
3
3
2
1
1

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

1
1
1
0
0

600
700
750
800
900

0
0
0
0
0

0
0
0
0
0

1000
1250
1500
1750
2000

0
0
0
0
0

14
12
10
8
6

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

8
6
4
4
3
3
2

13
11
7
6
5
4
4

18
15
11
9
8
6
5

28
23
16
14
12
10
8

37
31
22
19
16
13
11

48
41
28
24
20
17
14

1
1
1
1
1

1
1
1
1
1

3
2
2
1
1

4
4
3
3
2

7
6
5
4
4

9
8
7
6
5

12
10
9
8
7

0
0
0
0
0

1
0
0
0
0

1
1
1
1
1

1
1
1
1
1

1
1
1
1
1

3
3
2
2
2

4
4
3
3
3

5
5
4
4
4

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

0
0
0
0
0

1
1
1
0
0

1
1
1
1
1

1
1
1
1
1

3
1
1
1
1

3
3
2
1
1

14
10
6
3
2

24
17
11
6
4

39
29
18
10
7

68
49
31
18
13

91
67
42
24
17

149
109
68
39
28

211
154
97
56
40

326
238
150
86
62

436
318
200
115
83

562
410
258
149
107

4
3
2
1

1
1
1
1

3
2
1
1

4
4
3
2

8
6
5
4

10
9
7
5

17
15
12
9

25
21
17
13

38
32
27
20

51
43
36
27

66
56
47
35

1/0
2/0
3/0
4/0

1
1
0
0

1
1
1
1

1
1
1
1

3
3
2
1

4
4
3
2

8
6
5
4

11
9
7
6

17
14
12
9

23
19
16
13

29
24
20
17

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

1
1
1
1
0

1
1
1
1
1

1
1
1
1
1

3
3
2
2
1

5
4
4
3
3

8
7
6
5
4

10
9
8
7
6

13
12
10
9
7

600
700
750
800
900
1000

0
0
0
0
0
0

0
0
0
0
0
0

0
0
0
0
0
0

1
1
1
0
0
0

1
1
1
1
1
1

1
1
1
1
1
1

2
1
1
1
1
1

3
3
3
3
2
2

5
4
4
4
3
3

6
5
5
5
4
4

(Continues)

National Electrical Code Handbook

2011

1369

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.4 Continued


CONDUCTORS

Type
FEP, FEPB,
PFA, PFAH,
TFE

PFA, PFAH,
TFE
PFA, PFAH,
TFE, Z

XHH, XHHW,
XHHW-2, ZW

XHH, XHHW,
XHHW-2

1370

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

14
12
10
8
6
4
3
2
1

13
10
7
4
3
1
1
1
1

23
17
12
7
5
3
3
2
1

38
28
20
11
8
5
4
4
2

66
48
34
19
14
10
8
6
4

89
65
46
26
19
13
11
9
6

145
106
76
43
31
21
18
15
10

205
150
107
61
44
30
25
21
14

317
231
166
95
67
47
39
32
22

423
309
221
127
90
63
52
43
30

545
398
285
163
116
81
68
56
39

1/0
2/0
3/0
4/0
14
12
10
8
6
4
3
2
1
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

1
1
0
0
16
11
7
4
3
1
1
1
1
10
7
5
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
28
20
12
7
5
3
2
1
1
17
13
9
5
4
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
46
32
20
12
9
6
4
3
3
27
21
15
8
6
4
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
79
56
34
21
15
10
7
6
5
47
36
27
15
11
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0

5
4
3
3
107
76
46
29
20
14
10
8
7
64
49
36
20
15
11
9
7
5
5
4
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0

8
7
6
5
175
124
76
48
33
23
17
14
11
104
80
59
33
24
18
15
12
9
8
6
5
4
3
3
3
2
1
1
1
1
1
1
1
1
1
1
0

12
10
8
7
247
175
107
68
47
33
24
20
16
147
113
84
47
35
25
21
18
13
11
9
7
6
5
4
4
3
3
2
1
1
1
1
1
1
1
1
1

19
15
13
10
381
271
166
105
73
50
37
30
25
228
175
130
72
53
39
33
27
20
17
14
12
10
8
7
6
5
4
3
3
3
3
2
2
1
1
1
1

25
21
17
14
510
362
221
140
98
67
49
41
33
304
234
174
97
71
52
44
37
27
23
19
16
13
11
9
8
7
6
5
4
4
4
3
3
2
1
1
1

32
27
22
18
657
466
285
180
127
87
63
53
43
392
301
224
124
92
67
56
47
35
30
25
20
17
14
12
10
9
8
6
5
5
5
4
4
3
2
2
1

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.4 Continued


FIXTURE WIRES

Type
FHH-2, RFH-2,
RFHH-3
SF-2, SFF-2

SF-1, SFF-1
RFH-1, RFHH-2,
TF, TFF, XF, XFF
RFH-2, TF, TFF,
XF, XFF
XF, XFF
TFN, TFFN
PF, PFF, PGF,
PGFF, PAF, PTF,
PTFF, PAFF
ZF, ZFF, ZHF, HF,
HFF
KF-2, KFF-2

KF-1, KFF-1

XF, XFF

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

18
16
18
16
14
18
18

9
8
12
10
8
21
15

16
13
20
17
13
36
26

26
22
33
27
22
59
43

45
38
57
47
38
101
75

61
51
77
64
51
137
101

100
84
126
104
84
223
165

16

12

21

35

60

81

133

14
18
16
18
16
14
18
16
14

10
25
19
23
18
13
30
22
16

17
42
32
40
31
23
52
38
28

27
69
53
66
51
38
85
63
46

47
119
91
113
87
66
146
108
79

64
161
123
153
118
89
197
145
107

104
264
201
250
193
145
322
238
175

18
16
14
12
10
18
16
14
12
10
12
10

44
31
21
14
10
52
37
25
16
10
5
4

75
53
36
25
17
90
63
42
28
18
9
7

123
87
60
41
27
147
103
69
46
30
14
11

212
149
103
70
47
253
178
119
79
52
25
19

287
202
139
95
64
342
240
161
107
70
34
26

468
330
227
156
104
558
392
264
175
114
56
43

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.4(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*
Types RHH, RHW, and RHW-2 without outer covering.

National Electrical Code Handbook

2011

1371

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.4(A) Maximum Number of Compact Conductors in Intermediate Metal Conduit


(IMC) (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN,
THWN,
THWN-2

XHHW,
XHHW-2

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

5
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
6
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

7
6
4
3
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0

8
5
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
9
7
5
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0

13
10
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0

14
9
6
5
4
3
3
2
1
1
1
1
1
1
1
1
0
0
16
12
9
6
5
4
3
3
2
1
1
1
1
1
1
1
1
0
0

17
13
10
7
5
4
4
3
2
1
1
1
1
1
1
1
1
1
1

19
12
8
6
5
4
4
3
2
1
1
1
1
1
1
1
1
1
22
16
12
8
6
5
4
4
3
2
1
1
1
1
1
1
1
1
1

28
22
16
12
8
7
6
5
4
3
3
2
2
1
1
1
1
1
1

32
20
14
10
9
7
6
5
4
3
3
2
2
1
1
1
1
1
37
27
20
14
10
9
7
6
5
4
3
3
3
2
1
1
1
1
1

40
31
23
17
12
10
9
7
6
5
4
4
3
3
2
1
1
1
1

45
28
20
15
13
10
9
7
6
5
4
4
3
2
2
1
2
1
52
38
28
20
15
13
11
9
7
6
5
4
4
3
2
2
1
2
1

62
48
36
26
18
16
13
11
9
7
6
6
5
4
3
3
3
2
2

70
43
31
23
20
16
14
11
9
7
7
6
5
4
3
3
3
2
80
59
43
31
23
20
17
14
11
9
8
7
6
5
4
3
3
3
2

83
64
48
35
25
21
18
15
13
10
9
8
7
6
5
4
4
3
3

93
58
41
31
26
22
18
15
12
10
9
8
7
5
5
4
3
3
107
80
58
41
31
26
22
18
15
12
10
9
8
7
5
5
4
4
3

107
82
62
45
32
27
23
20
16
13
11
10
9
8
6
5
5
4
4

120
74
53
40
34
28
24
19
15
13
11
10
9
7
6
6
5
4
138
103
74
53
40
34
29
24
20
16
13
12
11
9
7
6
6
5
4

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that interstices (voids between strand wires) are virtually eliminated.

1372

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.5 Maximum Number of Conductors or Fixture Wires in Liquidtight Flexible


Nonmetallic Conduit (Type LFNC-B*) (Based on Table 1, Chapter 9)
CONDUCTORS

Type
RHH, RHW,
RHW-2

TW

RHH, RHW,
RHW-2 , THHW,
THW, THW-2
RHH , RHW ,
RHW-2 , THHW,
THW
RHH , RHW ,
RHW-2 , THHW,
THW, THW-2
RHH, RHW,
RHW-2, TW,
THW, THHW,
THW-2

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8

2
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5
4
3
1

4
3
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
9
7
5
3

7
6
5
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
15
12
9
5

12
10
8
4
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
25
19
14
8

21
17
14
7
6
4
4
3
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
44
33
25
14

27
22
18
9
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
57
43
32
18

844
36
29
15
12
9
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
93
71
53
29

14

10

16

29

38

62

12
10

3
1

5
3

8
6

13
10

23
18

30
23

50
39

11

14

23

11

18

13

11
(Continues)

National Electrical Code Handbook

2011

1373

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.5 Continued


CONDUCTORS

Type
RHH , RHW ,
RHW-2 , TW,
THW, THHW,
THW-2

THHN, THWN,
THWN-2

FEP, FEPB, PFA,


PFAH, TFE

1374

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
14
12
10
8
6

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
8
5
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
7
5
4
1
1

1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
13
9
6
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
12
9
6
3
2

1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
22
16
10
6
4
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
21
15
11
6
4

2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
36
26
16
9
7
4
3
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
35
25
18
10
7

4
3
2
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
63
46
29
16
12
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
61
44
32
18
13

6
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
81
59
37
21
15
9
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
79
57
41
23
17

9
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
133
97
61
35
25
15
13
11
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
129
94
68
39
27
2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.5 Continued


CONDUCTORS
Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

4
3
2

1
1
1

1
1
1

3
2
1

5
4
3

9
7
6

12
10
8

19
16
13

PFA, PFAH, TFE


PFA, PFAH
TFE, Z

1
1/0
2/0
3/0
4/0

0
0
0
0
0

1
1
1
0
0

1
1
1
1
1

2
1
1
1
1

4
3
3
2
1

5
4
4
3
2

9
7
6
5
4

14
12
10
8
6
4
3
2
1

9
6
4
2
1
1
1
0
0

15
10
6
4
3
1
1
1
1

26
18
11
7
5
3
2
1
1

42
30
18
11
8
5
4
3
2

73
52
32
20
14
9
7
6
5

95
67
41
26
18
12
9
7
6

156
111
68
43
30
20
15
12
10

XHH, XHHW,
XHHW-2, ZW

14
12
10
8
6
4
3
2

5
4
3
1
1
1
1
1

9
7
5
3
1
1
1
1

15
12
9
5
3
2
1
1

25
19
14
8
6
4
3
3

44
33
25
14
10
7
6
5

57
43
32
18
13
9
8
7

93
71
53
29
22
16
13
11

XHH, XHHW,
XHHW-2

1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0

5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0

8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0

Type

(Continues)

National Electrical Code Handbook

2011

1375

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.5 Continued


FIXTURE WIRES

Type
FFH-2, RFH-2
SF-2, SFF-2

SF-1, SFF-1
RFH-1, RFHH-2,
TF, TFF, XF, XFF
RFHH-2, TF, TFF,
XF, XFF
XF, XFF
TFN, TFFN
PF, PFF, PGF,
PGFF, PAF, PTF,
PTFF, PAFF
HF, HFF, ZF, ZFF,
ZHF
KF-2, KFF-2

KF-1, KFF-1

XF, XFF

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

18
16
18
16
14
18
18

5
4
6
5
4
11
8

8
7
11
9
7
19
14

15
12
19
15
12
33
24

24
20
30
25
20
53
39

42
35
53
44
35
94
69

54
46
69
57
46
122
90

89
75
113
93
75
199
147

16

11

20

32

56

72

119

14
18
16
18
16
14
18
16
14
18
16
14
12
10
18
16
14
12
10
12
10

5
14
10
13
10
7
17
12
9
24
17
12
8
5
29
20
14
9
6
3
1

9
23
17
21
16
12
28
20
15
40
28
19
13
9
48
34
23
15
10
5
3

15
39
30
37
29
21
48
35
26
70
49
34
23
15
83
58
39
26
17
8
6

25
63
48
60
46
35
77
57
42
112
79
54
37
25
134
94
63
42
27
13
10

44
111
85
105
81
61
136
100
73
197
139
95
65
44
235
165
111
73
48
23
18

57
144
110
136
105
79
176
129
95
255
180
123
85
57
304
214
144
95
62
30
23

93
236
180
223
173
129
288
212
156
418
295
202
139
93
499
350
236
156
102
50
39

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.5(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*
Corresponds to 356.2(2).

Types RHH, RHW, and RHW-2 without outer covering.

1376

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.5(A) Maximum Number of Compact Conductors in Liquidtight Flexible


Nonmetallic Conduit (Type LFNC-B*) (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN, THWN,
THWN-2

XHHW, XHHW-2

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
5
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

7
5
4
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0

7
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
9
6
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0

12
9
7
5
3
3
2
1
1
1
1
1
1
1
1
1
0
0
0

13
8
6
4
4
3
2
1
1
1
1
1
1
1
1
1
0
0
15
11
8
6
4
4
3
2
1
1
1
1
1
1
1
1
1
0
0

15
12
9
6
4
4
3
3
2
1
1
1
1
1
1
1
1
1
1

17
11
7
6
5
4
3
3
1
1
1
1
1
1
1
1
1
1
20
15
11
7
6
5
4
3
3
1
1
1
1
1
1
1
1
1
1

25
19
14
11
7
6
5
4
4
3
2
2
1
1
1
1
1
1
1

28
17
12
9
8
6
5
4
3
3
2
2
1
1
1
1
1
1
33
24
17
12
9
8
7
5
4
3
3
3
2
1
1
1
1
1
1

Corresponds to 356.2(2).
Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

National Electrical Code Handbook

2011

1377

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.6 Maximum Number of Conductors or Fixture Wires in Liquidtight Flexible


Nonmetallic Conduit (Type LFNC-A*) (Based on Table 1, Chapter 9)
CONDUCTORS

Type
RHH, RHW,
RHW-2

TW

RHH, RHW,
RHW-2, THHW,
THW, THW-2
RHH , RHW ,
RHW-2 , THHW,
THW
RHH , RHW ,
RHW-2 , THHW,
THW, THW-2
RHH, RHW,
RHW-2, TW, THW,
THHW, THW-2

1378

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
14

2
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
5
4
3
1
3

4
3
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
9
7
5
3
6

7
6
5
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
15
12
9
5
10

11
9
8
4
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
24
19
14
8
16

20
17
13
7
5
4
4
3
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
43
33
24
13
28

27
23
18
9
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
58
44
33
18
38

45
38
30
16
13
10
8
7
5
4
4
3
3
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
96
74
55
30
64

12
10

3
1

4
3

8
6

13
10

23
18

31
24

51
40

10

14

24

6
4
3
2
1
1/0
2/0
3/0
4/0

1
1
1
0
0
0
0
0
0

1
1
1
1
1
0
0
0
0

3
1
1
1
1
1
1
1
0

4
3
3
2
1
1
1
1
1

8
6
5
4
3
2
1
1
1

11
8
7
6
4
3
3
2
1

18
13
11
10
7
6
5
4
3

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.6 Continued


CONDUCTORS

Type

THHN, THWN,
THWN-2

FEP, FEPB, PFA,


PFAH, TFE

PFA, PFAH, TFE

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
14
12
10
8
6
4
3
2

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
8
5
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
7
5
4
1
1
1
1
1

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
13
9
6
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
12
9
6
3
2
1
1
1

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
22
16
10
6
4
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
21
15
11
6
4
3
2
1

1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
35
25
16
9
6
4
3
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
34
25
18
10
7
5
4
3

1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
62
45
28
16
12
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
60
44
31
18
13
9
7
6

1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
83
60
38
22
16
9
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
80
59
42
24
17
12
10
8

3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
137
100
63
36
26
16
13
11
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
133
97
70
40
28
20
16
13

9
(Continues)

National Electrical Code Handbook

2011

1379

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.6 Continued


CONDUCTORS

Type

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

PFA, PFAH, TFE, Z

1/0
2/0
3/0
4/0

0
0
0
0

1
1
0
0

1
1
1
1

1
1
1
1

3
3
2
1

5
4
3
2

8
6
5
4

14
12
10
8
6
4
3
2
1

9
6
4
2
1
1
1
1
1

15
10
6
4
3
1
1
1
1

25
18
11
7
5
3
2
1
1

41
29
18
11
8
5
4
3
2

72
51
31
20
14
9
7
6
4

97
69
42
26
18
13
9
8
6

161
114
70
44
31
21
15
13
10

XHH, XHHW,
XHHW-2, ZW

14
12
10
8
6
4
3
2

5
4
3
1
1
1
1
1

9
7
5
3
1
1
1
1

15
12
9
5
3
2
1
1

24
19
14
8
5
4
3
3

43
33
24
13
10
7
6
5

58
44
33
18
13
10
8
7

96
74
55
30
22
16
14
11

XHH, XHHW,
XHHW-2

1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0

5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0

8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0

1380

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.6 Continued


FIXTURE WIRES

Type
FFH-2, RFH-2,
RFHH-3
SF-2, SFF-2

SF-1, SFF-1
RFH-1, RFHH-2,
TF, TFF, XF, XFF
RFHH-2, TF, TFF,
XF, XFF
XF, XFF
TFN, TFFN
PF, PFF, PGF,
PGFF, PAF, PTF,
PTFF, PAFF
HF, HFF, ZF, ZFF,
ZHF
KF-2, KFF-2

KF-1, KFF-1

XF, XFF

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(114)

53
(2)

18
16
18
16
14
18
18

5
4
6
5
4
12
8

8
7
11
9
7
19
14

14
12
18
15
12
33
24

23
20
29
24
20
52
39

41
35
52
43
35
92
68

55
47
70
58
47
124
91

92
77
116
96
77
205
152

16

11

19

31

55

74

122

14
18
16
18
16
14
18
16
14
18
16
14
12
10
18
16
14
12
10
12
10

5
14
10
13
10
7
17
12
9
25
17
12
8
5
29
21
14
9
6
3
1

9
22
17
21
16
12
27
20
15
40
28
19
13
9
48
33
22
15
10
4
3

15
39
29
37
28
21
47
35
25
69
48
33
23
15
82
57
39
25
17
8
6

24
62
47
59
45
34
76
56
41
110
77
53
36
24
131
92
62
41
27
13
10

43
109
83
103
80
60
133
98
72
193
136
94
64
43
231
162
109
72
47
23
18

58
146
112
139
107
80
179
132
97
260
183
126
86
58
310
218
146
97
63
31
24

96
243
185
230
178
133
297
219
161
431
303
209
143
96
514
361
243
161
105
51
40

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.6(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*
Corresponds to 356.2(1).

Types RHH, RHW, and RHW-2 without outer covering.

