You are on page 1of 8

Produced on 6/5/2013 with Xpress Selection V5.7.4 - database DIL 8.1.

7
Project name
Project address
Reference
Client name
Client address
Revision

sm-carpark
pasay city
system1
sm
pasay city
revision3

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model
RXYQ28PAYL
FXFQ125PVE
FXFQ25PVE
FXFQ50PVE
KHRP26A22T
KHRP26A33T
KHRP26A72T
KHRP26A73T + KHRP26M73TP
BRC1E61
BYCP125K-W1
BHFP22P100
Piping 6,4
Piping 9,5
Piping 12,7
Piping 15,9
Piping 19,1
Piping 22,2
Piping 28,6
Piping 34,9

Qty
1
5
3
1
3
1
3
1
9
9
1
11.0m
29.0m
16.0m
31.0m
5.0m
4.0m
11.0m
5.0m

Description
Heat pump VRV III PA R410A
FR - Ceiling Mounted Cassette(Round Flow)
FR - Ceiling Mounted Cassette(Round Flow)
FR - Ceiling Mounted Cassette(Round Flow)
REFNET branch piping kit
REFNET branch piping kit
REFNET branch piping kit
REFNET branch piping kit
Wired Remote Controller (Navigation Remote Controller)
Decoration panel
Outdoor unit multi connection piping kit

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 1

Indoor Unit Details

1.1. Table of Abbreviations


Name
FCU
Tmp C
TC
SC
Tmp H
HC
Airflow
Sound
PS
MCA
Fuses
WxHxD
Wght

Logical name of the device, possibly preceeded by room name


Device model name
Indoor conditions in cooling (dry bulb temp. / RH)
Available total cooling capacity
Available sensible cooling capacity
Indoor temperature in heating
Available heating capacity (integrated heating capacity)
Supplied airflow at low and high fan speed
Sound pressure low and high
Power supply (voltage and phases)
Minimum Circuit Amps
Fuses
WidthxHeightxDepth
Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 2

Out 1 - RXYQ28PAYL
Actual capacity data at conditions and connection ratio (107%) as entered
Name
2:Ind 2
3:Ind 3
1:Ind 1
4:Ind 4
5:Ind 5
6:Ind 6
7:Ind 7
8:Ind 8
9:Ind 9
Total
Name
2:Ind 2
3:Ind 3
1:Ind 1
4:Ind 4
5:Ind 5
6:Ind 6
7:Ind 7
8:Ind 8
9:Ind 9

FCU

Tmp C
C
24.0 / 50%
24.0 / 50%
24.0 / 50%
24.0 / 50%
24.0 / 50%
24.0 / 50%
24.0 / 50%
24.0 / 50%
24.0 / 50%

FXFQ125PVE
FXFQ125PVE
FXFQ125PVE
FXFQ125PVE
FXFQ125PVE
FXFQ25PVE
FXFQ25PVE
FXFQ25PVE
FXFQ50PVE

Sound
dBA
34-44
34-44
34-44
34-44
34-44
27-30
27-30
27-30
27-32

PS
220V 1ph
220V 1ph
220V 1ph
220V 1ph
220V 1ph
220V 1ph
220V 1ph
220V 1ph
220V 1ph

MCA
A
1.5
1.5
1.5
1.5
1.5
0.3
0.3
0.3
0.3

TC
kW
11.7
11.6
11.6
11.4
11.3
2.2
2.2
2.2
4.4
68.7

SC
kW
8.5
8.5
8.4
8.3
8.3
2.2
2.2
2.2
3.5
52.1

Fuses
Factory Std
Factory Std
Factory Std
Factory Std
Factory Std
Factory Std
Factory Std
Factory Std
Factory Std

Tmp H
C
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0
20.0

WxHxD
mm
840x288x840
840x288x840
840x288x840
840x288x840
840x288x840
840x246x840
840x246x840
840x246x840
840x246x840

HC
kW
11.0
11.0
11.0
11.0
11.0
2.2
2.2
2.2
4.4
66.2

Airflow
l/s
375-550
375-550
375-550
375-550
375-550
167-217
167-217
167-217
183-267

Wght
kg
25
25
25
25
25
20
20
20
20

Outdoor unit placed 50.0m above the indoor units.


