Screw type chillers are inefficient due to higher mechanical friction losses. This is indicated by the
higher power consumption in screw type chillers as compared to centrifugal chillers.
Power consumption per ton of refrigerant :
Screw type
: 0.619 kWH
Centrifugal Type
: 0.550 kWH
Difference
: 0.069 kWH
- Extra power consumption per day (636 TR screw chiller as offered by Durham Bush) : 44kWH
- Extra power consumption per year
: 379,123kWH
- Extra cost incurred on power consumption
: RM 87,128 @ RM0.23/kWH
Which comes to 16% of the cost of the new Durham Bush screw type chiller (RM 535,000).
Hence we have to pay extra power cost of RM 87,128 per year which is very substantial
amount.
2.
3.
4.
5.
Centrifugal chillers are designed and tested as per ARI (American Air Conditioning and
Refrigeration Institute) whereas locally made screw chillers do not conform to these standards.
6.
To summarise the above, Mewah-Oils Sdn. Bhd. feels that screw chillers result in high cost of ownership
for the users in the form of higher maintenance, higher operation and not user friendly design features, thus
making the screw chiller operation non-competitive.
16/6/2001