National Electrical Code Handbook

2011

1381

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.6(A) Maximum Number of Compact Conductors in Liquidtight Flexible


Nonmetallic Conduit (Type LFNC-A*) (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN, THWN,
THWN-2

XHHW, XHHW-2

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

12
(38)

16
(12)

21
(34)

27
(1)

35
(114)

41
(114)

53
(2)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
5
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

6
5
4
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0

7
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
8
6
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0

11
9
7
5
3
3
2
1
1
1
1
1
1
1
1
1
0
0
0

13
8
6
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0
15
11
8
6
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0

16
12
9
6
4
4
3
3
2
1
1
1
1
1
1
1
1
1
1

18
11
8
6
5
4
3
3
1
1
1
1
1
1
1
1
1
1
20
15
11
8
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1

26
20
15
11
8
7
5
5
4
3
3
2
1
1
1
1
1
1
1

29
18
13
10
8
7
6
5
3
3
3
2
1
1
1
1
1
1
34
25
18
13
10
8
7
6
5
4
3
3
2
1
1
1
1
1
1

Corresponds to 356.2(1).
Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

1382

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.7 Maximum Number of Conductors or Fixture Wires in Liquidtight Flexible


Metal Conduit (LFMC) (Based on Table 1, Chapter 9)
CONDUCTORS

Type
RHH, RHW,
RHW-2

TW

RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*,
THHW, THW
RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*, TW,
THW, THHW,
THW-2

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
14

4
3
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
9
7
5
3
6

7
6
5
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
15
12
9
5
10

12
10
8
4
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
25
19
14
8
16

21
17
14
7
6
4
4
3
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
44
33
25
14
29

27
22
18
9
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
57
43
32
18
38

44
36
29
15
12
9
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
93
71
53
29
62

66
55
44
23
18
14
13
11
7
6
5
4
4
3
2
2
1
1
1
1
1
1
1
1
1
1
1
0
140
108
80
44
93

102
84
68
36
28
22
19
17
11
10
8
7
6
4
4
3
3
3
2
1
1
1
1
1
1
1
1
1
215
165
123
68
143

133
110
89
46
37
29
25
22
14
13
11
9
8
6
5
5
4
4
3
3
2
2
2
1
1
1
1
1
280
215
160
89
186

173
144
116
61
48
38
33
29
19
16
14
12
10
8
7
6
6
5
4
3
3
3
3
3
1
1
1
1
365
280
209
116
243

12

13

23

30

50

75

115

149

195

10

10

18

23

39

58

89

117

152

11

14

23

35

53

70

91

6
4
3
2
1

1
1
1
1
1

3
1
1
1
1

5
3
3
2
1

8
6
5
4
3

11
8
7
6
4

18
13
11
9
7

27
20
17
14
10

41
30
26
22
15

53
40
34
29
20

70
52
44
38
26

(Continues)

National Electrical Code Handbook

2011

1383

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.7 Continued


CONDUCTORS

Type

THHN,
THWN,
THWN-2

FEP, FEPB,
PFA, PFAH,
TFE

1384

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

1/0
2/0
3/0
4/0

0
0
0
0

1
1
1
0

1
1
1
1

2
2
1
1

250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
13
9
6
3
2
1
1
1
1
1
0
0
0

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
22
16
10
6
4
2
1
1
1
1
1
1
1

1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
36
26
16
9
7
4
3
3
1
1
1
1
1

250
300
350
400
500

0
0
0
0
0

0
0
0
0
0

600
700
750
800
900
1000
14
12
10
8
6

0
0
0
0
0
0
12
9
6
3
2

0
0
0
0
0
0
21
15
11
6
4

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

3
3
2
1

6
5
4
3

8
7
6
5

13
11
9
8

17
15
12
10

23
19
16
13

1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
63
46
29
16
12
7
6
5
4
3
2
1
1

1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
81
59
37
21
15
9
8
7
5
4
3
3
2

3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
133
97
61
35
25
15
13
11
8
7
6
5
4

4
3
3
3
2
1
1
1
1
1
1
1
1
1
1
201
146
92
53
38
23
20
17
12
10
8
7
6

6
5
5
4
3
3
2
2
2
1
1
1
1
1
1
308
225
141
81
59
36
30
26
19
16
13
11
9

8
7
6
6
5
4
3
3
3
3
2
1
1
1
1
401
292
184
106
76
47
40
33
25
21
17
14
12

11
9
8
7
6
5
4
4
4
3
3
2
2
1
1
523
381
240
138
100
61
52
44
32
27
23
19
15

1
1
1
0
0

1
1
1
1
1

1
1
1
1
1

3
3
2
1
1

5
4
3
3
2

7
6
5
5
4

10
8
7
6
5

12
11
9
8
7

0
0
0
0
0
0
35
25
18
10
7

1
1
0
0
0
0
61
44
32
18
13

1
1
1
1
1
0
79
57
41
23
17

1
1
1
1
1
1
129
94
68
39
27

1
1
1
1
1
1
195
142
102
58
41

3
3
3
2
2
1
299
218
156
89
64

4
4
3
3
3
3
389
284
203
117
83

6
5
5
4
4
3
507
370
266
152
108

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.7 Continued


CONDUCTORS

Type

PFA, PFAH,
TFE
PFA, PFAH,
TFE, Z

XHH, XHHW,
XHHW-2, ZW

XHH, XHHW,
XHHW-2

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

4
3
2
1

1
1
1
1

3
2
1
1

5
4
3
2

1/0
2/0
3/0
4/0
14
12
10
8
6
4
3
2
1
14
12
10
8
6

1
1
0
0
20
14
8
5
4
2
2
1
1
9
7
5
3
1

1
1
1
1
26
18
11
7
5
3
2
1
1
15
12
9
5
3

4
3
2

1
1
1

1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

9
7
6
4

12
10
8
5

19
16
13
9

29
24
20
14

44
37
30
21

58
48
40
28

75
63
52
36

1
1
1
1
42
30
18
11
8
5
4
3
2
25
19
14
8
6

3
3
2
1
73
52
32
20
14
9
7
6
5
44
33
25
14
10

4
4
3
2
95
67
41
26
18
12
9
7
6
57
43
32
18
13

7
6
5
4
156
111
68
43
30
20
15
12
10
93
71
53
29
22

11
9
8
6
235
167
102
64
45
31
23
19
15
140
108
80
44
33

18
14
12
10
360
255
156
99
69
48
35
29
23
215
165
123
68
50

23
19
16
13
469
332
203
129
90
62
45
38
30
280
215
160
89
66

30
25
20
17
611
434
266
168
118
81
59
49
40
365
280
209
116
86

2
1
1

4
3
3

7
6
5

9
8
7

16
13
11

24
20
17

36
31
26

48
40
34

62
52
44

1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0

5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0

8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0

12
10
9
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1

19
16
13
11
9
7
6
5
5
4
3
3
3
2
2
1
1
1
1
1

25
21
17
14
12
10
8
7
6
5
4
4
3
3
3
3
1
1
1
1

33
28
23
19
16
13
11
10
8
7
6
5
5
4
4
3
3
2
2
2

(Continues)

National Electrical Code Handbook

2011

1385

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.7 Continued


FIXTURE WIRES

Type
FFH-2, RFH-2,
RFHH-3
SF-2, SFF-2

SF-1, SFF-1
RFH-1, RFHH-2,
TF, TFF, XF, XFF
RFHH-2, TF, TFF,
XF, XFF
XF, XFF
TFN, TFFN
PF, PFF, PGF,
PGFF, PAF, PTF,
PTFF, PAFF
HF, HFF, ZF, ZFF,
ZHF
KF-2, KFF-2

KF-1, KFF-1

XF, XFF

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

18
16
18
16
14
18
18

8
7
11
9
7
19
14

15
12
19
15
12
33
24

24
20
30
25
20
53
39

42
35
53
44
35
94
69

54
46
69
57
46
122
90

89
75
113
93
75
199
147

16

11

20

32

56

72

119

14
18
16
18
16
14
18
16
14
18
16
14
12
10
18
16
14
12
10
12
10

9
23
17
21
16
12
28
20
15
40
28
19
13
9
48
34
23
15
10
5
3

15
39
30
37
29
21
48
35
26
70
49
34
23
15
83
58
39
26
17
8
6

25
63
48
60
46
35
77
57
42
112
79
54
37
25
134
94
63
42
27
13
10

44
111
85
105
81
61
136
100
73
197
139
95
65
44
235
165
111
73
48
23
18

57
144
110
136
105
79
176
129
95
255
180
123
85
57
304
214
144
95
62
30
23

93
236
180
223
173
129
288
212
156
418
295
202
139
93
499
350
236
156
102
50
39

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.7(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*
Types RHH, RHW, and RHW-2 without outer covering.

1386

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.7(A) Maximum Number of Compact Conductors in Liquidtight Flexible Metal


Conduit (LFMC) (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN,
THWN,
THWN-2

XHHW,
XHHW-2

Conductor
Size (AWG/
kcmil)
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

Metric Designator (Trade Size)


12 16 21
(38) (12) (34)

27
(1)

1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

7
5
4
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0

7
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
9
6
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
5
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

35
41
(114) (112)
12
9
7
5
3
3
2
1
1
1
1
1
1
1
1
1
0
0
0

13
8
6
4
4
3
2
1
1
1
1
1
1
1
1
1
0
0
15
11
8
6
4
4
3
2
1
1
1
1
1
1
1
1
1
0
0

15
12
9
6
4
4
3
3
2
1
1
1
1
1
1
1
1
1
1

17
11
7
6
5
4
3
3
1
1
1
1
1
1
1
1
1
1
20
15
11
7
6
5
4
3
3
1
1
1
1
1
1
1
1
1
1

53
(2)

63
(212)

78
(3)

25
19
14
11
7
6
5
4
4
3
2
2
1
1
1
1
1
1
1

28
17
12
9
8
6
5
4
3
3
2
2
1
1
1
1
1
1
33
24
17
12
9
8
7
5
4
3
3
3
2
1
1
1
1
1
1

38
29
22
16
11
10
8
7
6
4
4
3
3
3
1
1
1
1
1

43
26
19
14
12
10
8
7
5
4
4
3
3
2
1
1
1
1
49
37
26
19
14
12
10
8
7
5
5
4
4
3
2
1
1
2
1

58
45
34
25
17
15
13
11
9
7
6
5
5
4
3
3
3
2
1

66
41
29
22
19
15
13
10
8
7
6
5
5
4
3
3
2
2
76
56
41
29
22
19
16
13
11
8
7
6
6
5
4
3
3
2
2

91 103
(312) (4)
76
59
44
32
23
20
16
14
12
9
8
7
6
5
4
4
3
3
3

86
53
38
28
24
20
17
14
11
9
8
7
6
5
4
4
3
3
98
73
53
38
28
24
20
17
14
11
9
8
7
6
5
4
4
3
3

99
77
57
42
30
26
21
18
15
12
10
9
8
7
6
5
5
4
4

112
69
50
37
32
26
22
18
14
12
11
9
8
6
6
5
4
4
129
95
69
50
37
32
27
22
18
15
12
11
10
8
6
6
5
4
4