The minimum connection ratio for this height difference is 50%.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 3

Outdoor Unit Details

1.2. Table of Abbreviations


Name
Model
Comb
Tmp C
CC
Tmp H
HC
Piping
Bse Refr
Ex Refr
PS
MCA
MFA
Run Amps
St Curr
Fuses
WxHxD
Wght

Logical name of the device


Device model name
Connection ratio
Outdoor temperature in cooling
Cooling capacity
Outdoor temperature in heating
Heating capacity (integrated heating capacity)
Largest distance from indoor unit to outdoor unit
Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
Extra refrigerant charge
Power supply (voltage and phases)
Minimum Circuit Amps
Maximum Fuse Amps
Running Amps
Starting current
Fuses
WidthxHeightxDepth
Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 4

Outdoor Details
Name
Out 1
Name
Out 1

Model
RXYQ28PAYL
Model
RXYQ28PAYL
* RXYQ18PAYL
* RXYQ10PAYL

Comb
%
107

Tmp C
C
32.0

PS

CC
kW
71.7

MCA
A

MFA
A

34.9
22.8

40
30

Tmp H
C
0.0

HC
kW
66.2

Run Amps
A

Piping
m
39.0
St Curr
A

Bse Refr Ex Refr


kg
kg
19.6
6.9
Fuses

WxHxD
mm

Wght
kg

380V 3ph
Factory Std 1240x1680x765
Factory Std 930x1680x765

341
249

Sufficient distance should be respected between the modules according to the service & operation space rules as
mentioned in the databook.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 5

Piping Diagrams
Pipes marked with * in the diagrams must be connected to the device with a reducing joint.

1.3. Piping Out 1

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 6

2. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

2.1. Wiring Out 1


Q2
Y
X
R
A
P
8
t Y
u
O
L
1
, 2
1
Q

Q1
Y
X
R
AY
P
8
L

1 ,F
F
IN
2
,2 ,L
1
L
3
A3
5
h
p

, 2R
1
Q
Q1
Y
X
AY
P
0
L L
,2 L
1
,
3
A3
3
2
h
p

,2
1
F
,2
1
F
,2
1
F

XF
F
2
1
Q
In 5
E
V
P
2
d
XF
F
2
1
Q
In 5
E
V
P
3
d
XF
F
2
1
Q
In 5
E
V
P
1
d

1 ,P
P
2
C1
R
B
6
E
, N1
L
A1
.5
h
p
1 ,P
P
2
C1
R
B
6
E
, N1
L
A1
.5
h
p
1 ,P
P
2
C1
R
B
6
E

,2
1
F

, N1
L
A1
.5
h
p
In d
4P
1 ,P
2
C1
R
B
6
E
XF
F
25
1
Q
E
V
P
, N1
L
A1
.5
h
p
In d
5P
1 ,P
2
C1
R
B
6
E
XQ
F
F 5
2
1
E
V
P
, N1
L
A1
.5
h
p
In d
6P
1 ,P
2
C1
R
B
6
E
Q2
X
F
VE
P
5
, N0
L
A1
.3
h
p
In d
7P
1 ,P
2
C1
R
B
6
E
Q2
X
F
VE
P
5
, N0
L
A1
.3
h
p
In d
8P
1 ,P
2
C1
R
B
6
E
Q2
X
F
VE
P
5
, N0
L
A1
.3
h
p

,2
1
F

In d
9P
1 ,P
2
C1
R
B
6
E
Q5
X
F
VE
P
0
, N0
L
A1
.3
h
p

,2
1
F
,2
1
F
,2
1
F
,2
1
F

A1
.7
8
h
p

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

Page 7

3. Device Options
3.1. Outdoor Unit Options
Model
Description
BHFP22P100 Outdoor unit multi connection piping kit

Used by
Out 1 [RXYQ28PAYL]

3.2. Indoor Unit Options


Model
BYCP125K-W1

Description
Decoration panel

Used by
Ind 1 [FXFQ125PVE] Ind 2 [FXFQ125PVE] Ind 3 [FXFQ125PVE]
Ind 4 [FXFQ125PVE] Ind 5 [FXFQ125PVE] Ind 6 [FXFQ25PVE]
Ind 7 [FXFQ25PVE] Ind 8 [FXFQ25PVE] Ind 9 [FXFQ50PVE]

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection