CE 40 Q1 2015 07 - 06
A. The roof truss below is from an enclosed building used for heavy storage, located near the open coast of Sabang, Palawan. It is
propped on 10-meter high-columns and designed with a tributary width of 16m.
1. Determine the resultant dead load on the truss.
2. Determine the design wind loads on the truss using Method 1.
3. Determine the design wind loads on the truss using Method 2.
4. Determine the reactions at the supports of the truss for a design combination of dead load and live load, DL + LL.
5. Determine the reactions at the supports of the truss for a design combination of dead load, live load, and wind load (DL + LL
+ WL). Use design wind loads from #3 with negative internal pressure. (If multiple load cases are available, use one load
case only)
6. Determine the column base reactions due to wind load. Use design wind loads from #3 with negative internal pressure. (If
multiple load cases are available, use one load case only)
1.
2.
2.67 m
1.33 m
WIND
(2)(12.65m)(16m)(20kg/m2)(9.81m/s2)
(2)(7)(16m)(7.9kg/m)( 9.81m/s2)
(81.06 m)(1500mm2)(0.001)2(77.3 kN/m)
Total
:
Kzt:
Iw:
1.74
1.0
1.0
Zone**
79.42 kN
17.36 kN
9.40 kN
106.18 kN
For Category D
Exposure
Ps9***
Ps
ps T w
-0.13
-0.23 kPa
3.68 kN/m
-0.55
-0.96 kPa
15.36 kN/m
-0.42
-0.73 kPa
11.68 kN/m
CE 40 Q1 2015 07 - 06
WIND
3.
G:
Kzt:
Iw:
Kd:
V:
0.85
1.0
1.0
0.85
150 kph
Design wind pressure for roof (based on equation 207.17, design wind loads for all heights):
p = qhGCp qh(GCpi)
Cp:
15
-0.5
0.0
20
Normal to ridge, 10
-0.3
and h/L 0.25
0.2
(GCpi): +0.18, -0.18
qh:
qh = 47.3 106 2
Kz =1.22 (for z = 12m, Exposure Category D)
qh = 1.10
Design wind pressures, p:
Cp = -0.36
pTw
Cp = 0.14
+GCPi
-GCpi
+GCPi
-GCpi
-0.5346 kPa
-0.1386 kPa
-0.0671 kPa
0.3289 kPa
-8.48 kN/m
-2.22 kN/m
-1.07 kN/m
5.26 kN/m
Sample load diagram for design wind load, Cp = -0.36 and Gcpi = -0.18:
4.
CE 40 Q1 2015 07 - 06
FBD
Ra = 629.09 kN
Rby = 629.09 kN
Rbx = 0
5.
Load Combination
DL + LL
WL
DL + LL + WL
Ra
629.09 kN
-26.64 kN
602.45 kN
Rby
629.09 kN
-26.64 kN
602.45 kN
Rbx
0
0
0
CE 40 Q1 2015 07 - 06
WIND
*C and D have to be fixed to keep the structure stable. The structure is still statically determinate.
Design wind pressure for walls (based on equation 207.17,
design wind loads for all heights):
Windward:
p = qzGCp qh(GCpi)
Leeward:
p = qhGCp qh(GCpi)
Cp:
Windward: 0.8
Leeward: -0.5 (B 32 ; L/B 0.75)
(GCpi):
+0.18, -0.18
Support Reactions from Truss (wind load only)
Ra = -63.12 kN
Rb = -63.12 kN
Windward Column AC
z
Kz
qz
p (w/ -Gcpi)
pTw
4.5
1.03
0.93
0.83 kPa
13.31 kN/m
1.08
0.98
0.86 kPa
13.80 kN/m
7.5
1.12
1.01
0.89 kPa
14.19 kN/m
1.16
1.05
0.91 kPa
14.58 kN/m
10
1.18
1.07
0.92 kPa
14.78 kN/m
Leeward Column BD
Mc = 707.95 kN-m
Rcx = 138.53 kN
Rcy = - 26.64 kN
Kh
qh
p (w/ -Gcpi)
pTw
12
1.22
1.10
-0.27 kPa
-4.33 kN/m
Md = 216.5 kN-m
Rdx = 43.3 kN
Rdy = - 26.64 kN