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

National Electrical Code Handbook

2011

1387

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.8 Maximum Number of Conductors or Fixture Wires in Rigid Metal Conduit
(RMC) (Based on Table 1, Chapter 9)
CONDUCTORS

Type
RHH, RHW,
RHW-2

TW

RHH*, RHW*,
RHW-2*
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*,
THHW, THW
RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*, TW,
THW, THHW,
THW-2

1388

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)

Metric Designator (Trade Size)


35
41
(114) (112)

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)

155
(6)

276
229
185
97
77
60
53
46
30
26
23
20
17
13
11
10
9
8
6
6
5
5
5
4
3
3
2
2
581
446
332
185
387

398
330
267
139
112
87
76
66
44
38
33
28
24
18
16
15
13
11
9
8
8
7
7
6
5
4
4
3
839
644
480
267
558

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
14

4
3
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
9
7
5
3
6

7
6
5
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
15
12
9
5
10

12
10
8
4
3
2
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
25
19
14
8
17

21
17
14
7
6
4
4
3
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
44
33
25
14
29

28
23
19
10
8
6
5
4
3
2
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
59
45
34
19
39

46 66
38 55
31 44
16 23
13 18
10 14
9 12
7 11
5
7
4
6
4
5
3
4
3
4
1
3
1
2
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
0
1
0
1
0
0
98 140
75 107
56 80
31 44
65 93

102
85
68
36
29
22
19
17
11
10
8
7
6
4
4
4
3
3
2
1
1
1
1
1
1
1
1
1
216
165
123
68
143

136
113
91
48
38
30
26
23
15
13
11
10
8
6
5
5
4
4
3
3
3
2
2
1
1
1
1
1
288
221
164
91
191

176
146
118
61
49
38
34
29
19
17
14
12
11
8
7
6
6
5
4
4
3
3
3
3
1
1
1
1
370
284
212
118
246

12

13

23

32

52

75

115 154

198 311

448

10

10

18

25

41

58

90 120

154 242

350

11

15

24

35

54

72

92 145

209

6
4
3
2
1

1
1
1
1
1

3
1
1
1
1

5
3
3
2
1

8
6
5
4
3

11
8
7
6
4

18
14
12
10
7

27
20
17
14
10

41
31
26
22
15

55
41
35
30
21

71 111
53 83
45 71
38 60
27 42

160
120
103
87
61

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.8 Continued


CONDUCTORS

Type

THHN, THWN,
THWN-2

FEP, FEPB,
PFA, PFAH,
TFE

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
14
12
10
8
6
4
3
2

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
13
9
6
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
12
9
6
3
2
1
1
1

1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
22
16
10
6
4
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
22
16
11
6
4
3
2
1

1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
36
26
17
9
7
4
3
3
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
35
26
18
10
7
5
4
3

Metric Designator (Trade Size)


35
41
(114) (112)
2
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
63
46
29
16
12
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
61
44
32
18
13
9
7
6

3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
85
62
39
22
16
10
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
83
60
43
25
17
12
10
8

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
140
102
64
37
27
16
14
11
8
7
6
5
4
3
3
2
2
1
1
1
1
1
1
1
136
99
71
41
29
20
17
14

8
7
6
5
4
3
3
3
2
1
1
1
1
1
1
1
1
1
1
200
146
92
53
38
23
20
17
12
10
8
7
6
5
4
3
3
2
1
1
1
1
1
1
194
142
102
58
41
29
24
20

13
11
9
8
6
5
5
4
3
3
2
2
2
1
1
1
1
1
1
309
225
142
82
59
36
31
26
19
16
13
11
9
7
6
5
5
4
3
3
3
2
2
1
300
219
157
90
64
44
37
31

18
15
13
10
8
7
6
6
5
4
3
3
3
3
2
1
1
1
1
412
301
189
109
79
48
41
34
25
21
18
15
12
10
8
7
7
5
4
4
4
3
3
3
400
292
209
120
85
59
50
41

23
19
16
14
11
9
8
7
6
5
4
4
4
4
3
2
2
1
1
531
387
244
140
101
62
53
44
33
27
23
19
16
13
11
10
8
7
6
5
5
4
4
4
515
376
269
154
110
77
64
53

155
(6)

36
52
31
44
26
37
21
31
17
25
15
22
13
19
12
17
10
14
8
12
7
10
7
10
6
9
6
8
5
8
4
6
3
5
3
4
3
4
833 1202
608 877
383 552
221 318
159 230
98 141
83 120
70 100
51
74
43
63
36
52
30
43
25
36
20
29
17
25
15
22
13
20
11
16
9
13
8
11
7
11
7
10
6
9
6
8
808 1166
590 851
423 610
242 350
172 249
120 174
100 145
83 120
(Continues)

National Electrical Code Handbook

2011

1389

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.8 Continued


CONDUCTORS

Type
PFA, PFAH,
TFE
PFA, PFAH,
TFE, Z

XHH, XHHW,
XHHW-2, ZW

XHH, XHHW,
XHHW-2

1390

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)

Metric Designator (Trade Size)


35
41
(114) (112)

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)

14

21

28

37

1/0
2/0
3/0
4/0
14
12
10
8
6
4
3
2
1
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

1
1
0
0
15
10
6
4
3
1
1
1
1
9
7
5
3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
26
18
11
7
5
3
2
1
1
15
12
9
5
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
42
30
18
11
8
5
4
3
2
25
19
14
8
6
4
3
3
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0

3
3
2
1
73
52
32
20
14
9
7
6
5
44
33
25
14
10
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0

5
4
3
2
100
71
43
27
19
13
9
8
6
59
45
34
19
14
10
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0

8
6
5
4
164
116
71
45
31
22
16
13
10
98
75
56
31
23
16
14
12
9
7
6
5
4
3
3
2
2
1
1
1
1
1
1
1
1
1
0
0

11
9
8
6
234
166
102
64
45
31
22
19
15
140
107
80
44
33
24
20
17
12
10
9
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1

18
14
12
10
361
256
157
99
69
48
35
29
23
216
165
123
68
51
37
31
26
19
16
13
11
9
7
6
6
5
4
3
3
3
2
2
1
1
1
1
1

24
19
16
13
482
342
209
132
93
64
47
39
31
288
221
164
91
68
49
41
35
26
22
18
15
12
10
9
7
7
5
4
4
4
3
3
3
2
1
1
1

30
25
21
17
621
440
269
170
120
82
60
50
40
370
284
212
118
87
63
53
45
33
28
23
19
16
13
11
10
9
7
6
5
5
4
4
4
3
2
1
1

57

155
(6)
83

48
69
40
57
33
47
27
39
974 1405
691 997
423 610
267 386
188 271
129 186
94 136
78 113
63
92
581 839
446 644
332 480
185 267
137 197
99 143
84 121
70 101
52
76
44
64
37
53
30
44
25
36
20
30
18
25
15
22
14
20
11
16
9
13
8
11
7
11
7
10
6
9
6
8
4
6
4
5
3
5
3
4

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.8 Continued


FIXTURE WIRES

Type
FFH-2, RFH-2,
RFHH-3
SF-2, SFF-2

SF-1, SFF-1
RFH-1, RFHH-2,
TF, TFF, XF, XFF
RFHH-2, TF, TFF,
XF, XFF
XF, XFF
TFN, TFFN
PF, PFF, PGF,
PGFF, PAF, PTF,
PTFF, PAFF
HF, HFF, ZF, ZFF,
ZHF
KF-2, KFF-2

KF-1, KFF-1

XF, XFF

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

18
16
18
16
14
18
18

8
7
11
9
7
19
14

15
12
19
15
12
33
25

24
20
31
25
20
54
40

42
35
53
44
35
94
69

57
48
72
59
48
127
94

94
79
118
98
79
209
155

16

11

20

32

56

76

125

14
18
16
18
16
14
18
16
14
18
16
14
12
10
18
16
14
12
10
12
10

9
23
17
21
16
12
28
20
15
40
28
19
13
9
48
34
23
15
10
5
3

15
40
30
38
29
22
48
36
26
71
50
34
23
15
84
59
40
26
17
8
6

25
64
49
61
47
35
79
58
42
114
80
55
38
25
136
96
64
42
28
13
10

44
111
84
105
81
61
135
100
73
197
138
95
65
44
235
165
111
73
48
23
18

59
150
115
143
110
83
184
136
100
267
188
129
89
59
318
224
150
100
65
32
25

98
248
189
235
181
136
303
223
164
439
310
213
146
98
524
368
248
164
107
52
41

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.8(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*Types RHH, RHW, and RHW-2 without outer covering.

National Electrical Code Handbook

2011

1391

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.8(A) Maximum Number of Compact Conductors in Rigid Metal Conduit (RMC)
(Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN,
THWN,
THWN-2

XHHW,
XHHW-2

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

5
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
5
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

7
5
4
3
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0

8
5
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
9
6
5
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0

Metric Designator (Trade Size)


35
41
(114) (112)
12
9
7
5
3
3
2
1
1
1
1
1
1
1
1
1
0
0
0

13
8
6
4
4
3
2
1
1
1
1
1
1
1
1
1
0
0
15
11
8
6
4
4
3
2
1
1
1
1
1
1
1
1
1
0
0

16
12
9
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1

18
11
8
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
21
15
11
8
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)

155
(6)

26
20
15
11
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1

30
18
13
10
8
7
6
5
4
3
3
2
1
1
1
1
1
1
34
25
18
13
10
8
7
6
5
4
3
3
2
1
1
1
1
1
1

228
176
132
97
68
59
50
42
35
28
24
22
20
17
13
12
11
9
9

258
159
114
86
73
60
51
42
33
28
25
22
19
15
13
13
9
9
296
220
159
114
86
73
62
51
42
34
29
25
23
19
15
13
12
10
10

38
29
22
16
11
10
8
7
6
4
4
3
3
3
1
1
1
1
1

43
26
19
14
12
10
8
7
5
4
4
3
3
2
1
1
1
1
49
36
26
19
14
12
10
8
7
5
5
4
4
3
2
1
1
2
1

59
45
34
25
17
15
13
11
9
7
6
5
5
4
3
3
3
2
1

66
41
29
22
19
15
13
10
8
7
6
5
5
4
3
3
2
2
76
56
41
29
22
19
16
13
11
8
7
6
6
5
4
3
3
2
2

78
60
45
33
23
20
17
14
12
9
8
7
7
5
4
4
4
3
3

88
55
39
29
25
21
17
14
11
10
8
7
6
5
4
4
3
3
101
75
55
39
29
25
21
17
14
11
10
9
8
6
5
4
4
3
3

101
78
58
43
30
26
22
19
15
12
11
9
8
7
6
5
5
4
4

114
70
50
38
32
26
22
18
14
12
11
10
8
6
6
5
4
4
130
97
70
50
38
32
27
22
19
15
13
11
10
8
7
6
5
5
4

158
122
91
67
47
41
34
29
24
19
17
15
13
11
9
8
7
6
6

179
110
79
60
51
42
35
29
23
20
17
15
13
10
9
9
6
6
205
152
110
79
60
51
43
35
29
23
20
18
16
13
10
9
8
7
7

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

1392

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.9 Maximum Number of Conductors or Fixture Wires in Rigid PVC Conduit,
Schedule 80 (Based on Table 1, Chapter 9)
CONDUCTORS

Type
RHH, RHW,
RHW-2

TW

RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*,
THHW, THW
RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*, TW,
THW, THHW,
THW-2

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)

Metric Designator (Trade Size)


35
41
(114) (112)

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
1000
1250
1500
1750
2000
14
12
10
8
14

3
2
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
6
5
3
1
4

5
4
3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11
9
6
3
8

9
7
6
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
20
15
11
6
13

17
14
11
6
4
3
3
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
35
27
20
11
23

23
19
15
8
6
5
4
4
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
49
38
28
15
32

39 56
32 46
26 37
13 19
11 16
8 12
7 11
6
9
4
6
3
5
3
4
3
4
2
3
1
2
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
0
1
0
0
0
0
82 118
63 91
47 67
26 37
55 79

12

10

19

26

44

63

10

15

20

34

12

6
4
3
2
1

1
1
1
1
0

1
1
1
1
1

3
3
2
1
1

7
5
4
3
2

9
7
6
5
3

88
73
59
31
24
19
17
14
9
8
7
6
5
4
3
3
3
2
1
1
1
1
1
1
1
1
1
185
142
106
59
123

118
98
79
41
33
26
23
20
13
11
10
8
7
5
5
4
4
3
3
2
2
2
1
1
1
1
1
250
192
143
79
166

153
127
103
54
43
33
29
25
17
15
13
11
9
7
6
5
5
4
3
3
3
3
2
1
1
1
1
324
248
185
103
215

155
(6)

243
202
163
85
68
53
47
41
27
23
20
17
15
11
10
9
8
7
6
5
5
4
4
3
2
2
1
514
394
294
163
341

349
290
234
122
98
77
67
58
38
33
29
25
21
16
14
13
12
10
8
7
7
7
5
4
4
3
3
736
565
421
234
490

99

133 173 274

394

49

77

104 135 214

307

20

29

46

62

81 128

184

16
12
10
8
6

22
17
14
12
8

35
26
22
19
13

48
35
30
26
18

62
46
39
33
23

141
105
90
77
54

98
73
63
53
37

(Continues)

National Electrical Code Handbook

2011

1393

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.9 Continued


CONDUCTORS

Type

THHN,
THWN,
THWN-2

FEP, FEPB,
PFA, PFAH,
TFE

1394

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
14
12
10
8
6
4
3
2

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
9
6
4
2
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
8
6
4
2
1
1
1
1

1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
17
12
7
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
16
12
8
5
3
2
1
1

1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
28
20
13
7
5
3
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
27
20
14
8
6
4
3
3

Metric Designator (Trade Size)


35
41
(114) (112)
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
51
37
23
13
9
6
5
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
49
36
26
15
10
7
6
5

3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
70
51
32
18
13
8
7
6
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
68
50
36
20
14
10
8
7

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
118
86
54
31
22
14
12
10
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
115
84
60
34
24
17
14
12

7
6
5
4
3
3
2
2
1
1
1
1
1
1
1
1
1
1
0
170
124
78
45
32
20
17
14
10
9
7
6
5
4
3
3
3
2
1
1
1
1
1
1
164
120
86
49
35
24
20
17

11
10
8
7
5
5
4
4
3
2
2
1
1
1
1
1
1
1
1
265
193
122
70
51
31
26
22
16
14
11
9
8
6
5
5
4
3
3
2
2
2
1
1
257
188
135
77
55
38
32
26

15
13
11
9
7
6
6
5
4
3
3
3
3
2
2
1
1
1
1
358
261
164
95
68
42
35
30
22
18
15
13
10
8
7
6
6
5
4
3
3
3
3
2
347
253
182
104
74
52
43
35

20
17
14
12
9
8
7
7
5
4
4
4
3
3
3
2
1
1
1
464
338
213
123
89
54
46
39
29
24
20
17
14
11
9
8
7
6
5
4
4
4
3
3
450
328
235
135
96
67
56
46

155
(6)

32
46
27
39
23
33
19
27
15
22
13
19
12
17
10
15
9
13
7
10
6
9
6
8
6
8
5
7
5
7
4
5
3
4
3
4
2
3
736 1055
537 770
338 485
195 279
141 202
86 124
73 105
61
88
45
65
38
55
32
46
26
38
22
31
18
25
15
22
13
19
12
17
10
14
8
12
7
10
7
9
6
9
6
8
5
7
714 1024
521 747
374 536
214 307
152 218
106 153
89 127
73 105

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.9 Continued


CONDUCTORS

Type
PFA, PFAH,
TFE
PFA, PFAH,
TFE, Z

XHH, XHHW,
XHHW-2, ZW

XHH, XHHW,
XHHW-2

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)

Metric Designator (Trade Size)


35
41
(114) (112)

1/0
2/0
3/0
4/0
14
12
10
8
6
4
3
2
1
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

0
0
0
0
10
7
4
3
2
1
1
1
0
6
5
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
0
19
14
8
5
4
2
2
1
1
11
9
6
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
33
23
14
9
6
4
3
2
2
20
15
11
6
4
3
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0

3
2
1
1
59
42
26
16
11
8
5
5
4
35
27
20
11
8
6
5
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

4
3
2
1
82
58
36
22
16
11
8
6
5
49
38
28
15
11
8
7
6
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)
8

11

18

25

32

7 10
5
8
4
6
4
5
138 198
98 141
60 86
38 54
26 38
18 26
13 19
11 16
9 13
82 118
63 91
47 67
26 37
19 28
14 20
12 17
10 14
7 10
6
9
5
7
4
6
3
5
3
4
2
3
1
3
1
3
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
1
0
1
0
1

15
12
10
8
310
220
135
85
60
41
30
25
20
185
142
106
59
43
31
26
22
16
14
11
9
8
6
5
5
4
3
3
2
2
1

1
1
1
1
1

20
17
14
11
418
297
182
115
81
55
40
33
27
250
192
143
79
59
42
36
30
22
19
16
13
11
9
7
6
6
5
4
3
3
3
3
2
1
1
1
1

27
22
18
15
542
385
235
149
104
72
52
43
35
324
248
185
103
76
55
47
39
29
24
20
17
14
11
10
8
7
6
5
4
4
4
3
3
2
1
1
1

51

155
(6)
73

42
61
35
50
29
41
24
34
860 1233
610 875
374 536
236 339
166 238
114 164
83 119
69
99
56
80
514 736
394 565
294 421
163 234
121 173
87 125
74 106
62
89
46
66
39
56
32
46
27
38
22
32
18
26
15
22
14
20
12
17
10
14
8
11
7
10
6
9
6
9
5
8
5
7
4
6
3
5
3
4
2
4
(Continues)

National Electrical Code Handbook

2011

1395

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.9 Continued


FIXTURE WIRES

Type
FFH-2, RFH-2,
RFHH-3
SF-2, SFF-2

SF-1, SFF-1
RFH-1, RFHH-2,
TF, TFF, XF, XFF
RFHH-2, TF, TFF,
XF, XFF
XF, XFF
TFN, TFFN
PF, PFF, PGF,
PGFF, PAF, PTF,
PTFF, PAFF
HF, HFF, ZF, ZFF,
ZHF
KF-2, KFF-2

KF-1, KFF-1

XF, XFF

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

18
16
18
16
14
18
18

6
5
7
6
5
13
10

11
9
14
11
9
25
18

19
16
24
20
16
42
31

34
28
43
35
28
76
56

47
39
59
49
39
105
77

79
67
100
82
67
177
130

16

15

25

45

62

105

14
18
16
18
16
14
18
16
14
18
16
14
12
10
18
16
14
12
10
12
10

6
16
12
15
11
8
19
14
10
28
19
13
9
6
33
23
16
10
7
3
2

11
29
22
28
22
16
36
27
19
53
37
25
17
11
63
44
29
19
13
6
5

20
50
38
47
36
27
61
45
33
88
62
43
29
20
106
74
50
33
21
10
8

35
90
68
85
66
49
110
81
59
159
112
77
53
35
190
133
90
59
39
19
15

49
124
95
118
91
68
152
112
82
220
155
107
73
49
263
185
124
82
54
26
20

82
209
159
198
153
115
255
188
138
371
261
179
123
82
442
310
209
138
90
44
34

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.9(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*Types RHH, RHW, and RHW-2 without outer covering.

1396

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.9(A) Maximum Number of Compact Conductors in Rigid PVC Conduit,


Schedule 80 (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN, THWN,
THWN-2

XHHW,
XHHW-2

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0

3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
4
3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0

5
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

6
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
7
5
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0

Metric Designator (Trade Size)


35
41
(114) (112)
9
7
5
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0

11
6
5
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0
12
9
6
5
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0

13
10
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0

15
9
6
5
4
3
3
2
1
1
1
1
1
1
1
1
0
0
17
13
9
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)

155
(6)

22
17
13
9
6
6
5
4
3
2
2
1
1
1
1
1
1
1
1

25
15
11
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
29
21
15
11
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1

200
155
116
85
60
52
44
37
31
25
21
19
17
14
12
10
10
8
8

226
140
100
75
64
53
44
37
29
25
22
19
16
13
12
11
8
8
260
193
140
100
75
64
54
44
37
30
25
22
20
17
13
12
11
8
8

32
25
18
13
9
8
7
6
5
4
3
3
3
2
1
1
1
1
1

36
22
16
12
10
8
7
6
4
4
3
3
2
1
1
1
1
1
42
31
22
16
12
10
8
7
6
5
4
3
3
2
1
1
1
1
1

50
39
29
21
15
13
11
9
8
6
5
5
4
3
3
2
2
2
1

57
35
25
19
16
13
11
9
7
6
5
5
4
3
3
3
2
1
65
48
35
25
19
16
13
11
9
7
6
5
5
4
3
3
2
2
1

68
52
39
29
20
17
15
12
10
8
7
6
6
5
4
3
3
3
2

77
47
34
25
22
18
15
12
10
8
7
6
5
4
4
4
3
3
88
65
47
34
25
22
18
15
12
10
8
7
7
5
4
4
3
3
3

88
68
51
37
26
23
19
16
13
11
9
8
7
6
5
4
4
4
3

99
61
44
33
28
23
19
16
12
11
9
8
7
6
5
5
4
3
114
85
61
44
33
28
24
19
16
13
11
10
9
7
6
5
5
4
3

140
108
81
60
42
36
30
26
22
17
15
13
12
10
8
7
7
6
5

158
98
70
53
45
37
31
25
20
17
15
13
11
9
8
8
6
5
181
134
98
70
53
45
38
31
26
21
17
15
14
11
9
8
7
6
6

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

National Electrical Code Handbook

2011

1397

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.10 Maximum Number of Conductors or Fixture Wires in Rigid PVC Conduit,
Schedule 40 and HDPE Conduit (Based on Table 1, Chapter 9)
CONDUCTORS

Type
RHH, RHW,
RHW-2

TW

RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*,
THHW, THW
RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2* TW,
THW, THHW,
THW-2

1398

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)

Metric Designator (Trade Size)


35
41
(114) (112)

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)

155
(6)

269
224
181
94
76
59
52
45
29
26
22
19
16
12
11
10
9
8
6
6
5
5
5
4
3
3
2
2
568
436
325
181
378

390
323
261
137
109
85
75
65
43
37
32
28
24
18
16
14
13
11
9
8
8
7
7
6
5
4
3
3
822
631
470
261
546

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
14

4
3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
8
6
4
2
5

7
5
4
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
14
11
8
4
9

11
9
7
4
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
24
18
13
7
16

20
16
13
7
5
4
4
3
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
42
32
24
13
28

27
22
18
9
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
57
44
32
18
38

45
37
30
15
12
10
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
94
72
54
30
63

64
53
43
22
18
14
12
10
7
6
5
4
4
3
2
2
1
1
1
1
1
1
1
1
1
1
1
0
135
103
77
43
90

99
82
66
35
28
22
19
16
11
9
8
7
6
4
4
3
3
3
2
1
1
1
1
1
1
1
1
1
209
160
119
66
139

133
110
89
46
37
29
25
22
14
13
11
9
8
6
5
5
4
4
3
3
2
2
2
1
1
1
1
1
280
215
160
89
186

171
142
115
60
48
37
33
28
19
16
14
12
10
8
7
6
6
5
4
3
3
3
3
3
1
1
1
1
361
277
206
115
240

12

12

22

30

50

72

112 150

193 304

439

10

10

17

24

39

56

87 117

150 237

343

10

14

23

33

52

70

90 142

205

6
4
3
2
1

1
1
1
1
0

2
1
1
1
1

4
3
3
2
1

8
6
5
4
3

11
8
7
6
4

18
13
11
10
7

26
19
16
14
10

40
30
25
22
15

53
40
34
29
20

69 109
51 81
44 69
37 59
26 41

157
117
100
85
60

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.10 Continued


CONDUCTORS

Type

THHN, THWN,
THWN-2

FEP, FEPB,
PFA, PFAH,
TFE

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
14
12
10
8
6
4
3
2

0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11
8
5
3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11
8
6
3
2
1
1
1

1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
21
15
9
5
4
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
20
15
10
6
4
3
2
1

1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
34
25
15
9
6
4
3
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
33
24
17
10
7
5
4
3

Metric Designator (Trade Size)


35
41
(114) (112)
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
60
43
27
16
11
7
6
5
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
58
42
30
17
12
8
7
6

3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
82
59
37
21
15
9
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
79
58
41
24
17
12
10
8

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
135
99
62
36
26
16
13
11
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
131
96
69
39
28
19
16
13

8
7
6
5
4
3
3
3
2
1
1
1
1
1
1
1
1
1
1
193
141
89
51
37
22
19
16
12
10
8
7
6
4
4
3
3
2
1
1
1
1
1
1
188
137
98
56
40
28
23
19

13
11
9
8
6
5
5
4
3
3
2
2
2
1
1
1
1
1
1
299
218
137
79
57
35
30
25
18
15
13
11
9
7
6
5
5
4
3
3
2
2
2
1
290
212
152
87
62
43
36
30

17
15
12
10
8
7
6
6
5
4
3
3
3
3
2
1
1
1
1
401
293
184
106
77
47
40
33
25
21
17
14
12
10
8
7
6
5
4
4
3
3
3
3
389
284
204
117
83
58
48
40

22
19
16
13
11
9
8
7
6
5
4
4
4
3
3
2
1
1
1
517
377
238
137
99
61
51
43
32
27
22
18
15
12
11
9
8
7
5
5
4
4
4
3
502
366
263
150
107
75
62
51

155
(6)

35
51
30
43
25
36
21
30
17
25
15
21
13
19
12
17
10
14
8
11
7
10
6
10
6
9
6
8
5
7
4
6
3
5
3
4
3
4
815 1178
594 859
374 541
216 312
156 225
96 138
81 117
68
98
50
73
42
61
35
51
29
42
24
35
20
28
17
24
15
21
13
19
11
16
9
13
8
11
7
11
7
10
6
9
6
8
790 1142
577 834
414 598
237 343
169 244
118 170
98 142
81 117
(Continues)

National Electrical Code Handbook

2011

1399

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.10 Continued


CONDUCTORS

Type
PFA, PFAH,
TFE
PFA, PFAH,
TFE, Z

XHH, XHHW,
XHHW-2, ZW

XHH, XHHW,
XHHW-2

1400

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)

Metric Designator (Trade Size)


35
41
(114) (112)

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)

13

20

28

36

1/0
2/0
3/0
4/0
14
12
10
8
6
4
3
2
1
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

1
0
0
0
13
9
6
3
2
1
1
1
1
8
6
4
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
24
17
10
6
4
3
2
1
1
14
11
8
4
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
40
28
17
11
7
5
4
3
2
24
18
13
7
5
4
3
3
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

3
3
2
1
70
49
30
19
13
9
6
5
4
42
32
24
13
10
7
6
5
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

4
4
3
2
95
68
41
26
18
12
9
7
6
57
44
32
18
13
9
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0

8
6
5
4
158
112
69
43
30
21
15
12
10
94
72
54
30
22
16
13
11
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0

11
9
7
6
226
160
98
62
43
30
22
18
14
135
103
77
43
32
23
19
16
12
10
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1

17
14
12
9
350
248
152
96
67
46
34
28
23
209
160
119
66
49
35
30
25
19
16
13
11
9
7
6
5
5
4
3
3
2
2
2
1
1
1
1
1

23
19
16
13
469
333
204
129
90
62
45
38
30
280
215
160
89
66
48
40
34
25
21
17
14
12
10
8
7
6
5
4
4
3
3
3
3
1
1
1
1

30
24
20
16
605
429
263
166
116
80
58
49
39
361
277
206
115
85
61
52
44
32
27
23
19
15
13
11
9
8
7
5
5
4
4
4
3
3
2
1
1

56

155
(6)
81

47
68
39
56
32
46
26
38
952 1376
675 976
414 598
261 378
184 265
126 183
92 133
77 111
62
90
568 822
436 631
325 470
181 261
134 193
97 140
82 118
69
99
51
74
43
62
36
52
30
43
24
35
20
29
17
25
15
22
13
19
11
16
9
13
8
11
7
11
7
10
6
9
6
8
4
6
4
5
3
5
3
4

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.10 Continued


FIXTURE WIRES

Type
FFH-2, RFH-2,
RFHH-3
SF-2, SFF-2

SF-1, SFF-1
RFHH-2, TF, TFF,
XF, XFF RFH-1,
RFHH-2, TF, TFF,
XF, XFF
XF, XFF
TFN, TFFN
PF, PFF, PGF,
PGFF, PAF, PTF,
PTFF, PAFF
HF, HFF, ZF, ZFF,
ZHF
KF-2, KFF-2

KF-1, KFF-1

XF, XFF

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

18
16
18
16
14
18
18

8
6
10
8
6
17
13

14
12
17
14
12
31
23

23
19
29
24
19
51
38

40
33
50
42
33
89
66

54
46
69
57
46
122
90

90
76
114
94
76
202
149

16

10

18

30

53

73

120

14
18
16
18
16
14
18
16
14
18
16
14
12
10
18
16
14
12
10
12
10

8
20
16
19
15
11
25
18
13
36
26
17
12
8
43
30
20
13
9
4
3

14
37
28
35
27
20
45
33
24
65
46
31
22
14
78
55
37
24
16
8
6

24
60
46
57
44
33
74
54
40
107
75
52
35
24
128
90
60
40
26
12
10

42
105
80
100
77
58
129
95
70
187
132
90
62
42
223
157
105
70
45
22
17

57
144
110
137
106
79
176
130
95
256
180
124
85
57
305
214
144
95
62
30
24

94
239
183
227
175
131
292
216
158
424
299
205
141
94
506
355
239
158
103
50
39

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.10(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*Types RHH, RHW, and RHW-2 without outer covering.

National Electrical Code Handbook

2011

1401

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.10(A) Maximum Number of Compact Conductors in Rigid PVC Conduit,


Schedule 40 and HDPE Conduit (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN, THWN,
THWN-2

XHHW,
XHHW-2

Conductor
Size (AWG/ 16 21 27
(12) (34) (1)
kcmil)
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0

2
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

4
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
5
4
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

6
5
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0

7
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
8
6
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0

Metric Designator (Trade Size)


35
41
(114) (112)
11
9
6
5
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0

13
8
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0
14
11
8
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0

15
12
9
6
4
4
3
3
2
1
1
1
1
1
1
1
1
1
1

17
11
8
6
5
4
3
3
1
1
1
1
1
1
1
1
1
1
20
15
11
8
6
5
4
3
3
1
1
1
1
1
1
1
1
1
1

53
63
78
91 103 129
(2) (212) (3) (312) (4) (5)

155
(6)

26
20
15
11
7
6
5
5
4
3
2
2
1
1
1
1
1
1
1

29
18
13
9
8
7
5
4
3
3
3
2
1
1
1
1
1
1
33
25
18
13
9
8
7
5
5
4
3
3
2
1
1
1
1
1
1

224
173
129
95
67
58
49
42
35
27
24
21
19
16
13
12
11
9
9

253
156
112
84
72
59
50
41
32
28
24
22
18
15
13
12
9
9
290
215
156
112
84
72
60
50
42
33
28
25
22
18
15
13
12
9
9

37
28
21
15
11
9
8
7
5
4
4
3
3
2
1
1
1
1
1

41
25
18
14
12
9
8
6
5
4
4
3
3
2
1
1
1
1
47
35
25
18
14
12
10
8
7
5
4
4
3
3
2
1
1
1
1

57
44
33
24
17
15
12
10
9
7
6
5
5
4
3
3
2
2
1

64
40
28
21
18
15
12
10
8
7
6
5
4
4
3
3
2
2
73
55
40
28
21
18
15
12
10
8
7
6
5
4
4
3
3
2
2

76
59
44
32
23
20
16
14
12
9
8
7
6
5
4
4
3
3
3

86
53
38
29
24
20
17
14
11
9
8
7
6
5
4
4
3
3
99
73
53
38
29
24
20
17
14
11
9
8
7
6
5
4
4
3
3

98
76
57
42
29
25
21
18
15
12
10
9
8
7
5
5
5
4
4

111
68
49
37
31
26
22
18
14
12
10
9
8
6
5
5
4
4
127
94
68
49
37
31
26
22
18
14
12
11
10
8
6
5
5
4
4

155
119
89
66
46
40
34
29
24
19
16
15
13
11
9
8
7
6
6

175
108
77
58
49
41
34
28
22
19
17
15
13
10
9
8
6
6
200
149
108
77
58
49
42
34
29
23
19
17
15
13
10
9
8
6
6

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

1402

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.11 Maximum Number of Conductors or Fixture Wires in Type A, Rigid PVC
Conduit (Based on Table 1, Chapter 9)
CONDUCTORS

Type
RHH, RHW,
RHW-2

TW

RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*,
THHW, THW
RHH*, RHW*,
RHW-2*,
THHW, THW,
THW-2
RHH*, RHW*,
RHW-2*, TW,
THHW, THW,
THW-2

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
14

5
4
3
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
11
8
6
3
7

9
7
6
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
18
14
10
6
12

15
12
10
5
4
3
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
31
24
18
10
20

12

10

10

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

24
20
16
8
6
5
4
4
2
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
51
39
29
16
34

31
26
21
11
9
7
6
5
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
67
51
38
21
44

49
41
33
17
14
11
9
8
5
5
4
3
3
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
105
80
60
33
70

74
61
50
26
21
16
14
12
8
7
6
5
4
3
3
2
2
1
1
1
1
1
1
1
1
1
1
1
157
120
89
50
104

112
93
75
39
31
24
21
18
12
10
9
8
7
5
4
4
4
3
2
2
1
1
1
1
1
1
1
1
235
181
135
75
157

146
121
98
51
41
32
28
24
16
14
12
10
9
7
6
5
5
4
3
3
3
3
2
2
1
1
1
1
307
236
176
98
204

187
155
125
65
52
41
36
31
20
18
15
13
11
8
7
7
6
5
4
4
4
3
3
3
2
1
1
1
395
303
226
125
262

16

27

35

56

84

126

164

211

13

21

28

44

65

98

128

165

12

16

26

39

59

77

98

13

20

30

45

59

75

(Continues)

National Electrical Code Handbook

2011

1403

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.11 Continued


CONDUCTORS

Type
RHH*, RHW*,
RHW-2*, TW,
THW, THHW,
THW-2

THHN,
THWN,
THWN-2

FEP, FEPB,
PFA, PFAH,
TFE

1404

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
14
12
10
8
6

1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
16
11
7
4
3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
15
11
8
4
3

2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
27
19
12
7
5
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
26
19
13
8
5

4
4
3
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
44
32
20
12
8
5
4
3
2
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
43
31
22
13
9

7
6
5
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
73
53
33
19
14
8
7
6
4
4
3
2
1
1
1
1
1
1
1
1
1
1
0
0
70
51
37
21
15

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

9
8
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
96
70
44
25
18
11
9
8
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
93
68
48
28
20

15
13
11
7
6
5
4
4
3
2
2
1
1
1
1
1
1
1
1
1
1
0
0
150
109
69
40
28
17
15
12
9
8
6
5
4
3
3
2
2
1
1
1
1
1
1
1
146
106
76
44
31

22
19
16
11
10
8
7
6
4
4
3
3
2
1
1
1
1
1
1
1
1
1
1
225
164
103
59
43
26
22
19
14
11
10
8
6
5
4
4
3
3
2
1
1
1
1
1
218
159
114
65
46

33
29
24
17
14
12
10
9
7
6
5
5
4
3
3
3
2
2
1
1
1
1
1
338
246
155
89
64
39
33
28
21
17
14
12
10
8
7
6
5
4
3
3
3
3
2
2
327
239
171
98
70

44
37
32
22
19
16
13
11
9
8
7
6
5
4
4
3
3
3
3
1
1
1
1
441
321
202
117
84
52
44
37
27
23
19
16
13
10
9
8
7
6
5
4
4
4
3
3
427
312
224
128
91

56
48
41
29
24
21
17
14
12
10
9
8
7
5
5
4
4
4
3
3
2
1
1
566
412
260
150
108
66
56
47
35
29
24
20
17
14
12
10
9
7
6
5
5
5
4
4
549
400
287
165
117

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.11 Continued


CONDUCTORS

Type

PFA, PFAH,
TFE
PFA, PFAH,
TFE, Z

XHH, XHHW,
XHHW-2, ZW

XHH, XHHW,
XHHW-2

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

4
3
2
1

1
1
1
1

4
3
2
1

6
5
4
3

10
8
7
5

14
11
9
6

21
18
15
10

32
27
22
15

49
40
33
23

64
53
44
30

82
68
56
39

1/0
2/0
3/0
4/0
14
12
10
8
6
4
3
2
1
14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

1
1
1
0
18
13
8
5
3
2
1
1
1
11
8
6
3
2
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0

1
1
1
1
31
22
13
8
6
4
3
2
1
18
14
10
6
4
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0

2
1
1
1
52
37
22
14
10
7
5
4
3
31
24
18
10
7
5
4
3
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0

4
3
3
2
85
60
37
23
16
11
8
7
5
51
39
29
16
12
8
7
6
4
4
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0

5
4
3
3
112
79
48
30
21
15
11
9
7
67
51
38
21
15
11
9
8
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0
0
0
0

8
7
6
5
175
124
76
48
34
23
17
14
11
105
80
60
33
24
18
15
12
9
8
6
5
4
3
3
3
2
1
1
1
1
1
1
1
1
1
1
0

13
10
9
7
263
186
114
72
50
35
25
21
17
157
120
89
50
37
26
22
19
14
12
10
8
7
5
5
4
3
3
2
1
1
1
1
1
1
1
1
1

19
16
13
11
395
280
171
108
76
52
38
32
26
235
181
135
75
55
40
34
28
21
18
15
12
10
8
7
6
5
4
3
3
3
3
2
2
1
1
1
1

25
21
17
14
515
365
224
141
99
68
50
41
33
307
236
176
98
72
52
44
37
28
23
19
16
13
11
9
8
7
6
5
4
4
4
3
3
2
1
1
1

32
27
22
18
661
469
287
181
127
88
64
53
43
395
303
226
125
93
67
57
48
35
30
25
20
17
14
12
10
9
8
6
5
5
5
4
4
3
2
2
1

(Continues)

National Electrical Code Handbook

2011

1405

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.11 Continued


FIXTURE WIRES

Type
FFH-2, RFH-2,
RFHH-3
SF-2, SFF-2

SF-1, SFF-1
RFH-1, RFHH-2,
TF, TFF, XF, XFF
RFHH-2, TF, TFF,
XF, XFF
XF, XFF
TFN, TFFN
PF, PFF, PGF,
PGFF, PAF, PTF,
PTFF, PAFF
HF, HFF, ZF, ZFF,
ZHF
KF-2, KFF-2

KF-1, KFF-1

XF, XFF

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

18
16
18
16
14
18
18

10
9
13
11
9
23
17

18
15
22
18
15
40
29

16

14

14
18
16
18
16
14
18
16
14
18
16
14
12
10
18
16
14
12
10
12
10

11
28
21
26
20
15
34
25
18
49
35
24
16
11
59
41
28
18
12
6
4

27
(1)

35
(114)

41
(112)

53
(2)

30
25
37
31
25
66
49

48
41
61
51
41
108
80

64
54
81
67
54
143
105

100
85
127
105
85
224
165

24

39

65

85

134

18
47
36
45
34
26
58
42
31
84
59
40
28
18
100
70
47
31
20
10
8

31
79
60
74
58
43
96
71
52
140
98
67
46
31
167
117
79
52
34
16
13

51
128
98
122
94
70
157
116
85
228
160
110
76
51
272
191
128
85
55
27
21

67
169
129
160
124
93
206
152
112
300
211
145
100
67
357
251
169
112
73
35
28

105
265
202
251
194
146
324
239
175
470
331
228
157
105
561
394
265
175
115
56
44

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.11(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*Types RHH, RHW, and RWH-2 without outer covering.

1406

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.11(A) Maximum Number of Compact Conductors in Type A, Rigid PVC


Conduit (Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN,
THWN,
THWN-2

XHHW,
XHHW-2

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

16
(12)

21
(34)

27
(1)

35
(114)

41
(112)

53
(2)

63
(212)

78
(3)

91
(312)

103
(4)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

3
2
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0

3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
4
3
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0

5
4
3
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
0

5
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
6
5
3
2
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0

8
6
5
3
2
1
1
1
1
1
1
1
1
1
0
0
0
0
0

9
6
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0
11
8
6
4
3
2
1
1
1
1
1
1
1
1
0
0
0
0
0

14
10
8
6
4
3
3
2
1
1
1
1
1
1
1
1
1
0
0

15
9
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0
18
13
9
7
5
4
3
3
2
1
1
1
1
1
1
1
1
1
0

18
14
10
7
5
4
4
3
3
1
1
1
1
1
1
1
1
1
1

20
12
9
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1
23
17
12
9
7
6
5
4
3
2
1
1
1
1
1
1
1
1
1

28
22
16
12
8
7
6
5
4
3
3
2
2
1
1
1
1
1
1

32
20
14
10
9
7
6
5
4
3
3
2
2
1
1
1
1
1
37
27
20
14
10
9
7
6
5
4
3
3
3
2
1
1
1
1
1

42
33
24
18
13
11
9
8
6
5
4
4
3
3
2
1
1
2
1

48
30
21
16
13
11
9
8
6
5
4
4
3
3
2
2
2
1
55
41
30
21
16
13
11
9
8
6
5
5
4
3
3
2
2
2
1

64
49
37
27
19
16
14
12
10
8
7
6
5
4
3
3
3
2
2

72
45
32
24
20
17
14
11
9
8
7
6
5
4
3
3
3
2
83
62
45
32
24
20
17
14
12
9
8
7
6
5
4
3
3
3
2

84
65
48
36
25
21
18
15
13
10
9
8
7
6
5
4
4
3
3

94
58
42
31
27
22
18
15
12
10
9
8
7
5
5
4
4
3
108
80
58
42
31
27
22
18
15
12
10
9
8
7
5
5
4
4
3

107
83
62
46
32
28
23
20
17
13
11
10
9
8
6
5
5
4
4

121
75
54
40
34
28
24
19
15
13
11
10
9
7
6
6
5
4
139
103
75
54
40
34
29
24
20
16
13
12
11
9
7
6
6
5
4

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

National Electrical Code Handbook

2011

1407

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.12 Maximum Number of Conductors in Type EB, PVC Conduit (Based on
Table 1, Chapter 9)
CONDUCTORS

Type
RHH, RHW,
RHW-2

TW

RHH*, RHW*,
RHW-2*, THHW,
THW, THW-2
RHH*, RHW*,
RHW-2*, THHW,
THW
RHH*, RHW*,
RHW-2*, THHW,
THW, THW-2
RHH*, RHW*,
RHW-2*, TW,
THW, THHW,
THW-2

1408

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

53
(2)

78
(3)

91
(312)

103
(4)

129
(5)

155
(6)

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000
14
12
10
8
14

53
44
35
18
15
11
10
9
6
5
4
4
3
2
1
1
1
1
1
1
1
1
1
1
1
0
0
0
111
85
63
35
74

119
98
79
41
33
26
23
20
13
11
10
8
7
5
5
4
4
3
3
2
2
2
1
1
1
1
1
1
250
192
143
79
166

155
128
104
54
43
34
30
26
17
15
13
11
9
7
6
5
5
4
3
3
3
3
2
2
1
1
1
1
327
251
187
104
217

197
163
132
69
55
43
38
33
21
19
16
14
12
9
8
7
6
5
4
4
4
4
3
3
2
1
1
1
415
319
238
132
276

303
251
203
106
85
66
58
50
33
29
25
22
18
14
12
11
10
9
7
6
6
6
5
5
3
3
3
2
638
490
365
203
424

430
357
288
151
121
94
83
72
47
41
36
31
26
20
17
16
14
12
10
9
9
8
7
7
5
4
4
3
907
696
519
288
603

12

59

134

175

222

341

485

10

46

104

136

173

266

378

28

62

81

104

159

227

6
4
3
2
1
1/0
2/0
3/0
4/0

21
16
13
11
8
7
6
5
4

48
36
30
26
18
15
13
11
9

62
46
40
34
24
20
17
14
12

79
59
51
43
30
26
22
18
15

122
91
78
66
46
40
34
28
24

173
129
111
94
66
56
48
40
34

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.12 Continued


CONDUCTORS

Type

THHN, THWN,
THWN-2

FEP, FEPB, PFA,


PFAH, TFE

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


53
(2)

78
(3)

91
(312)

103
(4)

129
(5)

155
(6)

250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

3
3
2
2
1
1
1
1
1
1
1
1
1
1
0

7
6
6
5
4
3
3
3
3
2
2
1
1
1
1

10
8
7
7
5
4
4
4
3
3
3
2
1
1
1

12
11
9
8
7
6
5
5
4
4
4
3
2
2
1

19
17
15
13
11
9
8
7
7
6
6
4
4
3
3

27
24
21
19
16
13
11
11
10
9
8
6
6
5
4

14
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000

159
116
73
42
30
19
16
13
10
8
7
5
4
4
3
3
2
1
1
1
1
1
1
1

359
262
165
95
68
42
36
30
22
18
15
13
10
8
7
6
6
5
4
3
3
3
3
2

468
342
215
124
89
55
46
39
29
24
20
17
14
11
10
8
7
6
5
4
4
4
3
3

595
434
274
158
114
70
59
50
37
31
26
21
18
14
12
11
10
8
6
6
5
5
4
4

915
667
420
242
175
107
91
76
57
48
40
33
27
22
19
17
15
12
10
9
8
8
7
6

1300
948
597
344
248
153
129
109
80
68
56
47
39
31
27
24
21
18
14
12
12
11
10
9

14
12
10
8

155
113
81
46

348
254
182
104

454
332
238
136

578
422
302
173

888
648
465
266

1261
920
660
378

6
4
3
2

33
23
19
16

74
52
43
36

97
68
56
46

123
86
72
59

189
132
110
91

269
188
157
129
(Continues)

National Electrical Code Handbook

2011

1409

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.12 Continued


CONDUCTORS

Type

Conductor
Size (AWG/
kcmil)

Metric Designator (Trade Size)


53
(2)

78
(3)

91
(312)

103
(4)

129
(5)

155
(6)

PFA, PFAH, TFE


PFA, PFAH, TFE, Z

1
1/0
2/0
3/0
4/0

11
9
7
6
5

25
20
17
14
11

32
27
22
18
15

41
34
28
23
19

63
53
43
36
29

90
75
62
51
42

14
12
10
8
6
4
3
2
1

186
132
81
51
36
24
18
15
12

419
297
182
115
81
55
40
34
27

547
388
238
150
105
72
53
44
36

696
494
302
191
134
92
67
56
45

1069
759
465
294
206
142
104
86
70

1519
1078
660
417
293
201
147
122
99

XHH, XHHW,
XHHW-2, ZW

14
12
10
8
6
4
3
2

111
85
63
35
26
19
16
13

250
192
143
79
59
42
36
30

327
251
187
104
77
56
47
39

415
319
238
132
98
71
60
50

638
490
365
203
150
109
92
77

907
696
519
288
213
155
131
110

XHH, XHHW,
XHHW-2

1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
800
900
1000
1250
1500
1750
2000

10
8
7
6
5
4
3
3
2
1
1
1
1
1
1
1
1
1
1
0

22
19
16
13
11
9
7
6
6
5
4
3
3
3
3
2
1
1
1
1

29
25
20
17
14
11
10
9
8
6
5
4
4
4
3
3
2
1
1
1

37
31
26
22
18
15
12
11
10
8
6
6
5
5
4
4
3
3
2
1

58
48
40
33
27
22
19
17
15
12
10
9
8
8
7
6
5
4
4
3

82
69
57
47
39
32
28
24
22
18
14
12
12
11
10
9
7
6
5
5

Notes:
1. This table is for concentric stranded conductors only. For compact stranded conductors, Table C.12(A)
should be used.
2. Two-hour fire-rated RHH cable has ceramifiable insulation which has much larger diameters than other
RHH wires. Consult manufacturers conduit fill tables.
*
Types RHH, RHW, and RHW-2 without outer covering.

1410

2011

National Electrical Code Handbook

Informative Annex C

Conduit and Tubing Fill Tables for Conductors and Fixture Wires of the Same Size

TABLE C.12(A) Maximum Number of Compact Conductors in Type EB, PVC Conduit
(Based on Table 1, Chapter 9)
COMPACT CONDUCTORS

Type
THW, THW-2,
THHW

THHN, THWN,
THWN-2

XHHW, XHHW-2

Metric Designator (Trade Size)

Conductor
Size (AWG/
kcmil)

53
(2)

78
(3)

91
(312)

103
(4)

129
(5)

155
(6)

8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000
8
6
4
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
600
700
750
900
1000

30
23
17
13
9
8
6
5
4
3
3
3
2
1
1
1
1
1
1

34
21
15
11
9
8
6
5
4
4
3
3
2
1
1
1
1
1
39
29
21
15
11
9
8
6
5
4
4
3
3
2
1
1
1
1
1

68
52
39
29
20
17
15
12
10
8
7
6
6
5
4
3
3
3
2

77
47
34
25
22
18
15
12
10
8
7
6
5
4
4
4
3
3
88
65
47
34
25
22
18
15
12
10
8
7
7
5
4
4
3
3
3

89
69
51
38
26
23
19
16
14
11
9
8
7
6
5
4
4
4
3

100
62
44
33
28
23
20
16
13
11
9
8
7
6
5
5
4
3
115
85
62
44
33
28
24
20
16
13
11
10
9
7
6
5
5
4
4

113
87
65
48
34
29
24
21
17
14
12
11
10
8
6
6
5
5
4

128
79
57
42
36
30
25
20
16
14
12
11
9
7
6
6
5
4
146
109
79
57
42
36
30
25
21
17
14
12
11
9
7
6
6
5
5

174
134
100
74
52
45
38
32
27
21
19
17
15
12
10
9
8
7
7

196
121
87
65
56
46
38
32
25
22
19
17
14
11
10
9
7
7
225
167
121
87
65
56
47
38
32
26
22
19
17
14
11
10
9
7
7

247
191
143
105
74
64
54
46
38
30
26
24
21
18
14
13
12
10
9

279
172
124
93
79
65
55
45
35
31
27
24
20
16
14
14
10
10
320
238
172
124
93
79
67
55
46
37
31
28
25
20
16
14
13
10
10

Definition: Compact stranding is the result of a manufacturing process where the standard conductor is
compressed to the extent that the interstices (voids between strand wires) are virtually eliminated.

National Electrical Code Handbook